20
MV Overhead Feeder Automation Sophistication

MV Overhead Feeder Automation Sophistication · the fault is removed and the protection equipment is turned back on. During a permanent fault the following actions would typically

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

  • MV Overhead FeederAutomation Sophistication

  • 2

    Introduction

    Due to the importance of electricity in the everyday life of people, electricity providers are under immense pressure to improve the reliability of supply to their customers. Providers have a number of options available to improve supply reliability.

    Additional primary substationsTo a large degree the likelihood of fault is proportional to the length of distribution circuit, and obviously the longer the circuit the greater the probability of a fault.It is possible to reduce the feeding distances substantially by installing additional primary substations. That is also going to reduce the number of customers affected by each fault. Installing new substations can however be very expensive.

    Additional feeder circuitsNew feeders could be established from existing primary substations and this option also reduces the number of customers per circuit and therefore the number of customers affected by each fault. This option would however be less effective than the addition of primary substations and may not be very efficient. It is again negated by excessive cost.

    Vegetation managementBoth of the first two options focus on reducing the affects of faults but do not in themselves do anything to reduce the number of faults. One thing that all utilities, with overhead rural feeders, have to focus upon is vegetation management. This is of course an operational expenditure rather than a capital expenditure but nevertheless an extremely important activity for electrical utilities and essential if unnecessary interruptions are to be avoided.

    Covered ConductorAnother option to reduce the number of faults would be to remove bare overhead conductors and replace them with covered conductors. This will reduce faults caused by birds, animals, tree branches or other wind blown material contacting the line. Using covered conductor particularly in wooded areas will help to reduce faults. Covered conductors are certainly not fool proof and its performance under high impulse conditions can be a problem. The biggest drawback with it however is the cost. Replacing the conductors in large portions of the network is not generally an economically viable option.

    Underground circuitsA theoretically better option again would be to underground all circuits. This would remove any weather or vermin related faults and will undoubtedly improve reliability and win favour with environmentalist lobby groups. The use of trench-less or narrow trench technology can significantly reduce cost. However considering the feeding distances involved the cost would still be astronomical. A significant redesign of networks would also be required, as the typical overhead circuit with very long feeding distancs and many spur lines teed-off is not really suited to an underground system.Some practical difficulties could be manifested in complications with future fault location which could cause long interruptions to supply. Low cost, pad mounted transformers and switchgear would be an essential requirement of such a system.

    Feeder automation sophisticationIn an effort to improve reliability of supply, providers are rethinking the levels of sophistication deployed in their Medium Voltage (MV) Overhead Feeders.Studies of faults on overhead feeder networks have shown that 60 - 70% of the faults are transient/temporary.Examples of transient faults include:b Conductors clashing in the wind;

    b Tree branches falling on overhead conductors;

    b Animals or birds coming in contact with overhead conductors; and

    b Lightning strikes.

    An auto-reclose cycle should clear a transient fault without interrupting supply to the customer. In most cases no further operator assistance would be required to clear the fault.Some faults are however more permanent. Examples include distribution

    Figure 1: Permanent Fault Example

  • 3

    equipment, such as transformer, failures and fallen power lines due to motor accidents or storms. Protection equipment is designed to minimise damage by interrupting supply to a segment containing a fault. The supply will remain off until the fault is removed and the protection equipment is turned back on.During a permanent fault the following actions would typically be taken to minimise the effects of the fault:b Protection equipment (circuit breaker or recloser) would interrupt supply to the affected segment/s of the feeder.

    b Identify the faulty segment of the feeder.

    b For looped networks isolate the faulty segment by opening the switchgear upstream and downstream of the fault.

    b Reconfigure the network for alternative power flow.

    b Restore power upstream of the faulty segment.

    b If an open loop network is used, close the open point to restore power downstream of the faulty segment.

    b Maintenance crews remove the fault.

    b Restore the network to the normal configuration.

    It is possible that outages can last for hours and even days. To minimise the duration of the outages it is necessary to quickly identify the exact location of the fault and to provide alternative power supplies to segments not containing the fault. This can be done manually or by using sophisticated switchgear controllers to enable electricity providers to incorporate advanced automation functions in Feeder Networks thus substantially reducing the outage time.This paper explores the effectiveness of feeder segmentation and considers the effects of using different arrangements or types of switchgear to construct an overhead MV network run as an open ring.Two possible scenarios giving increasing levels of automation sophistication are compared for cost and benefits, and operational risks under fault conditions:b Telecontrolled switches in a remotely controlled, but not necessarily automated network; and

    b Reclosers and sectionalisers in an automated, but not necessarily remotely-controlled network.

    A glossary is provided at the end of the document.

