NEUDORFER ENGINEERS INC.
5516 1st Ave SSeattle, WA 98108 Vancouver, WA 98661
Phone (206) 621-1810 Phone (503) 235-8924Fax (206) 343-9820 Fax (503) 235-8925
Project Completion Date:
BALANCE REPORT
2015-297
2501 SE Columbia Way, Ste. #230
1550 Irving Street Tenant Improvement
Tumwater, Washington
TEST, ADJUST & BALANCE
Revision Date: Revision Number:05/19/15
PROJECT 1550 Irving Street , T.I. LOCATION Tumwater, WA
TABLE OF CONTENTS
Cover
Report Title 3
Certification 4
Warranty 5
Terms & Abbreviations 6-7
Executive Summary 8-9
Roof Top Units 10-13
Fan Units 14-17
Duct Traverse 18
TAB Drawings 19-21
Instrument Calibration 22
2
Report Title
Project: 1550 Irving Street Tenant ImprovementTumwater, Washington
NEI Job#: 2015-297
Engineer: Capital Heating and Cooling
Contractor: Capital Heating & Cooling
TAB Firm: Neudorfer Engineers Inc5516 1st Avenue SouthSeattle, WA 98108
Test Engineer: Architect: --
5516 1st Ave SSeattle, WA 98108 Vancouver, WA 98661
Phone (206) 621-1810 Phone (503) 235-8924Fax (206) 343-9820 Fax (503) 235-8925
BALANCE REPORTCERTIFIED TEST:
Ryan Niemi
2501 SE Columbia Way, Ste. #230
3
Submitted and Certified by:
NEBB TAB Firm: Neudorfer Engineers IncCertification No: 2465
Expiration Date: March 31, 2017
Certification Date: May 19, 2015(Date completed)
Signed and Sealed by:
NEBB Supervisor: William C. Neudorfer
Noted deficiencies are not Neudorfer Engineers responsibility to repair. Prior to issuance of this report, Deficiency Reports are forwarded to our contracted agent.
Warranty is limited to one year from date of this report. Within that time, any discrepancies, ambiguities, or omissions found in this report will be retested, adjusted, or balanced as needed. A written notification will be required.
The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the NEBB Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems. Any variances from design quantities, which exceed NEBB tolerances, are noted in the Test-Adjust-Balance Report Project Summary.
Significant / Noteworthy Remarks are noted on the General Remarks and General Field Notes pages. Other remarks are noted on individual test sheets.
CERTIFICATION
1550 Irving Street
4
Warranty
Project: 1550 Irving Street
Warranty of Services:
Warranty Procedures:
Voided Warranty and Additional Charges:
Document ArchivingAn electric file of all test documents will be kept on file until the end of the Warranty period. During that time andelectronic copy of the test data will be provided a no charge. Any additional hard / bound copies requested willbe subject to a fee.
For all warranty items, Neudorfer Engineers requires written request. The written request should be specific onthe areas of concern, such rooms, or equipment, and the type of issue the occupants are having. Once writtennotification is received Neudorfer Engineers will schedule a Technician. It is recommended that and Owner orA/E Representative be on site at that time.
If a complaint issue is due to a mechanical equipment failure, control or maintenance related, the return tripmaybe subject to a service charge, not covered under warranty. Neudorfer Engineers reserves the right toresolve any TAB issue. If a third party or competing Test & Balance/ Commissioning firm test or adjust anyequipment, all project warranty is voided. (This is typical standard for the Mechanical industry, as Manufacture,Mechanical and Control Contractor voids all warranty when a competing firm test or manipulates their systems.)Any return trip to the job site are subject to a service charge and a purchase order will be required beforereturning to the job site.
Neudorfer Engineers, Inc. warrants that the air balancing, evaluated during this performance evaluation areoperating at the specified levels as documented within this report. At and only this time, and makes no otherwarranties, stated or implied, concerning the continued performance, operation or safety in the use of thisequipment past this time. Neudorfer Engineers warrants the air and hydronic balancing for 1 year from the dateof substantial completion. Neudorfer Engineers reserves the right to correct errors or omissions in thecollections of data.
