A publication of Tyco Electronics Handbook for the MPO system Thorsten Punke Dipl. Ing. Global Program Manager Building Networks Program Manager Data Center EMEA

MPO Handbook Customer

Embed Size (px)

DESCRIPTION

Manual

Citation preview

  • A publication of Tyco Electronics

    Handbook for the MPO system

    Thorsten Punke Dipl. Ing. Global Program Manager Building Networks

    Program Manager Data Center EMEA

  • 2

    MPO ASSEMBLY Description The MPO optical fiber system is made up of pre-terminated multi-core optical fibre cables (trunks) that plug into pre-terminated optical fiber cassettes. The MPO optical fibre cable consists of 12 core, pair-wise flipped, optical fiber cable trunk terminated in 12-way, MPO connectors that plug into a straight optical fiber cassette, at each end. The MPO system is available in multimode and singlemode versions. The trunks are available in customized lengths. The AMP NETCONNECT MPO system is designed to provide very low loss and requires an odd number of cross-overs in the channel to comply with TIA-568-B1-7 Connectivity method C. The MPO system components are manufactured and tested at the Tyco Electronics AMP NETCONNECT optical fiber assembly manufacturing plant. When the system is installed on site, it is required to be field tested in accordance with ISO/IEC 14763-3 (1 Jumper or Three test cord method) using a light source- power meter test set.

    Diagram A (Equipment cross-connect)

    Diagram B (Equipment to fanout option)

  • 3

    Diagram D (MPO fanout extension system)

    Diagram C (Equipment inter-connect)

  • 4

    559552-2 Fibre Enclosure 0-1671082-8 Drawer panel 1671114-4 Breakout-Panel for 3 MPO Cassettes 4RU accepts 12 Cassettes 1RU accepts 3 Cassettes 1-711314-x Rear Cable Manager (fits to the back of a Rack Rail for MPO and MRJ21) 0-1711314-2 MPO back cable manager 175 mm depth 0-1711314-3 MPO back cable manager 275 mm depth

    MPO cassette LC OM3 12 fold straight 1 x MPO 12 x LC/PC

    0-1920209-7

    MPO cassette LC , OM3 12 fold pair flipped 1 x MPO 12 x LC/PC

    0-1920209-8

    MPO cassette LC, OM3 24 fold straight 2 x MPO 24 x LC/PC

    0-1920033-7

    MPO cassette LC, OM3 24 fold pair flipped 2 x MPO 24 x LC/PC

    0-1920033-8

    MPO cassette SC, OM3 12 fold straight 1 x MPO 12 x SC 0-6695133-1 MPO cassette SC, OM3 12 fold pair flipped 1 x MPO 12 x SC 1-6695133-1 MPO patch panel 96 port, OM3

    96 fold, straight 8 x MPO 96 LC/ PC

    0-1966328-1

    MPO patch panel 96 port, OM3

    96 fold, flipped 8 x MPO 96 LC/ PC

    2-1966328-1

    MPO cassette LC, OS2 12 fold straight 1 x MPO 12 x

    LC/PC 0-1920209-1

    MPO cassette LC, OS2 12 fold flipped 1 x MPO 12 x LC/PC

    0-1920209-2

    MPO cassette LC, OS2 24 fold pair flipped 2 x MPO 24 x LC/PC

    0-1920033-2

    MPO cassette LC, OS2 24 fold pair straight 2 x MPO 24 x LC/PC

    0-1920033-1

  • 5

    MPO trunk cable MPO trunk cables shall be used in all areas where some robustness is required, such as backbone cabling, dado trunking and construction sites with rough mechanical conditions.

