Nepro PVC Rigid Conduit and Duct Pipes

New Products Industries (Nepro) National Factory for Plastic pipes and fittings took the early initiative in 1969 of introducing uPVC pipes production to the Saudi Market, becoming the first Saudi local uPVC pipes manufacturer. From this pioneering achievement in the production of high quality PVC and cPVC pipes and fittings for water and sewerage distribution lines, Nepro has expanded its extruded product range to include PVC Ducts and Conduits for Electric and Telecommunication Installations generally acceptable for use in aboveground & underground applications for either concrete encased or direct burial.

NEPRO PVC ducts and Conduits meet the requirements prescribed by the following standards Organizations:

1) National Electrical Manufacturer’s Association (NEMA-USA) 2) American Society for Testing & Material (ASTM) 3) Saudi Arabian Standard Organization (SASO) 4) British Standards Conduit for Electrical Installation

Nepro PVC Ducts and Conduits Are subjected to strict quality control to ensure that only products that meet the standard are delivered to customers. NEPRO has a well-equipped laboratory capable of carrying out the required tests. It also maintains contact with local and overseas independent laboratories for conducting third party product testing and analysis. NEPRO quality activities start from selection and purchase of raw materials and equipment, through the manufacturing process, and finally to loading and delivery. NEPRO is currently adopting ISO 9002 quality system as the basic foundation for its quality management, certified & assessed by SASO registered firm.

NEPRO PVC Ducts and Conduits Are tested and approved by independent laboratory for UL-651 to meet the use with maximum 90 0C wire requirements.

NEPRO PVC ducts and Conduits Are available in 3 and 6-meter lengths. These can be supplied in plain or with bellied ends for solvent cement joint. Bends and fittings accessories for wire and cable protection systems are also available.

NEPRO PVC Ducts and Conduits Are quick and easy to install using commercially available solvent cements.

NEPRO PVC ducts and Conduits is Approved by the following Organizations: SAUDI ARAMCO, SCECO, ROYAL COMMISSION, MOPTT and several consulting Offices as well as various ministries etc. For further information please contact our technical staff at your nearest branch.

Page 4: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

?

NEPRO PVC ducts and Conduits have the following Advantages:

Lightweight Easy to Install

Weight less than 1/5 as much as steel and half as much as aluminum. Means quick, easy installation, labor saving, and reduced total job time.

Non-Corrosive Since PVC can’t corrode and is not affected concrete additives, electrolysis, corrosive atmospheres, soils, salts or excessive humidity, Its service life under these conditions is far superior to that of other conduit materials.

Fire Resistant

PVC is a thermoplastic that inherently resists continuous combustion. It is classified as self-extinguishing when tested to ASTM D 635.

Non-Magnetic

PVC is nonmagnetic; thus it reduces voltage drop and minimizes power loss.

Reliable joint & Easy Pull Through

Installations with simple, fast, solvent cement joints, NEPRO PVC Conduit require no threading. Its smooth, uniform interior walls make wire pull through faster and easier.

Safety

PVC Conduit is nonconductive and non-sparking. PVC conduits eliminate the dangerous second point of contact and phase to ground faults.

Page 5: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

?

MATERIAL PROPERTIES

NEPRO Rigid Conduits and fittings are made from PVC Polyvinyl Chloride plastic compounds which meets or exceeds the requirements of PVC Class 12454-B described in ASTM D-1784 and ASTM D 4396 specification as specified in NEMA standards TC-2, TC-6, TC-8. Table No 1 All below values are at (73 0F) 23 0C

General Properties Test Method

(ASTM) Unit Value

Density Flammability

a) Average extend of burning b) Average Time of Burning c) U.Lab rating d) Flammability

Thermal

a) Vicat Softening Point b) Heat Deflection c) Coefficient of Thermal Expansion

Mechanical

a) Tensile Strength b) Modulus of Elasticity c) IZOD Impact d) Hardness (Rockwell) e) Flexural Strength