5
Terms and AbbreviationsProject:
AC or ACU Air Conditioner or Air Conditioning Unit Des. DesignAct. Actual Dia. Diameter
ACCU Air Cooled Condensing Unit Disch. DischargeAddress Equipment designation number given DNL Data Not Listed
on the Control Program EA Exhaust AirAH or AHU Air Handler or Air Handling Unit EAT Entering Air Temperature
Amps Amperage Economizer Controls and components that allow anAP Access Point air handler to logically utilize outdoor air
APP. Application for cooling as opposed to the use of Arr Arrangement mechanical cooling.
AVG Average EDC Electric Duct CoilBHP Brake Horsepower EDH Electric Duct HeaterBTU British Thermal Units EF Exhaust Fan
BTUH British Thermal Units per Hour EG Exhaust GrilleCAV Constant Air Volume EMCS Energy Management Control SystemCBV Calbirated Balancing Valve ERU Energy Recovery Unit
(Circuit Setter) E.S.P. External Static PressureCC Cooling Coil Evap. EvaporatorCD Ceiling Diffuser EWT Entering Water Temperature
CFLA Correct Full Load Amperage FCU Fan Coil UnitCFM Cubic Feet per Minute FD Fire Damper
CH Chiller FH Fume HoodCHWS Chilled Water Supply FLA Full Load Amperage: Maximum CHWR Chilled Water Return amperage a motor can draw.Coeff. Coefficient Flow Hood Instrument that captures air and
CP Circulating Pump converts the reading to CFM.CR Ceiling Register FPB Fan Powered Box
CRAC Computer Room Air Conditioner FPM Feet per MinuteCRU Computer Room Unit FR Field Report
CT Cooling Tower FT Foot, FeetCU Condenser Unit FTU Fan Terminal Unit
CUH Cabinet Unit Heater GPM Gallons per MinuteCWS Condenser Water Supply HC Heating CoilCWR Condenser Water Return HD Pressure Difference across the entering DAT Discharge Air Temperature and leaving side of a pump.
DB Dry Bulb Heater O.L. Thermal overload protection for motorsDD Direct Drive located at the motor starter (starter heaters)
DDC Direct Digital Controls: EMS Control HEPA High Efficiency Particulate ArrestanceSystem for the HVAC HOA Hand / Off / Auto Switch
Delta Difference, net decrease or increase HP Horsepower
6
Terms and AbbreviationsProject:
HRC Heat Recovery Coil RVA Rotating Vane Anemometer -reads HUH Hydronic Unit Heater air velocity in feet per minute
HVAC Heating Ventilation and Air Conditioning SA Supply AirHWS Heating Water Supply SAT Supply Air TemperatureHWR Heating Water Return S.F. Service Factor
HX Heat Exchanger Schedule Design data obtained from the HZ Hertz, cycle per second (sched) mechanical prints' schedule ofI.D. Inside Diameter equipment.in. inches SCR Silcon Controlled Rectifier
in.w.g. inches of water gauge Speed ControllerKfactor Correction factor to the free area need to SF Supply Fan
calculate CFM. SFD Smoke/Fire DamperKW Kilowatts SP Static PressureLAT Leaving Air Temperature Spec(s) Specifications
LWG Low Wall Grille sq.ft. square feetLWR Low Wall Register Submittals Submitted data on equipment LWT Leaving Water Temperature (subs) capabilities.MAU Make-up Air Hangling Unit Suct. SuctionMBH 1,000 BTUH SWG Sidewall GrilleMAX. Maximum Flow Requirements for DDC SWR Sidewall RegisterMBH Mega BTUs per hour (1MBH=1,000BTUH) TAB Test; Adjust; and BalanceMIN Minimum Flow Requirements for DDC Tach TachometerN/A Not Available Tech TechnicianN/S Not Shown or Specified TSP Total Static Pressure: Difference OA Outside Air between the entering and leaving
OBD Opposed Blade Damper static pressure of a fan.O.D. Outside Diameter TP Traverse or Test Point
PD Pressure Drop. UH Unit HeaterPH Phase VAV Variable Air Volume; box that
PHC Preheat Coil contains a motorized damper that Prim. Primary modulates airflow.