    Fan-Out MPO: MPO (Female) LC&SC 12 x SC Duplex 12x LC Duplex OS1 9/125 m (Yellow) x-1920112-x x-6695463-x OM3 50/125 m 10 Gb/s XG (Aqua) x-6695460-x x-6695464-x

    MPO Patch Cords MPO patch cords shall be used for equipment cabling and in controlled environments such as a data center where the cabling is installed in pathways, open trays or other cabling supporting systems (AMP Hi-D). Trunk: Fibre type Ribbon Style straight Female/Female OS1 9/125 m (Yellow) OS2 y-6391907-x OM3 50/125 m 10 Gb/s XG (Aqua) Y-639108-x

    Y- - X Length 0- -5 5 m 1- -0 10 m 1- -5 15 m 2- -0 20,0

    Trunk: 12 Fibre type Ribbon Style straight OS1 9/125 m (Yellow) OS2 x-2055161-x OM3 50/125 m 10 Gb/s XG (Aqua) x-2055158-x

    Fan-Out MPO: MPO (Male) connection to cassettes LC&SC to active equipment) 12 x SC Duplex 12x LC Duplex OS1 9/125 m (Yellow) x-1920357-x x-1920353-x OM3 50/125 m 10 Gb/s XG (Aqua) x-1920356-x x-1920352-x

  • 6

    MPO Trunk Assembly Performance Characteristics Multimode Trunk Assembly Description The MPO trunk assembly consists of OM3 type optical fibres, laid together to form a 12 core cable (round distribution style or flat ribbon style), and terminated in a 12 fibre MPO connector at each end. The cable jacket material is LSZH type. Overall cable diameter: Round Distribution Flat Ribbon Round Distribution style: 6.4 mm (nom) 5.0 x 2.0 mm (nom) Minimum Bending Radius during install: 140 mm 100 mm Minimum Bending Radius after install: 130 mm 80 mm Nominal Mass: 32 kg/km Maximum Pulling Tension during install1: 350 N Insertion Loss @ 850 nm: 0.5 dB per mated MPO pair

    excluding optical fibre cable loss (3 dB/km) Return Loss @ 850 nm: 25 dB per mated MPO pair Minimum Bandwidth @ 850 nm: 1500/2000 MHz*km Minimum Bandwidth @ 1300 nm: 500/500 MHz*km Singlemode Trunk Assembly Description The MPO trunk assembly consists of OS2 type optical fibres, laid together to form a 12 core cable, terminated in a 12 fibre MPO connector at each end. The cable jacket material is LSZH type. Overall cable diameter: Round Distribution Flat Ribbon Round Distribution style: 6.4 mm (nom) 5.0 x 2.0 mm (nom) Minimum Bending Radius during install: 140 mm 100 mm Minimum Bending Radius after install: 130 mm 80 mm Nominal Mass: 32 kg/km Maximum Pulling Tension during install: 350 N Insertion Loss @ 1310 nm: 0,5 dB per mated MPO pair

    Excluding optical fibre cable loss (1.0 dB/km)

    Return Loss @ 1310 nm: > 35 dB

    ISO/IEC 11801, AS/NZS 3080 ISO/IEC 611754-7, ISO/IEC 61280-4-1 TIA/EIA-455-21A, FOTP-21A, Mating Durability of Fiber Optic Interconnecting

    Devices. TIA /EIA 604-5 FOCIS 5, TIA / EIA 568-B.1-7

    1 With installed pulling sock

  • 7

    Male and Female connectivity MT-technology always needs male and female connectivity. The guide pins act here as a kind of sleeve function, as in single ferrule technology.

    MPO products from Tyco Electronics have the following configuration as standard: Product Male/Female Cassettes Male Trunk cables Female MPO patch cord Female MPO Transceiver Male MPO Fanout Female Note: All cassettes have a male MPO connector; hence any trunk cable must have a female connector

    MPO cable straight configuration and without pins

    MPO male and female connector

  • 8

    Note: In principle all these products can be built in the opposite way, ie cassettes have no pins but the cables have pins etc. Fan out assemblies The configuration for fan out cords can be different from that which applies in particular for direct connections. Application: Fan out assemblies are most likely to be used as a direct connection to a switch. The application is the same as for MRJ21 to RJ45 connectors. In the case of MPO one assembly is with, the other one without pins.

