12
1 - 1 NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06 1 Important: Retain these instructions Installation Instructions - Sheet 1 NBOX/EINC Node Controller Sheet 2 Sheet 1 Installation Instructions TG200152 /230 only /24 only /24/USA only Sheet 3 1.2 STORING H 2 O +50 °C (122 °F) 0 -10 °C (14 °F) 90 %RH 1.3 INSTALLATION - MOUNTING It is recommended that the installation should comply with the HSE Memorandum of Guidance on Electricity at Work Regulations 1989. For USA install equipment in accordance with the National Electric Code. 1 INSTALLATION 1.1 UNPACKING EINC 70 mm (2.76") 230 mm (9.06") 181 mm (7.13") EINC 50 mm (2") 100 mm (4") Dimensions Requirements EINC EINC a b c H 2 O 0 °C (32 °F) +45 °C (113 °F) 0 %RH 95 %RH d 1 2 EINC Protection: IP30 e For UL rating (NBOX/EINC/24 only) The unit is UL rate as 'UL916, accessory to enclosed energy management equipment' EINC CONTENTS 1.1 Unpacking 1 - 1 1.2 Storing 1 - 1 1.3 Installation Instructions - Mounting 1 - 1 1.4 Installation Instructions - Configuration 1 - 4 3.1 Replacing the Fuse 3 - 1 4 Disposal 3 - 3

NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

  • Upload
    others

  • View
    3

  • Download
    2

Embed Size (px)

Citation preview

Page 1: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

1 - 1NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

1Important: Retain these instructions

Installation Instructions - Sheet 1

NBOX/EINCNode Controller

EJ105

383

Sheet 2

Sheet 1

Installation Instructions TG200152

/230only

/24 only /24/USAonly Sheet 3

1.2 STORING

���

+50 °C(122 °F)

0-10 °C(14 °F)

90 %RH

1.3 INSTALLATION - MOUNTING

It is recommended that the installation shouldcomply with the HSE Memorandum of Guidanceon Electricity at Work Regulations 1989.For USA install equipment in accordance withthe National Electric Code.

1 INSTALLATION1.1 UNPACKING

EINC

70 mm (2.76")230 mm (9.06")

181

mm

(7.1

3")

EINC

50 mm(2")

100 mm (4")

Dimensions

Requirements

1 2 3 4 5 6

EINC

EINC

4

a

b

c

���

0 °C(32 °F)

+45 °C(113 °F)

0 %RH 95 %RH

d

12

EINC

Protection: IP30

e For UL rating (NBOX/EINC/24 only)The unit is UL rateas 'UL916,accessory toenclosed energym a n a g e m e n tequipment'

� � � �

� � � � � � � � � � � � � � � � � � �

� �

� � � � � � � � � �

EINC

CONTENTS1.1 Unpacking 1 - 11.2 Storing 1 - 1

1.3 Installation Instructions - Mounting 1 - 11.4 Installation Instructions - Configuration 1 - 43.1 Replacing the Fuse 3 - 14 Disposal 3 - 3

Page 2: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

1 - 2 NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

NBOX/EINC Installation Instructions - Sheet 1

209 mm (8.23")

172

mm

(6.7

7")

104.5 mm (4.11")

7 mm (0.28")

�� � � �

� � � � � � � � ��� �

� � � � �

9 10

Connecting Power5

/230 version

E N L

E N L

WARNING: This apparatus must be earthed/grounded (using input power earthground terminal).

DO NOTSWITCH ON

~

Shrouded plug kit Screw terminalE N L

a b dc eEarth/groundthe bus bar

1.3 INSTALLATION - MOUNTING (Continued)

Mount MBOX3 4

Mounting

9 10

EINC

a

Ø 6 mm(0.24”)

Ø 6 mm(0.24”)

ef

If using ENCLS/MBOX/IQ22x

ENCLS/MBOX/IQ22x InstallationInstructions TG200203.

bc d

Terminal size 0.5 to 2.5 mm2 (14 to 20 AWG)