PSI Pounds per Square Inch VD Volume DamperRA Return Air VFD Variable Frequency Drive
RAT Return Air Temperature Velgrid Instrument that reads used to read RF Return Fan velocity in feet per minute.RH Relative Humidity VP Velocity Pressure
RHC Reheat Coil VVT Variable Volume TerminalRPM Revolutions per Minute WC Water ColumnRTU Roof Top Unit W.G. Water Gauge
WB Wet Bulb
7
PROJECT 1550 Irving Street TI LOCATION Olympia, Washington
NATIONAL ENVIRONMENTAL BALANCING BUREAU
EXECUTIVE SUMMARY
This project has been per and specification using the National Environmental Balancing Bureau
(NEBB) standards and procedures.
All of the supply outlets and exhaust inlets have been proportioned to the requirements of the
Specification unless otherwise noted in the report.
A diagram is attached to this report with the supply, and exhaust grilles, registers, and diffusers
(GRD’s) numbered that reference the numbering system used in this report.
Roof Top Unit • RTU-2 is serving the second floor VVT dampers that Neudorfer Engineers balanced in
the T.I. space only. This unit is operating at 40 HZ. Please see below there are VVT
zones that are short on airflow. Neudorfer Engineers did not speed up this unit due to
the existing condition of existing spaces and did not want to disrupt the other space.
• Zone 216 serves the Entry and Office Space. This zone is designed for 550 CFM and is
operating at 555 CFM (101%) of design.
• Zone 217 serves Office Space. This zone is designed for 370 CFM and is operating at
375 CFM (101%) of design.
• Zone 218 serves the open Office Space. This zone is designed for 945 CFM and is
operating at 700 CFM (74%) of design with the VVT damper full open. The damper was
calibrated at a lower CFM and then the set point was raised back up
• Zone 219 serves the Conference Room. This zone is designed for 400 CFM and is
operating at 400 CFM (100%) of design.
8
PROJECT 1550 Irving Street TI LOCATION Olympia, Washington
NATIONAL ENVIRONMENTAL BALANCING BUREAU
EXECUTIVE SUMMARY (CONTD.)
• Zone 220 serves the open Office Space. This zone is designed for 945 CFM and is
operating at 845 CFM (89%) of design with the VVT damper full open. The damper was
calibrated at a lower CFM and then the set point was raised back up.
• Zone 221 serves the Hallway and Office Space. This zone is designed for 300 CFM and is
operating at 320 CFM (108%) of design.
• Zone 222 serves the Break Room and Office. This zone is designed for 375 CFM and is
operating at 600 CFM (63%) of design. with the VVT damper full open. The damper was
calibrated at a lower CFM and then the set point was raised back up.
Exhaust Fans
• EF-1 This unit is a constant volume exhaust fan that serves the Break Room. It is a single
inlet, direct drive fan with a speed controller that has been set to 220 CFM (110% of
design). The total design airflow is 200 CFM.
• TF-1 This unit is a constant volume exhaust fan that serves the Conference Room. It is a
single inlet, direct drive fan with a speed controller that has been set to 220 CFM (110% of
design). The total design airflow is 200 CFM.