    Figure 2: Open Loop Network Example

    Introduction

  • 4

    As discussed in the Introduction of this paper, supply authorities have a number of options available to improve the reliability of supply. These are:b Additional primary substations;b Additional feeder circuits;b Vegetation management;b Covered Conductor;b Underground circuits; andb Feeder automation sophistication.Reliability gains are also made by increasing the protection sophistication. This is not limited to the latest protection algorithms. It also includes breaking the feeder into smaller segments. This reduces the number of customers per segment and therefore the number of customers affected by a fault. The following paragraph explores the affect that segment lengths have on reliability.

    Increased number of segments per feederFor this example, consider a theoretical radial feeder. Assume that the probability of a fault is the same along the length of the feeder. By dividing the feeder into multiple segments the probability that a fault would occur in a specific segment is:PZ = PF x (LZ / L) where:L = the length of the feeder;LZ = the length of the segment; andPF = the probability that a fault would occur anywhere on the feeder.It is possible to calculate the impact when the feeder is divided into multiple segments of equal length.

    Unfortunately these improvement figures do not tell the full story. To get the full picture it is necessary to revisit the basic radial feeder, look at the probability of an outage in each segment and then expand the theory to a looped network.

    Number of Segments

    Segment fault probability

    Improvement

    1 P1 = PF

    2 P2 = PF x 50% P2 / P1 = 50%

    3 P3 = PF x 33% P3 / P2 = 66%

    4 P4 = PF x 25% P4 / P3 = 75%

    Table 1:Reliability Improvement

    Radial feeder

    The example above clearly shows how the outages in each segment are affected by the number of faults in that specific segment and the faults occurring in upstream segments.Looped networks are used to reduce the number of outages for segments located further away from the substation and to overcome this stepped increase in outages.

    Seg A B C D

    Where "F" represents the switchgear closest to the substation and "MP" represent switchgear anywhere along the feeder.

    Probability of a fault in each segment is:

    PA PB PC PD

    Probability of an outage in each segment is:

    PS PS+A PS+A+B PS+A+B+C PS+A+B+C+D

    Where PS is the probability of losing supply at the primary substation. PS should be negligible and this simplifies the probability of an outage in each segment. (Notation: PA+B+C+D = PA + PB +PC + PD).

    PA PA+B PA+B+C PA+B+C+D

    For equal segment lengths and by using PZ = PF x (LZ / L) and the above it is possible to show what percentage of permanent faults will affect each segment. For feeders with four segments:

    4 25% 50% 75% 100%

    For feeders with three segments:

    3 33% 66% 100%

    For feeders with two segments:

    2 50% 100%

    Notice how the probability of an outage increases further away from the substation. From this example it is clear that not all customers benefit equally from additional segments on the feeder. Only customers connected to the first segment will experience the improvements calculated in Table 1.

    Table 2: Radial Feeder

    F MP1 MP2

    Feeder segmentation

  • 5

    Open loop networkIn a looped network, the switchgear immediately upstream and downstream of a fault are opened to isolate the fault, and the normally-open point is closed to restore power downstream of the faulty segment. Only the segment containing the fault experiences an outage until the fault is removed and the network is restored to the original configuration.The outage probability of each segment is therefore not affected by the probability in adjacent segments.

    By reducing the length and increasing the number of segments in a feeder it is possible to improve the reliability of supply. However not all customers benefit equally from this investment and looped networks are often used to improve supply reliability throughout the feeder. Feeder segmentation is achieved by using different technologies ranging from sophisticated reclosers and sectionalisers through telecontrolled load-break switches to manually operated air-break switches. The technology used in feeders differs from country to country and is also affected by the population density (number of customers per segment). In reality underground circuits may be used in the inner city, reclosers in substations and outer city feeders and sectionalisers in rural feeders.The subsequent sections discuss in detail the benefit and operation of each technology based on a common feeder topology.

    How would a looped network affect these figures?

    Seg A B C D

    Probability of an outage in a looped network is:

    PA PB PC PD

    For feeders with multiple segments of equal length the probability of an outage in each segment is 25%, 33% or 50% respectively for four, three or two segments.By comparing these probability figures to those determined for a radial feeder it is possible to calculate the improvements achieved with a loop network.

    4 25% 25% 25% 25%

    Improvement 25% 50% 75%

    3 33% 33% 33%

    Improvement 33% 66%

    2 50% 100%

    Improvement 50%

    Table 3: Open Loop Network

    F MP1 MP2 NO

    Feeder segmentation

  • 6

    In this example, remotely-controlled load-break switches (commonly referred to as telecontrolled switches) are used in an overhead feeder. Remotely-monitored Fault Passage Indicators (FPIs) are used with the load-break switches, sometimes separately, sometimes built into the switch. The switches are used for general switching operations and in the event of a permanent fault, an operator uses the FPI indication to determine which switches to open in order to isolate the faulted segment of the feeder. To operate such a network, a communications system is necessary, and the operation of the switches is typically performed manually in a control room. During a fault condition the feeder reconfiguration is typically not automatic.