Electrical Properties

a) Dielectric Strength b) Power Factor c) Dielectric Constant d) Volume resistively

D-792 D-635 SECS (UL-94/0.062m) D-635 D-1525 (rate A) D-648 (264 psi) D-696 D-638/Type 1 D-639/Type 1 D-256 D-785 D-790 D-150 D-150 D-150 D-257

Gm/cm 3 Mm <10 rating Resistance 0C 0C in/in 0F psi psi ft/Ib/in of notch R ‘psi Volts/mm 60 cps @ 300C 60 cps @ 20 0C ohm.cm

1.43

<25

V-0 Self

Extinguishing

>80 78

3.38x10-5

7,500 500,000

4.0 119

13,500

1100 1.93 4.00

>10 14

Page 6: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

?

NEPRO Rigid PVC Electrical Plastic Tubing (EPT) & Conduit (EPC-40 and EPC-80) Table No 2 NEMA TC-2 Dimensions Nominal Outside EPT-W-PVC EPC 40-PVC EPC 80-PVC Pipe Size Dia W/T N.Weight W/T N.Weight W/T N.Weight Inch Inch/mm mm Kgs/M mm Kgs/M mm Kgs/M ½” 0.840/21.34 1.52 0.155 2.77 0.248 3.73 0.309 ¾” 1.050/26.67 1.52 0.197 2.87 0.329 3.91 0.418 1” 1.315/33.40 1.52 0.250 3.38 0.483 4.55 0.614 11/4” 1.660/42.16 1.78 0.365 3.56 0.652 4.85 0.850 11/2” 1.900/48.26 2.03 0.468 3.68 0.779 5.08 1.030 2” 2.375/60.32 2.54 0.717 3.91 1.04 5.54 1.430 21/2” 2.875/73.02 2.79 0.952 5.16 1.65 7.01 2.18 3” 3.500/88.9 3.18 1.310 5.49 2.160 7.62 2.90 4” 4.500/114.30 3.81 2.000 6.02 3.070 8.56 4.260 5” 5.563/141.30 ------ ------- 6.55 4.17 9.52 5.910 6” 6.625/168.28 ------ ------- 7.11 5.410 10.97 8.130 EPT-A-PVC Electrical Plastic tubing for encasement concrete. EPC- 40(Sch 40) Electrical Plastic Conduit for normal duty. EPC -80(Sch80) Electrical Plastic Conduit for heavy duty.

Pipe length: Standard size is three meters (3m), other sizes can be produced upon request.

Page 7: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

O

NEPRO Rigid PVC Utilities Duct for Underground Installation Table No 3 NEMA TC-6 and ASTM F512 Dimensions PVC/Type EB 20 PVC/Type DB 60 Nom Pipe Size Inch

Outside Dia Mm

Wall Thick (Minimum) mm

Net Weight Kgs/M

Wall Thick Min Mm

Kgs/M

2 60.32 1.52 0.463 1.52 0.465 3 88.90 1.55 0.702 2.34 1.000 4 114.30 2.08 1.170 3.07 1.650 5 141.30 2.62 1.710 3.86 2.50 6 168.28 3.18 2.530 4.62 3.570 Type EB for Encased Burial in Concrete Pipe length:Standard 6 Mtr (6m) Type DB for Direct Burial without Concrete NEPRO Rigid PVC Extra Strength for Underground Installation Table No 4 NEMA TC-8 and ASTM F512 Dimensions PVC/Type EB 135 PVC/Type DB 120 Nom Pipe Size Inch

Outside Dia Mm

Wall Thick (Minimum) mm

Net Weight Kgs/M

Wall Thick Min Mm

Kgs/M

1 33.40 ------ ----- 1.52 0.251 1 ½ 48.26 ------- ----- 1.52 0.369 2 60.32 1.52 0.465 1.96 0.576 3 88.90 1.93 0.847 3.00 1.250 4 114.30 2.54 1.390 3.91 2.050 5 141.30 3.20 2.09 4.85 3.12 6 168.28 3.86 3.020 5.77 4.420 Type EB for Encased Burial in Concrete Pipe length:Standard 6 Mtr (6m) Type DB for Direct Burial without Concrete Figures 20,60,135 & 120 pipe Stiffness (Minimum).