    MPO coupler with 2 MPO connectors

  • 9

    Duplex Patch Cord Specification Description: TYCO ELECTRONICS duplex mini-zip cables designed to be used in patch leads within buildings. Optical Fibre Performance Characteristics 50/125 OM3 Multi-mode Fibres

    Bandwidth (MHz x Km)

    Max Link Length For 1Gbit/s (m)

    Max. Attenuation per Fibre (db/km) (Incoming fiber)

    Diameter (m)

    ISO/IEC 11801 850nm 1300nm 850nm 1300nm 850nm 1300nm Core Cladding OM3 (10 Gbit/s) 1500 500 300 - 3.5 1.5 50 125 Connector Specifications Connector Type: LC IEC 61754-20; TIA/EIA 604-10

    SC IEC 60874-14-x; IEC 61754-4 Test Method: relevant parts of IEC61300-x-x Insertion Loss (typ.) < 0,3 dB Return Loss (typ.) > 30 dB (MM); > 45 dB (SM) Durability > 500 mating cycles Optical fiber Cable Assemblies (Patch-cords): Optical fibre patchcords are constructed of OM3 duplex fibre cable terminated in LC duplex connectors, at both ends. These cable assemblies are available in Aqua as a standard product. Note: The standard solution in nowadays is OM3. This allows one system solution for a wide range of applications.

    2 Fibre Duplex cable

    Aramid yarn strength members

    Low smoke outer jacket

  • 10

    Patchcord Specification External diameter: 3.7 x 1.8mm Bend Radius (service): 25 mm Bend Radius (installation): 25 mm Max. Tension (installation/service): 220/150 N Crush Resistance: 2000 N /10cm Smoke Density: Yes Halogen free: Yes

    The cable assemblies are available in the following standard lengths: 1m, 2 m, 3m, 5m, 10m, 15m. OM3 patch cords have controlled endfaces. Typ Description Part Number LC-Duplex/LC-Duplex 10 GBit XG, 50/125, OM3, MM Y-6536969-X LC-Duplex/LC-Duplex 9/125 m, SM Y-6536501-X SC-Duplex/SC-Duplex 10 GBit XG, 50/125, OM3, MM Y-6536464-X SC-Duplex/SC-Duplex 9/125 m, SM Y-6348260-X SC-Duplex/LC-Duplex 10 GBit XG, 50/125, OM3, MM Y-6536967-X SC-Duplex/LC-Duplex 9/125 m, SM Y-6536508-X Other lengths are available on request.

    Y- - X Length 0- -1 1,0 m 0- -2 2,0 m 0- -3 3,0 m 0- -5 5,0 1- -0 10,0 m

  • 11

    Optical Performance Description The MPO cassette consists of one or two, twelve core OM3/OS2 type, optical fibre cable assemblies, each assembly terminated in a 12 fiber MPO connector at one end and simplex or duplex optical fiber connectors at the other end. These connectors may be LC or SC type. The assembly is put together in a metal enclosure that can be installed in a horizontal 1 RU optical fiber enclosure that can hold up to three such cassettes. Alternatively, the cassette can be mounted vertically in a 4 U optical fiber enclosure that can hold up to 12 such cassettes.

    Mechanical Properties Material: Aluminum Colour Finish: Black Height: 27.6 mm Width: 129.5 mm Depth: 114.0 mm Maximum number of simplex fibre ports per cassette: 24 Maximum number of MPO trunk ports: 2 Maximum number of cassettes in 1 U enclosure: 3 Maximum number of cassettes in 4 U enclosure: 12 Customer Interface type: LC-D, SC-D Optical Performance Multimode Insertion Loss @ 850 nm: 1 dB per MPO cassette Return loss @ 850 nm 30 dB per MPO cassette Singlemode Insertion Loss @ 1310 nm: 1.0 dB per MPO cassette Return loss @ 1310 nm 35 dB per MPO cassette

  • 12

    MPO Polarity Configurations

    In each fiber optic system, the link from Transmitter (Tx) to receiver (Rx) needs to be flipped once. In a complete MPO link this flipping is provided by one flipped cassette, whilst all other components in this link shall be installed as straight version. The picture above is the standard configuration and ensures at any time that the link is working. The picture below shows a 4 cassette example.

