NCR 4072 500–1400 VA Uninterruptible Power Systems (UPS) Site Preparation, Installation, and Operation Manual

NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Embed Size (px)

Citation preview

Page 1: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

NCR 4072500–1400 VA

Uninterruptible Power Systems (UPS)

Site Preparation,Installation, and Operation Manual

Page 2: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Class B EMC StatementsFCC Part 15NOTE This equipment has been tested and found to comply with the limits for a Class B digital device,pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection againstharmful interference in a residential installation. This equipment generates, uses and can radiate radiofrequency energy and, if not installed and used in accordance with the instructions, may cause harmfulinterference to radio communications. However, there is no guarantee that interference will not occur ina particular installation. If this equipment does cause harmful interference to radio or televisionreception, which can be determined by turning the equipment off and on, the user is encouraged to try tocorrect the interference by one or more of the following measures:

� Reorient or relocate the receiving antenna.

� Increase the separation between the equipment and the receiver.

� Connect the equipment into an outlet on a circuit different from that to which the receiver isconnected.

� Consult the dealer or an experienced radio/TV technician for help.

ICES-003This Class B Interference Causing Equipment meets all requirements of the Canadian InterferenceCausing Equipment Regulations ICES-003.

Cet appareil numérique de la classe B respecte toutes les exigences du Reglement sur le matérielbrouilleur du Canada.

ECopyright 2001–2005 NCR Corporation, Dayton, Ohio. All rights reserved. No part of this document maybe reproduced in any way without the express written approval of NCR Corporation.

Page 3: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Requesting a Declaration of ConformityUnits that are labeled with a CE mark comply with the following harmonized standards and EUdirectives:

� Harmonized Standards: IEC 62040-1-1 and IEC 62040-2; IEC 60950 Third Edition

� EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltagelimits

93/68/EEC, Amending Directive 73/23/EEC89/336/EEC, Council Directive relating to electromagnetic compatibility92/31/EEC, Amending Directive 89/336/EEC relating to EMC

The EC Declaration of Conformity is available upon request for products with a CE mark. For copies ofthe EC Declaration of Conformity, contact:

Loren SchideNCR1611 South Main StreetDayton, OH 45479Phone: 937-445-5305

Page 4: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Special SymbolsThe following are examples of symbols used on the UPS to alert you to importantinformation:

Risk of Electric ShockDo Not Open Cover

CAUTION

CAUTION To reduce the risk of electric shock,Do not remove cover (or back)

No user-serviceable parts insideRefer servicing to the factory

RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and theassociated warning should be observed.

CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manualfor additional information, such as important operating and maintenance instructions.

SAFETY EARTHING TERMINAL - Indicates the primary safety ground.

LOAD ON/OFF - Press the button with this symbol to energize the output receptacles(µ indicator illuminates) or to de-energize the output receptacles (µ indicator isoff).

RJ-45 RECEPTACLE - For 230V units only: this receptacle provides network interfaceconnections. Do not plug telephone or telecommunications equipment into thisreceptacle.

This symbol indicates that you should not discard the UPS or the UPS batteries in thetrash. The UPS may contain sealed, lead-acid batteries. Batteries must be recycled.

Page 5: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

iNCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Table of Contents

1 NCR 4072 – One of the Best! 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2 Safety Warnings 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 Installation 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Inspecting the Equipment 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS Internal Battery Connection 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Installing the UPS 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS Rear Panels 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4 Operation 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Turning the UPS On 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Starting the UPS on Battery 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Turning the UPS Off 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Standby Mode 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS Front Panel 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Initiating the Self-Test 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5 Additional UPS Features 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Voltage Configuration 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Communication Options 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .USB Port 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .DB-9 Communication Port 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Network Transient Protector 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6 UPS Maintenance 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .UPS and Battery Care 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Storing the UPS and Batteries 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Replacing Batteries 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Testing New Batteries 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Recycling the Used Battery 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 6: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Table of Contents

ii NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

7 Specifications 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8 Troubleshooting 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Audible Alarms and UPS Conditions 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Silencing an Audible Alarm 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Site Wiring Fault (120V Models Only) 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service and Support 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 7: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

1NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Chapter 1 NCR 4072 – One of the Best!

The NCR 4072 uninterruptible power system (UPS) protects yoursensitive electronic equipment from basic power problems such as powerfailures, power sags, power surges, brownouts, and line noise.

Power outages can occur when you least expect it and power quality canbe erratic. These power problems have the potential to corrupt criticaldata, destroy unsaved work sessions, and damage hardware — causinghours of lost productivity and expensive repairs.

With the NCR 4072 UPS, you can safely eliminate the effects of powerdisturbances and guard the integrity of your equipment. The NCR 4072UPS’s flexibility to handle an array of network devices makes it theperfect choice to protect your LANs, servers, workstations, and otherelectrical equipment.

Figure 1. The NCR 4072 UPS

Page 8: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

NCR 4072 – One of the Best!

2 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Providing outstanding performance and reliability, the NCR 4072 UPS’sunique benefits include the following:

� Battery Save technology doubles battery service life, optimizesrecharge time, and provides a warning before the end of usefulbattery life.

� Buck and Boost voltage regulation ensures consistent voltage to yourload by correcting voltage fluctuations.

� Hot-swappable batteries simplify maintenance by allowing you toreplace batteries safely without powering down the critical load.

� Start-on-battery capability allows you to power up the UPS even ifutility power is not available.

� Two standard communication options with a USB port and DB-9 serialport.

� Network Transient Protector guards your network communicationsequipment from surges. Low voltage models can also protectmodems, fax machines, or other telecommunications equipment.

� The NCR 4072 UPS is backed by worldwide agency approvals.

Page 9: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

3NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Chapter 2 Safety Warnings

Read the following precautions before you install the UPS.

IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONS

This manual contains important instructions that you should follow duringinstallation and maintenance of the UPS and batteries. Please read allinstructions before operating the equipment and save this manual for futurereference.

DANGERThis UPS contains LETHAL VOLTAGES. All repairs and service should beperformed by AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USERSERVICEABLE PARTS inside the UPS.

WARN ING� This UPS contains its own energy source (batteries). The output receptaclesmay carry live voltage even when the UPS is not connected to an AC supply.

� For 220–240V models, the output receptacles may remain electrically live. Ifthe input power source in your application is wired line-to-neutral (as inmost European applications), the voltage to the output receptacles is 0V.With line-to-line input wiring, the voltage to the output receptacles is110–120V (measured from line-to-ground or line-to-neutral, depending onthe UPS wiring).

� Do not remove or unplug the input cord when the UPS is turned on. Thisremoves the safety ground from the UPS and the equipment connected tothe UPS.

� To reduce the risk of fire or electric shock, install this UPS in a temperatureand humidity controlled, indoor environment, free of conductivecontaminants. Ambient temperature must not exceed 40�C (104�F). Do notoperate near water or excessive humidity (95% max).

� To comply with international standards and wiring regulations, the totalequipment connected to the output of this UPS must not have an earthleakage current greater than 1.5 milliamperes.

Page 10: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

4 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

CAUT ION� The wall outlet must be within 2 meters of the equipment and accessible tothe operator.

� Batteries can present a risk of electrical shock or burn from highshort-circuit current. The following precautions should be observed:1) Remove watches, rings, or other metal objects; 2) Use tools with insulatedhandles; 3) Do not lay tools or metal parts on top of batteries; 4) Disconnectcharging source prior to connecting or disconnecting battery terminals.

� Proper disposal of batteries is required. Refer to your local codes fordisposal requirements.

� Never dispose of batteries in a fire. Batteries may explode when exposed toflame.

� Never open or mutilate batteries. Released electrolyte is harmful to the skinand eyes, and may be extremely toxic.

� Replace batteries with the same number and type of batteries as originallyinstalled in the UPS.

