Multi Pressure Refrigeration Cycles

Embed Size (px)

Citation preview

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    1/41

    1

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    2/41

    Multi -pressure Systems

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    3/41

    Industrial refrigeration plants operate with a large

    difference between evaporating and condensing

    temperatures

    50 ~ 80 C

    Opportunities: Multi-stage compression, Flash gas,

    intercooling, number of evaporators at different

    temperatures

    Multipressure systems - classified as compound

    systemsor cascade systems

    Multi-stage compression used when ratio of suction to

    discharge pressure is high enough to cause a serious

    drop in efficiency or an unacceptably high discharge

    temperature

    Introduction

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    4/41

    A multi-pressure system is a refrigeration system that

    has two or more low side pressures

    The low side pressure is the pressure of the refrigerantbetween the expansion valve and the intake of

    compressor

    Different than the single pressure system which has but

    one low side pressure

    In Dairy where one evaporator operates at -35 C to

    harden ice cream while another evaporator operates at 2

    C to cool milk

    Two functions often integral to multi-pressure systems

    are; Removal of flash gas

    Inter-cooling

    Several combinations of multiple evaporators and

    compressors May have same or different refrigerants

    Introduction

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    5/41

    Flash gas - the mass of vaporized refrigerant per kg of

    total refrigerant which is just leaving the throttling valve Flash chamber/tank is that portion of the expansion

    valve system where liquid-vapour mixture of refrigerant

    gets accumulated before entering into the evaporator

    Saving in the power requirement results if the flash gasthat develops in the throttling process between the

    condenser and evaporator is removed and recompressed

    before complete expansion

    When saturated liquid expands through an expansion

    valve, the fraction of vapour or flash gas progressively

    increases

    Removal of F lash Gas

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    6/41

    Removal of F lash Gas

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    7/41

    The expansion process shown on the pressure enthalpy

    diagram takes place from 1 to 2

    The state point as the expansion proceeds moves into aregion of a greater fraction of vapour

    The end point of expansion, 2, could have been achieved

    by interrupting the expansion at 3 and separating the

    liquid vapour phases which are 4 and 6 respectively The expansion could then continued by expanding the

    liquid at 4 and the vapour at 6 to the final pressure, giving

    5 and 7 respectively

    The combination of refrigerant at 5 and 7 gives point 2

    The expansion process from 6 to 7 is wasteful because of

    the following two reasons;

    The refrigerant at 7 can do no refrigerating

    Work will be required to compress the vapour back to

    the pressure it had at 6

    Removal of F lash Gas

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    8/41

    Why not perform the part of expansion, separate the liquid

    from the vapour, continue expanding the liquid, and

    recompress the vapour without further expansion The equipment to achieve this separation is called a flash

    tank

    Removal of F lash Gas

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    9/41

    The expansion from 1 to 3 takes place through a float

    valve, which serves the further purpose of

    maintaining a constant level in the flash tank

    To recompress the vapour at 6, a compressor must be

    available with a suction pressure of 6

    Thus two compressors are needed in the system

    Removal of F lash Gas

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    10/41

    Intercooling between two stages of compression reduces

    the work of compression per kg of vapour

    Intercooling

    In two stage compression of air, for example an

    intercooler from point 2 to 4 on PV diagram saves some

    work

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    11/41

    This figure shows how compression with Intercooling

    appears on the ph diagram of a refrigerant Processes 1- 2 - 3 & 4 - 5 are on lines of constant entropy

    Between the same two pressures, therefore, process 4 5

    shows a smaller increase in enthalpy, which indicates that

    less work is required than in 2

    3

    Intercooling

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    12/41

    Between the two given pressures, the work of

    compression is proportional to the specific volume ofentering gas

    Sp. Volume at 2 is greater than it is at 4 so work required

    for compressing from 2 to 3 is greater than in

    compressing from 4 to 5

    Intercooling in a refrigerating system can be

    accomplished by two ways:

    Using a water cooled heat exchanger

    Using a refrigerant

    The water-cooled intercooler may be satisfactory for two-

    stage air compression, but for refrigerant compression,

    the water is usually not cold enough

    Multipurpose Refr igeration Systems

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    13/41

    Another way of Intercooling uses liquid refrigerant fromthe condenser to do the Intercooling

    Discharge gas from the low-stage compressor bubbles

    through the liquid in the intercooler

    Refrigerant leaves the intercooler at 4 as saturated vapour

    IntercoolingMultipurpose Refr igeration Systems

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    14/41

    Intercooling

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    15/41

    Intercooling

    Example: Calculate the power needed to compress 1.2 kg/s

    of ammonia from saturated vapour at 80 kPa to 1000 kPa (a)

    by single-stage compression and (b) by two stage

    compression with intercooling by liquid refrigerant at 300

    kPa.