    Note: The Tyco Electronics solution is a straight trunk cable and one flipped cassette in the channel.

    MPO polarity with 4 cassettes

    Configuration of straight and flipped versions

  • 13

    Patch cords All patch cords shall be as shown in the picture below. This configuration is defined in all global cabling standards such as:

    IS 11801 2007 TIA/EIA-568-B.1 EN 50173 2007

    Patch cords from Tyco Electronics follow this configuration even though they offer a removable clip. This clip shall be used only in case of installed channels which are not standard compliant.

  • 14

    Optical Fibre Enclosures 1-U patch panel or frontplate The 1-U patch panel accepts up to three (3) Snap-in Adapter Plates or MPO Cassettes. The cassettes or adaptor plates (including blank plates) can be quickly inserted into the front panel using the quick release mechanism. The enclosure fits into standard 19" racks and includes side mounting ears, fiber management rings, cable strain relief and standard glands in the rear.

    The enclosure can support the following connectivity:

    1. A total of three MPO cassettes (maximum 36 (72 simplex) duplex connectors) 2. A total of 3 LC-duplex adapter plates (maximum 36 duplex (72 simplex)

    connectors) 3. A total of 3 SC-duplex adaptor plates (maximum 18 duplex (36 simplex)

    connectors) Configuration Fibers 10 GB/s channels 1 adapter plate (6xMPO) 72 36 2 adapter plate (12xMPO) 144 72 3 adapter plate (18xMPO) 216 108 Description Part Number 1U Drawer panel for 3 MPO cassettes1U patch panel (w/o) glands&managers)

    0-1671082-8

    1U Drawer panel for 3 Snap-in-Modules /with glands&managers) 0-1348876-4 MPO coupler 6x12 fibers 0-1374598-1 Blank module 0-1671146-1

  • 15

    4-U Enclosure The 4-U high enclosure accepts up to twelve (12) snap-in adapter plates or MPO Cassettes. The cassettes or adaptor plates (including blank plates) can be quickly inserted into the enclosure using the quick release mechanism. The enclosure fits into standard 19" racks and includes side mounting ears and optical fiber patch-cord management at the front including plastic D-rings.

    The enclosure can support the following connectivity:

    1. A total of twelve MPO cassettes (maximum 144 duplex (288 simplex) connectors) 2. A total of twelve LC-duplex adapter plates (maximum 144 duplex (288 simplex)

    connectors); 3. A total of twelve SC-duplex adaptor plates (maximum 72 duplex (144 duplex)

    connectors)

    The integral patch-cord management supports up to 144 duplex patch-cords and ensures the optical fiber patch-cord minimum bending radius is observed. The clear plastic lid cover protects the patch-cords from unintended damage. An optional security kit, complete with lock, is available if required. Description Part Number 4U patch panel 0-0559552-2 Blank plate 0-0559523-1 MPO coupler 6x12 fibers 0-1374598-1

  • 16

    4-U AMP Hi-D enclosure The 4-U high enclosure accepts up to twelve (12) snap-in adapter plates or MPO Cassettes. The cassettes or adaptor plates and blank plates can be quickly inserted into the enclosure using the quick release mechanism. The enclosure fits into standard 19" racks and includes side mounting ears and optical fiber patch-cord management at the back. The enclosure can support the following connectivity:

    1 A total of twelve MPO cassettes (maximum 144 duplex (288 simplex) connectors) 2 A total of twelve LC-duplex adapter plates (maximum 144 duplex (288 simplex)

    connectors); 3 A total of twelve SC-duplex adaptor plates (maximum 72 duplex (144 duplex)

    connectors)