Page 11: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

5NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

SikkerhedsanvisningerVIGTIGE SIKKERHEDSANVISNINGERGEM DISSE ANVISNINGERDENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGESIKKERHEDSANVISNINGER

FAREDenne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer ogvedligeholdelse bør kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen afUPS’ens indvendige dele kan repareres af brugeren.

ADVARSE L !� Denne UPS indeholder egen energiforsyning (batterier). Udgangsnetstikkenekan lede strøm, selv når UPS’en ikke er tilsat en AC-energikilde.

� Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en ertændt. Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der ersat til.

� Installér denne UPS i et temperatur- og fugtighedskontrolleretindendørsmiljø, frit for ledende forureningsstoffer for at formindske risikoenfor brand og elektrisk stød. Rumtemperaturen må ikke overstige 40�C.UPS’en bør ikke betjenes nær vand eller høj fugtighed (maksimalt 95%).

� I overensstemmelse med internationale normer og bestemmelser forel-installation må det udstyr, der er forbundet til udgangen af denne UPS,tilsammen ikke overskride en jordafdelingsspænding på mere end 1,5milliampere.

ADVARSE L� Stikkontakten skal være højest 2 meter fra udstyret og skal være tilgængeligttil operatøren.

� Batterier kan udgøre en fare for elektrisk stød eller forbrændingerforårsaget af høj kortslutningsspænding. De korrekte forholdsregler børoverholdes.

� Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokaleregler for bortskaffelsesprocedurer.

� Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kaneksplodere ved åben ild.

� Batterierne bør aldrig åbnes eller skilles ad. Udløst elektrolyt er skadeligt forhud og øjne og kan være yderst giftigt.

Page 12: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

6 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Belangrijke VeiligheidsinstructiesBELANGRIJKE VEILIGHEIDSINSTRUCTIESBEWAAR DEZE INSTRUCTIESDEZE HANDLEIDING BEVAT BELANGRIJKEVEILIGHEIDSINSTRUCTIES

GEVAARDeze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparatiesen onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL teworden uitgevoerd. Er bevinden zich GEEN ONDERDELEN in de UPS die DOORDE GEBRUIKER kunnen worden GEREPAREERD.

WAARSCHUWING� Deze UPS bevat zijn eigen energiebron (batterijen). De uitgangsaansluitingenkunnen onder spanning staan wanneer de UPS niet op een wisselstroomvoeding is aangesloten.

� Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er nietuit terwijl de UPS aan staat. Hierdoor zou de UPS en uw aangeslotenapparatuur geen aardebeveiliging meer hebben.

� Teneinde de kans op brand of elektrische schok te verminderen dient dezeUPS in een gebouw met temperatuur- en vochtigheidregeling te wordengeïnstalleerd, waar geen geleidende verontreinigingen aanwezig zijn. Deomgevingstemperatuur mag 40�C niet overschrijden. Niet gebruiken in debuurt van water of bij zeer hoge vochtigheid (max. 95%).

� Om aan de internationale normen en bedradingsvoorschriften te voldoenmag de gehele apparatuur die op de uitgang van deze UPS is aangesloten,geen aardlekstroom van meer dan 1,5 milliampère hebben.

OPGE L ET� De hoofdvoedingcontactdoos moet zich op minder dan 2 meter vandeapparatuur bevinden en makkelijk bereikbaar zijn voor de gebruiker.

� Batterijen kunnen gevaar voor elektrische schok of brandwondenveroorzaken als gevolg van un hoge kortsluitstroom. Volg de desbetreffendeaanwijzingen op.

� De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeghiervoor uw plaatselijke voorschriften.

� Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.� Nooit batterijen openen of verminken. Vrijkomend elektrolyt is schadelijkvoor de huid en ogen, en kan uiterst giftig zijn.

Page 13: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

7NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Tarkeita Turvaohjeita

TÄRKEITÄ TURVAOHJEITA - SUOMISÄILYTÄ NÄMÄ OHJEETTÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA

VAARATämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset jahuollot on jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS eisisällä MITÄÄN KÄYTTÄJÄN HUOLLETTAVIA OSIA.

VARO I TUS� Tämä UPS sisältää oman energialähteen (akuston). Ulostuloliittimissä voi ollajännite, kun UPS ei ole liitettynä verkkojännitteeseen.

� Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaaturvamaadoituksen UPS-laitteesta ja siihen liitetystä laitteistosta.

� Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin,joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtaviaepäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40��C. Älä käytä lähellävettä ja vältä kosteita tiloja (95 % maksimi).

� Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämänUPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä1,5 milliampeeria (mA).

VARO� Päävirtapistokkeen täytyy olla 2 m:n säteellä laitteistosta ja käyttäjänsaatavilla. UPS-laitteen virtakytkin ei eristä sisäosia virran saannilta.

� Akusto saattaa aiheuttaa sähköiskun tai syttyä tuleen, jos akusto kytketäänoikosulkuun. Noudata asianmukaisia ohjeita.

� Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisiamääräyksiä.

� Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.� Älä avaa tai riko akkua. Paljastunut elektrolyytti on vahingollinen iholle jasilmille ja voi olla erittäin myrkyllistä.

Page 14: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

8 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Consignes de sécuritéCONSIGNES DE SÉCURITÉ IMPORTANTESCONSERVER CES INSTRUCTIONSCE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉIMPORTANTES

DANGER !Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretienet de réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNELQUALIFIÉ AGRÉÉ. AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouvedans l’onduleur.

AVERT I S S EMENT !� Cet onduleur renferme sa propre source d’énergie (batteries). Les prises desortie peuvent être sous tension même lorsque l’onduleur n’est pas branchésur le secteur.

� Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tensionsous peine de supprimer la mise à la terre de l’onduleur et du matérielconnecté.

� Pour réduire les risques d’incendie et de décharge électrique, installerl’onduleur uniquement à l’intérieur, dans un lieu dépourvu de matériauxconducteurs, où la température et l’humidité ambiantes sont contrôlées. Latempérature ambiante ne doit pas dépasser 40 �C. Ne pas utiliser àproximité d’eau ou dans une atmosphère excessivement humide (95 % max).

� Afin d’être conforme aux normes et règlements internationaux de câblage,le courant de fuite à la terre de la totalité du matériel branché sur la sortiede l’onduleur ne doit pas dépasser 1,5 mA.

ATTENT ION !� La prise principale secteur doit se trouver à moins de 2 mètres du matérielet être accessible à l’utilisateur.

� Les batteries peuvent présenter un risque de décharge électrique ou debrûlure par des courts-circuits de haute intensité. Prendre les précautionsnécessaires.

� Une mise au rebut réglementaire des batteries est obligatoire. Consulter lesrèglements en vigueur dans votre localité.

� Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de lesfaire exploser.

� Ne jamais ouvrir ou mutiler des batteries. L’électrolyte qui s’en échappe estnuisible à la peau et aux yeux et peut s’avérer extrêmement toxique.

Page 15: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

9NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

SicherheitswarnungenWICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAHREN.DIESES HANDBUCH ENTHÄLT WICHTIGESICHERHEITSANWEISUNGEN.

WARNUNGDie USV führt lebensgefährliche Spannungen. Alle Reparatur- undWartungsarbeiten sollten nur von Kundendienstfachleuten durchgeführtwerden. Die USV enthält keine vom Benutzer zu wartenden Komponente

ACHTUNG� Diese USV ist mit einer eigenen Energiequelle (Batterie) ausgestattet. An denAusgangssteckdosen kann auch dann Spannung anliegen, wenn die USVnicht an einer Wechselspannungsquelle angeschlossen ist.

� Das Eingangskabel nicht entfernen oder abziehen, während die USVeingeschaltet ist, weil hierdurch die Sicherheitserdung von der USV und dendaran angeschlossenen Geräten entfernt wird.

� Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur inGebäuden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren, indenen keine leitenden Schmutzstoffen vorhanden sind. DieUmgebungstemperatur darf 40�C nicht übersteigen. Die USV nicht in derNähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %)betreiben.

� Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfendie an den Ausgang dieser USV angeschlossenen Geräte zusammen einenErdschlußstrom von insgesamt 1,5 Milliampere nicht überschreiten.

VORS I CHT !� Batterien können aufgrund des hohen Kurzschlußstroms Elektroschocksoder Verbrennungen verursachen. Folgende Vorkehrungen sollten getroffenwerden, wenn Sie mit der Battery arbeiten: 1) Entfernen Sie Uhren, Ringund andere metallische Objekte; 2) Verwenden Sie Werkzeug mit isoliertenGriffen.

� Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind dieörtlichen Bestimmungen zu beachten.

� Batterien niemals verbrennen, da sie explodieren können.� Öffnen oder beschädigen Sie nicht die Batterien, ausfließendes Elektrolyt istschädlich für Haut und Augen.

� Falls Sie die Batterien austauschen, verwenden Sie bitte ausschließlich diegleiche Anzahl und die Batterietypen.

Page 16: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

10 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

ÐñïåéäïðïéÞóåéò ÁóöÜëåéáòÓÇÌÁÍÔÉÊÅÓ ÏÄÇÃÉÅÓ ÁÓÖÁËÅÉÁÓÖÕËÁÎÔÅ ÁÕÔÅÓ ÔÉÓ ÏÄÇÃÉÅÓÔÏ ÐÁÑÏÍ ÅÃ×ÅÉÑÉÄÉÏ ÐÅÑÉÅ×ÅÉ ÓÇÌÁÍÔÉÊÅÓ ÏÄÇÃÉÅÓÁÓÖÁËÅÉÁÓ

Ê ÉÍÄÕÍÏÓÁõôü ôï UPS ðåñéÝ÷åé ÈÁÍÁÔÇÖÏÑÁ ÔÁÓÇ. ¼ëåò ïé åðéóêåõÝò êáé ïéóõíôçñÞóåéò ðñÝðåé íá ãßíïíôáé ÌÏÍÏ ÁÐÏ ÅÎÏÕÓÉÏÄÏÔÇÌÅÍÏ ÃÉÁÔÇ ÓÕÍÔÇÑÇÓÇ ÐÑÏÓÙÐÉÊÏ. Ôï UPS ÄÅÍ ÐÅÑÉÅ×ÅÉ ÊÁÍÅÍÁÅÎÁÑÔÇÌÁ ÐÏÕ ÍÁ ÌÐÏÑÅÉ ÍÁ ÅÐÉÓÊÅÕÁÓÔÅÉ ÁÐÏ ÔÏ ×ÑÇÓÔÇ.

ÐÑÏÅ ÉÄÏÐÏ ÉÇÓÇÊ� Ôï óõãêåêñéìÝíï UPS ðåñéÝ÷åé ôç äéêÞ ôïõ ðçãÞ åíÝñãåéáò(óõóóùñåõôÝò). Ïé ñåõìáôïäüôåò åîüäïõ ìðïñåß íá Ý÷ïõí åíåñãü ôÜóçáêüìç êáé üôáí ôï UPS äåí åßíáé óõíäåäåìÝíï óå ðçãÞåíáëëáóóüìåíïõ ñåýìáôïò (AC).

� Ìçí âãÜæåôå áðü ôçí ðñßæá ôï êáëþäéï ôñïöïäïóßáò üôáí ôï UPS åßíáéáíïé÷ôü. Ì’ áõôü ôïí ôñüðï áöáéñåßôå ôç ãåßùóç áóöáëåßáò áðü ôïUPS êáé áðü ôïí åîïðëéóìü ðïõ åßíáé óõíäåäåìÝíïò ìå ôï UPS.

� Ãéá íá ìåéþóåôå ôïí êßíäõíï ðõñêáãéÜò Þ çëåêôñïðëçîßáò,åãêáôáóôÞóôå ôï óõãêåêñéìÝíï UPS óå åóùôåñéêü ÷þñï ìååëåã÷üìåíç èåñìïêñáóßá êáé õãñáóßá, ï ïðïßïò íá ìçí ðåñéÝ÷åéáãþãéìá õëéêÜ. Ç èåñìïêñáóßá ðåñéâÜëëïíôïò äåí ðñÝðåé íáîåðåñíÜåé ôïõò 40� C. Ìç ÷ñçóéìïðïéåßôå ôï UPS êïíôÜ óå íåñü ÞõðåñâïëéêÞ õãñáóßá (ìÝãéóôç ôéìÞ: 95%).

� Ãéá íá óõìöùíåß ìå ôá äéåèíÞ ðñüôõðá êáé ôïõò êáíïíéóìïýòêáëùäßùóçò, ôï ñåýìá äéáññïÞò ðñïò ôç ãç ïëüêëçñïõ ôïõ åîïðëéóìïý,ðïõ åßíáé óõíäåäåìÝíïò ìå ôçí Ýîïäï ôïõ óõãêåêñéìÝíïõ UPS, äåíðñÝðåé íá åßíáé ìåãáëýôåñï áðü 1,5 mA.

ÐÑÏÓÏ×Ç� Ïé óõóóùñåõôÝò ìðïñåß íá ðñïêáëÝóïõí çëåêôñïðëçîßá Þ Ýãêáõìááðü õøçëü ñåýìá âñá÷õêõêëþìáôïò. ËáìâÜíåôå ôéò êáôÜëëçëåòðñïöõëÜîåéò.

� Áðáéôåßôáé óùóôÞ äéÜèåóç ôùí óõóóùñåõôþí. Äåßôå ôïõò ôïðéêïýòêáíïíéóìïýò ðïõ áöïñïýí ôéò áðáéôÞóåéò äéÜèåóÞò ôïõò.

� ÐïôÝ ìçí ðåôÜôå ôïõò óõóóùñåõôÝò óôç öùôéÜ, ãéáôß ìðïñåß íáåêñáãïýí.

Page 17: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

11NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Avvisi di sicurezza

IMPORTANTI ISTRUZIONI DI SICUREZZACONSERVARE QUESTE ISTRUZIONIQUESTO MANUALE CONTIENE IMPORTANTI ISTRUZIONIDI SICUREZZA

PER I COLOla TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte leoperazioni di riparazione e di manutenzione devono essere effettuateESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO. All’interno delgruppo statico di continuità NON vi sono PARTI RIPARABILI DALL’UTENTE.

AVVERTENZA� Questo gruppo statico di continuità contiene una fonte di energia autonoma(le batterie). Le prese di uscita possono condurre tensione energizzataquando il gruppo statico di continuità non è collegato con una fonte dialimentazione a corrente alternata.

� Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico dicontinuità è acceso poichè in tal modo si disattiverebbe il collegamento aterra di sicurezza del gruppo statico di continuità e dell’apparecchiatura adesso collegata.

� Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppostatico di continuità in un ambiente interno a temperatura ed umiditàcontrollata, privo di agenti contaminanti conduttivi. La temperaturaambiente non deve superare i 40�C. Non utilizzare l’unità in prossimità diacqua o in presenza di umidità eccessiva (95% max).

� Per conformità con gli standard internazionali e con le norme in merito alcablaggio, tutta l’apparecchiatura collegata con l’uscita del gruppo statico dicontinuità non deve avere una corrente di dispersione di terra superiore a1,5 milliampere.

ATTENZ IONE� La presa di alimentazione principale non deve trovarsi a oltre 2 metridall’apparecchiatura e deve essere accessibile all’operatore.

� Le batterie possono presentare rischio di scossa elettrica o di ustioniprovocate da alta corrente dovuta a corto circuito. Osservare le appositeistruzioni.

� Le batterie devono essere smaltite in modo corretto. Per i requisiti dismaltimento fare riferimento alle disposizioni locali.

Page 18: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

12 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

� Non gettare mai le batterie nel fuoco poichè potrebbero esplodere seesposte alle fiamme.

� Mai aprire nè mutilare le batterie poichè l’elettrolita da esse rilasciato ènocivo alla cute e agli occhi e può essere altamente tossico.

