3
1 1/4" Install a minimum of (4) 10d nails into the top Install a minimum of (6) 10d nails into the face Install a minimum of (12) 10d nails into back MUGT15 Support Beam Designed By Others Min 3" x 3" x 1/4" Bearing Plate 5/8" Bolt USP supplies quality products to build Stronger Safer Structures www.USPconnectors.com Use in conjunction with USP’s current Canadian Product Catalogue for detailed hanger information. USP2320-MUGT15 Revised September 2014 Designed for higher uplift resistance for wood frame and concrete block construction. The MUGT15 can accommodate various truss bearing depths. Materials: 12 gauge Finish: G90 galvanizing Codes: Factored resistances are derived from data submitted to various North American building code evaluators and are in accordance with CSA O86-09. Installation: • Use all specified fasteners. • When straps are wrapped over the truss, install nails in backside of truss. See MUGT15 installation diagram for mini- mum nail requirements into the face and on top of the truss. • If installed straight-up with no wrap over the top of the truss, fill all nail holes. Moisture barrier may be required. MUGT15 Girder Tiedown Typical MUGT15 wood installation with PHD4A MUGT15 14 5 / 8˝ 2 7 / 16˝ 3 11 / 16˝ 1 1 / 4˝ 1 1/4˝ Install a minimum of (4) 10d nails into the top Install a minimum of (6) 10d nails into the face Typical MUGT15 to support beam installation PHD4A PHD4A Top Face Back Ref. No. Qty Dia. Qty Qty Qty Type Lbs kN Lbs kN Face-Max 1 5/8 -- -- 28 -- -- 10d 4650 20.69 4000 17.79 Top-Min 1 5/8 4 6 12 10d 4320 19.22 3715 16.53 1) Factored resistances have been increased 15% for short-term loads such as wind and earthquake; reduce for other load durations in accordance with the code. 2) Additional anchorage products to be designed by others. 3) Designer must specify anchor bolt type, length, and embedment. 4) NAILS: 10d nails are 0.148˝ dia. x 3˝ long. Anchor Bolt 3 Rafter/Truss DF-L S-P-F Factored Uplift Resistance (115%) 1 Fastener Schedule 2,3,4 MUGT15 MGT 12 Mounting Condition USP Stock No. Steel Gauge

MUGT15 Girder Tiedown - USP Connectors and are in accordance with CSA O86-09. Installation: • Use all specified fasteners. • When straps are wrapped over the truss, install nails

  • Upload
    lamkien

  • View
    230

  • Download
    3

Embed Size (px)

Citation preview

Page 1: MUGT15 Girder Tiedown - USP Connectors and are in accordance with CSA O86-09. Installation: • Use all specified fasteners. • When straps are wrapped over the truss, install nails

1 1/4"

Install a minimumof (4) 10d nailsinto the top

Install a minimumof (6) 10d nailsinto the face

Install a minimumof (12) 10d nailsinto back

MUGT15

Support BeamDesignedBy Others

MUGT15 CONNECTIONTO SUPPORT BEAM

Min 3" x 3" x 1/4"Bearing Plate

5/8" Bolt

USP supplies quality productsto build Stronger Safer Structures

www.USPconnectors.com

Use in conjunction with USP’s current Canadian Product Catalogue for detailed hanger information.

USP2320-MUGT15Revised September 2014

Designed for higher uplift resistance for wood frame and concrete block construction. The MUGT15 can accommodate various truss bearing depths.

Materials: 12 gaugeFinish: G90 galvanizingCodes: Factored resistances are derived from data submitted to various North American building code evaluators and are in accordance with CSA O86-09.

Installation:• Use all specified fasteners. • When straps are wrapped over the truss, install nails in backside of truss. See MUGT15 installation diagram for mini-mum nail requirements into the face and on top of the truss.• If installed straight-up with no wrap over the top of the truss, fill all nail holes.• Moisture barrier may be required.

MUGT15 Girder Tiedown

Typical MUGT15wood installation

with PHD4A

MUGT15

14 5/8˝

2 7/16˝3 11/16˝

1 1/4˝

1 1/4˝

Install a minimumof (4) 10d nailsinto the top

Install a minimumof (6) 10d nailsinto the face

PHD4Apage 41

Typical MUGT15to support beam

installation

PHD4A

PHD4A

Top Face Back

Ref. No. Qty Dia. Qty Qty Qty Type Lbs kN Lbs kNFace-Max 1 5/8 -- -- 28 -- -- 10d 4650 20.69 4000 17.79Top-Min 1 5/8 4 6 12 10d 4320 19.22 3715 16.53

1) Factored resistances have been increased 15% for short-term loads such as wind and earthquake; reduce for other load durations in accordance with the code. 2) Additional anchorage products to be designed by others. 3) Designer must specify anchor bolt type, length, and embedment. 4) NAILS: 10d nails are 0.148˝ dia. x 3˝ long.

Anchor Bolt3 Rafter/Truss DF-L S-P-FFactored Uplift Resistance (115%)1Fastener Schedule2,3,4

MUGT15 MGT 12

MountingCondition

USPStock No.