    The patch panel is part of the AMP Hi-D cabling platform. For cable management, cable managers and additional fiber organizer drum plates, are available. Description Part Number AMP Hi-D Modular Panel, 4U 0-1671055-1 Blank Module 0-1671146-1

  • 17

    AMP Hi-D AMP Hi-D is a cabling platform for your IT infrastructure. The platform embraces different kinds of products and features designed for future IT infrastructures requiring high density solutions. In line with the desire of organizations to provide more performance in less space within their Data Center environment while meeting power consumption objectives, AMP NETCONNECT has realized the need to develop focused product sets for these environments that meet the design objectives of ensured high density performance, seamless migration and user flexibility at a reduced power level.

    AMP Hi-D is an excellent cabling platform for fiber installations. With our cable managers and fiber drums we can offer a robust solution in order to address the following subjects:

    More information is here: www.ampnetconnect.eu

  • 18

    Installation Procedure The MPO trunk shall be laid in pathways (not pulled), unless it is being installed in conduits. Ideally, the best pathway is a duct (metallic or non-metallic) that fully protects the MPO trunks from other cable types.

    Where a cable must be pulled any tension shall only be applied to the installed pulling sock with a maximum of 350 Newtons.

  • 19

    The minimum bending radius specified for the trunk type shall be observed at all times. The trunk shall be fixed to the panel. The pathway fill specified in the pathways and spaces standard (30% to 50%) shall be observed. The trunks shall be connected to the cassette by simply plugging the MPO connector into the appropriate MPO coupler as identified in the design plan. Prior to plugging into the coupler, both MPO plug and coupler shall be cleaned using the method described in the cleaning section. All trunks and cassettes shall be labelled in accordance with the administration standard and the specified requirements. The equipment cords shall be the duplex type and installed to complete the communication channel. Appropriate patch cord management shall be provided to ensure minimum bending radius, crush resistance and fill ratios are observed.

  • 20

    Cleaning MPO Connectors, Cassettes and Trunks

    1918809-1 MPO IBC Cassette Cleaner: Suitable for MPO Cassettes, MPO coupler and MPO plugs

    1918808-1 1.25 mm stick cleaners: Suitable for LC couplers 1918807-1 2.5 mm stick cleaners: Suitable for SC couplers 0-2064499-1 Suitable for SC connectors 0-2064500-1 Suitable for LC connectors Note: Cleaning is an essential part of MPO and any high speed fiber system. Reason is the low budget of such systems. If the budget for 10 Gigabit Ethernet is 2.55 dB, it is going to be about 1.7 dB for 40 Gb/s.

  • 21

    Cleaning Procedure MPO Connectors, Cassettes and Trunks

    LC, SC couplers 1. Insert the tip of the cleaning stick into the adaptor

    opening 2. Rotate the cleaning stick clockwise while applying

    varying pressure to create a gentle back and forth pumping action where the tip of the cleaning stick contacts the ferrule.

    3. Inspect with microscope for cleanliness and repeat steps 1and

    4. 2 if needed until any contamination is removed. 5. Discard the stick after use.

    MPO Cassette/Coupler 1. Insert the cleaning tool tip into the MPO adapter as shown. 2. Rotate the wheel in the direction indicated on the cleaning

    tool. 3. Remove the cleaning tool from the MPO adapter. 4. Inspect with microscope for cleanliness and repeat steps 3,

    4 and 5 if needed until any contamination is removed.

    MPO Plug (Trunk connectors) 1. With the clear cover installed it is also possible to clean

    the MPO connector plugs 2. Lift the clear front cover, Insert the MPO plug as

    shown. 3. Rotate the wheel in the direction indicated on the

    cleaning tool 2 or 3 times. 4. Inspect with microscope for cleanliness and repeat

    steps if needed until any contamination is removed.

    LC/SC coupler IBC cleaner 1. Insert the tip of the IBC tool into

    the adaptor opening 2. Push carefully until you hear an audible click 3. Take out the tool and Inspect with microscope for

    cleanliness and repeat steps 1 and 2 if needed until any contamination is removed.