~230V

RDS/RS232 !24V

~

MODEM

9 10

/24 versionNBOX/EINC/24 consumption < = 24 VA

Earth/groundthe bus bar

EJ1

0538

324

V

24 Vac:24 Vac

Earth

0V

24 Vac

Earth

Bla

ck

Red

Wh

ite

/USA only

~E N L

NBOX/EINC/230 consumption < = 18 VA

2 partMat-N-Locconnector(supplied)

Mat-N-Locto terminala d a p t o r(supplied)

Page 3: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

1 - 3NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

Installation Instructions - Sheet 1 NBOX/EINC

X

TT

RR

T- T+ R- R+

9 10

1.3 INSTALLATION - MOUNTING (Continued)

�� � � �

� � � � � � � � ��� �

� � � � �

using AUI Transceiver

OR

�� � � �

� � � � � � � � ��� �

� � � � �

15 way Dtype Male

no connection

Drop cable

100

m (

110

yds)

Ethernet hub/switch10BASE-T

RJ45 Connector

no connectionRJ45 Connector

Connect Ethernet6Connect to an Ethernet hubUse Ethernet cable.

IQ SystemProductsEngineeringGuide TE200369

� � � � � � � � � � � �

� � � � � � � � � � � �

2 wire

Connect Current Loop7

4 wire

Additional terminals

Note only 1 INC type node on a single Lan.Maximum Cable distance

Terminal size 0.5 to 2.55m2 (14 to 20 AWG)

Cable 1k2 baud 9k6 baud 19k2 baud 38k4 baud * No. of WiresBelden 9182 1000 m (1090 yds) 1000 m (1090 yds) 700 m (765 yds) 500 m (545 yds) 2Belden 9207 1000 m (1090 yds) 1000 m (1090 yds) 500 m (545 yds) 350 m (380 yds) 2IQ SystemTP/1/1/22/HF/200(Belden 8761)

1000 m (1090 yds) 700 m (765 yds) 350 m (380 yds) 250 m (270 yds) 2

IQSystemTP/2/2/22/HF/200(Belden 8723)

1000 m (1090 yds) 500 m (545 yds) 250 m (270 yds) 125 m (135 yds) 4

X

TT

RRTT

RR

T- T+ R- R+

Terminal size 0.5 to 2.55m2 (14 to 20 AWG)

Close Flap8

a

b

IMPORTANTEINCs do NOT support automatic addressing, and MUST NOT be installed on an Ethernet network where automaticaddressing is being used.

Transceiver

Page 4: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

1 - 4 NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

NBOX/EINC Installation Instructions - Sheet 1

Sheet 27EINC L Installation Instructions - Sheet 22

Mount Unit1EINC Installation Instructionssection 1.3

Switch off2O

I1

1.4 INSTALLATION - CONFIGURATION

Open MBOX (If fitted in ENCLS/MBOX/IQ22x)3

ba

Open Flap5

Set Internetwork Address (Lan number)6

9 10

ADDRESS

ON

SET

NOT SETe.g.

Address = 2 + 16 + 64 = 82

ON= A

EINC L

Lan

Lan/= A

Lan/= A

Lan/= A

If address < 100, INC Mode If address = > 100, Internetwork Extension Mode

Address = A

address 1, 4 to 9, 11 to 119

0, 2, 3, 10 or >119

EINC EINC

Internetwork(on Ethernet)

Internetwork(on Ethernet)

EINC

Lan(on current loop)

Internetwork(on Ethernet)

Internetwork(on Ethernet)

EINC

Internetwork(on current loop)

Open Panel

If appropriate4

TX RX

LAN

LAN

7 8 14 1524V

19 20

Page 5: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

2 - 1NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

2Installation Instructions - Sheet 2

NBOX/EINCNode Controller

9 10

9 10

Set Current Loop Baud Rate9

SET

NOT SET EINC

Baud Rate = C

=C

=C

=C

=C

38k4 baud

1k2 baud

Note 1: 38k4 Lan not available with IQ2xx, IQ1xx, INC, LINC,CNC, CNC2, INC2,and TMN.