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    16/41

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    17/41

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    18/41

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    19/41

    Heat & Mass Balance Around Intercooler

    &

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    20/41

    Heat & Mass Balance Around Intercooler

    O E t & O C

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    21/41

    One Evaporator & One Compressor

    With one compressor and one evaporator the flash tank may function as shown below

    A pressure reducing valve throttles the flash gas from the intermediate pressure to the

    evaporator pressure

    Throttling is necessary because there is no compressor available with a high suction

    pressure

    Calculations show that the flash tank does not improve the performance of the system and

    the system is used infrequently

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    22/41

    T E t & O C

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    23/41

    Two Evaporators & One Compressor

    A pressure reducing valve is installed after the high-temperature evaporator

    regulates the pressure and maintains a temperature in the air-conditioning

    evaporator of 5 C

    T C A d O E t

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    24/41

    Two Compressors And One Evaporator

    Two stage compression with Intercooling and removal of flash gas is often the ideal

    way to serve one low-temperature evaporator

    The system requires less power than with a single compressor

    T C A d O E t

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    25/41

    Two Compressors And One Evaporator

    T C & T E t

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    26/41

    Two Compressors & Two Evaporators

    The system which has two evaporators operating at

    different temperatures is common in industrial

    refrigeration Example of dairy cooling milk & manufacturing ice cream

    Frozen food plant requires two evaporators at different

    temperatures

    Evaporators at two different temperatures can be handled

    efficiently by a two-stage system which employs

    Intercooling and removal of flash gas

    Example

    In an ammonia system one evaporator is to provide 180 kW ofrefrigeration at -300C and another evaporator is to provide 200kW

    at 50C. The system uses two-stage compression with intercooling

    and is arranged as in Fig. Below. The condensing temperature is

    400C. Calculate the power required by the compressors.

    T C & T E t

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    27/41

    Two Compressors & Two Evaporators

    Press re Enthalp Diagram

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    28/41

    Pressure Enthalpy Diagram

    Solution: Sketch the pressure-enthalpy diagram as shown

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    29/41

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    30/41

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    31/41

    Two Compressors & Two Evaporators

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    32/41

    Two Compressors & Two EvaporatorsThe discharge pressure of the low-stage compressor and the suction pressure of the

    high-stage compressor are the same as the pressure in the 5 C evaporator.

    Next determine the enthalpies at the state points.

    The simplest way to calculate the mass rate of flow handled by the high-stage

    compressor is to make a heat and mass balance about the high-temperatureevaporator and the intercooler, as shown

    Two Compressors & Two Evaporators

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    33/41

    Two Compressors & Two Evaporators

    Two Compressors & Two Evaporators

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    34/41

    Two Compressors & Two Evaporators

    Multi Stage Systems

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    35/41

    35

    a. Compound

    Two low compression ratios = 1 high

    First stage compressor meets cooling load

    Second stage compressor meets load evaporator and

    flash gas

    Single refrigerant

    b. Cascade

    Preferred for -46 C to -101 C

    Two systems with different refrigerants

    Multi -Stage Systems

    Cascade Refr igeration Systems

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    36/41

    Very low temperatures can be achieved by operating two or more vapor-compression

    systems in series, called cascading.

    Cascade Refr igeration Systems

    65,21,

    inin

    LR

    WW

    QCOP

    Advantages:Different refrigerants, equipment, and oils can

    be used for the higher and the lower systems. Also, COP ofthe system increases.

    Disadvantage:High first cost; More complicated.

    Cascade Refr igeration Systems

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    37/41

    Consider a two-stage cascade refrigeration system operating between the pressure

    limits of 0.8 and 0.14 MPa. Each stage operates on an ideal vapor compression cycle

    with R134a as the working fluid. Heat rejection from the lower cycle to the upper

    cycle takes place in an adiabatic counterflow heat exchanger where both streamsenter at about 0.32 MPa. If the mass flow rate of the refrigerant is 0.05kg/s,

    determine

    (a) The mass flow rate of the refrigerant through the lower cycle,

    (b) The rate of heat removal from the refrigerated space and the power input to the

    compressor,

    (c) The COP of the refrigerator.

    Cascade Refr igeration Systems

    Multistage Compression with F lash Chamber

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    38/41

    Multistage Compression with F lash Chamber

    I ntercooling (Compound System)

    Optimum Intermediate pressure?

    Multistage Compression with F lash Chamber

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    39/41

    Multistage Compression with F lash Chamber

    I ntercooling (Compound System)

    The optimum intermediate pressure is given by:

    The optimum intermediate pressure in a two-stage refrigeration system is quite close,

    but not equal, to that shown in above equation. The reason for the deviation is that the

    cooling process in air compression is without cost, but in the refrigeration system there

    is a power cost associated. with compressing the refrigerant vapor that performs thecooling.

    Interstage pressure is usually set so that the compression ratio at each stage is nearly

    the same for higher COPs.

    Multistage Compression with F lash Chamber

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    40/41

    Consider a two-stage cascade refrigeration system operating between the pressure

    limits of 0.8 and 0.14 MPa as before but, this time, with a flash chamber operating at

    0.32 MPa. Determine

    (a) The fraction of the refrigerant that evaporates as it is throttled to the flash

    chamber,

    (b) The amount of heat removed from the refrigerated space and the compressor

    work per unit mass of refrigerant flowing through the condenser,

    (c) The COP of the refrigerator.

    Multistage Compression with F lash Chamber

    I ntercooling (Compound System)

    Multipurpose Refr igeration Systems

  • 7/22/2019 Multi Pressure Refrigeration Cycles

    41/41

    A refrigerator with a single compressor can provide refrigeration at several

    temperatures by throttling the refrigerant in stages.

    Multipurpose Refr igeration Systems

    Assignment:Whats the COP and heat transfer amounts for conditions used in

    the previous problem (Check for both paths)? Assume QL,Ris a third of QL,F.

    Also called

    pressure-regulating

    valve