    NO

    Substation circuit breaker/recloserClosed telecontrolled switchOpen telecontrolled switch

    Figure 3: Typical Switch Network

    Basic operation during fault conditionsWhen a permanent fault occurs, the following steps are taken:b The substation circuit breaker or recloser trips automatically to interrupt supply to the affected feeder;

    b An operator in the control room:v identifies the faulty segment of the feeder by using the FPI indication displayed in the control room;v opens (via a communications network such as optical fibre) the nearest upstream and downstream switches to isolate the faulty segment;v reconfigures the protection in substation breakers;v closes the substation circuit breaker to restore power upstream of the faulty segment, andv closes the normally-open point to restore power downstream of the faulty segment.Power is restored to the healthy parts of the network and it is possible for the operator to despatch the maintenance crews to the faulted segment of the feeder to remove the fault. Once the entire feeder is healthy, the operator can open the normally-open point and close the telecontrolled switches to restore the network to the normal configuration.

    Operational risksControl roomThe reaction time of the control room has a significant impact on the feeder restoration times. In practice the reaction time is influenced by:b The availability of an operator 24 hours per day, 7 days a week;

    b Enough operators to monitor and react during periods of extreme fault activity, such as large storms;

    b Reliability of communications to monitor FPI indication and to control the switchgear;

    b Feeder complexity; and

    b Level of automation in control room and network.

    However, if managed correctly, control room operations may not degrade the operational efficiency of this type of network.

    Fault passage indicationFPIs are the "eyes" of the operator. When the operator does not have a clear understanding of the fault location the operational efficiency of the network will be reduced.FPI functionality can be incorporated in the switchgear. These utilise switchgear mounted Current Transformers (CTs) and sensing electronics to detect fault conditions. FPIs can also be separate from the switchgear and these typically measure the magnetic field around the transmission line and are simply clipped onto the conductor making it extremely easy to install. The major advantage of clip-on FPIs is that they can be installed anywhere along the feeder, at different intervals and it is possible to relocate them as requirements change.Two risks are associated with FPIs - false indication and no indication at all.

    Figure 4: Telecontrolled Load-Break Switch

    Telecontrolled switches

  • 7

    False indication is the situation where the FPI indicates a fault without a fault being present. This can be caused by inrush currents during switching operations and reclosing cycles. In general, no indication can occur when low level phase and earth fault conditions are not detected by the FPIs, resulting in the absence of FPI indication. It is possible to overcome these risks by matching the detection capabilities of the FPI to that of the primary protection devices in the feeder.It is also possible that the absence of indication is caused by communication failure.In either case, an operator, may be left with a dead feeder and misleading FPI indication on the mimic panel. This will mislead the operator as to the actual location of the faulted segment, resulting in incorrect switching operations and increased time taken to restore power.

    CommunicationsThe integrity of the telecontrolled switch network relies wholly on the availability of communications and this key part of the system affects all aspects of network operation. During a fault condition the protection equipment will trip and without communications the operator will not be able to reconfigure and restore supply. Maintenance crews will have to locate the fault and manually reconfigure the network by driving to each unit before power is restored. This will take many hours and will cause unacceptable delays in restoring power to the customers.

    Advantages b Relatively low initial cost of switchgear.

    b Much lower outage times when compared with manually-operated switches without communications.

    Disadvantages b Faults affect all customers connected to the feeder.

    b As the switches are manually, remotely operated, the duration of the outage is dependent on the response time of the operator;

    b Expensive communications infrastructure;

    b Operation is highly dependent on the integrity of the communications network;

    b All faults cause substation circuit breaker operation - this results in a shorter service life.

    b Protection functionality is limited. Only one circuit breaker to detect high fault levels close to the substation and low fault levels some distance away;

    b Low fault levels can go undetected by circuit breaker and FPIs, e.g. Sensitive Earth Fault (SEF).

    Evolving sophistication Where a communications network is expensive or difficult to implement, and in more critical parts of networks, there is a move away from telecontrolled switches to "infilling" with reclosers and using the telecontrolled switches as sectionalisers. This introduces protection and automation sophistication to the feeder.An example of a more "sophisticated" feeder is where Load Break Switch / Sectionalisers are used instead of telecontrolled switches. Communications is not essential to the operation of feeders where reclosers and sectionalisers are used. These networks can be automated to improve response times and do not have to be remotely-controlled.