Note 2: 38k4 Internetwork not available with INC, and LINC.19k2 baud

9k6 baud

Sheet 18EINC Installation Instructions - Sheet 11

1.4 INSTALLATION - CONFIGURATION (Continued)

Switch On11

Check Node Controller12

Check supply

EINC Faulty

(watchdog)

(power)(green)

(red)

Close Flap10

13 Check Ethernet

9 10

if 10 BASE-T

Check Ethernet connection

Check other Ethernet device

Check other Ethernet device

If another device on Ethernet

check other decice

RX

TXOK

(Link integrity)(yellow)

(yellow)

(yellow)(green)

Page 6: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

2 - 2 NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

NBOX/EINC Installation Instructions - Sheet 2

9 10

~230V

RDS/RS232 !24V

~

MODEM

EINC

O

I

NBOX/EINC

?

NBOX/EINC

?

� � � � � � � � � � � � � � � �

� � � � � � � � � � � � � � � �

9 10

13 Check Current Loop Network

b TX

a RX

c OK

IQ Faulty Check network cabling forshort circuits with amultimeter (NOT Megger)

Network Address Invalid

OK OK NBOX/EINC

Power up other nodes untilfaulty node is found(OK ). Correct fault.

(yellow)

(yellow)

(green)

0,2,3 or >119

Check baud rate

1.4 INSTALLATION - CONFIGURATION (Continued)

14 Connect to EINC with IP Tool

SET Manual TE200147IP Tool Manual TE200638

Router

EINC

Router

Either over Ethernet

or Local PC Ethernet Connection

SET v6(including IP Tool)

XCITE/XA crossover adaptororder separately (XCITE/XA/5pack of 5)

SET v6(including IP Tool)

Local PC (Ethernet) connection can be either to adjacent Ethernethub using standard cable only, or directly to EINC using standardcable and crossover adaptor, XCITE/XA.

Initially access EINC via its MAC address

15Configure Addressing Details with IPTool EINC Data Sheet TA200137

IP Tool Manual TE200638

Parameter Setting Default Function Condition Note

Address Module

IP AddressIP address0.0.0.0 to 255.255.255.255

128.1.1.<address switch>

Ethernet IP addressLast section set automaticallyto address switch setting

1

Subnet MaskMask0.0.0.0 to 255.255.255.255

255.255.255.0

Mask applied to IP address to generatesubnet number

All EINCs on same channelmust be on same subnet tocreate internetwork

1

UDP Port 0 to 65535 57612Ethernet UDP port used by IQ systemequipment on Ethernet

All IQ system devices mustuse same port tointercommunicate

2

Router 1IP address0.0.0.0 to 255.255.255.255

0.0.0.0IP address of router on same subnet asEINC

MUST be set up forcommunications outside ownsubnet

3

Lan number Lan number 1, 4 to 9, 11 to 119 20Lan number of EINC on internetwork<SET BY ADDRESS SWITCH>

4

Identifier15 alphanumeric characters -not /\({;?* characters

EINC Identifier for EINCAlways set up forsupervisors/display panels

Page 7: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

2 - 3NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

Installation Instructions - Sheet 2 NBOX/EINC

15Configure Addressing Details with IPTool (Continued)

1. Change if address clash on Ethernet or if routers between EINCs.2. May change UDP port if port already used on Ethernet, or if multiple internetworks (i.e. sites) required on subnet (see Data Sheet).3. Enables EINC virtual CNC to access Ethernet PC across router, or EINC to find other IQ system Ethernet devices acrossrouter.4. Also used by IQ system Supervisors and software tools to access EINC (Device address always 126).5. Virtual CNCs inoperative until address set up.6. Set up each virtual CNC used, separately.7. Same port number to be set up in supervisor to communicate with virtual CNC.8. Use virtual CNC in alarm mode to send alarms to Ethernet 962 v3 or greater/963 which connects via TCP dial up.9. Lowest IP address (IQ3xcite or EINC) on each subnet across router to be set up; as many as possible in each subnet recommended.10. If using 'updatelist' facility (not recommeded for mixed EINC/IQ3xcite system) also set up this EINC's details (and otherEINC's on this EINC's subnet, if not broadcast).11. Out of the factory mode is ‘unconfigured’ which changes to ‘networked’ on first write to EINC by IPTool.