Viktig SikkerhetsinformasionFARL IG

Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og servicemå kun utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKEUTFØRE SERVICE PÅ NOEN AV DELENE i UPS’en.

FARL IG� Denne UPS’en har en egen energikilde (batterier). Stikkontaktene kan værestrømførende selv om UPS’en ikke er tilsluttet en vekselstrømforsyning.

� Strømforsyningskabelen må ikke fjernes eller trekkes ut når UPS’en er på,slik at ikke sikkerhetsjordingen fjernes fra UPS’en og det utstyret som erforbundet med den.

� For å redusere fare for brann eller elektriske støt, bør denne UPS’eninstalleres i et innendørs miljø med kontrollert temperatur og luftfuktighetsom er fritt for ledende, forurensende stoffer. Romtemperaturen må ikkeoverskride 40�C. Den må ikke brukes i nærheten av vann eller ved megethøy luftfuktighet (95% maks.).

� Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha ensterkere total lekkasjestrøm enn 1,5 milliampere for å være ioverensstemmelse med internasjonale standarder ogforkablingsbestemmelser.

FORS IKT IG� Stikkontakten må befinne seg innen 2 m fra utstyret og må være tilgjengeligfor operatøren.

� Batterier kan forårsake elektriske støt eller forbrenning på grunn av høykortslutningsstrøm. Følg instruksene.

� Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende kravom fjerning av batterier.

� Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes foråpen ild.

� Batterier må aldri åpnes eller ødelegges. Frigjorte elektrolytter er skadeligefor hud og øyne og kan være ekstremt giftige.

Page 19: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

13NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Regulamentos de SegurançaINSTRUÇÕES DE SEGURANÇA IMPORTANTESGUARDE ESTAS INSTRUÇÕESESTE MANUAL CONTÉM INSTRUÇÕES DE SEGURANÇAIMPORTANTES

CU IDADOA UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnicadevem ser executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICAAUTORIZADO. Não há nenhuma PEÇA QUE POSSA SER REPARADA PELOUSUÁRIO dentro da UPS.

ADVERTÊNC IA� Esta UPS contém sua própria fonte de energia (baterias). Os receptáculos desaída podem conter voltagem ativa quando a UPS não se encontraconectada a uma fonte de alimentação de corrente alternada.

� Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada.Isto removerá o aterramento de segurança da UPS e do equipamentoconectado.

� Para reduzir o risco de incêndios ou choques elétricos, instale a UPS emambiente interno com temperatura e umidade controladas e livres decontaminadores condutíveis. A temperatura ambiente não deve exceder40�C. Não opere próximo a água ou em umidade excessiva (máx: 95%).

� Para estar de acordo com os padrões internacionais e os regulamentos defiação, o equipamento total conectado à saída desta UPS não deve ter umacorrente de fuga à terra maior que 1,5 miliampères.

PER IGO� O soquete de alimentação principal deve estar à no máximo dois metros doequipamento e acessível ao operador.

� As baterias podem apresentar o risco de choque elétrico, ou queimadurasprovenientes de alta corrente de curto-circuito. Observe as instruçõesadequadas.

� Siga as instruções apropriadas ao desfazer-se das baterias. Consulte oscódigos do local para maiores informações sobre os regulamentos dedescarte de produtos.

� Nunca jogue as baterias no fogo, porque há risco de explosão.� Nunca abra ou danifique as baterias. O eletrólito liberado é prejudicial àpele e aos olhos e pode ser extremamente tóxico.

Page 20: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

14 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Предупреждения по мерам безопасностиВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИСОХРАНИТЕ ЭТИ УКАЗАНИЯДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ УКАЗАНИЯ ПОМЕРАМ БЕЗОПАСНОСТИ

ОПАСНОВ данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ.Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКОУПОЛНОМОЧЕННЫМОБСЛУЖИВАЮЩИМПЕРСОНАЛОМ.Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ.

ПРЕДУПРЕЖДЕНИЕ� Данный ИБП содержит собственные источники энергии

(аккумуляторы). На выходных розетках может иметься напряжение,даже когда ИБП не подключен к сети переменного тока.

� Не отсоединяйте сетевой шнур и не извлекайте его вилку из розеткипри включенном ИБП. При этом защитное заземление отключаетсяот ИБП и от оборудования, подключенного к ИПБ.

� Для снижения опасности пожара или поражения электрическимтоком устанавливайте ИБП в закрытом помещении сконтролируемыми температурой и влажностью, в которомотсутствуют проводящие загрязняющие вещества. Температураокружающего воздуха не должна превышать 40�С. Неэксплуатируйте устройство около воды или в местах с повышеннойвлажностью (макс. 95%).

� Для обеспечения соблюдения требований международных стандартови требований к разводке электрических цепей, суммарная величинатока утечки на землю всего оборудования, подключенного к выходуИБП, не должна превышать 1,5 миллиампера.

ОСТОРОЖНО� Аккумуляторы могут вызвать опасность поражения электрическим

током или ожога от тока короткого замыкания. Соблюдайтесоответствующие меры предосторожности.

� Необходимо соблюдать правила утилизации аккумуляторов.Обратитесь к местным нормативным актам за информацией отребованиях к утилизации.

� Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могутвзорваться под воздействием огня.

Page 21: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

15NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Advertencias de SeguridadINSTRUCCIONES DE SEGURIDAD IMPORTANTESGUARDE ESTAS INSTRUCCIONESESTE MANUAL CONTIENE INSTRUCCIONES DESEGURIDAD IMPORTANTES

PE L I GROEste SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el serviciotécnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIOTÉCNICO AUTORIZADO. No hay NINGUNA PARTE QUE EL USUARIO PUEDAREPARAR dentro del SIE.

ADVERTENC IA� Este SIE contiene su propia fuente de energía (las baterías). Los receptáculosde salida pueden transmitir corriente eléctrica aun cuando el SIE no estéconectado a un suministro de corriente alterna (c.a.).

� No retire o desenchufe el cable de entrada mientras el SIE se encuentreencendido. Esto suprime la descarga a tierra de seguridad del SIE y de losequipos conectados al SIE.

� Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE enun lugar cubierto, con temperatura y humedad controladas, libre decontaminantes conductores. La temperatura ambiente no debe exceder los40�C. No trabaje cerca del agua o con humedad excesiva (95% máximo).

� Para cumplir con los estándares internacionales y las normas de instalación,la totalidad de los equipos conectados a la salida de este SIE no debe teneruna intensidad de pérdida a tierra superior a los 1,5 miliamperios.

PRECAUC IÓN� El tomacorriente de pared debe encontrarse dentro de los 2 metros dedistancia del equipo y ser accesible para el operador.

� Las baterías pueden presentar un riesgo de descargas eléctricas o dequemaduras debido a la alta corriente de cortocircuito. Preste atención a lasinstrucciones correspondientes.

� Es necesario desechar las baterías de un modo adecuado. Consulte lasnormas locales para conocer los requisitos pertinentes.

� Nunca deseche las baterías en el fuego. Las baterías pueden explotar si selas expone a la llama.

� Nunca abra o mutile las baterías. El electrolito liberado es peligroso para lapiel y los ojos, y puede ser extremadamente tóxico.

Page 22: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Safety Warnings

16 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Säkerhetsföreskrifter

VIKTIGA SÄKERHETSFÖRESKRIFTERSPARA DESSA FÖRESKRIFTERDENNA BRUKSANVISNING INNEHÅLLER VIKTIGASÄKERHETSFÖRESKRIFTER

FARADenna UPS-enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERADSERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar somANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS-enheten.

VARN ING� Denna UPS-enhet har en egen energikälla (batterier). De utgåendekontakterna kan vara strömförande när UPS-enheten inte är ansluten till enväxelströmkälla.

� Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bortskyddsjordningen från både UPS-enheten och den anslutna utrustningen.