    Figure 5: Fault Passage Indicator

    Telecontrolled switches

  • 8

    To analyse the use of Sectionaliser logic in a feeder, let us consider the same open loop topology from the previous example but replace the telecontrolled switches with sectionalising switches.A sectionalising switch (sectionaliser) is a load break switch capable of monitoring both current and voltage on all three phases. The switch is combined with a controller capable of detecting through-faults and upstream recloser operation. The current sensors detect the number of fault currents which pass through the switch, and the voltage sensors detect when the line is de-energised due to upstream recloser operation. When the programmed number of reclosing operations occurs, the controller opens the sectionaliser during the dead time to isolate the downstream fault.These networks are graded on the number of operations. That is upstream devices are set to open at a higher number of Supply Interruptions (SI) than the downstream devices. Therefore in this example the SI counter for the sectionalisers is set to 3, 2 and 1 respectively.This example will demonstrate how the introduction of basic automation can significantly reduce the operational risks.

    NO

    SI=3 2 1

    SI=3 2 1

    Substation circuit breaker/recloserClosed sectionalising switchOpen sectionalising switch

    Figure 6: Typical Sectionaliser Network

    Basic operation during fault conditionsb When a permanent fault occurs, the following steps are taken:

    b The substation circuit breaker or recloser trips and recloses automatically while the sectionalisers count the supply interruptions;

    b The first sectionaliser to reach its set SI count opens during the dead time of the recloser. This isolates the fault, and supply to the upstream portion of the feeder is restored automatically on the next reclose. The change of state in the sectionaliser is reported via a communications network to the control room to fulfil the FPI function;

    b An operator:v opens the next downstream switch to isolate the faulty segment;v reconfigures the protection in substation breakers if necessary; andv closes the normally-open point to restore power downstream of the faulty segment.At this point, power is restored to the healthy parts of the network and it is possible for the operator to despatch the line crews to the faulted segment of the feeder to remove the fault. Once the entire feeder is healthy, the operator can open the normally-open point and close the sectionalisers to restore the network to the normal configuration.

    Figure 7: Automated Sectionaliser

    Sectionalising switchgear

  • 9

    Operational risksControl roomOnly the segments downstream of the fault are affected by the reaction time of the control room. It is therefore possible to prioritise the segments in the feeder and plan the restoration times for each one. In practice the reaction time for the remainder of the feeder is still influenced by the same factors as in a telecontrolled feeder.The impact of operators and the control room on the operational efficiency of this type of network is less than before.

    Fault passage indicationMonitored sectionalisers can be used for fault passage indication. Fully featured sectionalisers offer improved fault detection and controller capabilities. This may reduce false indication issues when features such as inrush restraint and cold load pickup are used. Additional FPIs can be installed to improve network monitoring.Similar to the telecontrolled switch network, communication failure can result in incorrect switching operations and an increase in the time taken to restore power.

    CommunicationsDue to the sectionaliser logic, the feeder upstream from the fault is unaffected by communication problems. However, communications are required to sectionalise the downstream portion of the network and to control the normally-open point. If a complete breakdown of communications is experienced, it is possible for the control room to use customer calls to determine the affected parts of the feeder. In this way the maintenance crews can focus their effort on the first sectionaliser within the "complaints area", open it and then close the normally-open point. Although not an ideal solution, in this case customers can be very helpful.

    Advantages b Relatively low initial cost of switchgear;

    b Power is automatically restored to the upstream portion of the feeder;

    b The importance of communications is slightly reduced although it is still required; Coordination between sectionalisers is easier.

    b Improved fault detection capabilities are possible; and

    b FPI functionality is provided by the sectionalisers.

    Disadvantages b Faults affect all the customers connected to a feeder;

    b Although improved, the level of automation is still low;

    b Expensive communications infrastructure is still required;

    b Operation is still dependent on the integrity of the communications network;

    b All faults cause substation circuit breaker operation - this results in a shorter service life; and

    b Protection functionality is limited. Only one circuit breaker to detect high fault levels near the substation or low fault levels some distance away.

    Evolving sophistication The operational risks were substantially reduced with the introduction of sectionalisers in the feeder. However due to the limited protection features and the faults affecting the entire feeder, this solution may not be suitable for high priority customers - especially industrial customers. Automatic circuit reclosers (reclosers) are designed to overcome these problems.

    Sectionalising Switchgear

  • 10

    Today's reclosers are capable of sophisticated protection, communication, automation and analytical functionality. With an abundance of processing power at their disposal, utilities have the flexibility to use the recloser as a standalone unit in a remote location, or to integrate several units into sophisticated substation automation systems. Whatever the application, the reclosers are flexible enough to evolve with the utility's requirements.Reclosers monitor current, voltage, frequency and the power flow direction to protect the feeder. By coordinating the reclosers correctly, only the recloser that is the closest to the fault will trip. This is very important for the successful implementation of reclosers. A recloser can be programmed to automatically reclose when it tripped due to a fault. In this way, power is restored automatically in the event of a transient fault. If however the fault is permanent the recloser will trip again and remain open. It is possible to have up to a maximum of 4 trips to lockout