1.4 INSTALLATION - CONFIGURATION (Continued)

Parameter Setting Default Function Condition Note

Virtual CNCx(x = 1 to 4)

CNCAddress

node address 1, 4 to 9, 11 to119

4Node address of virtual CNC on virtualTrend Lan

If virtual CNC is to be used 5,6

Port address Ethernet port 1 to 32767 disabled Ethernet port of virtual CNCIf virtual CNC is to be usedand if default needs to bechanged

6,7

alarm IPaddress

IP addresse.g. 171.193.6.106

disabledIP address of target device (e.g.supervisor)

if CNC used in alarm mode 6,8

Remote TrendDevice x(remote EINCs)(x = 1 to 20)

IP AddressIP address0.0.0.0 to 255.255.255.255

empty listIP address of IQ system Ethernet deviceother side of router

If network to span router9,10

Subnet MaskMask0.0.0.0 to 255.255.255.255

empty listSubnet mask of IQ system Ethernetdevice other side of router

Device Mode networked unconfigured networked/stand alone on EthernetSet to stand alone if only IQsystem device on Ethernet

11

16 a Enter configuration mode using SET. The top levelprompt will be displayed as below.

b Configure the optional settings the relevant uppercase letter and pressing ENTER. If a value has beenchanged X+ENTER will confirm it and return to thetop menu, whereas Q+ENTER will quit and returnwith the value unchanged. The table below describesthe settings.

SET Manual TE200147Configure Optional Settings Using SET

Note that it may be necessary to set up a virtual CNC in theEINC if one is not available elsewhere on the network.

EINC L Data Sheet TA200137

1 If set to zero - no alarms reported.2 Language type values:0=English, 1=Spanish, 2=Finnish, 3=Swedish, 4=Norwegian, 5=Danish, 6=German, 7=Italian, 8=Portuguese, 9=French.3 Broadcast preferable as it enables the internetwork link to be made via the subnet of EINCs across router, rather than one EINC. However,

normally stopped by router.4 This facility allows remoteEincs list in one EINC to be set up, and then the list (including Broadcast status) to be copied to all other EINCs

so that internetwork across routers can be formed (not recommended for mixed EINC/IQ3 system).

Parameter Setting Function Condition Note

addRessiDentifier

15 alphanumericcharacters - not/\({;?* characters

Identifier for Lan Always set for supervisors/Display Panels

localnetworkalarms to

Addressnode address 1, 4-9,11-119

node address of EINC alarm target forTrend current loop network alarms

If current loop network alarms to be reported 1

Remotelan

Lan number1, 4-9, 11-119

Lan number of EINC alarm target forTrend current loop network alarms

If current loop network alarms to be reported 1

ethernetalarms to

addrEssnode address 1, 4-9,11-119

node address of EINC alarm target forEthernet alarms

If Ethernet alarms to be reported 1

remoTelan

Lan number1, 4-9, 11-119

Lan number of EINC alarm target forEthernet alarms

If Ethernet alarms to be reported 1

alarm language tyPe 0 to 9 (digit) Selects language of network alarms If language to be changed 2

UserPin number Protects changes in configuration mode

Default is blank (unprotected). Set up if securityrequired.

generator number random number for default PIN generationRead only, give to Technical Support with Ethernetmac address for default PIN see steps (17 and 19).

remoteEincs send as Broadcast Y (1) or N (0)Broadcast to EINC subnet if Y or directedto 1 EINC on subnet if N

Default Y, broadcast. Change if broadcast messagesprohibited by router

3

uPdatelistCopy your remote EINClist to other EINCs (Y/N)

Copies remoteEincs list to local subnet and all subnets withEINC in list

If internetwork to span router, and to faciliate setup 4

Page 8: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

2 - 4 NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

NBOX/EINC Installation Instructions - Sheet 2

EINC Installation Instructions - Sheet 312 Sheet 3

3

Write on Label16

Tear off Label Strip17

XTEND -400007096� � � � � � �

� � � � � 00.10.70.00.UD.BB

� � �

S/No:

� � � � � � � Location

� � � � � 00.10.70.00.UD.BB

S/No:Q3B____X73010003

� � � � � � �

� � � � � 00.10.70.00.UD.BB S/No:Q3B____X73010003

� � � � � � � Location

1 2 3 4 5 6 7 8 9 10

TX RX

OK

LAN

OK

TX RX

� � � � � 00.10.70.00.UD.BB

� � �

S/No:Q3B____X73010003

� � � � � � � Location

� � � � � 00.10.70.00.UD.BB

S/No:Q3B____X73010003EINC -400007096

� � � � � � �

� � � � � � � �

� � � � � 00.10.70.00.UD.BB

� � �

S/No:Q3B____X73010003

� � � � � � � Location

� � � � � 00.10.70.00.UD.BB

S/No:Q3B____X73010003XTND -400007096

� � � � � � �

� � � � � � �

recommendede.g. location/identifier

IP Address, Location, Lan, network address,

1.4 INSTALLATION - CONFIGURATION (Continued)

22 Check Communications

EINC

Lan IQ

Lan

Ethernet

EINC

INC

Lan

Lan

EINC

IQ

Ethernet

EINC

I/N

If address =>100If address <100

24Close MBOX if fitted in ENCLS/MBOX/IQ22x

ba

25Close Panel

For UL rating (NBOX/EINC/24 only)

� � � �

� � �

� � �

� � � � � � � � � � � � � � � �

� �

� � � � � � � �

The unit is UL rate as 'UL916,accessory to enclosedenergy managementequipment'

23 Check Virtual CNCs Virtual CNCs in Alarm Mode

Ethernet

CNCBCNCA

EINC

CNCDCNCC

SET, or 963

Virtual CNC inSupervisor mode

Virtual CNCs in Supervisor Mode

Ethernet

CNCBCNCA

EINC

CNCDCNCC

963Connected toremote site

CNC inAlarm mode

Alarms from system sent to virtual CNC

Page 9: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

3 - 1NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

3Installation Instructions - Sheet 3

NBOX/EINCNode Controller

Switch Off1O

I

Open MBOX (If fitted in ENCLS/MBOX/IQ22x)3

ba

Open Flap4

3 REPLACING THE FUSE

a b

Open Panel (If appropriate)2

TX RX

LAN

LAN

7 8 14 1524V

19 20

1 2 3 4 5 6 7 8 9 10

Remove Cover

9 10

b c

Replace Fuse

230 V 125 mA (T) 250V 20 mm24 V 1.6 A(T) 20 mm

5a

6 b ca d

Caution: This unit contains static sensitive devices. Suitableanti-static precautions should be takenthroughout this operation to prevent damage tothe unit. 417-IEC-5134

Page 10: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

3 - 2 NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

NBOX/EINC Installation Instructions - Sheet 3

3 REPLACING THE FUSE (Continued)

Replace Cover7

Close Flap8

Switch On11

9Close MBox (If fitted in ENCLS/MBOX/IQ22x)

ba

ba

10Close Panel (For UL rating NBOX/EINC/24 only)

� � � �

� � �

� � �

� � � � � � � � � � � � � � � �

� �

� � � � � � � �

The unit is UL rate as'UL916, accessory toenclosed energym a n a g e m e n tequipment'

Page 11: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

3 - 3NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

Installation Instructions - Sheet 3 NBOX/EINC

WEEE Directive :

At the end of their useful life the packaging ,product, and batteries should be disposed ofby a suitable recycling centre.

Do not dispose of with normal household waste.Do not burn.

4 DISPOSAL

Page 12: NBOX/EINC Installation Instructions€¦ · Subnet Mask Mask 0.0.0.0 to 255.255.255.255 255.255. 255.0 Mask applied to IP address to generate subnet number All EINCs on same channel

3 - 4 NBOX/EINC Installation Instructions TG200152 Issue 2/D 4/7/06

NBOX/EINC Installation Instructions - Sheet 3

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Routedu Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the contenthereof without obligation to notify any person of such revisions or changes.

Trend Control Systems LimitedP.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.comTrend Control Systems USA6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)869-8400, Fax: (425)869-8445 www.trend-controls.com

This page is intentionally left blank