� Minska risken för brand eller elektriska stötar genom att installera dennaUPS-enhet inomhus, där temperatur och luftfuktighet är kontrollerade ochdär inga ledande föroreningar förekommer. Omgivande temperatur får ejöverstiga 40�C. Använd inte utrustningen nära vatten eller vid högluftfuktighet (max 95 %).

� För att överensstämma med internationell standard ochinstallationsföreskrifter får inte den totala utrustning som anslutits tilluttagen på denna UPS-enhet ha läcksström som överstiger 1,5 milliampere.

V IKT IGT� Huvudkontakten måste vara högst 2 meter från utrustningen och inomräckhåll för användaren.

� Batterierna kan ge elektriska stötar eller brännskador från högkortslutningsström. Följ tillämpliga anvisningar.

� Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning.� Använda batterier får aldrig brännas upp. De kan explodera.� Öppna aldrig batterierna eller ta isär dem. Utsläppt elektrolyt är skadlig förhud och ögon och kan vara mycket giftig.

Page 23: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

17NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Chapter 3 Installation

This section explains:

� Equipment inspection

� UPS installation

� UPS rear panels

Inspecting the EquipmentIf any equipment has been damaged during shipment, keep the shippingcartons and packing materials for the carrier or place of purchase andfile a claim for shipping damage. If you discover damage afteracceptance, file a claim for concealed damage.

To file a claim for shipping damage or concealed damage: 1) File withthe carrier within 15 days of receipt of the equipment; 2) Send a copy ofthe damage claim within 15 days to Customer Service.

NOTE Check the battery recharge date on the shipping carton label. Ifthe date has expired and the batteries were never recharged, do not usethe UPS. Contact Customer Service.

Page 24: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Installation

18 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

UPS Internal Battery ConnectionUse the following procedure to ensure proper battery operation beforeinstalling the UPS:

1. Verify that the UPS is off and unplugged.

2. Remove the UPS front panel.

Figure 2. Removing the Front Panel

3. Slide up and remove the metal battery cover.

1400 VA500–1000 VA

Figure 3. Removing the Battery Cover

Page 25: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Installation

19NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

4. Remove the protective label from the internal batteryconnector.

Figure 4. Removing the Protective Label

5. Connect the red wire to the ( ) battery connector.

NOTE A small amount of arcing may occur when connecting thebatteries. This is normal and does not damage the unit or present anysafety concern.

Figure 5. Connecting the Red Wire

6. Reinstall the metal battery cover.

Figure 6. Reinstalling the Battery Cover

Page 26: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Installation

20 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

7. Reinstall the UPS front panel.

Figure 7. Reinstalling the Front Panel

8. If the UPS requires any type of transportation in the future,disconnect the UPS internal battery connector using the abovesteps in reverse order.

Installing the UPSThe following steps explain how to install the UPS. Figure 8 shows atypical installation only. See “UPS Rear Panels” on page 22 for the rearpanel of each model.

1. If you are installing power management software, connect yourcomputer to the USB port or UPS communication port using thesupplied cable (see page 30).

NOTE If you need to change the factory-set defaults for the output voltageor input voltage range, see “Voltage Configuration” on page 29 beforeinstalling the UPS.

2. On 230V models, plug the detachable power cord into the inputconnector on the UPS rear panel.

Page 27: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Installation

21NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Press the ON button(on the front panel)

1Connect communicationcable from computer toUPS (optional)

Connect UPS to power2 & 3

4Connect equipment to UPS

5

This is a typical setup;your setup may vary.

NOTE

Figure 8. Typical UPS Installation (120V Model Shown)

3. Plug the UPS power cord into a power outlet.

Verify that the circuit has an upstream overcurrent protection of15A for 120V models or 10A for 230V models.

4. Plug the equipment to be protected into the UPS outputreceptacles.

NOTE DO NOT protect laser printers with the UPS because of theexceptionally high power requirements of the heating elements.

5. Press and hold the button until you hear the UPS beep(approximately two seconds).

Theµ indicator illuminates indicating that power is availablefrom the UPS output receptacles. The UPS conducts a self-testand enters Normal mode.

If the alarm beeps or a UPS alarm indicator stays on, see Table 9on page 44.

NOTE The batteries charge to 90% capacity in approximately 3 hours.However, it is recommended that the batteries charge for 6 to 24 hoursafter installation or long-term storage.

Page 28: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Installation

22 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

UPS Rear PanelsThis section shows the rear panels of the NCR 4072 UPS models.

Communication Port

Four 5-15 Receptacles

6-ft Power Cordwith 5-15 Plug

DIP Switches

Network TransientProtector

Site Wiring FaultIndicator

USB Port

Input OvercurrentProtector

Figure 9. 500 VA, 120V Rear Panel

Four 5-15 Receptacles

6-ft Power Cordwith 5-15 Plug

Network TransientProtector

Fan

Communication PortDIP Switches

Site Wiring FaultIndicator

USB Port

Input OvercurrentProtector

Figure 10. 750 VA, 120V Rear Panel

Page 29: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Installation

23NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Network TransientProtector

Two 5-15 Receptacles

Four 5-15 Receptacles

6-ft Power Cordwith 5-15 Plug

Fan

Communication PortDIP Switches

Site Wiring FaultIndicator

USB Port

Input OvercurrentProtector

Figure 11. 1000 VA, 120V Rear Panel

Six 5-15 Receptacles

6-ft Power Cordwith 5-15 Plug

Network TransientProtector

Fan

Communication PortDIP Switches

Site Wiring FaultIndicator

USB Port

Input OvercurrentProtector

Figure 12. 1400 VA, 120V Rear Panel

Page 30: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Installation

24 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Communication Port

Four 10A, IEC-320Receptacles

DIP Switches

Network TransientProtector

10A, IEC-320Input Connector

USB Port

Figure 13. 500 VA, 230V Rear Panel

Four 10A, IEC-320Receptacles

DIP SwitchesNetwork TransientProtector

10A, IEC-320Input Connector

Fan

Communication PortUSB Port

Figure 14. 750 VA, 230V Rear Panel

Page 31: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Installation

25NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Two 10A, IEC-320Receptacles

Four 10A, IEC-320Receptacles

10A, IEC-320Input Connector

Fan

DIP SwitchesNetwork TransientProtector

Communication PortUSB Port

Figure 15. 1000 VA, 230V Rear Panel

Six 10A, IEC-320Receptacles

Fan

10A, IEC-320InputConnector

DIP SwitchesNetwork TransientProtector

Communication PortUSB Port

Figure 16. 1400 VA, 230V Rear Panel

Page 32: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Installation

26 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Page 33: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

27NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Chapter 4 Operation

This section describes:

� Turning the UPS on and off

� Starting the UPS on battery

� Standby mode

� The UPS front panel and indicators

� Initiating the self-test

Turning the UPS OnAfter the UPS is connected to a power outlet, the UPS enters Standbymode. To turn on the UPS, press and hold the button until you hearthe UPS beep (approximately two seconds). After the UPS is turned on, itconducts a self-test and enters Normal mode. Theµ indicatorilluminates indicating that power is available from the UPS outputreceptacles.

Starting the UPS on Battery

NOTE The UPS does not auto-detect the input frequency when startingon battery; the default is the last frequency used by the UPS.

To turn on the UPS without using utility power, press and hold thebutton for two seconds. The UPS supplies power to your equipment

and goes into Battery mode. When the UPS starts on battery, it does notconduct a self-test to conserve battery power.

Turning the UPS OffTo turn off the UPS, press and hold the button for two seconds andthen unplug the UPS from the power outlet. If you do not unplug theUPS, it remains in Standby mode.

Page 34: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Operation

28 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Standby ModeWhen the UPS is turned off and remains plugged into a power outlet, theUPS is in Standby mode. All indicators are off and power is not availableto your equipment. The battery recharges when necessary.

NOTE For 220–240V models, the output receptacles may remainelectrically live (up to 110–120V). Unplug the UPS to ensure power is notavailable to the output receptacles.