SteelGauge

jting
ON
jting
2015
jting
Typewritten Text
Sept. 12, 2014
Page 2: MUGT15 Girder Tiedown - USP Connectors and are in accordance with CSA O86-09. Installation: • Use all specified fasteners. • When straps are wrapped over the truss, install nails

1 1/4"

Install a minimumof (4) 10d nailsinto the top

Install a minimumof (6) 10d nailsinto the face

Install a minimumof (12) 10d nailsinto back

MUGT15

Support BeamDesignedBy Others

MUGT15 CONNECTIONTO SUPPORT BEAM

Min 3" x 3" x 1/4"Bearing Plate

5/8" Bolt

USP supplies quality productsto build Stronger Safer Structures

www.USPconnectors.com

Use in conjunction with USP’s current Canadian Product Catalogue for detailed hanger information.

USP2320-MUGT15Revised September 2014

Designed for higher uplift resistance for wood frame and concrete block construction. The MUGT15 can accommodate various truss bearing depths.

Materials: 12 gaugeFinish: G90 galvanizingCodes: Factored resistances are derived from data submitted to various North American building code evaluators and are in accordance with CSA O86-09.

Installation:• Use all specified fasteners. • When straps are wrapped over the truss, install nails in backside of truss. See MUGT15 installation diagram for mini-mum nail requirements into the face and on top of the truss.• If installed straight-up with no wrap over the top of the truss, fill all nail holes.• Moisture barrier may be required.

MUGT15 Girder Tiedown

Typical MUGT15wood installation

with PHD4A

MUGT15

14 5/8˝

2 7/16˝3 11/16˝

1 1/4˝

1 1/4˝

Install a minimumof (4) 10d nailsinto the top

Install a minimumof (6) 10d nailsinto the face

PHD4Apage 41

Typical MUGT15to support beam

installation

PHD4A

PHD4A

Top Face Back

Ref. No. Qty Dia. Qty Qty Qty Type Lbs kN Lbs kNFace-Max 1 5/8 -- -- 28 -- -- 10d 4650 20.69 4000 17.79Top-Min 1 5/8 4 6 12 10d 4320 19.22 3715 16.53

1) Factored resistances have been increased 15% for short-term loads such as wind and earthquake; reduce for other load durations in accordance with the code. 2) Additional anchorage products to be designed by others. 3) Designer must specify anchor bolt type, length, and embedment. 4) NAILS: 10d nails are 0.148˝ dia. x 3˝ long.

Anchor Bolt3 Rafter/Truss DF-L S-P-FFactored Uplift Resistance (115%)1Fastener Schedule2,3,4

MUGT15 MGT 12

MountingCondition

USPStock No.

SteelGauge

jting
Typewritten Text
Sept. 24, 2014
jting
AB
jting
BC
jting
Typewritten Text
Sept. 24, 2014
jting
MB
jting
Typewritten Text
Sept. 24, 2014
jting
SK
jting
Typewritten Text
Sept. 24, 2014
jting
2015
Page 3: MUGT15 Girder Tiedown - USP Connectors and are in accordance with CSA O86-09. Installation: • Use all specified fasteners. • When straps are wrapped over the truss, install nails

1 1/4"

Install a minimumof (4) 10d nailsinto the top

Install a minimumof (6) 10d nailsinto the face

Install a minimumof (12) 10d nailsinto back

MUGT15

Support BeamDesignedBy Others

MUGT15 CONNECTIONTO SUPPORT BEAM

Min 3" x 3" x 1/4"Bearing Plate

5/8" Bolt

USP supplies quality productsto build Stronger Safer Structures

www.USPconnectors.com

Use in conjunction with USP’s current Canadian Product Catalogue for detailed hanger information.

USP2320-MUGT15Revised September 2014

Designed for higher uplift resistance for wood frame and concrete block construction. The MUGT15 can accommodate various truss bearing depths.

Materials: 12 gaugeFinish: G90 galvanizingCodes: Factored resistances are derived from data submitted to various North American building code evaluators and are in accordance with CSA O86-09.

Installation:• Use all specified fasteners. • When straps are wrapped over the truss, install nails in backside of truss. See MUGT15 installation diagram for mini-mum nail requirements into the face and on top of the truss.• If installed straight-up with no wrap over the top of the truss, fill all nail holes.• Moisture barrier may be required.

MUGT15 Girder Tiedown

Typical MUGT15wood installation

with PHD4A

MUGT15

14 5/8˝

2 7/16˝3 11/16˝

1 1/4˝

1 1/4˝

Install a minimumof (4) 10d nailsinto the top

Install a minimumof (6) 10d nailsinto the face

PHD4Apage 41

Typical MUGT15to support beam

installation

PHD4A

PHD4A

Top Face Back

Ref. No. Qty Dia. Qty Qty Qty Type Lbs kN Lbs kNFace-Max 1 5/8 -- -- 28 -- -- 10d 4650 20.69 4000 17.79Top-Min 1 5/8 4 6 12 10d 4320 19.22 3715 16.53

1) Factored resistances have been increased 15% for short-term loads such as wind and earthquake; reduce for other load durations in accordance with the code. 2) Additional anchorage products to be designed by others. 3) Designer must specify anchor bolt type, length, and embedment. 4) NAILS: 10d nails are 0.148˝ dia. x 3˝ long.

Anchor Bolt3 Rafter/Truss DF-L S-P-FFactored Uplift Resistance (115%)1Fastener Schedule2,3,4

MUGT15 MGT 12

MountingCondition

USPStock No.

SteelGauge

jting
2015
jting
PEI
jting
NF
jting
NS
jting
NB
jting
Typewritten Text
Sept. 24, 2014
jting
Typewritten Text
Sept. 24, 2014
jting
Typewritten Text
Sept. 24, 2014
jting
Typewritten Text
Sept. 24, 2014