  • 22

    The importance of a clean endface is shown in the pictures below. Two connectors have been mated one, two and five times. Each time more dust is collected and even more important the dust particles are moving towards the core (see pictures and table). This has a deep impact for 1 and 10 Gb/s channel testing. As ISO/IEC 11801 has defined a channel budget of 2.55 dB for OM 300 channels any contamination of the endface is critical.

    Initial

    (dB) Limit (dB) 1st (dB) 3rd (db) 5th (dB)

    IL 0.11 0.13 0.12 0.23 0.57 RL 53 52 53 28 19 Status - - Pass Fail Fail Always check if end faces are clean before connecting connectors to each other, and after every re-patching also first check if end faces are clean. Always remove dust and dirt, after removal check again

    Check (Look) Clean Check (Look) !! Always make sure that the transmitter is turned off or there is no network connection before inspection (Always pay attention / be careful when using a microscope)

    1st mating 3rd mating

    5th mating

    After cleaning

    Before

    Tool

  • 23

    Testing the installed MPO System The installed MPO system shall be tested to ISO/IEC 14763.3:2007, using the 3-test cord method. Channel loss 3-Test cord Method

    Channel Set-up 3-Test cord Method Powermeter Launch Kits

    OTDR Launch Kits

    Panel 1 Panel 2Channel under test

    Tail cord PM

    Rx

    Tx

    LS

    LC reference connector

    MPO random-random connectors LC non-reference connector

  • 24

    Data Centers The MPO solution is ideal for data center applications. The latest data center structured cabling standard, TIA 942, defines the cabling layout and cabling performance requirements. Structured Cabling Concepts in Data Centre

    The ISO / IEC data center communication cabling standard defines the topology and performance specifications of the cabling media that could be used in such an environment. The minimum optical fibre cable defined in this standard is OM3. The MPO solution is ideally suited to fulfill the performance requirements defined in this standard.

  • 25

    A typical data center layout is shown above. The communication network enables the various network devices to perform their activity in the most efficient manner. The MPO trunks are reticulated in modular, (yellow) light weight, Low Smoke Zero Halogen polymeric ducting, designed and manufactured specifically to protect the optical fiber trunks from abrasion and sharp edges and to provide segregation of the optical fibre installation from the copper cabling system. Optical fiber systems like the The AMP NETCONNECT PLUG&GO MPO system require much smaller pathways than copper cabling systems. This reduces space in congested ceilings, while segregating the optical fibre cabling from other services. This pathway system provides the appropriate minimum bending radii required by the optical fiber trunks to prevent performance deterioration and simplifies installation by allowing the optical fiber trunks to be laid into the ducts, rather than pulled.

  • 26

    AMP NETCONNECT Regional Headquarters:

    North America Greensboro, NC, USA Ph: +1-800-553-0938 Fx: +1-717-986-7406

    Latin America Buenos Aires, Argentina Ph: +54-11-4733-2200 Fx: +54-11-4733-2282

    Europe Kessel-Lo, Belgium Ph: +32-16-35-2190 Fx: +32-16-35-2188

    Mid East & Africa Cergy-Pontoise, France Ph: +33-1-3420-2122 Fx: +33-1-3420-2268

    Asia Hong Kong, China Ph: +852-2735-1628 Fx: +852-2735-1625

    Pacific Sydney, Australia Ph: +61-2-9554-2600 Fx: +61-2-9554-2519

    AMP NETCONNECT in Europe, Middle East, Africa and India:

    While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalog, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgment to evaluate the suitability of a product for a certain purpose and test each product for its intended application. In case of any potential ambiguities or questions, please dont hesitate to contact us for clarification.

    1308716-1 PDF-08/09 2009 Tyco Electronics Corporation All rights reserved AMP, AMP NETCONNECT, MPOptimate, Tyco Electronics and TE Logo are trademarks. http://www.ampnetconnect.eu