3
CUSTOMER : NO. : GOODS NO. OF. CUSTOMER : FILE NO. : 1 - GENERAL GUARANTEED - Producer : HES HACILAR ELEKTRİK SAN. VE TİC. A.Ş. - Cable Code : A2XS(F)2Y - Aplied Standards : IEC 60502 - Rated Voltage (U0/Um) (kV) : 12/20 - Max. Operating Voltage (Um) (kV) : 24 2 - STRUCTURAL P ROPERTIES 2.1 CONDUCTOR . Type :Compacted Conductor  . Material : Aluminium . Cross-sectional Area (mm²) : 3x1x185ş/25 . Number of Wir es : 37 . Type of Stranding : Circular  . Outer Diameter of Strand (max) (mm) :17,5 2.2 INNER SEMICONDU CTI NG SCREEN . Material : Semiconductive XLPE . Nominal Thickness (mm) : 0,6 . Minimum Thickness (mm) : 0,3 . Outer Diameter of Screen (mm) :18,7 2.3 INSULATION . Material : XLPE . Nominal Thickness (mm) : 5,5 . Minimum Thickness (mm) : 4,85 . Outer Diameter of Insulation (mm) :2 9,7 2.4 OUTER SEMICONDUCTING SCREEN . Material : Semiconductive XLPE . Nominal Thickness (mm) : 0,6 . Minimum Thickness (mm) : 0,3 . Outer Diameter of Screen (mm) : 30,9 2.5 METALLIC SCREEN . Material : Copper  . Type : Wire & Tape . Number & Diameter of Wires (mm) :90x0.55 DATE 13.03.2009 Page 1 MEDIUM VOLTAGE CROSS-LINKED PE (XLPE) INSULA TED POWER CABLES LIST OF GUARANTEED CHARACTERISTICS

NA2XS(F)2Y_12-20_kV_3x1x185-25

Embed Size (px)

Citation preview

Page 1: NA2XS(F)2Y_12-20_kV_3x1x185-25

 

CUSTOMER :

NO. :

GOODS NO. OF. CUSTOMER :

FILE NO. :

1 - GENERAL GUARANTEED- Producer : HES HACILAR ELEKTRİK SAN. VE TİC. A.Ş.- Cable Code : A2XS(F)2Y- Aplied Standards : IEC 60502- Rated Voltage (U0/Um) (kV) : 12/20- Max. Operating Voltage (Um) (kV) : 24

2 - STRUCTURAL PROPERTIES

2.1 CONDUCTOR. Type : Compacted Conductor  . Material : Aluminium. Cross-sectional Area (mm²) : 3x1x185ş/25. Number of Wires : 37. Type of Stranding : Circular  . Outer Diameter of Strand (max) (mm) : 17,5

2.2 INNER SEMICONDUCTING SCREEN. Material : Semiconductive XLPE. Nominal Thickness (mm) : 0,6. Minimum Thickness (mm) : 0,3. Outer Diameter of Screen (mm) : 18,7

2.3 INSULATION. Material : XLPE. Nominal Thickness (mm) : 5,5. Minimum Thickness (mm) : 4,85. Outer Diameter of Insulation (mm) : 29,7

2.4 OUTER SEMICONDUCTING SCREEN. Material : Semiconductive XLPE. Nominal Thickness (mm) : 0,6. Minimum Thickness (mm) : 0,3. Outer Diameter of Screen (mm) : 30,9

2.5 METALLIC SCREEN. Material : Copper  . Type : Wire & Tape. Number & Diameter of Wires (mm) : 90x0.55

DATE13.03.2009

Page 1

MEDIUM VOLTAGE CROSS-LINKED PE (XLPE) INSULATED POWER CABLESLIST OF GUARANTEED CHARACTERISTICS

Page 2: NA2XS(F)2Y_12-20_kV_3x1x185-25

 

CUSTOMER :

NO. :

GOODS NO. OF. CUSTOMER :

FILE NO. :

GUARANTEED. Number of Copper Tape & Dimensions (mm) : 1 - (0.1x30). Geometrical Area (mm²) : 25. Outer Diameter (mm) : 34,5

