Upload
dhsv43
View
166
Download
1
Embed Size (px)
Citation preview
DC Power SolutionforBusiness-Critical Continuity
TM
Platform Power System, NetSure 701 Series-48 VDC, up to 19.2 kWNetSure 701 A61 (PS48300-4/2900-Y6 and PS48300-4/2900-W6 )
Introduction
Platform Power System NetSure 701 A61 is Emerson next generation
system for medium exchanges, rural telecom networks and access
networks, 2G and 3G base station, transmission relay station,
microwave/satellite communication stations as well as other applications
requiring the power up to 19.2 kW.
The system can be optimized cost-effectively to meet initial requirements,
whilst allowing for easy expansion in the future. Configurable distribution
and number of rectifier modules are available to meet various demands
Features
�
�
�
�
�
�
�
�
�
High flexible configuration to meet various customer
requirements, easy for fast construction of communication
sites
Hot swap rectifier and controller, high power density
Safety EN60950
Compliant with global standards delivers quality,
performance and dependability
Two over-voltage protection methods for options:
hardware protection and software protection.
Perfect battery management includes the LLVD,
temperature compensation, auto voltage regulation,
stepless current limiting, battery capacity calculation and
on-line battery test, etc
The monitoring module can save up to 200 pieces of
historical alarm records, and 10 sets of battery test data
records
Perfect lightning protection at perfect lightning protection
at both AC side and DC side
The high power density rectifier uses the active Power
Factor Compensation (PFC) technology, raising the power
factor to 0.99
NetSure 701 A61
Technical specifications -Environmental Parameter
Operating Temperature -5 C 45
Storage Temperature -40 70
Relative Humidity 5%RH 95%RH
Elevation 2000m (derating is necessary above 2000m)
o o
o o
C
C C
600 600 2000 (Y6)
600 600 1800 (SFA)
600 600 500 (W6)
Rectifier 85.3 272 87.9
540 545 350
(accommodating 4 165Ah battery)
540 545 280
(Accommodating 4 100Ah battery)
Cabinet(excludingrectifiers,
Monitoring module and
Batteries)
Rectifier 2.0
Size (W D H)(mm)
Weight (kg)
Mechanical Parameter
Configuration
Item PS48300-4/2900-Y6 or PS48300-4/2900-W6
Model: R48-3200 or R482900U Optional configuratio
2piece 6pieces Standard configuration: 5 pieces
Monitoring module Model: M520S Standard configuration: 1 piece
AC input AC input mode:3P+N+PE/380V+SPD
6 BLVD routes:2 63A/1P, 2 32A/1P, 2 10A/1P MCB
9LLVD routes: 3 32A/1P, 6 63A/1P MCB
Battery MCB:3 100A/1P(SFA)
Maximum configuration:
Optional parts Temperature sensors, modem
3 4 (12V/165Ah) or 3 4 (12V/100Ah)
Rectifier
DC distribution
Battery routes
2000mm cabinet 140
1800mm cabinet 130
500mm cabinet 50
Cabinet
Battery compartment
DC Power Solutionfor Business-Critical ContinuityTM
Platform Power System, NetSure 701 Series-48 VDC, up to 19.2 kWNetSure 701 A61 (PS48300-4/2900-Y6 and PS48300-4/2900-W6 )
Emerson Network Power Co., Ltd.
Address:No.1 Ke Fa Road, Science & IndustryPark,
Nanshan District,518057 Shenzhen, China Telep
hone: 86-755-86010808
Postcode: 518057
Battery Cabinet (rack)
See separate datasheet for the detailed cabinet (rack) information
Controller: M520S
Intelligent battery management Latest 200 alarm history log
Display LCD with 4 16 characters
Language: English, Chinese
External Communication: RS232(modem) or TCP/IP
Protocol: YDN23
Inputs: 8 Digital Inputs Alarms/Events
Outputs: 8 Relay Outputs 1A, max 60V
Examples of Alarms: DC Power Plant Alarms AC mains failure, Rectifier failure, DC/DC converter failure, High voltage shut-down,
Fan failure, Thermal derating
Emerson Network PowerA global leader for critical business continuityTM
Emerson Network Power and the Emerson
Network Power Logo are trademarks and
service marks of Emerson Electric Co.
2009 Emerson All Rights Reserved
2009.11
Rectifier Module R48-2900 ,R48-3200
Features
Input voltage nominal 200 to 240 Vac
Input voltage permitted variation 85 to 290 Vac
Power factor 0.99
THD <5% from 50 to 100% of rated load
Output voltage -42 to -58 Vdc
Output power 3200 W
Max output current 67A
Efficiency 92% or 96% for HE R48-3200
Temperature range -40 to +75 C for R48-3200 and -40 to +65 C for R48-2900U
RH (non-condensing) 0 to 95%
EMC EN 300 386:2001, class B & FCC part 15, class B
Safety IEC / EN / UL 60950
Dimensions (H W D) 132 85.3 287 mm, 5.20 3.36 11.3 inches
Weight 3.5 kg, 7.7 lbs
o o