MSA-RM-2 Relay Module For MINI-SCREEN ® and MICRO-SCREEN ® Systems Printed in USA P/N 59664 MSA-RM-2 Relay Module Features FSD1, FSD2, and CNC outputs are rated for 6 amps (resistive) at 250V ac. SSD is rated for 4 amps (resistive) at 250V ac. If a MINI-SCREEN or MICRO-SCREEN manual is accompanied by this data sheet, the optional MSA-RM-2 Relay Module is factory-installed in the control box. Important Information It is important for the safe operation of the light screen system that the user comply with all relevant product manuals and regulations. If the Complementary Normally Closed Auxiliary output (“CNC AUX”) is used as a stand-alone output (it is not interfaced with one or both of the FSD outputs), it is a non-safety-related output. The CNC AUX output is typically used for monitoring purposes and may not be suitable for safety applications. The CNC AUX output status is the opposite of the FSD1 and FSD2 safety outputs. The figure on page 2 shows the output relay connections in a generic interfacing solution. The connections between the safety light screen outputs and the machine primary and secondary control elements must be direct, and arranged so that any single line fault or earth fault will not result in a circuit failure to a potentially dangerous state. WARRANTY: Banner Engineering Corp. warrants its products to be free from defects for one year. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture found to be defective at the time it is returned to the factory during the warranty period. This warranty does not cover damage or liability for the improper application of Banner products. This warranty is in lieu of any other warranty either expressed or implied.

MSA-RM-2 Relay Module

Embed Size (px)

DESCRIPTION

Banner Module ManualMSA-RM-2 Relay Module

Citation preview

  • MSA-RM-2 Relay ModuleFor MINI-SCREEN and MICRO-SCREEN Systems

    Printed in USA P/N 59664

    MSA-RM-2 Relay Module Features FSD1, FSD2, and CNC outputs are rated for 6 amps (resistive) at 250V ac.

    SSD is rated for 4 amps (resistive) at 250V ac.

    If a MINI-SCREEN or MICRO-SCREEN manual is accompanied by this data sheet,the optional MSA-RM-2 Relay Module is factory-installed in the control box.

    Important Information

    It is important for the safe operation of the light screen system that the user complywith all relevant product manuals and regulations.

    If the Complementary Normally Closed Auxiliary output (CNC AUX) is used as astand-alone output (it is not interfaced with one or both of the FSD outputs), it is anon-safety-related output. The CNC AUX output is typically used for monitoringpurposes and may not be suitable for safety applications. The CNC AUX output status isthe opposite of the FSD1 and FSD2 safety outputs.

    The figure on page 2 shows the output relay connections in a generic interfacingsolution. The connections between the safety light screen outputs and the machineprimary and secondary control elements must be direct, and arranged so that anysingle line fault or earth fault will not result in a circuit failure to a potentially dangerousstate.

    WARRANTY: Banner Engineering Corp. warrants its products to be free from defects for one year. Banner Engineering Corp. will repair orreplace, free of charge, any product of its manufacture found to be defective at the time it is returned to the factory during the warrantyperiod. This warranty does not cover damage or liability for the improper application of Banner products. This warranty is in lieu of anyother warranty either expressed or implied.

  • Banner Engineering Corp., 9714 Tenth Ave. No., Minneapolis, MN 55441 Phone: 888.373.6767 www.baneng.com E-mail: [email protected]

    MSA-RM-2 Relay Module

    TB1

    MSCE

    Machine SecondaryControl Element

    Secondary SwitchingDevice

    SSD

    MINI-SCREEN or MICRO-SCREEN Control Box

    MINI-SCREEN or MICRO-SCREEN

    Control Box

    Arc Suppression(see warning)

    TB1

    Machine PrimaryControl Element #1

    Arc Suppression(see warning)

    TB1

    K1

    K1K2

    K2

    K1

    K2

    Machine PrimaryControl Element #2Final SwitchingDevice #2

    FSD 2

    Arc Suppression(see warning)

    MachineControlCircuit

    TB1

    TB1TB1

    MPCE1 MPCE2

    MPCE1

    MPCEMonitorContacts

    MPCE2

    Final SwitchingDevice #1

    FSD 1

    ComplementaryNormally Closed

    Auxiliary

    CNCAUX

    MPCE1

    EarthGround

    *N (V ac)or

    (V dc)

    *N (V ac) or (V dc)

    *L (V ac)or

    + (V dc)

    *L (V ac) or + (V dc)

    MPCE2

    WARNING . . . Arc SuppressorsNever install arc suppressors directly across the output contacts of any safeguarding device.If arc suppressors are used, they must be installed as shown across the coils of the safety relays. It is possiblefor suppressors to fail as a short circuit.

    If installed directly across the contacts of a safety light screen switching device, a short-circuited suppressor will create anunsafe condition that could result in serious injury or death.

    WARNING . . . Use All Safety Light Screen Output ContactsAll MINI-SCREEN (or MICRO-SCREEN) System output contacts (FSD1, FSD2, and SSD) must be used.The generalized wiring configuration shown here is provided only to illustrate the importance of proper installation.

    The specific actual wiring of the safety light screen system to any particular machine is solely the responsibility of theinstaller and end user.

    *WIRING NOTE:In USA and Canadian 115V ac and European 230Vac supply systems, L is ac hot and N is acneutral. In USA and Canadian 230V ac systems,L and N are both ac hot.

    Generic Machine Interface, MINI-SCREEN or MICRO-SCREEN System