UPS Front PanelThe UPS front panel indicates the UPS status and also identifies potentialpower problems. Figure 17 shows the UPS front panel indicators andcontrols.

On/Off Button

Test/Alarm Reset Button

Power On Indicator (Green)

On Battery Indicator (Yellow)

Overload Indicator (Red)

Service Indicator (Red)

Figure 17. UPS Front Panel

If the alarm beeps or a UPS alarm indicator stays on, see Table 9 onpage 44 to identify and correct the problem.

Initiating the Self-TestNOTE The batteries must be fully charged and the UPS must not be inBattery mode to perform the self-test.

Press and hold the button for three seconds to initiate the self-test. Ifthe UPS finds a problem, an LED indicates where the problem is. Formore information, see “Troubleshooting” on page 43.

Page 35: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

29NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Chapter 5 Additional UPS Features

This section describes:

� Changing the voltage configuration

� Using the USB or DB-9 communication port

� The Network Transient Protector

Voltage ConfigurationThe DIP switches on the rear panel of each unit (see Figure 18) are usedto configure the output voltage and input voltage range.

1. The UPS must be completely shutdown.

To turn off the UPS, press and hold the button for twoseconds and then unplug the UPS from the power outlet.

2. Set the DIP switches according to the configurations in Table 1.

3. Plug the UPS power cord into a power outlet.

4. Press and hold the button until you hear the UPS beep(approximately two seconds) to turn the UPS on.

UPS Rear Panel

ON

OFF2 1

Figure 18. DIP Switches

Page 36: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Additional UPS Features

30 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Table 1. DIP Switch Settings120V Models

Output Voltage Input Voltage Range DIP Switch 1 DIP Switch 2

110V 99V-116V ON OFF/ON

120V* 108V–127V* OFF OFF/ON

230V Models

Output Voltage Input Voltage Range DIP Switch 1 DIP Switch 2

220V 198V–233V ON OFF

230V* 207V–243V* OFF OFF/ON

240V 216V–254V ON ON

*Default position

Communication OptionsThe UPS is equipped with a USB and a DB-9 communication port. Eitherthe USB port or the DB-9 communication port may be used to monitorthe UPS; however, they cannot operate simultaneously.

USB PortThe UPS can communicate with a USB-compliant computer using powermanagement software. To establish communication between the UPS anda computer:

1. Connect the USB cable to the USB port on the UPS rear panel.

Connect the other end of the USB cable to the USB port onyour computer.

USB Port

Figure 19. The USB Port

2. Install the power management software.

Page 37: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Additional UPS Features

31NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

DB-9 Communication PortTo establish communication between the UPS and a computer, connectyour computer to the UPS communication port using the suppliedcommunication cable.

When the communication cable is installed, power management softwarecan exchange data with the UPS. The software polls the UPS for detailedinformation on the status of the power environment. If a poweremergency occurs, the software initiates the saving of all data and anorderly shutdown of the equipment.

The cable pins are identified in Figure 20 and the pin functions aredescribed in Table 2.

3

87 9

1

6

2 4 5

UPS Rear Panel

Figure 20. Communication Port

Table 2. Communication Port Pin AssignmentPinNumber

Signal Name Function Directionfrom the UPS

1 Low Batt Low Battery relay contact; 20 mA,30 Vdc contact rating

Out

2 TxD Transmit to external device Out

3 RxD Receive from external device In

4 DTR PnP (Plug and Play) from externaldevice (tied to Pin 6)

In

5 GND Signal common (tied to chassis) —

6 DSR To external device (tied to Pin 4) Out

7 — No Connection —

8 AC Fail AC Fail relay contact; 20 mA, 30 Vdccontact rating

Out

9 Power Source +V (8 to 24 volts DC power) Out

Page 38: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Additional UPS Features

32 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Network Transient ProtectorThe Network Transient Protector, shown in Figure 21, is located on therear panel and has jacks labeled IN and OUT. This feature accommodatesa single RJ-45 (10BaseT) network connector.

Low voltage models can also accommodate an RJ-11 telephoneconnector that provides protection for modems, fax machines, or othertelecommunications equipment. As with most modem equipment, it isnot advisable to use this jack in digital PBX (Private Branch Exchange)environments.

NOTE DO NOT connect any telephone or fax/modem equipment to the230V models; only network protection is available for 230V models.

1. Connect the input connector of the equipment you areprotecting to the jack labeled IN.

2. Connect the network or telephone cable (low voltage modelsonly) to the jack labeled OUT.

OUT IN

IN

OUT

NETWORK TRANSIENT PROTECTOR

Figure 21. Network Transient Protector

Page 39: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

33NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Chapter 6 UPS Maintenance

This section explains how to:

� Care for the UPS and batteries

� Replace the batteries

� Test new batteries

� Recycle used batteries

UPS and Battery CareFor the best preventive maintenance, keep the area around the UPSclean and dust-free. If the atmosphere is very dusty, clean the outside ofthe system with a vacuum cleaner.

For full battery life, keep the UPS at an ambient temperature of25°C (77°F).

NOTE If the UPS requires any type of transportation in the future,disconnect the UPS internal battery connector using the steps in “UPSInternal Battery Connection” on page 18 in reverse order.

Storing the UPS and BatteriesIf you store the UPS for a long period, recharge the battery every6 months by plugging the UPS into a power outlet. The batteries chargeto 90% capacity in approximately 3 hours. However, it is recommendedthat the batteries charge for 6 to 24 hours after long-term storage.

Check the battery recharge date on the shipping carton label. If the datehas expired and the batteries were never recharged, do not use the UPS.Contact Customer Service.

Page 40: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

UPSMaintenance

34 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Replacing BatteriesNOTE DO NOT DISCONNECT the batteries while the UPS is in Batterymode.

With the hot-swappable battery feature, UPS batteries can be replacedeasily without turning the UPS off or disconnecting the load.

If you prefer to remove input power to change the battery, press andhold the button for two seconds and then unplug the UPS.

Consider all warnings, cautions, and notes before replacing batteries.

WARN ING� Batteries can present a risk of electrical shock or burn from high shortcircuit current. The following precautions should be observed: 1) Removewatches, rings, or other metal objects; 2) Use tools with insulated handles;3) Do not lay tools or metal parts on top of batteries.

� ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring orconnectors. Attempting to alter wiring can cause injury.

� Replace batteries with the same number and type of batteries as originallyinstalled in the UPS.

CAUT IONPull the battery out onto a flat, stable surface. The battery is unsupported whenyou pull it out of the UPS.

Use the following steps to replace the batteries:

1. Remove the UPS front panel.

Page 41: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

UPSMaintenance

35NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

2. Slide up and remove the metal battery cover.

1400 VA500–1000 VA

3. 500 VA models. Disconnect the red battery cable and thendisconnect the black battery cable. Pull the battery out onto aflat, stable surface.

500 VA

Page 42: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

UPSMaintenance

36 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

4. 750/1000 VA models. Disconnect the red battery cable and thenpull the battery out onto a flat, stable surface. Disconnect theblack battery cable to the UPS as shown.

750/1000 VA

5. 1400 VA models. Disconnect the red battery cable and then pullthe battery out onto a flat, stable surface. Remove the batterytie around the black cable set and disconnect the black batterycable to the UPS as shown.

1400 VA

Page 43: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

UPSMaintenance

37NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

6. Replace the battery. See “Recycling the Used Battery” onpage 38 for proper disposal.

7. Connect the black battery cable to the new battery and thenconnect the red battery cable.

8. Reinstall the battery.

9. Reinstall the metal battery cover and front panel.

Testing New Batteries

NOTE Allow batteries to charge for 6 to 24 hours before testing.

Press and hold the button for three seconds to initiate a self-test.The 15-second test automatically distributes the load to the batteries andtests the battery’s performance. While the test is in progress, theindicators cycle through and the alarm sounds. When complete, the UPSreturns to Normal mode as indicated by theµ indicator.