9
PROJECT: 1550 Irving Street TI
LOCATION: Tumwater, WA
DATE: 5/22/2015
CONTACT: Ryan Niemi
Roof Top Unit
PROJECT #: 2015-297
Test Date: May 19, 2015 SYSTEM/UNIT: RTU-01AREA:
Tested By: Ryan Niemi
* Notes
Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / Zone Damper-216AREA:
Tested By: Ryan Niemi
Unit Data
Manufacturer Siemens Bacnet
Cooling Inlet Size 12 inches
Cooling K Factor .55
Air Test Data
Clg Max Des. Primary Flow 550 CFM
Clg Min Des. Primary Flow 555 CFM
RTU-01 / Zone Damper-216 Supply Outlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AK Size
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
202 Flowhood CDOutlet-01 102 (1)255250 22510''ø 1 -
204 Flowhood CDOutlet-02 100300300 28510''ø 1 -
------- 550 510 555Totals : 101 %
19-May-15 Readings were taken with zone damper full open RTU-01 / Zone Damper-216 Ryan Niemi* Notes
Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / Zone Damper-217AREA:
Tested By: Ryan Niemi
Unit Data
Manufacturer Siemens Bacnet
Cooling Inlet Size 12 inches
Cooling K Factor .90
Air Test Data
Clg Max Des. Primary Flow 375 CFM
Clg Min Des. Primary Flow 370 CFM
RTU-01 / Zone Damper-217 Supply Outlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AK Size
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
200 Flowhood CDOutlet-01 97145150 1958''ø 1 -
203 Flowhood CDOutlet-02 * 100 (1)150150 1958''ø 1 -
219 Flowhood CDOutlet-03 1007575 1008''ø 1 -
------- 375 490 370Totals : 99 %
20-May-15 (1) Volume damper is full open. RTU-01 / Zone Damper-217
/ Outlet-02
Ryan Niemi* Notes
Neudorfer Engineers, Inc. 10
PROJECT: 1550 Irving Street TI
LOCATION: Tumwater, WA
DATE: 5/22/2015
CONTACT: Ryan Niemi
Roof Top Unit
PROJECT #: 2015-297
Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / Zone Damper-218AREA:
Tested By: Ryan Niemi
Unit Data
Manufacturer Siemens Bacnet
Cooling Inlet Size 12 inches
Cooling K Factor .68
Air Test Data
Clg Max Des. Primary Flow 945 CFM
Clg Min Des. Primary Flow 700 CFM
RTU-01 / Zone Damper-218 Supply Outlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AK Size
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
218 Flowhood CDOutlet-01 * 76 (1)240315 22012''ø 1 -
218 Flowhood CDOutlet-02 75235315 23012''ø 1 -
218 Flowhood CDOutlet-03 71225315 26012''ø 1 -
------- 945 710 700Totals : 74 %
20-May-15 Readings were taken with zone damper full open RTU-01 / Zone Damper-218 Ryan Niemi
20-May-15 (1) Volume damper is full open. RTU-01 / Zone Damper-218
/ Outlet-01
Ryan Niemi* Notes
Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / Zone Damper-219AREA:
Tested By: Ryan Niemi
Unit Data
Manufacturer Siemens Bacnet
Cooling Inlet Size 12 inches
Cooling K Factor .50
Air Test Data
Clg Max Des. Primary Flow 400 CFM
Clg Min Des. Primary Flow 400 CFM
RTU-01 / Zone Damper-219 Supply Outlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AK Size
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
216 Flowhood CDOutlet-01 100400400 30910''ø 1 -
------- 400 309 400Totals : 100 %
* Notes
Neudorfer Engineers, Inc. 11
PROJECT: 1550 Irving Street TI
LOCATION: Tumwater, WA
DATE: 5/22/2015
CONTACT: Ryan Niemi
Roof Top Unit
PROJECT #: 2015-297
Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / Zone Damper-220AREA:
Tested By: Ryan Niemi
Unit Data
Manufacturer Siemens Bacnet
Cooling Inlet Size 14 inches
Cooling K Factor .73
Air Test Data
Clg Max Des. Primary Flow 945 CFM
Clg Min Des. Primary Flow 840 CFM
RTU-01 / Zone Damper-220 Supply Outlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AK Size
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
218 Flowhood CDOutlet-01 * 87 (1)275315 29010''ø 1 -
218 Flowhood CDOutlet-02 92 (1)290315 29010''ø 1 -
218 Flowhood CDOutlet-03 87 (1)275315 31010''ø 1 -
------- 945 890 840Totals : 89 %
20-May-15 Readings were taken with zone damper full open RTU-01 / Zone Damper-220 Ryan Niemi
20-May-15 (1) Volume damper is full open. RTU-01 / Zone Damper-220
/ Outlet-01
Ryan Niemi* Notes
Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / Zone Damper-221AREA:
Tested By: Ryan Niemi
Unit Data
Manufacturer Siemens Bacnet
Cooling Inlet Size 12 inches
Air Test Data
Clg Max Des. Primary Flow 300 CFM
Clg Min Des. Primary Flow 320 CFM
RTU-01 / Zone Damper-221 Supply Outlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AK Size
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
213 Flowhood CDOutlet-01 * 107 (1)160150 2358''ø 1 -
215 Flowhood CDOutlet-02 107160150 2458''ø 1 -
------- 300 480 320Totals : 107 %
20-May-15 Damper was set to 70% due to the duct run was
only 8'' from the main trunk run. The controller
would not stay stable. Controll contractor was not
able to calibrate due to this issue.
RTU-01 / Zone Damper-221 Ryan Niemi
19-May-15 (1) Volume damper is full open. RTU-01 / Zone Damper-221
/ Outlet-01
Ryan Niemi
* Notes
Neudorfer Engineers, Inc. 12
PROJECT: 1550 Irving Street TI
LOCATION: Tumwater, WA
DATE: 5/22/2015
CONTACT: Ryan Niemi
Roof Top Unit
PROJECT #: 2015-297
Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / Zone Damper-222AREA:
Tested By: Ryan Niemi
Unit Data
Manufacturer Siemens Bacnet
Cooling Inlet Size 12 inches
Cooling K Factor 1.17
Air Test Data
Clg Max Des. Primary Flow 600 CFM
Clg Min Des. Primary Flow 375 CFM
RTU-01 / Zone Damper-222 Supply Outlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AK Size
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
211 Flowhood CDOutlet-01 65130200 2008''ø 1 -
210 Flowhood CDOutlet-02 61245400 2008''ø 1 -
------- 600 400 375Totals : 63 %
19-May-15 Readings were taken with zone damper full open RTU-01 / Zone Damper-222 Ryan Niemi* Notes
Neudorfer Engineers, Inc. 13
PROJECT: 1550 Irving Street TI
LOCATION: Tumwater, WA
DATE: 5/22/2015
CONTACT: Ryan Niemi
Fan Unit
PROJECT #: 2015-297
Test Date: May 20, 2015 SYSTEM/UNIT: EF-01AREA:
Tested By: Ryan Niemi
Unit Data
Fan Manufacturer Cook
Fan Model Number 90-SQN-90SQ17DEC
Fan Serial Number 033SF68792-00/0000701
Fan Rotation Clockwise
Fan Discharge Horizontal
Drive Type Direct Drive
Test Data
Total Design Flow 200 CFM
Total Actual Flow 220 CFM
Fan RPM Design 1098 RPM
Fan RPM Actual 1050 RPM
Motor RPM Actual 1050 RPM
Motor Volts T1-T2 121 Volts
Motor Amps T1 0.50 Amps
Motor Data
Motor Manufacturer (1)
Motor Frame (1)
Motor HP 1/4 HP
Motor RPM 1725 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor Full Load Amps (1) Amps
Test Pressures
Fan Suction SP -0.11 in. wc
Fan Discharge SP 0.14 in. wc
Design External SP 0.25 in. wc
Actual External SP 0.25 in. wc
EF-01 Exhaust Inlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AKSize
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
210 Flowhood EGInlet-01 110220200 34010''ø 1 -
------- 200 340 220Totals : 110 %
20-May-15 (1) Motor data blocked by motor frame EF-01 Ryan Niemi* Notes
Neudorfer Engineers, Inc. 14
PROJECT: 1550 Irving Street TI
LOCATION: Tumwater, WA
DATE: 5/22/2015
CONTACT: Ryan Niemi
Fan Unit
PROJECT #: 2015-297
Test Date: May 20, 2015 SYSTEM/UNIT: TF-01AREA:
Tested By: Ryan Niemi
Unit Data
Fan Manufacturer Cook
Fan Model Number 90-SQN-90SQ17DEC
Fan Serial Number 033SF68792-00/0000701
Fan Rotation Clockwise
Fan Discharge Horizontal
Drive Type Direct Drive
Test Data
Total Design Flow 200 CFM
Total Actual Flow 220 CFM
Fan RPM Design 1098 RPM
Fan RPM Actual 1050 RPM
Motor RPM Actual 1050 RPM
Motor Volts T1-T2 121 Volts
Motor Amps T1 0.60 Amps
Motor Data
Motor Manufacturer (1)
Motor Frame (1)
Motor HP 1/4 HP
Motor RPM 1725 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor Full Load Amps (1) Amps
Test Pressures
Fan Suction SP 0.55 in. wc
Fan Discharge SP 0.11 in. wc
Design External SP 0.25 in. wc
Actual External SP 0.66 in. wc
TF-01 Exhaust Inlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AKSize
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
216 Flowhood EGInlet-01 110220200 31510''ø 1 -
------- 200 315 220Totals : 110 %
20-May-15 Volume damper was cut to set CFM due to no
accessvto SCR inside of fan box.
TF-01 Ryan Niemi* Notes
Neudorfer Engineers, Inc. 15
PROJECT: 1550 Irving Street TI
LOCATION: Tumwater, WA
DATE: 5/22/2015
CONTACT: Ryan Niemi
Fan Unit
PROJECT #: 2015-297
Test Date: May 20, 2015 SYSTEM/UNIT: EF-01AREA:
Tested By: Ryan Niemi
Unit Data
Fan Manufacturer Cook
Fan Model Number 90-SQN-90SQ17DEC
Fan Serial Number 033SF68792-00/0000701
Fan Rotation Clockwise
Fan Discharge Horizontal
Drive Type Direct Drive
Test Data
Total Design Flow 200 CFM
Total Actual Flow 220 CFM
Fan RPM Design 1098 RPM
Fan RPM Actual 1050 RPM
Motor RPM Actual 1050 RPM
Motor Volts T1-T2 121 Volts
Motor Amps T1 0.50 Amps
Motor Data
Motor Manufacturer (1)
Motor Frame (1)
Motor HP 1/4 HP
Motor RPM 1725 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor Full Load Amps (1) Amps
Test Pressures
Fan Suction SP -0.11 in. wc
Fan Discharge SP 0.14 in. wc
Design External SP 0.25 in. wc
Actual External SP 0.25 in. wc
EF-01 Exhaust Inlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AKSize
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
210 Flowhood EGInlet-01 110220200 34010''ø 1 -
------- 200 340 220Totals : 110 %
20-May-15 (1) Motor data blocked by motor frame EF-01 Ryan Niemi* Notes
Neudorfer Engineers, Inc. 16
PROJECT: 1550 Irving Street TI
LOCATION: Tumwater, WA
DATE: 5/22/2015
CONTACT: Ryan Niemi
Fan Unit
PROJECT #: 2015-297
Test Date: May 20, 2015 SYSTEM/UNIT: TF-01AREA:
Tested By: Ryan Niemi
Unit Data
Fan Manufacturer Cook
Fan Model Number 90-SQN-90SQ17DEC
Fan Serial Number 033SF68792-00/0000701
Fan Rotation Clockwise
Fan Discharge Horizontal
Drive Type Direct Drive
Test Data
Total Design Flow 200 CFM
Total Actual Flow 220 CFM
Fan RPM Design 1098 RPM
Fan RPM Actual 1050 RPM
Motor RPM Actual 1050 RPM
Motor Volts T1-T2 121 Volts
Motor Amps T1 0.60 Amps
Motor Data
Motor Manufacturer (1)
Motor Frame (1)
Motor HP 1/4 HP
Motor RPM 1725 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor Full Load Amps (1) Amps
Test Pressures
Fan Suction SP 0.55 in. wc
Fan Discharge SP 0.11 in. wc
Design External SP 0.25 in. wc
Actual External SP 0.66 in. wc
TF-01 Exhaust Inlet Summary
RemarksFinal
%
Final
Reading
Prelim
Reading
Design
Value
Design
Velocity
AKSize
LxW / D
Outlet
Type
Type of
Reading
Area ServedSystem / Unit
216 Flowhood EGInlet-01 110220200 31510''ø 1 -
------- 200 315 220Totals : 110 %
20-May-15 Volume damper was cut to set CFM due to no
accessvto SCR inside of fan box.
TF-01 Ryan Niemi* Notes
Neudorfer Engineers, Inc. 17
PROJECT: 1550 Irving Street TI
LOCATION: Tumwater, WA
DATE: 5/22/2015
CONTACT: Ryan Niemi
Duct Traverse
PROJECT #: 2015-297
Test Date: May 20, 2015 SYSTEM/UNIT: Duct-01 Tested By: Ryan Niemi
Unit Data
Type of Traverse Rectangular
Outer Height 22.00 in.