    Coordination of reclosers To achieve current co-ordination on reclosers in series, the operating time of each recloser must be faster than any upstream device and slower than any downstream device. That is, for the typical recloser network shown in Figure 8 where a specific fault current is flowing through the network, "MP2" will trip quicker than "MP1" and "MP1" will trip quicker than "F". This ensures that only the recloser immediately upstream of the fault will trip. Pre-programmed Inverse Definite Minimum Time (IDMT) protection curves or definite time to trip are used for Phase and Earth Overcurrent protection. These protection curves allow close grading with substation protection relays and other protection devices. A safe margin (approximately 200 ms) between operating times of successive devices must be maintained for all fault levels on the network being protected.Feeders with different electrical characteristics require different protection strategies. Distribution Utilities worldwide have developed their own strategies to suit their particular system conditions. For example, fault analysis may show that the primary causes of transient faults on a network are:b lightning induced power surges;

    b wildlife getting caught in the power lines; and

    b trees or branches falling on the lines.

    Independent configuration of the time to trip for each protection operation in the reclose sequence allows the utilities to optimise the protection strategy for each network.The strategy could typically be:A - The fault is first assumed to be lightning related. A fast IDMT curve with a small time multiplier (eg 0.05x) and an instantaneous element is used to ensure short exposure to the initial fault current.B - This operation is followed by a very short reclose time (eg 0.5 sec) to limit the effects on electronic equipment such as PC's, VCR's, microwave ovens, etc.C - If the fault is not cleared, on the subsequent auto-reclose a slow IDMT curve with a long operating time allows tree or animal induced faults on rural spur lines to be cleared by upstream fuses.D - The reclose time that follows is long (eg 5 sec) to allow the animal or branch to fall clear of the line if it is on the feeder or did not cause fuse operation.E - If the fault is still present after the auto-reclose it is assumed to be permanent and a fast IDMT curve minimises exposure to fault currents.

    Figure 8: Typical time diagram of a reclose sequence

    Recloser systems

  • 11

    Basic operation during fault conditionsIt is possible to operate this type of network in either a "manual" mode where the operator has to perform the reconfiguration of the network, or in a "Loop Automation" mode where the reclosers perform all the task automatically.

    Manual modeIn the "manual mode" the following actions are taken:b The recloser immediately upstream of the fault automatically trips, recloses to lockout and remains open;

    b An operator:v determines the location of the fault from the recloser status and/or additional FPIs;v opens the next downstream recloser to isolate the faulty segment;v reconfigures the protection settings in anticipation of reverse power flow; andv closes the normally-open point to restore power downstream of the faulty segment.With power restored to the healthy parts of the network it is possible for the operator to despatch the line crews to the faulted segment of the feeder. Once the entire feeder is healthy, the operator can open the normally-open point, reconfigure, and close the reclosers to restore the network to the normal configuration.

    Figure 10: Solid Dielectric Recloser

    .

    NO

    F MP1 MP2

    F MP1 MP2TIE

    Substation circuit breaker/recloserClosed automatic circuit recloserOpen automatic circuit recloser

    Figure 9: Typical Recloser Network

    Recloser systems

  • 12

    Loop AutomationIt is important to note that protection is the first and foremost function of the reclosers, even in a loop automation scheme. A more sophisticated recloser is required to perform both protection and automation functions. In addition to these, the reclosers have to measure power flow and voltage on both sides of the recloser.To explain the basic operation of a Loop Automation scheme, let's first define the reclosers as follows:b Feeder recloser (F) - Recloser closest to the substation;

    b Tie (TIE) - The open point recloser where the two feeders meet. This is a normally-open point (NO); and

    b Mid-point reclosers (MP) - All the reclosers positioned between the Feeder and Tie reclosers.

    Each of these reclosers is programmed with a different set of rules when controlled by Loop Automation, which can be simplified as follows:b The Feeder recloser trips when it loses supply.

    b The Mid-point recloser changes to the reverse power flow protection settings when it loses supply.

    b The Tie recloser closes when it detects that supply to one side of the network has been lost.

    Loop Automation uses time, voltage, power flow and these simple rules to isolate the fault and reconfigure the network without any communications or operator assistance.In a loop automation network the following actions will take place when a fault occurs:b The recloser immediately upstream of the fault automatically trips, recloses to lockout and remains open;

    b Reclosers downstream of the fault automatically change the protection settings in anticipation of power flowing in the opposite direction; and

    b The normally-open tie recloser closes automatically.

    b Due to the fault still being present, the recloser immediately downstream of the fault trips and locks out without reclosing.

    This will automatically restore power to the healthy parts of the network. An operator can now despatch line crews to the faulted segment. It is also possible for the loop automation system to restore the original configuration when the fault is cleared.

    Recloser systems

  • 13

    Operational risksControl room In a manual system the segment downstream of the fault is affected by the reaction time of the control room. To assist the operator during feeder reconfiguration, recloser systems are capable of automatically applying forward or reverse protection settings when power flow changes. In such a system the operator is not required to change the settings in all the reclosers.A loop automation system does not require any operator intervention - all the operator has to do is despatch the line crews.

    Fault passage indicationThe ON/OFF status and even logs of reclosers are commonly used to determine the location of faults on feeders. With this inherent FPI functionality of the recloser, false indication is eliminated. Separate FPIs can be used in conjunction with the reclosers to assist the operators in determining the exact location of faults on long feeders.

    CommunicationsCommunications are not required at all in the loop automation scheme. However, it may be desirable in order to monitor the status of the network at several key points to assist maintenance crews.In a manual recloser system, the feeder upstream from the fault is unaffected by communication problems but communications are required to reconfigure the downstream portion of the network and to control the normally-open point.

    Advantages b Customers upstream from the fault are not affected at all.

    b The Loop Automation scheme does not require communications; and

    b Power is restored quickly without any operator intervention, when the loop automation scheme is used.

    b Advanced protection features are available;

    b Multiple groups of settings are pre-set to ensure an effortless feeder reconfiguration when needed.

    b Diagnostic tools are available with reclosers to assist in feeder analysis.

    b The manual system still requires communications although the importance is reduced;

    b With minimal effort the manual system can be upgraded to the loop automation system.

    Disadvantages b The manual system may still require communications and it can affect the integrity of the feeder.

    Evolving sophistication Reclosers provide a very robust system, capable of protecting the feeder irrespective of many operational factors. The number of customers affected by permanent faults is minimised. However to further improve the feeder's immunity to operational risks is very difficult and can be extremely expensive.To further improve these sophisticated networks, the focus shifts away from reducing operational risks to improving reliability of supply through feeder automation.

    Recloser systems

  • 14

    A feeder automation network combines reclosers and sectionalisers in a feeder to provide grading on both current/time and number of operations. This is accomplished by introducing up to two sectionalisers in each zone protected by a recloser.

    SI=3 2 SI=3 2 F MP

    F SI=3 SI=2 sect 1

    sect 2

    sect 3

    Closed automatic circuit recloserClosed sectionaliser

    Figure 11: Feeder Automation Network

    Basic operation during fault conditionsIn a feeder automation network the reclosers protect the downstream portion of the feeder up to the next recloser. Similarly to the recloser network described earlier, the recloser will trip and reclose in the presence of a fault and the sectionalisers count the through-faults similarly to the sectionalising switchgear network described earlier. The difference is that if the fault occurs downstream of a sectionaliser, the sectionaliser closest to the fault will open before the recloser reaches lockout. Therefore, for this system to work correctly, it is essential that the recloser is configured with four trips to lockout and the sectionalisers are configured with supply interrupt counters of three and two respectively.For a feeder using one sectionaliser instead of two, the recloser is set to three trips to lockout and the supply interrupt counter in the sectionaliser is set to two. Please see the sectionaliser timing diagram below for more information.

    The sectionaliser timing diagram shows the importance of having a recloser dead time greater than the sectionaliser operating time. If this rule is ignored the sectionaliser contacts can open when the power is ON. This will result in the switch interrupting fault current, which can drastically shorten the operational life of the switch, and the recloser will trip to lockout.

    Figure 12: Gas Insulated Recloser

    Operat ingt im e

    Sect ionaliser cont act posit ion ON

    OFF

    Sect ionaliser source side vo lt age LIVE

    DEAD

    Sect ionaliser Current Fault Zero

    Sect ionaliser Open com m and Tr ip Of f

    Recloser Dead t im e

    SI = SI+1

    Figure 13: Sectionaliser Timing Diagram

    Feeder automation

  • 15

    The logic of a feeder automation network is best explained using timing diagrams for different fault locations. Firstly, what happens when a fault occurs in Section 1?The recloser "F" trips to lockout, remains Open (OFF) and the sectionalisers do not change state.

    When a fault occurs in section 2 the recloser trips and recloses twice before the sectionaliser "S1" opens to isolate the fault. The third reclose operation restores power up to "S1". The recloser "F" sequence resets after the sequence reset time.

    A fault in section 3 will cause the recloser to trip and reclose once before the sectionaliser "S2" opens to isolate the fault. Both sectionalisers count the interruptions. The second reclose restores power upstream of "S2". The sequence resets in the recloser "F" and "S1" after the sequence reset time.