Page 8: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

?

NEPRO Fabricated Long Radius Bends (Elbow) to NEMA TC3.

Bends is table No. 5 are to be used with NEMA TC-2

Rigid PVC Conduit EPT-A, EPC-40, & EPC-80 A)Fabricated Bends Table No 5

Nominal

Out Side Radius ®

Size Dia

Inch Inch Mm Inch Mm

½ 0.840 21.34 4.0 102

¾ 1.050 26.67 4.50 114

1 1.315 33.40 5.75 146

11/2 1.900 48.26 8.25 210

2 2.375 60.32 9.5 241

2.1/2 2.875 73.02 10.50 266

3 3.500 88.90 13 330

4 4.500 114.30 16 406

5 5.563 141.30 24 610

6 6.628 168.28 30 762

NOTE: The above dimensions are of 30 o, 45 o, & 90 o elbows

Other Radii bends are available upon request Plain ended, Single & double solvent weld sockets are available.

Sizes of couplings and bell ends ranges from ½”, ¾”,1,11/2”, 2”,3”,4”,5” to 6”

Page 9: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

?

NEPRO Fabricated Long Radius Bends (Elbow) to NEMA TC9. Bends is table No. 6 to be used with NEMA TC-6 & TC-8 Rigid PVC Conduit EB and type DB

Table No 6 U.S. Units Metric

Nominal Size of 22 o, 30 o, 45 o &

90 o Bends, Radius Maximum Straight

Tangent length at end (X)

Fittings Inches R Meters R Inch ‘mm

11/2 18, 24, 36, 48 0.46,0.61,0.91,1.22 1 3/4 44

2 18, 24, 36, 48 0.46,0.61,0.91,1.22 2 50.8

3 18, 24, 36, 48 0.46,0.61,0.91,1.22 3 1/8 79.4

4 18, 24, 36, 48 0.46,0.61,0.91,1.22 3 3/8 85.7

5 18, 24, 36, 48 0.46,0.61,0.91,1.22 3 5/8 92.1

6 18, 24, 36, 48 0.46,0.61,0.91,1.22 3 3/4 95.2

Dimensions of 22 o, 30 o, 45 o, & 90 o. NOTE: Plain ended, Single & double solvent weld sockets are available as per request.

Page 10: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

I ?

NEPRO Conduits for Electrical Installations As per Saudi Arabian standards SSA 255/1981 Table No 7 Dimensions of Rigid PVC Conduit

Nominal Outside Diameter Minimum Inside

Size/of mm Dimension/mm Tolerance/mm Diameter/mm

16 16 +0.0 13.0

20 20 -0.3 16.9

25 25 +0.0 21.4

32 32 -0.4 27.8

NEPRO Conduits for Electrical Installations As per Saudi Arabian standards BS-6099

Table No 8 Dimensions of Rigid PVC Conduit

Light Gauge Medium Gauge Heavy Gauge

Size W/Thick Min.Inside W/Thick Min.Inside W/Thick Min.Inside

Mm Mm Dia.mm Mm Dia.mm Mm Dia.mm

16 1.15 13.7 1.5 13.0 1.90 12.2

20 1.30 17.4 1.55 16.9 2.10 15.8

25 1.45 22.1 1.80 21.4 2.20 20.6

32 1.70 28.6 2.10 27.8 2.70 26.6

38 2.00 34.0 2.25 33.5 2.75 32.5

40 2.10 35.8 2.30 35.4 2.80 34.4

50 2.45 45.1 2.85 44.3 3.40 43.2

63 3.00 57.0 ----- ------ ------ -----

NEPRO Conduit are offered in 3 or 2.9 meters long and black color. Fittings for the above Conduits in Table No.9 are available upon request.

Page 11: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

I I

NEPRO UPVC Conduit Suitable for Cable Ducting Size & Dimensions as per SSA DIN 8061/62

Table No 9

Nominal Class Class 3 Class 4 Class 5 Outside Dia W/Thick W/Thick W/Thick W/Thick Mm Mm Mm Mm Mm 16 ------ ------ ------- 1.2 20 ------ ------ ------- 1.5 25 ------ ------ 1.5 1.9 32 ------ ------ 1.8 2.4 40 ------ 1.8 1.9 3.0 50 ------ 1.8 2.4 3.7 63 ------ 1.9 3.0 4.7 75 1.8 2.2 3.6 5.6 90 1.8 2.7 4.3 6.7 110 2.2 3.2 5.3 8.2 125 2.5 3.7 6.0 9.3 140 2.8 4.1 6.7 10.4 160 3.2 4.7 7.7 11.9 200 4.0 5.9 9.6 14.9 225 4.5 6.6 10.8 16.7 250 4.9 7.3 11.9 18.6 280 5.5 8.2 13.4 20.8 315 6.2 9.2 15.0 23.8 400 7.9 11.7 19.1 29.7

Note: Cable Ducts in Table No 9 are Grey color with standard length of 6 meters.

NEPRO Pipes to local Bahrain & Qatar requirements

Table No: 10

BPO-LN173 Ducts to BN & QTR Needs Duct

Outside Dia Wall/Thick Nominal Outside Dia Wall/Thick

No. Mm Mm Mm Mm Size Mm Mm Mm Mm

Min Max Min Max Inch/mm Min Max Min Max

56 53.8 54 1.55 1.70

54D 96.3 96.7 3.05 3.45

57 114.1 114.5 3.4 3.8 4” (110) 110 110.4 2.2 2.7

57A 114.4 114.5 4.5 4.9 6” (160) 160 160.6 3.0 3.5

Note: Ducts in Table 10 are black with standard length of 5.8 or 6 Meters.

Page 12: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

I I

NEPRO Conduit Weight Comparison Chart (Pounds Per Hundred Feet) Table No 11

Size

Rigid PVC EPC-40

Rigid PVC EPC-80

Alum

Elec.Metalic Tubing (EMT)

Intermediate Metallic Conduit (IMC)

Rigid Steel Conduit (GALV)

½ 17 21 27 30 57 79 ¾ 22 28 36 46 78 105 1 33 41 53 66 112 153 11/4 44 56 70 96 144 201 11/2 53 68 86 112 176 249 2 69 95 116 142 235 334 3 143 193 239 270 483 690 4 204 280 340 400 625 982 6 358 ----- 612 ----- ------ 1770

NEPRO PVC CONDUIT INSTALLATION UNDER CHANGING TEMPERATURE CONDITIONS.

A Constantly changing temperature at the Installation site with long runs involved requires Precautions against expansion. The chart indicates the expansion that can be expected at various temperatures. The coefficient of linear expansion of NEPRO Conduit 3.38x10-5 in/in/F0 Deg

When Nepro PVC conduit is encased in concrete it will only expand indirect proportion to the expansion rate of the concrete thus no expansion couplings are necessary in this application.

Table No 12 Temperature Rise or Drop in Degree F

Change in length of a 10-foot length shown in inches.

Note: PVC Conduit must be supported (not strapped tight) to allow movement of the conduit.

Page 13: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

I ?

Temperature Consideration for Liner Expansion Expansion Characteristics of PVC rigid on non-metallic Conduit (Table1) Coefficient of Thermal Expansion = 3.38x10-5 IN-IN/F . Table No 13

Temperature Changes In Deg. F

Length Change In Inches per 100 ft

Temperature Changes In Deg. F

Length Change In Inches per 100 ft

Of PVC Conduit

5 0.2 100 4.1 10 0.4 105 4.2

15 0.6 110 4.5 20 0.8 115 4.7 25 1.0 120 4.9 30 1.2 125 5.1 35 1.4 130 5.3 40 1.6 135 5.5 45 1.8 140 5.7 50 2.0 145 5.9 55 2.2 150 6.1 60 2.4 155 6.3 65 2.6 160 6.5

70 2.8 165 6.7 75 3.0 170 6.9

80 3.2 175 7.1 85 3.4 180 7.3 90 3.6 185 7.5 95 3.8 195 7.9

100 4.1 200 8.1

PVC CEMENT Below chart lists the average number of joints that can be made per pint of cement. Table No 14 Nominal Conduit Size

1/2 3/4 1 11/4 11/2 2 3 4 6

Joint per Pint of Cement

350 200 150 110 80 45 35 25 15

Page 14: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

I ?

CERTIFICATE OF TEST 3 July 1997 Nepro Plastics RO.Box 460 Jeddah21411

Saudi Arabia

Stanger YourRef.: S/152/09/95 ourRef.:2071/1257/95/AA/st

A Sample of rigid PVC Conduit of nominal outside diameter of 1 10 mm and 5.3 mm wall thickness

Date of Receipt : Reference Number: Number Tested : Test Method : Identification Marks : Date of Test : Remarks :

12 September 1995 EE4256 150 UL 651, 5th edition. Paragraph 15.1 EE 4256 9th April 1996-9th May 1997 The test specimens were found to comply with the test requirem ent of paragraph 15.1 of UL 651, 5th Edition.

Signed : A M Ali Component Engineer Stanger Science & Environment Acrewood way St. Albans Herts AL4 OSY Telephone (01 727)840580 Fax (01 727)81 6700 Stanger Science & Environment is a trading name of Stanger Limited Registered in England No. 2495300 Registered Office Construction House Birch Street Wolverhampton WVI 4HY A TormacGroup Company

(Met/A/361CCOT)

NEPRO Manufacturing Plant, JEDDAH RO. Box 460-Zip Code 21411 Tel.: 02-6363558, 1596, 1205 Fax: 02-6362364

Marketing Offices National Marketing Jeddah PO. Box 16375-Zip Code 21464 Tel.: 02-647-5010 Fax: 02-647-4503 E-mail : [email protected] E-mail : [email protected] National Marketing Bani Malik PO.Box 16375 Tel.: 02617-1631 Fox.: 02 673-6384 E-mail : [email protected] National Marketing Yanbu PO. Box 773, Yanbu Tel.: 04391-7483 Fax: 04 322-3857 E-mail : [email protected] National Marketing Taif PO. Box Tel.: 07 742-3683

Fox: 07748-3519

National Marketing Export Office PO Box 1 6375 - Zip Code 21464 Tel.: 02-647-4204 Fax: 02-647-4503 E-mail : [email protected] National Marketing Dammam PO. Box 2145 - Zip Code 31952 Tel.: 03847-1315 Fax:03847-1312 E-mail : [email protected] National Marketing Abha PO. Box 298 Tel.: 07 223-4608 Fax: 07222-0195 National Marketing AI-Hassa PO. Box 4251 Tel.: 03 582-3033 Fax: 03 585-5837

E-mail : [email protected]

National Marketing Riyadh PO. Box 2729 - Zip Code 11461 Tel.: 01 477 3378 Fax: 01 478 2567 E-mail : [email protected] National Marketing Qassim PO Box 2218, Qassim, Buraida Tel,: 06 382-0916 Fax: 06381-3350 National Marketing Madina PO. Box 5362, Al Medina Tel.: 04 838-0202 Fax: 04 833-0011

E-mail : [email protected]

Page 15: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

I ?

Page 16: Nepro PVC Rigid Conduit and Duct Pipes - NAMATnamat.com/pdf/pdfv1/NEPRO-conduit pvc1.pdf · Nepro PVC Rigid Conduit and Duct Pipes ... SAUDI ARAMCO, SCECO, ROYAL ... ASTM D-1784 and

I ?