2.6 ARMOUR. Material : -. Thickness of Zinc Coating of Armour Wires (g/m²) : -. Width & Thickness or Diameter of Armour Wires (mm) : -. Thickness of Galvanize Coating of Steel Tape (g/m²) : -. Width & Thickness of Steel Tape (mm) : -

2.7 OUTER SHEATH. Material : PE. Colour : Black. Nominal Thickness (mm) : 2,1. Minimum Thickness (mm) : 1,48

3.0 ELECTRICAL PROPERTIES

3.1 Power Freq. Test Voltages of 5 Minute Duration (kV-rms) : 42,03.2 Impulse Test Voltages (kV-Peak) : 1253.3 Continuous Current Carrying Capacity3.3.1 Under Ground at a depth of 70 cm (ground temperature

20 °C, ground thermal resistance 1,0 k.m/W) (A) : 3683.3.2 In Air (Ambient Temperature 45 °C) (A) : 4223.3.3 In Ducts (Ambient Temperature 40 °C) (A) : 2843.4 Losses3.4.1 Dielectric Losses (at 20 °C, 3 phases) (W/km) : 1283.4.2 Dielectric Losses (at 90 °C, 3 phases) (W/km) : 2563.4.3 Copper Losses ( At Conditions of Clause 3.3.1) (W/km) : 673.5 Maximum Continuous Conductor Temperature (°C) : 903.6 Maximum Temperature & Duration of Conductor 

at Short Circuit Condition (°C,seconds) : 250 , 53.7 Maximum Short-Circuit Current

Start Temperature 90 °C, End Temperature 250 °C)3.7.1 Duration of 5 seconds (kA) : 7,83.7.2 Duration of 1seconds (kA) : 17,43.7.3 Duration of 0.5 seconds (kA) : 24,6

DATE13.03.2009

MEDIUM VOLTAGE CROSS-LINKED PE (XLPE) INSULATED POWER CABLESLIST OF GUARANTEED CHARACTERISTICS

Page 2

Page 3: NA2XS(F)2Y_12-20_kV_3x1x185-25

 

CUSTOMER :

NO. :

GOODS NO. OF. CUSTOMER :

FILE NO. :

GUARANTEED3.8 Maximum Short-Circuit Current

at Metallic Screen3.8.1 Duration of 1seconds (kA) : 3,63.8.2 Duration of 0.5 seconds (kA) : 5,13.9 Conductor DC Resistance at 20 °C (Ω/km) : 0,1643.10 Conductor AC Resistance at 90 °C (Ω/km) : 0,2103.11 Insulation Resistance at 20 °C (MΩ/km) : 109063.12 Operating Capacitance (20 °C ) (nF/km) : 0,253.13 Operating Inductance (mH/km) : 0,673.14 Dielektrik Kayıp Faktörü ( tan Ù)3.14.1 At 20 °C : 0,0043.14.2 At Maximum Operating Temperature (90 °C) : 0,0083.15 Partial Discharge (at 2 Uo) max. ( pC) : 5

4. OTHER PROPERTIES

4.1 Outer Diameter of Cable (With Tolerance) (mm) : 84 ± 34.2 Minimum Bending Radius (mm) : 12604.3 Lowest Laying Temperature (°C) : +34.4 Weight of Cable (kg/km) : 56504.5 Weight of Copper (kg/km) : 4904.6 Weight of Steel (kg/km) : -

4.7 Drums . Type : HES 240 . Flange (wheel) Diameter (mm) : 2400 . Barrel Diameter (mm) : 1200 . Barrel Length (mm) : 1430 . Outside Width (mm) : 1630 . Length of Cable (m) : 500

4.8 Gross & Net Weight (kg) : 3775 2825

DATE SEAL/SIGN13.03.2009 Asım MERCAN

Quality Control Lab. Manager 

Note : Test voltage at article 3.1 is applied as AC.

Page 3

MEDIUM VOLTAGE CROSS-LINKED PE (XLPE) INSULATED POWER CABLESLIST OF GUARANTEED CHARACTERISTICS