Outer Width 74.00 in.
Air Flow Area 11.31 sq. ft.
Number Of Rows 1
Readings Per Row 7
Total Readings 7
Final Data
Sum of Readings 317
Average Reading 45 FPM
Design Total Flow 475 CFM
Actual Total Flow 509 CFM
20-May-15 (1) Shortridge Multimeter with velgrid was used to
obtain velocity readings.
Duct-01 Ryan Niemi
20-May-15 OSA was raised fromm 750 CFM to 1252 CFM.
Drawings inducates a raise of 475 CFM.
Duct-01 Ryan Niemi
NOTES:
Duct Traverse Data Points
Neudorfer Engineers, Inc. 18
Stamp
Issue/Revision:
No.Proj. No.Date: Description
Consultant
Co/ Title: Date:
Scale: Issue Date:
Drawn By: Reviewed By:
Sheet:
Copyright Statement:All drawings and written material appearing hereinconstitute original and unpublished original work of thearchitect and may not be duplicated, used, or disclosed
without prior written consent of the architect.
Approval Signature:
MECHANICAL
NOTES AND
SPECIFICATIONS
M1.0
S
H
T
Z
19
Stamp
Issue/Revision:
No.Proj. No.Date: Description
Consultant
Co/ Title: Date:
Scale: Issue Date:
Drawn By: Reviewed By:
Sheet:
Copyright Statement:All drawings and written material appearing hereinconstitute original and unpublished original work of thearchitect and may not be duplicated, used, or disclosed
without prior written consent of the architect.
Approval Signature:
CONDENSATE DRAINCONNECTION DETAIL
TRANSFER GRILLEDUCT CONNECTION DETAIL
DUCT CONNECTIONTO DIFFUSER DETAIL
EQUIPMENT MOUNTING DETAIL
SPLIT SYSTEMREFRIGERANT PIPING DETAIL
MECHANICAL
SCHEDULES
AND DETAILS
M1.1
GRILLES/REGISTERS/DIFFUSERS SCHEDULE
MARK DESCRIPTION TYPEMODULE
SIZEOBD FRAME MATERIAL MANUF.FINISH MODEL REMARKS
FAN COIL UNIT
MODEL NO. CFM
DUCTLESS SPLIT SYSTEM A/C UNIT SCHEDULE
MANUFACTURER
WB (F)
ENT. AIR TEMP
DB (F)
REMARKSMODEL NO.
CONDENSING UNIT
SEEREQUIP.
NO.
VOLTS/
PHASE
EQUIP.
NO.
VOLTS/
PHASE TOTAL
MBH
SENS.
MBH
WEIGHT(LBS)
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Stamp
Issue/Revision:
No.Proj. No.Date: Description
Consultant
Co/ Title: Date:
Scale: Issue Date:
Drawn By: Reviewed By:
Sheet:
Copyright Statement:All drawings and written material appearing hereinconstitute original and unpublished original work of thearchitect and may not be duplicated, used, or disclosed
without prior written consent of the architect.
Approval Signature:
MECHANICAL
FLOOR PLAN
2M2.021
Instrument Type Air Data Meter with FlowhoodInstrument Manufacturer Shortridge
Instrument Model Number ADM 870Instrument Serial # M99620
Calibration Due Date 1/13/2016
Instrument Type TachometerInstrument Manufacturer Shimpo DT-207L
Instrument Model Number Type BInstrument Serial # C1CB0033
Calibration Due Date 4/20/2016
Instrument Type Amp ProbeInstrument Manufacturer Fluke
Instrument Model Number Fluke 902Instrument Serial # 79611561
Calibration Due Date 2/26/2016
Instrument Type Temperature ProbeInstrument Manufacturer Shortridge
Instrument Model Number ADM 870Instrument Serial # M99620
Calibration Due Date 1/13/2016
Instrument Type Air FoilInstrument Manufacturer Shortridge
Instrument Model Number ADM 870Instrument Serial # M99620
Calibration Due Date 1/13/2016
Instrument Type Hydrodata MultimeterInstrument Manufacturer Shortridge
Instrument Model Number HDM-250Instrument Serial # W11009
Calibration Due Date 3/2/2016
Instrument Calibrations
22