If there is a problem with the battery, the alarm beeps, the + --- indicatorilluminates and the indicator flashes. Check the battery connectionsand be sure the battery is fully charged. Call Customer Service if theproblem persists.

Page 44: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

UPSMaintenance

38 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Recycling the Used BatteryContact your local recycling or hazardous waste center for informationon proper disposal of the used battery.

WARN ING� Do not dispose of the battery or batteries in a fire. Batteries may explode.Proper disposal of batteries is required. Refer to your local codes fordisposal requirements.

� Do not open or mutilate the battery or batteries. Released electrolyte isharmful to the skin and eyes. It may be toxic.

CAUT IONDo not discard the UPS or the UPS batteries in the trash. This product containssealed, lead-acid batteries and must be disposed of properly. For moreinformation, contact your local recycling or hazardous waste center.

Page 45: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

39NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Chapter 7 Specifications

This section provides the following specifications for the NCR 4072 UPSmodels:

� Dimensions and weights

� Electrical input and output

� Environmental and safety

� Battery

Table 3. Model List and Mechanical120V Models 230V Models

UPS Models 4072-0500-71944072-0750-71944072-1000-71944072-1400-7194

4072-0500-74944072-0750-74944072-1000-74944072-1400-7494

UPS Dimensions(WxHxD)

500 VA: 15.0 x 19.3 x 27.0 cm (5.9� x 7.6� x 10.6�)750–1000 VA: 15.0 x 19.3 x 33.5 cm (5.9� x 7.6� x 13.2�)1400 VA: 15.0 x 19.3 x 39.0 cm (5.9� x 7.6� x 15.4�)

UPS Weights 500 VA: 7.8 kg (17.2 lb)750 VA: 12.4 kg (27.3 lb)1000 VA: 12.6 kg (27.8 lb)1400 VA: 16.8 kg (37.0 lb)

Table 4. Electrical Input120V Models 230V Models

Nominal Voltage 110V, 120V selectable 220V, 230V, 240V selectable

Voltage Range ±20% for nominal voltage at full load

Nominal Frequency 45–65 Hz, 50/60 Hz auto-sensing

Efficiency (Normalmode)

95%

Noise Filtering Full-time EMI/RFI filtering

Overcurrent Protection Resettable input overcurrent protector N/A

Connections 6-ft, 5-15P power cord (90° angle) 10A, IEC-320 input connector

Page 46: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Specifications

40 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Table 5. Electrical Output120V Models 230V Models

Power Levels (rated atnominal inputs)

500 VA, 320W750 VA, 500W1000 VA, 670W1400 VA, 950W

Power Factor 500 VA, 0.64750–1400 VA, 0.67

Regulation (Normalmode)

-10% to +6% of nominal voltage

Regulation (Batterymode), NominalVoltage ±5%

Same as selected nominal inputvoltage

110V, 120V

Same as selected nominal inputvoltage

220V, 230V, 240V

Voltage Waveform Sine wave

Overcurrent Protection Inverter saturation current limited

Output Receptacles 500–750 VA: (4) 5-151000–1400 VA: (6) 5-15

500–750 VA: (4) 10A, IEC-3201000–1400 VA: (6) 10A, IEC-320

Table 6. Environmental and Safety120V Models 230V Models

OperatingTemperature

Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)Above 1,500 meters: 0°C to 35°C (32°F to 95°F)

Transit/StorageTemperature

-15°C to 55°C (5°F to 131°F)

Relative Humidity 5–95% noncondensing

Operating Altitude Up to 3,000 meters above sea level

Audible Noise Less than 45 dBA typical

Surge Suppression ANSI C62.41 Category A (formerly IEEE 587)

Safety Conformance UL 1778; UL 497A;CSA C22.2, No. 107.1

UL 1778, UL 497A (data line only);CSA C22.2, No. 107.1;

EN 50091-1-1 and IEC 60950

Safety Markings UL, cUL UL, cUL, CE, TÜV, C-Tick

EMC (Class B) FCC Part 15, ICES-003 EN 50091-2, FCC Part 15, ICES-003

Page 47: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Specifications

41NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Table 7. BatteryConfiguration 500 VA: (1) 12V, 9 Ah internal battery

750 VA: (2) 12V, 7 or 7.2 Ah internal batteries1000 VA: (2) 12V, 9 Ah internal batteries1400 VA: (3) 12V, 9 Ah internal batteries

Voltage 500 VA: 12 Vdc750–1000 VA: 24 Vdc1400 VA: 36 Vdc

Type Sealed, maintenance-free, valve-regulated, lead-acid

Charging Advanced charging for faster recovery; approximately 3 hours to 90% usablecapacity at nominal line and no supplementary power supply load

Monitoring Advanced monitoring for earlier failure detection and warning

Table 8. Battery Run Times (in Minutes)UPS Models by VA Ratings

Load (VA) Watts 500 750 1000 1400

200 128 17 38 41 58

300 192 11 27 28 41

500 320 5 14 15 28

600 402 9 10 19

750 503 6 8 14

900 603 6 10

1000 670 5 8

1200 804 6

1400 938 5

NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.

Page 48: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Specifications

42 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Page 49: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

43NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Chapter 8 Troubleshooting

This section explains:

� UPS alarms and conditions

� How to silence an alarm

� Site wiring fault on 120V models

� Service and support

Audible Alarms and UPS ConditionsThe UPS has an audible alarm feature to alert you of potential powerproblems. Use Table 9 to determine and resolve the UPS alarms andconditions.

On/Off Button

Test/Alarm Reset Button

Power On Indicator (Green)

On Battery Indicator (Yellow)

Overload Indicator (Red)

Service Indicator (Red)

Flashing

Unlit

Lit

Indicator Legend

Figure 22. UPS Front Panel

Page 50: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Troubleshooting

44 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Silencing an Audible AlarmBefore silencing an alarm, check the alarm condition and perform theapplicable action to resolve the condition (see Table 9). To silence thealarm for an existing fault, press the button. If UPS status changes,the alarm beeps, overriding the previous alarm silencing. The alarm doesnot silence if there is a UPS fault, low battery condition, or if the batteryneeds to be replaced.

Site Wiring Fault (120V Models Only)The Site Wiring Fault indicator on the UPS rear panel illuminates if theground wire connection does not exist or the line and neutral wires arereversed in the line receptacle. This indicator stays on until the conditionis resolved. Have a qualified electrician correct the wiring fault. The UPSoperates when the indicator is illuminated, but does not provide ratednoise and surge suppression.

Table 9. TroubleshootingAlarm or Condition Possible Cause Action

The indicator is not on;the UPS does not start.µ The power cord is not

connected correctly.Check the power cord connections.

the UPS does not start.

The UPS is in Standbymode.

Press and hold the button until you hear theUPS beep (approximately two seconds) tosupply power to the connected equipment.

The wall outlet is faulty. Have a qualified electrician test and repair theoutlet.

The UPS operates in Batterymode only, even thoughnormal utility power is present.

The input overcurrentprotector is open (120Vmodels only).

Save your work and turn off your equipment.Turn off the UPS. Reduce the load, then pressthe input overcurrent protector on the UPS rearpanel.

The UPS does not provide theexpected backup time.

The batteries needcharging or service.

Plug the UPS into a power outlet for 24 hours tocharge the battery. Press the button, if thealarm beeps, see “Replacing Batteries” onpage 34 to replace the batterypage 34 to replace the battery.During extended power outages, turn off theUPS after saving your work and shutting downyour computer to conserve battery power.

Page 51: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Troubleshooting

45NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

ActionPossible CauseAlarm or Condition

Normal operation. None. The UPS is operating in Normal modeand automatically provides consistent voltagewith the Buck and Boost feature.

1 beep every 4seconds.

The UPS is on batterydue to a utility failure.