    Advantages b Improved supply reliability when the segments are broken into smaller sections, therefore reducing the length of feeder that can be isolated in the event of a fault.

    b Protection coordination is relative easy.

    b Flexible solutions are possible.

    b Existing recloser or sectionaliser networks can be upgraded to incorporate full feeder automation with relative ease.

    b The advantages of sectionalising switch and recloser networks are combined in feeder automation networks.

    b Creative protection solutions are possible at relatively low cost.

    b With full directional capabilities, the network will automatically reconfigure itself when the normally-open point is closed in the event of a fault.

    Figure 14: Fault in Section 1

    Figure 15: Fault in Section 2

    Figure 16: Fault in Section 3

    Feeder automation

  • 16

    When feeder automation is used in a looped network, it is necessary to consider using reclosers and sectionalisers with advanced capabilities such as directional protection and loop automation.With full directional capabilities, the reclosers and sectionalisers are configured for protection with power flowing in both the forward and reverse directions. Protection in both directions is active at any given point in time. This allows the utility to manually close the normally-open point in the event of a fault, without having to reconfigure the other switchgear in the feeder. It is therefore possible to focus on the communications link to the normally-open point and by ensuring that it is reliable, power restoration will always be possible.

    In a network using Loop Automation, the switchgear controllers will automatically reconfigure the protection settings during fault conditions. Operation is very similar to that of a recloser-only loop automation scheme. The major difference is that reclosing is allowed to enable sectionalising, however the SI settings are reduced.

    In the segment shown above, recloser "F" protects the segment during the normal configuration while recloser MP1 is protecting the segment when power is restored. In a forward direction the following settings are used:b "F" - forward protection and 4 trips to lockout.

    b "S1" - forward detection and SI = 3.

    b "S2" - forward detection and SI = 2.

    b "MP1" - forward protection and 4 trips to lockout.

    In the reverse direction the settings will change to:b "F" is the closest recloser to the substation. A fault upstream of "F" will cause a loss of supply at the recloser and it will open to isolate the substation. It therefore does not change protection settings.

    b "S1" - reverse detection and SI = 1.

    b "S2" - reverse detection and SI = 2.

    b "MP1" - reverse protection and three trips to lockout.

    With only one sectionaliser per segment the settings are slightly different.

    In a forward direction the following settings are used:b "F" - forward protection and 3 trips to lockout.

    b "S1" - forward detection and SI = 2.

    b "MP1" - forward protection and 3 trips to lockout.

    In the reverse direction the settings will change to:b "F" is the closest recloser to the substation. A fault upstream of "F" will cause a loss of supply at the recloser and it will open to isolate the substation. It therefore does not change protection settings.

    b "S1" - reverse detection and SI = 1.

    b "MP1" - reverse protection and two trips to lockout.

    A feeder automation network provides a flexible solution to any protection challenge and is capable of evolving with the distribution requirements.

    Figure 17: Feeder Automation Loop

    F S1 S2 MP1sect 1

    sect 2

    sect 3

    Norm al pow er f low direct ion

    Figure 18: Feeder Automation with 1 Sectionaliser

    F S1 MP1sect 1

    sect 2

    Norm al pow er f low d irect ion

    Feeder automation in a looped network

  • 17

    In the diagram below of a basic network, reclosers are used as substation breakers. Switchgear locations are indicated along the main-line and the length of each section is shown. The location of the sectionalisers used in analysing the feeder automation circuit is also shown on the diagram. These sectionalisers are ignored in the analysis of other network configurations.The load per feeder is typically 4MW with 2MW, 1.5MW and 0.5MW of load in segment A, B and C respectively. (A is the closest to the substation.)

    Network DescriptionThe basic network shown below will be used to analyse the cost implications of applying different levels of sophistication in a network. The network contains two radial feeders, tied together using a normally-open point. Each feeder comprises three segments and each segment contains two spur lines. The main-line of Feeder 1 is 37.5km long and the total length of the spur lines is 62.5km. Feeder 2's main-line is 40km long and the combined length of the spur lines is 60km. The overall length of each feeder is 100km and the network supplies power to and area of approximately 2000km².

    Figure 19: Network Example Used in Cost Analysis

    Cost analysis

  • 18

    Costs ConsideredThe cost of the MV infrastructure is assumed equal for all of the network configurations and is not included in this analysis. Communication modems and other equipment associated with the control room are also not part of the analysis.Table 4 provides a breakdown of the costs considered in the analysis. To remove the effects of exchange rates, the cost of each item is expressed as a multiple of the telecontrolled switch's cost. These relationships may vary slightly from country to country.The analysis firstly considers average revenue lost due to outages. This average is based on the level of sophistication, topology and segment lengths used in the network. The same average response and fault repair times were assumed for each network type. Although networks often evolve substantially during the useful service life of 30 years, this analysis assumed the same load distribution throughout the period.A telecontrolled switch network relies heavily on the integrity of the communications infrastructure to work reliability. Therefore the analysis includes an optical fibre communications line installed along the entire length of the main-line. Separate FPIs are also included for each switch.A dial-up or radio control network is assumed for both the sectionalising and manually controlled recloser networks. Although communications are not required in the automated recloser and feeder automation networks, some basic communications were included to alert the control room of automation actions. Due to the inherent FPI functionality of recloser and sectionalisers, separate FPIs are not included in the analysis where these devices are used.The analysis also refers to two types of reclosers and sectionalisers - advanced and normal. Additional features such as full directional protection capabilities, additional automation features (such as loop automation), and powerful analytical tools are available in the advanced products.

    ResultsThe analysis considers the initial capital investment and the impact of supply reliability to determine the optimum long-term investment. Table 4 shows the impact of each component in the analysis and helps to derive an order of preferred solutions to MV power distribution:1. Feeder Automation network,2. Automated Recloser network,3. Manual Recloser network,4. Sectionaliser network,5. Telecontrolled Switch network.The lack of sophistication in the telecontrolled switch network contributes to the high level of revenue lost due to outages and the cost of the communications network increases the cost of the initial investment substantially. These "hidden" costs are sometimes overlooked and can drastically reduce the return on investment. Although the feeder automation network requires the largest initial capital investment of all, the benefit of such a network is easily realised when the reduction in revenue loss due to outages are considered.

    ConclusionThis paper describes a range of protection and segmentation options available in today's technology-driven market. Although the options were explained using switchgear located on the main-line of the network, it is possible to apply the techniques to spur lines too. Existing networks can also keep up with future requirements by evolving to more sophisticated technology. In some cases it may be as easy as a firmware/software upgrade.Select your supplier carefully and ensure that the hardware platform is powerful and flexible enough to ensure sophistication where and when it is needed.

    Cost analysis

  • 19

    Cost analysis

    Glossary

    DescriptionCost Multiple TeleControlled Sectionaliser Manual Recloser Automated Recloser Feeder Automation

    Cost due to outages (30years) Qty Value Qty Value Qty Value Qty Value Qty Value

    TeleControlled 9.08 p/a 30 272 - - - -

    Sectionaliser 8.76 p/a - 30 263 - - -

    Man. Recloser 8.45 p/a - - 30 254 - -

    Auto. Recloser 7.65 p/a - - - 30 230 -

    Feeder Auto 4.58 p/a - - - - 30 137

    Protection equipment - - - - -

    Substation recloser 5 2 10 2 10 2 10 2 10 2 10

    TeleControlled Switch 1 5 5 - - - -

    FPIs 0.5 5 2.5 - - - -

    Sectionalisers 3 - 5 15 - - -

    Advanced Sectionalisers 4 - - - - 6 24

    Reclosers 5 - - 5 25 - -

    Advanced Reclosers 6 - - - 5 30 5 30

    Installed opticalfibre comms/km 0.3 77.5 23.25 - - -

    Phone or RadioCommunications per point 0.2 - 5 1 5 1 5 1 5 1

    Cost due to outages 272 263 254 230 137

    Cost of protection equipment 41 26 36 41 65

    Normalised cost 313 289 290 271 202

    Cost differential [%] -8 -8 -14 -35

    Table 4: Cost Analysis

    Term Description

    Cold Load Pickup When a feeder has been without power for an extended period of time the load will lose its diversity. All the thermostats will be turned on. That is air conditioners, fridges, freezers, hot water systems etc. will all turn on when the feeder is energised. This will cause an overload which can last for several minutes. Cold load pickup overcomes this effect.

    Dead time This is the duration where the recloser is OFF, after a protection trip and before it recloses.

    Inrush Restraint The short term overcurrent flowing through a feeder the instant it is energised is known as inrush current. Inrush restraint takes into consideration the short burst of these currents.

    Lockout Lockout is the state where the recloser remains open and no further close operation is possible until the operator resets the recloser.

    Operating Time This is the time it takes for a sectionaliser to OPEN after a trip command was issued.

    Supply Interrupt (SI) Counter A sectionaliser increments the supply interrupt counter when, after it detected a downstream fault, the current and voltage drop to zero.

  • As standards, specifications and designs change from time totime, please ask for confirmation of the information given in thispublication.

    Corporate office &factory35-37 South StreetLytton, 4178QueenslandAustralia

    Tel: +61 7 3249 5444Fax: +61 7 3249 5888

    e-mail: [email protected]://www.nulec.com.au

    Nu-Lec Industries USA officeNu-Lec LLCC/- Square D Services2979 Pacific Dr, Ste ENorcross, Georgia, 30071United States of America

    Tel: +1770 521 2000Fax: +1770 521 2100

    e-mail: [email protected]://www.nulec.com

    11/2006

    AD

    C-1

    018-

    NI