The UPS is powering your equipment withbattery power. Prepare your equipment forshutdown. If this is an extended power outage,save your work and turn off your equipment toconserve battery power.

1 beep every 2seconds.

The battery is runninglow.

Two minutes or less of battery power remains(depending on load configuration and batterycharge).Save your work and turn off your equipment.The alarm cannot be silenced.

1 beep every 2seconds.

The UPS is running onbattery power becausethe input voltage is toohigh or too low.

Correct the input voltage, if possible. The UPScontinues to operate on battery until thecondition is corrected or the battery iscompletely discharged.If the condition persists, the input voltage inyour area may differ from the UPS nominal.Change the UPS input voltage to match yourlocal voltage (see “Voltage Configuration” onpage 29).

1 beep persecond.

Power requirementsexceed UPS capacity(overload is greater than120%) or the load isdefective.

The UPS will automatically shut down in3 minutes. Save your work immediately and turnoff your equipment. Turn off the UPS.Remove some of the equipment from the UPS.You may need to obtain a larger capacity UPS.

1 beep persecond.

The UPS is on battery,and the powerrequirements exceedUPS capacity (overload isgreater than 120%) orthe load is defective.

Shutdown is imminent (30 seconds). Save yourwork and turn off your equipment. Turn off andunplug the UPS.Remove some of the equipment from the UPS.Wait at least 5 seconds until all LEDs are off andrestart the UPS. You may need to obtain a largercapacity UPS.

Continuousbeep.

Battery test failed. Check the battery connections and be sure thebattery is fully charged.If the indicator still flashes, see “ReplacingBatteries” on page 34 to replace the battery. CallCustomer Service if the problem persists.

Page 52: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Troubleshooting

46 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

ActionPossible CauseAlarm or Condition

Continuousbeep.

UPS internaltemperature is too high.

Shutdown is imminent. Save your work and turnoff your equipment. Turn off the UPS.Clear vents and remove any heat sources.Ensure the airflow around the UPS is notrestricted. Wait at least 5 minutes and restartthe UPS. If the condition persists, contactCustomer Service.

Continuousbeep.

UPS fan fault(750–1400 VA modelsonly).

Save your work and turn off your equipment.Turn off the UPS. Contact Customer Service.

3 beeps every 10seconds.

Failed attempt to startthe UPS on battery.

Plug the UPS into a power outlet for 24 hours tocharge the battery. After charging the battery,press and hold the button for 3 seconds;then check the indicator.If the indicator still flashes, see “ReplacingBatteries” on page 34 to replace the battery.

Continuousbeep.

The output wave isabnormal while the UPSis on battery.

Shutdown is imminent. Save your work and turnoff your equipment. Turn off the UPS. ContactCustomer Service.

Continuousbeep.

The output voltage isbelow or above the limitwhile the UPS is onbattery.

Save your work and turn off your equipment.Turn off the UPS. Contact Customer Service.

Page 53: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Troubleshooting

47NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

Service and SupportIf you have any questions or problems with the UPS, call NCR at1-800-262-7782 and ask for a UPS technical representative.

Please have the following information ready when you call CustomerService:

� Model number

� Serial number

� Version number (if available)

� Date of failure or problem

� Symptoms of failure or problem

� Customer return address and contact information

If repair is required, you will be given a Returned Material Authorization(RMA) Number. This number must appear on the outside of the packageand on the Bill Of Lading (if applicable). Use the original packaging orrequest packaging from the Customer Service or the distributor. Unitsdamaged in shipment as a result of improper packaging are not coveredunder warranty. A replacement or repair unit will be shipped, freightprepaid by NCR for all warrantied units.

NOTE For critical applications, immediate replacement may beavailable. Call Customer Service for the dealer or distributornearest you.

Page 54: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Troubleshooting

48 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

NCR Limited WarrantyThis warranty applies to uninterruptible power system (UPS) products you purchase from NCRCorporation (“NCR”) and use in the United States, unless you have another applicable written agreementwith NCR. You indicate your acceptance of this NCR Limited Warranty by your initial use of your NCRproducts. Any software warranties are contained in the “break seal” license agreement shipped with thesoftware or any other applicable written agreement you may have with NCR.

What Is CoveredThe failure of any NCR UPS to operate in accordance with its specifications during the period of thiswarranty.

What We Will DoIf your NCR product becomes defective within 3 years of the date of purchase, we will repair it or, at ouroption, replace it at no charge to you. You may call the number listed below for dispatch of an NCRservice representative for on-site repair or replacement. All warranty service will be subject to NCR’sstandard policies.

If we repair your NCR product, we may use new or reconditioned parts. If we choose to replace your NCRproduct, we may replace it with a new or reconditioned one of the same or similar design. The repair orreplacement will be warranted for either (a) 90 days or (b) the remainder of the original warranty period,whichever is longer.

LimitationsIF YOU ARE A CONSUMER UNDER APPLICABLE LAW, ALL EXPRESS AND IMPLIEDWARRANTIES,INCLUDING THOSE OF FITNESS FOR A PARTICULAR PURPOSE ANDMERCHANTABILITY (ANUNWRITTENWARRANTY THAT THE PRODUCT IS FIT FOR ORIGINAL USE) ARE LIMITED TO ONEYEAR FROM THE DATE YOU PURCHASED YOUR NCR PRODUCT. IF YOU ARE NOT A CONSUMER,THERE ARE NO IMPLIED WARRANTIES, INCLUDING THOSE OF FITNESS FOR A PARTICULARPURPOSE ANDMERCHANTABILITY. WEWILL NOT PAY FOR LOSS OF TIME, INCONVENIENCE,LOSS OF DATA, LOSS OF USE OF YOUR NCR PRODUCT, OR PROPERTY DAMAGE CAUSED BY YOURNCR PRODUCT OR ITS FAILURE TOWORK, OR ANY OTHER DIRECT, INCIDENTAL, ORCONSEQUENTIAL DAMAGES.

Some states do not allow limitations on how long an implied warranty lasts, or the exclusion or limitationof incidental or consequential damages, so those aspects of the above limitations or exclusions may notapply to you.

What We Ask You To DoTo get warranty service for your NCR product, you must provide proof of the date of purchase. Call ustoll free at the number below to report problems or for the address of an authorized service location. Ifyou ship your NCR product to the authorized service location, you must prepay all shipping costs. Wesuggest you retain your original packing material in the event you need to ship your NCR product. Whensending your NCR product to a service location, include you name, address, phone number, proof of dateof purchase, and a description of the operating problem. After repairing or replacing your NCR product,we will ship it to your business or home (if you are a consumer) in the United States at no cost to you.

Page 55: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Troubleshooting

49NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy

What This Warranty Does Not CoverThis warranty does not cover defects resulting from accidents, damage while in transit to our servicelocation, alterations, unauthorized repair, failure to follow instructions, misuse, use outside the UnitedStates, fire, floods, acts of God. If your NCR product is not covered by our warranty, call us toll free at thenumber below for advice as to whether we will repair your NCR product and other repair information,including charges. We, at our option, may replace rather than repair your NCR product with a new orreconditioned one of the same or similar design. The repair or replacement will be warranted for 90 daysor the remainder of the original warranty period, whichever is longer.

This limited warranty is the only one we give on your NCR product, and it sets forth all ourresponsibilities regarding your NCR product. There are no other express warranties. Repair orreplacement of your NCR product during the warranty period is your exclusive remedy.

Dispute ResolutionAny controversy or claim between you and NCR regarding NCR products or services will be resolved bybinding arbitration under the current rules and supervision of the American Arbitration Association.The Arbitrator’s decision and award will be final and binding and may be entered in any court withjurisdiction.

State Law RightsThis warranty gives you specific legal rights, and you may also have other legal rights which vary fromstate to state.

The number to call is: 1-800-262-7782

Page 56: NCR 4072 500–1400 VA Uninterruptible Power …lit.powerware.com/ll_download.asp?file=NCR5115manual.pdf · NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374

Troubleshooting

50 NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy