150
MPA pneumatics manual Valve terminal with MPA pneumatics Type VT32−.. Manual 534 241 en 0302NH [665 561] MPA valve terminal

MPA valve terminal - Festo...MPA pneumatics manual Valve terminal with MPA pneumatics Type VT32−.. Manual 534 241 en 0302NH [665 561] MPA valve terminal Contents and general instructions

  • Upload
    others

  • View
    37

  • Download
    1

Embed Size (px)

Citation preview

MPA pneumaticsmanual

Valve terminal withMPA pneumaticsType VT32−..

Manual534 241en 0302NH [665 561]

MPA valve terminal

Contents and general instructions

IFesto P.BE−MPA−EN en 0302NH

Author M. Simons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Editor M. Holder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Layout Festo AG & Co. KG, Dept. KG−GD. . . . . . . . . . . . . . . .

Type setting KI−DT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Edition en 0302NH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Designation P.BE−MPA−EN. . . . . . . . . . . . . . . . . . . . . . . . . .

Order no. 534 241. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E (Festo AG�&�Co. KG, D�73726 Esslingen, Federal Republic of Germany, 2003)Internet: �http://www.festo.comE−Mail: �[email protected]

The copying, distribution and utilization of this document aswell as the communication of its contents to others withoutexpressed authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved, in particular the right to carry out patent, utility model or ornamental design registration.

Contents and general instructions

II Festo P.BE−MPA−EN en 0302NH

Contents and general instructions

IIIFesto P.BE−MPA−EN en 0302NH

Contents

Designated use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Target group VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Notes on this manual VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Important user instructions XI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1. Summary of components 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1 The MPA valve terminal 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1.1 Overview of variants 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1.2 Description of components 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2. Fitting 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 General instructions on fitting and dismantling 2−4 . . . . . . . . . . . . . . . . . . . . . . .

2.2 Fitting variants 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2.1 Hat rail fitting/removal 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2.2 Fitting onto / removing from a wall 2−10 . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Fitting/removing the inscription label holder 2−13 . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Fitting/removing the manual override cap (optional) 2−15 . . . . . . . . . . . . . . . . . .

3. Installation 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Preparing the compressed air 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.1 Operation with non−lubricated compressed air 3−4 . . . . . . . . . . . . . . . .

3.1.2 Operation with lubricated compressed air 3−4 . . . . . . . . . . . . . . . . . . . .

3.2 General notes on connecting the tubing 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2.1 Laying the tubing 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Connecting the MPA valve terminal 3−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.1 Pilot control of the valve solenoid coils (auxiliary pilot air) 3−10 . . . . . . .

3.3.2 MPA valve terminal with pressure zone separation 3−13 . . . . . . . . . . . . .

3.3.3 Vacuum/low pressure operation 3−18 . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.4 Connecting the pneumatic tubing 3−19 . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.5 Connecting the electric cables 3−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Address assignment of the valves 3−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Contents and general instructions

IV Festo P.BE−MPA−EN en 0302NH

4. Commissioning 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1 General instructions 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.1 Before commissioning 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.2 Pressure increase in the complete supply 4−4 . . . . . . . . . . . . . . . . . . . .

4.2 Manual override 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3 Checking the valves and the valve−actuator combination 4−8 . . . . . . . . . . . . . . .

4.4 LED display of the valves 4−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.5 Eliminating faults 4−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.5.1 Impairment of function 4−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.5.2 Operating states of the pneumatic system 4−18 . . . . . . . . . . . . . . . . . . .

5. Maintenance and conversion 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.1 General precautionary measures 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.2 Dismantling the MPA valve terminal 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3 Servicing the MPA valve terminal 5−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.1 Cleaning the large surface−mounted silencer 5−7 . . . . . . . . . . . . . . . . .

5.4 Replacing MPA valve terminal components 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . .

5.4.1 Replacing valve plates or blanking plates 5−8 . . . . . . . . . . . . . . . . . . . .

5.4.2 Replacing the electronic modules 5−11 . . . . . . . . . . . . . . . . . . . . . . . . . .

5.4.3 Fitting/removing the large surface−mounted silencer or the exhaust plate5−14

5.4.4 Replacing the sub−base 5−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.5 Converting the MPA valve terminal 5−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.5.1 Conversion to internal or external pilot air 5−18 . . . . . . . . . . . . . . . . . . . .

5.5.2 Converting the MPA valve terminal to different pressure zones 5−21 . . .

5.5.3 Adding valve locations 5−27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Contents and general instructions

VFesto P.BE−MPA−EN en 0302NH

A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.1 Technical specifications A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2 Festo accessories A−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B. Supplementary overview of components B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1 Overview of valve plates B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2 Separating the MPA valve terminal from the CPX terminal B−7 . . . . . . . . . . . . . .

C. Index C−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C.1 Index C−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Contents and general instructions

VI Festo P.BE−MPA−EN en 0302NH

Contents and general instructions

VIIFesto P.BE−MPA−EN en 0302NH

Designated use

The MPA valve terminals described in this manual are in�

tended for fitting into a machine or automated system. Pleaseobserve the safety regulations specified in this manual aswell as the instructions concerning the designated use of the

relevant MPA valve terminal. MPA valve terminals may only beused as follows:

� as specified in industrial applications

� without any modifications by the user. Only the conversions or modifications described in thedocumentation

accompanying the product are permitted.

� in faultless technical condition.

When used together with commercially available compo�

nents, such as actuators, the specified limits for pressures,temperatures, electrical data, torques etc. must be observed.National and local safety regulations must also be observed.

Target group

This manual is directed exclusively at technicians trained incontrol and automation technology.

Service

Please consult your local Festo repair service if you have anytechnical problems.

Contents and general instructions

VIII Festo P.BE−MPA−EN en 0302NH

Notes on this manual

This manual contains specific information on fitting, installing,

commissioning, servicing and converting the MPA valve ter�minal. This manual describes only the pneumatic componentsand refers to the valve terminal variants listed in the table

below.

Variants of the MPA valve terminal type VT32

with CPX terminal:Information on CPX modules can befound in the manual for the relevant mo�dule. The following table provides anoverview.

with MP connection:Information on the electric/electroniccomponents: see leaflet with product

Table.�0/1: Connection variants of the MPA valve terminal

Contents and general instructions

IXFesto P.BE−MPA−EN en 0302NH

Manuals on the CPX terminal

Manual �CPX systemmanual " type: PBE−CPX−SYS−Manual �CPX system manual," type: P.BE−CPX−SYS−..

Contents Overview of structure, components and method of operation of CPX terminals; instruc�tions on installation and commissioning as well as basic information on parametrizing.

Manual �CPX field bus node"type: P.BE−CPX−FB...

�CPX I/O modules"type: P.BE−CPX−EA−...

�Valve terminal with:� MPA �pneumatics"

type: P.BE−MPA−...�� CPA pneumatics"

type: P.BE−CPA−...� Midi/Maxi pneumatics"

type: P.BE−MIDI/MAXI−03−...

Contents Instructions on fitting,installing, commission�ing and diagnosing therelevant field bus node

Connection techniquesand instructions on fit�ting, installing and com�missioning input andoutput modules of typeCPX−...

Information on fitting, installingand commissioning the relevantpneumatic modules

Table.�0/2: Manuals on the MPA valve terminal with CPX terminal

Contents and general instructions

X Festo P.BE−MPA−EN en 0302NH

The MPA valve terminal consists of the following pneumaticand electric components: The most important pneumatic

components are shown below.

1 Exhaust plate orlarge surface−mounted silencer

2 Valve plates

3 Blanking plate

4 End plate

5 Supply unit

6 Sub−base

7 Multipin sub−base or pneuma�tic interface

1 2 3 4

56

7

Fig.�0/1: Main components of the MPA valve terminal

This manual contains the documentation for the valve plateswith Ident. codes B, D, E, G, H, J, K, M, N and X (see

chapter�System overview, description of components"). �

Contents and general instructions

XIFesto P.BE−MPA−EN en 0302NH

Important user instructions

Danger categories

This manual contains instructions on the possible dangerswhich may occur if the product is not used correctly. Theseinstructions are marked (Warning, Caution, etc.), printed on ashaded background and marked additionally with a picto�gram. A distinction is made between the following dangerwarnings:

WarningThis means that failure to observe this instruction mayresult in serious personal injury or damage to property.

CautionThis means that failure to observe this instruction mayresult in personal injury or damage to property.

Please noteThis means that failure to observe this instruction mayresult in damage to property.

The following pictogram marks passages in the text whichdescribe activities with electrostatically sensitive compo�nents.

Electrostatically sensitive components may be damaged ifthey are not handled correctly.

Contents and general instructions

XII Festo P.BE−MPA−EN en 0302NH

Marking special information

The following pictograms mark passages in the text contain�ing special information.

Pictograms

Information:Recommendations, tips and references to other sources ofinformation.

Accessories:Information on necessary or sensible accessories for theFesto product.

Environment:Information on environment−friendly use of Festo products.

Text markings

· The bullet indicates activities which may be carried out inany order.

1. Figures denote activities which must be carried out in thenumerical order specified.

� Hyphens indicate general activities.

Contents and general instructions

XIIIFesto P.BE−MPA−EN en 0302NH

The following product−specific terms and abbreviations areused in this manual:

Term/abbreviation Meaning

Exhaust plate Plate for ducted exhaust with connection 3/5

Sub−base Pneumatic manifold sub−base with 4 valve locations, for single−solenoid,double−solenoid or mid−position valves, with work connections 2 and 4.

Basic components Components (pneumatic interface, MP sub−base, sub−base or supply unit)on which further components can be mounted (exhaust plates, large sur�face−mounted silencer, valve plate or blanking plate).

CPX modules Common term for the various modules which can be incorporated in a CPXterminal

CPX terminal Modular electric terminal type 50

I/O input/output modules

Electronic modules Module in the sub−base with LED and coil management

End plate Extreme right−hand plate of the MPA valve terminal and extreme left−handplate of the CPX terminal with holes for fitting onto a wall

Manual override Manual override

Components Common term for pneumatic interface, MP sub−base, exhaust plate, largesurface−mounted silencer, pneu. sub−base, supply unit, end plate, valveplate and blanking plate

MP connection Electric multipin connection

MP sub−base Base with electric multipin connection and pneumatic connections

MPA1 Designation of the MPA valve terminal with 10mm−wide valve plates

MPA valve terminal Modular Performance Sub−base valve terminal (type 32) with MP connec�tion or for CPX terminal

MPA valve terminal withmultipin connection (MPconnection)

MPA valve terminal variant with sub−D plug via which all valve solenoid coilsare centrally connected.

Pneumatic interface The pneumatic interface is the interface between the modularelectrical periphery of the CPX terminal and the MPA pneumatics.

Contents and general instructions

XIV Festo P.BE−MPA−EN en 0302NH

Term/abbreviation Meaning

Pneumatic modules Module consisting of sub−base, electronic module, valve plate or blankingplates

Blanking plate Plate without valve function for sealing non−usd valve locations on sub−bases

Valve plate Plate with single−solenoid valve, double−solenoid valve or mid−positionvalve

Connecting the tubing Connecting the supply lines (tubing) to the MPA valve terminal

Supply unit Unit for additional supply of compressed air to the valve plates, e.g. withseveral pressure zones

Table.�0/3: Product−specific terms and abbreviations

Summary of components

1−1Festo P.BE−MPA−EN en 0302NH

Chapter 1

1. Summary of components

1−2 Festo P.BE−MPA−EN en 0302NH

Contents

1. Summary of components 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1 The MPA valve terminal 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1.1 Overview of variants 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1.2 Description of components 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1. Summary of components

1−3Festo P.BE−MPA−EN en 0302NH

Contents of this chapter This chapter provides an overview of the following aspects ofthe MPA valve terminal:

� connection variants and components of the valve terminal

� the maximum number of valve locations

� the identification code of the valve plates

� the connecting, display and operating elements

Further information Information on the electric multipin can be found in the briefdescription of the MPA valve terminal with multipin connec�tion.

Information on the modules of the CPX terminal can be foundin the CPX system manual.

Information on the electronic modules of the MPA valve ter�minal can be found in the CPX I/O modules manual.

1. Summary of components

1−4 Festo P.BE−MPA−EN en 0302NH

1.1 The MPA valve terminal

Festo assists you in solving your automation tasks at machinelevel with MPA valve terminals. The modular structure of theMPA valve terminal enables you to use this valve terminal

optimally in your machine or system.

The valve terminal pneumatics provide the following:

� the common channels for supply and exhaust air

� the electric signals from all valve solenoid coils

Work connections 2 and 4 are provided for each valve loca�tion on the individual pneumatic modules. The valves aresupplied with compressed air via the common channels andconnections in the basic components. Both the exhaust airand pilot exhaust air from the valves are also exhausted viathese common channels. Further modules for pressure sup�ply are also available, e.g. in order to supply pressure zones.

The MPA valve terminal is fitted with current reduction. The

rated current of the valve solenoid coils is then reduced afterthe high−current phase (switching procedure). The currentreduction offers the following advantages:

� the MPA valve terminal has a lower energy consumption

� the power unit for the voltage supply to the MPA valveterminal can be designed more economically dependingon the individual case

� the valve solenoid coils have less leakage power and pro�duce less waste heat

1. Summary of components

1−5Festo P.BE−MPA−EN en 0302NH

1.1.1 Overview of variants

MPA valve terminal

MPA valve terminal withCPX terminal

This MPA valve terminal is available with 4 to max. 32 valvelocations. Maximum 64 valve coils can be actuated.

Fig.�1/1: MPA valve terminal with CPX terminal

1. Summary of components

1−6 Festo P.BE−MPA−EN en 0302NH

MPA valve terminal withMP connection

This MPA valve terminal is available with 4 to max. 24 valvelocations. Maximum 24 valve coils can be actuated. Theelectrical connection of the valve solenoid coils is made cen�trally via the multipin plug.

Fig.�1/2: MPA valve terminal with multipin connection

Sizes of the MPA valve ter�minal

All MPA valve terminal variants are available with valves insizes of 10 mm (MPA1).

1. Summary of components

1−7Festo P.BE−MPA−EN en 0302NH

1.1.2 Description of components

The MPA valve terminal with CPX terminal consists of the fol�lowing components: ��

1 2 3

5

4

67

5

8

1 CPX field bus node

2 Pneumatic interface with supply con�nections, exhaust plate or large sur�face−mounted silencer

3 Valve plates or blanking plates

4 Supply unit with exhaust plate or largesurface−mounted silencer

5 End plate

6 Sub−base with work connections, in�scription label holders, serial linking(bus) and electronic module with LEDs

7 Sheet seal (optional with pressurezone separation)

8 Further optional CPX modules

Fig.�1/3: Components of the MPA valve terminal with CPX terminal

1. Summary of components

1−8 Festo P.BE−MPA−EN en 0302NH

The MPA valve terminal with MP connection consists of thefollowing components: ��

1

2 3 4

5

7 6

1 Multipin sub−base with multipin plug,supply connections, exhaust plate orlarge surface−mounted silencer

2 Electrical linking

3 Valve plates or blanking plates

4 Supply unit with exhaust plate or largesurface−mounted silencer

5 Right−hand end plate

6 Sub−base with work connections, in�scription label holders and electronicmodule with LEDs

7 Sheet seal (optional with pressurezone separation, for forming maximum2 pressure zones)

Fig.�1/4: Components of the MPA valve terminal with MP connection

1. Summary of components

1−9Festo P.BE−MPA−EN en 0302NH

The MPA valve terminals with MP connection or CPX terminalcan control a different number of solenoid coils. The maxi�

mum possible number of valve locations is also different. Thefollowing table gives an overview:

Valve ter�minal vari�ants

Max. number ofsolenoid coilswhich can becontrolled

Max.number of valvelocations

Remarks

CPXterminal

64 32 Two solenoid coils can be controlled pervalve location.

MPconnection

24 24 1) With the maximum number of valve locationsone solenoid coil can be controlled per valvelocation.

1) If the MPA valve terminal with MP connection also provides valve locations which support controlof 2 solenoid coils, the maximum possible number of valve locations will be reduced. See alsotable 3/5 in chapter 3.

Table�1/1: Maximum number of valve locations depending on the MPA valve terminalvariants

1. Summary of components

1−10 Festo P.BE−MPA−EN en 0302NH

The valves of the MPA valve terminal are marked with identifi�cation codes.

Ident. code Valve plate

B Valve plate, 5/3−way, mid position pressurized

D Valve plate, two 2/2−way, single−solenoid, in basic position closed

E Valve plate, 5/3−way, mid position exhausted

G Valve plate, 5/3−way, mid position closed

H Valve plate, two 3/2−way, control side 12 in basic position opencontrol side 14 in basic position closed

J Valve plate, 5/2−way, double−solenoid

K Valve plate, two 3/2−way, single−solenoid, in basic position closed

M Valve plate, 5/2−way, single−solenoid

N Valve plate, two 3/2−way, single−solenoid, in basic position open

X Valve plate, 3/2−way, single−solenoid, in basic position closedexternal auxiliary pilot air

Table�1/2: Ident. codes of the valve plates

Further information on the valve plates can be found in Ap�pendix B.

1. Summary of components

1−11Festo P.BE−MPA−EN en 0302NH

You will find the following pneumatic connecting and operat�ing elements on the MPA valve terminal: �

1 2

3

5 446

7

1 Manual override (per pilot solenoid, turning/locking ornon−locking)

2 Exhaust connections (3/5)

3 Pilot air exhaust connection (82/84)

4 Compressed air connections (1)

5 Work connections (2, 4) per valve plate

6 Pilot air connection (12/14)

7 Manual override cap

Fig.�1/5: Pneumatic connecting and operating elements ofthe MPA valve terminal

1. Summary of components

1−12 Festo P.BE−MPA−EN en 0302NH

You will find the following electrical connecting and displayelements on the MPA valve terminal with CPX terminal:

1 2 3

456

1 Service interface for handheld, etc.

2 Field bus connection (bus specific)

3 LEDs yellow: Signal status display of the pilot solenoids red: Fault display

4 Identification fields

5 Power supply connection

6 Earth/ground connection

Fig.�1/6: Electrical connecting and display elements of the

MPA valve terminal with CPX terminal

1. Summary of components

1−13Festo P.BE−MPA−EN en 0302NH

You will find the following electrical connecting and displayelements on the MPA valve terminal with MP connection:

1

3

2

4

5

2

1 Sub−D multipin plug

2 Inscription label holder with inscription field for ad�dresses

3 Earth/ground connection

4 Sub−D connection

5 LEDs yellow: Signal status display of the pilot solenoids

Fig.�1/7: Electrical connecting and display elements of the

MPA valve terminal with MP connection

1. Summary of components

1−14 Festo P.BE−MPA−EN en 0302NH

Fitting

2−1Festo P.BE−MPA−EN en 0302NH

Chapter 2

2. Fitting

2−2 Festo P.BE−MPA−EN en 0302NH

Contents

2. Fitting 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 General instructions on fitting and dismantling 2−4 . . . . . . . . . . . . . . . . . . . . . . .

2.2 Fitting variants 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2.1 Hat rail fitting/removal 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2.2 Fitting onto / removing from a wall 2−10 . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Fitting/removing the inscription label holder 2−13 . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Fitting/removing the manual override cap (optional) 2−15 . . . . . . . . . . . . . . . . . .

2. Fitting

2−3Festo P.BE−MPA−EN en 0302NH

Contents of this chapter The MPA valve terminal is already assembled when suppliedfrom the factory. Accessories such as inscription labels andmanual override caps (optional) must be fitted on site.

This chapter describes how to fit and remove:

� the complete MPA valve terminal

� the inscription labels

� the manual override caps

Further information Special information on replacing or adding pneumatic compo�nents can be found in chapter 5.

MPA valve terminal with CPX terminal:

� Information on fitting the MPA valve terminal with CPXterminal can be found in the CPX system manual.

� Information on fitting and dismantling the I/O modulescan be found in the manual CPX I/O modules.

� Information on fitting modules and components orderedat a later stage can be found in the leaflet supplied withproduct.

2. Fitting

2−4 Festo P.BE−MPA−EN en 0302NH

2.1 General instructions on fitting and dismantling

WarningSudden unexpected movements of the connected actua�tors and uncontrolled movements of loose tubing cancause injury to human beings or damage to property.

Before carrying out installation and maintenance work,switch off the following:

� the compressed air supply

� the operating and load voltage supplies.

Please noteHandle all modules and components of the MPA valve ter�minal with great care. Please note especially the following:

� The specified torques must be observed.

� Electrostatically sensitive componentsDo not therefore touch any contact surfaces.

2. Fitting

2−5Festo P.BE−MPA−EN en 0302NH

2.2 Fitting variants

You can fit the MPA valve terminal in one of two ways:

Type of fitting Description

Fitting onto a hat rail The valve terminal is suitable for fittingonto a hat rail (support rail as per EN50022). There is a guide groove on theback for hanging the valve terminal ontothe hat rail.

Fitting onto a wall The multipin sub−base or the pneumaticinterface and the end plates contain holesfor fitting the terminal onto a wall. In thecase of MPA valve terminals with morethan 5 sub−bases, additional fasteningbrackets on the supply unit may benecessary (see the following instructionsand specifications in Appendix A).

Table�2/1: Methods of fitting the MPA valve terminal

Please noteFit the MPA valve terminal so that there is sufficient spacefor heat dissipation and ensure that the maximum limitsfor temperatures are observed (see �Technical specifica�tions").

2. Fitting

2−6 Festo P.BE−MPA−EN en 0302NH

2.2.1 Hat rail fitting/removal

Caution� When fitting onto a hat rail, observe the details on vibra�tion and shock in the technical specifications in Appen�dix A.

� A hat−rail fitting without a hat−rail clamping unit is notpermitted.

· If the terminal is fitted in a sloping position or if it is sub�jected to vibration, secure the hat−rail clamping unitadditionally− against sliding down and − against unintentionalloosening or opening with the locking screws (see Fig. 2/1, item 2)

In order to fit the valve terminal onto a hat rail you will requirethe following mounting kits:

� for MPA valve terminal with MP connection: CPA−BG−NRH.This kit consists of 2 M4x10 screws and 2 clamping el�ements.

� for MPA valve terminals with CPX terminal: CPX−CPA−BG−NRH. This kit consists of 3 M4x10 screws and3 clamping elements.

2. Fitting

2−7Festo P.BE−MPA−EN en 0302NH

Variants Fastening possibilities

1 1

MPA valve terminal with CPX ter�minal 2

Hole for hat railclamping units:1 in the end plates2 in the pneumatic interface

1

MPA valve terminal with MP connection

2

Hole for hat railclamping units:1 in the MP sub−base2 in the right−hand end plate

Table�2/2: Holes for the hat rail clamping unit

Fitting Proceed as follows:

1. Make sure that the fastening surface can support theweight of the MPA valve terminal (weights see AppendixA).

2. Fit the hat rail (support rail as per EN 50022 − 35x7.5;

width 35 mm, height 7.5 mm). Make sure there is suffi�cient space for connecting the power cables and com�pressed air tubing.

3. Fasten the hat rail to the fastening surface at intervals ofapprox. every 100 mm.

2. Fitting

2−8 Festo P.BE−MPA−EN en 0302NH

4. Fit the hat rail clamping units (see table 2/2)

5. Hang the MPA valve terminal onto the hat rail (see Fig.2/1, arrow A).

6. Swing the MPA valve terminal onto the hat rail (see Fig.2/1, arrow B). Make sure that the clamping element lieshorizontally to the hat rail.

1 Hat rail

2 Locking screw ofthe hat railclamping unit

3 Clamping el�ement of the hatrail clamping unit

ÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔ

ÔÔÔÔÔÔÔÔ

(A)

(B)

1

2

3

Fig.�2/1: Fitting the MPA valve terminal onto a hat rail

7. Fasten the MPA valve terminal, as with the CPX terminal,against tilting or sliding by tightening the locking screw

with 1.3 Nm..

2. Fitting

2−9Festo P.BE−MPA−EN en 0302NH

1 Hat rail

2 Clamping el�ement of the hat−rail clamping unit 1

2

Fig.�2/2: Rear view: Fitting the CPX terminal onto a hat rail

Further instructions on fitting the MPA valve terminal withCPX terminal onto a hat rail can be found in the CPX systemmanual.

Dismantling Proceed as follows:

1. Loosen the locking screw of the hat rail clamping unit

�(position of the screws see table 2/2). Make sure that theclamping element lies horizontally to the hat rail.

2. Swing the MPA valve terminal forwards from the hat rail(see Fig. 2/3).

3. Lift the MPA valve terminal off the hat rail (see Fig. 2/3).

2. Fitting

2−10 Festo P.BE−MPA−EN en 0302NH

1 Hat rail

2 Locking screw ofthe hat railclamping unit

3 Clamping el�ement of the hatrail clamping unit

ÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔ

ÔÔÔÔÔÔÔÔ

1

A

B

2

3

Fig.�2/3: Dismantling the MPA valve terminal

2.2.2 Fitting onto / removing from a wall

The end plates, the MP sub−base or the pneumatic interfacehave holes for fitting the terminal onto a wall (see table 2/3).

2. Fitting

2−11Festo P.BE−MPA−EN en 0302NH

CautionMPA valve terminals can become distorted and thereforedamaged if they are mounted on an uneven pliable sur�face.

· Fit the MPA valve terminal only onto a flat fixed surface.

Overstressing the fastening holes, bending the MPA valveterminal with CPX terminal or internal vibrations can causedamage.

· If the MPA valve terminal has more than 5 sub−bases,use additional wall brackets of type: VMPA−BG−RW. Thesupply units have threaded holes to enable the wallbrackets to be fitted.

· In these cases use the additional fastenings for the CPXterminal (see instructions in the manual for the CPX sys�tem).

Fitting Proceed as follows:

1. Make sure that the fastening surface is flat and can sup�

port the weight of the MPA valve terminal (weights seeAppendix A).

Make sure there is sufficient space for connecting the powercables and compressed air tubing.

2. Drill mounting holes in the fastening surface.

3. Fasten the MPA valve terminal with M4 or M6 screws ofsufficient length to the fastening surface.

2. Fitting

2−12 Festo P.BE−MPA−EN en 0302NH

Variants Fastening possibilities

1

2

11

2

2

1

1

2

1

3

MPA valve terminal with CPX ter�minal

� End plates: 2 screws each ofsize M4 or M6

� Pneumatic interface:two M4 screws

� Fastening bracket on the sup�ply unit (optional): one M6 screw

1 Hole for M4 screw2 Hole for M6 screw3 Hole for M6 screw

in the wall bracket (op�tional)

1

1

1

1

2

2 2

2

MPA valve terminal with MP connec�tion

� MP sub−base: two M4 or M6 screws

� right−hand end plate:two M4 or M6 screws

1 Hole for M4 screw2 Hole for M6 screw

Table�2/3: Possibilities of fastening the MPA valve terminal

Dismantling Proceed as follows:

1. Prevent a hanging−mounted MPA valve terminal from fal�ling down before you loosen it from the fastening surface.

2. Loosen the fastening screws (see table 2/3).

3. Remove the MPA valve terminal from the fastening surface.

2. Fitting

2−13Festo P.BE−MPA−EN en 0302NH

2.3 Fitting/removing the inscription label holder

An inscription label holder can be fitted onto each sub−baseto enable the valves or work connections to be marked.

Fitting Proceed as follows:

· Clip the inscription label holders into the grooves in thesub−bases (see diagram):

1 Recess for the in�scription labelholder in the sub−base

2 Inscription labelholder

1

2

Fig.�2/4: Fitting the inscription label holder

2. Fitting

2−14 Festo P.BE−MPA−EN en 0302NH

Dismantling Proceed as follows:

1. Remove the 3rd. and 4th. valve from the relevant sub−base.

2. Unlock the inscription label holder by using a screwdriver(blade width max. 3.5 mm) to press down the snap hook(see diagram).

1 Holes for unlock�ing the inscrip�tion label holder

2 Inscription labelholder

1

2

Fig.�2/5: Dismantling the inscription label holder

3. Pull the inscription label holder out of the recess in thesub−base.

2. Fitting

2−15Festo P.BE−MPA−EN en 0302NH

2.4 Fitting/removing the manual override cap (optional)

The locking/non−locking function of the manual override canbe modified to only non−locking actuation if a cap is fitted inthe manual override.

Fitting Proceed as follows:

1. Make sure that the relevant manual overrides are in anon−actuated state. If necessary, set locking manual over�rides to the basic position (see chapter 4, table 4/5).

2. Clip the manual override caps into the grooves in themanual overrides (see diagram):

1 Manual overridecap

2 Manual override

1

2

Fig.�2/6: Fitting the manual override caps

2. Fitting

2−16 Festo P.BE−MPA−EN en 0302NH

Dismantling Proceed as follows:

· Use a suitable screwdriver to lift the manual override capsout of the manual overrides (see diagram):

Fig.�2/7: Dismantling the manual override caps

Installation

3−1Festo P.BE−MPA−EN en 0302NH

Chapter 3

3. Installation

3−2 Festo P.BE−MPA−EN en 0302NH

Contents

3. Installation 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Preparing the compressed air 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.1 Operation with non−lubricated compressed air 3−4 . . . . . . . . . . . . . . . .

3.1.2 Operation with lubricated compressed air 3−4 . . . . . . . . . . . . . . . . . . . .

3.2 General notes on connecting the tubing 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2.1 Laying the tubing 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Connecting the MPA valve terminal 3−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.1 Pilot control of the valve solenoid coils (auxiliary pilot air) 3−10 . . . . . . .

3.3.2 MPA valve terminal with pressure zone separation 3−13 . . . . . . . . . . . . .

3.3.3 Vacuum/low pressure operation 3−18 . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.4 Connecting the pneumatic tubing 3−19 . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.5 Connecting the electric cables 3−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Address assignment of the valves 3−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3. Installation

3−3Festo P.BE−MPA−EN en 0302NH

Contents of this chapter This chapter describes the tubing and cabling of the MPAvalve terminal. The following in particular belong here:

� General instructions on preparing the compressed air andon connecting the tubing

� Instructions on pilot control of the valve solenoid coilswith internal or external auxiliary pilot air

� Instructions on operating MPA valve terminals with pres�sure zone separation

� Fitting the QS screw connectors

� Connecting the power supply

� Earthing the MPA valve terminal

� Address assignment of the valves

Further information Instructions on connecting the electric components of theMPA valve terminal with MP−connection can be found in theleaflet supplied with the product.

Instructions on the electrical connections can be found inchapter 3 of the CPX system manual.

Detailed instructions on connecting the CPX modules (fieldbus node, I/O modules etc.) can be found in the relevantmanuals for the CPX module.

Detailed instructions on addressing the pneumatic modulesof the MPA valve terminal with CPX terminal can be found inthe �Manual for the CPX I/O modules."

3. Installation

3−4 Festo P.BE−MPA−EN en 0302NH

3.1 Preparing the compressed air

CautionNon−filtered or incorrectly lubricated compressed air willreduce the service life of the valve terminal.

3.1.1 Operation with non−lubricated compressed air

CautionToo much residual oil in the compressed air will reduce theservice life of the valve terminal.

� If bio−oils are used (oils with synthetic ester or true esterbasis, e.g. rape oil methylester) the residual oil contentmust not exceed 0.1 mg/m3 (see ISO 8573−1 class 2).

� If mineral oils are used (e.g. HLP oils as per DIN 51524parts 1 to 3) or corresponding oils on a polyalphaolefinebasis (PAO), the residual oil content must not exceed 5mg/m3 (see ISO 8573−1 class 4).

You will thereby avoid functional damage to the valves.

Excessive residual oil cannot be permitted irrespective of thecompressor oil, as otherwise the basic lubrication will bewashed out during the course of time.

3.1.2 Operation with lubricated compressed air

If possible, operate your system with non−lubricated com�pressed air. This will prevent pollution of the environment.Festo pneumatic valves and cylinders have been designed sothat, if used as intended, they will not require additional lu�brication and will still achieve a long service life.

3. Installation

3−5Festo P.BE−MPA−EN en 0302NH

CautionOperation with lubricated compressed air will cause theservice life lubrication, which is necessary for non−lubri�cated operation, to be �washed out."

Please note the following instructions if lubricated com�pressed air must be used. The compressed air prepared with the compressor mustcorrespond in quality to non−lubricated compressed air. Ifpossible, do not operate the complete system with lubricatedcompressed air. If possible, always install the lubricators di�rectly in front of the consuming cylinder.

CautionIncorrect additional oil and too much residual oil content inthe compressed air will reduce the service life of the valveterminal.

� Use Festo special oil OFSW−32 or the other oils listed inthe Festo catalogue (as per DIN 51524−HLP32, basicviscosity 32cST at 40 °C).

� The additional lubrication must not exceed 25 mg/m3

(ISO 8573−1 class 5).

� Make sure that the lubricator setting is correct (see fol�lowing section)

You will thereby avoid functional damage to the valves.

Setting the lubricator: with the machine running (typical operating status) 0.2 tomax. 1 drop/min. or 0.5 to 5 drops/1000 l air.

Checking the setting: The procedure described below can be used for checking thesetting of the lubricator.

Proceed as follows:

· Check the service units in respect of condensate and lu�bricator setting twice a week.

1. Ascertain the cylinder which is furthest from the lubrica�tor.

3. Installation

3−6 Festo P.BE−MPA−EN en 0302NH

2. Ascertain the valve terminal which controls this cylinder.

3. Remove the silencer, if fitted, from connection 3/5.

4. Hold a piece of white cardboard 10 cm in front of the ex�haust port.

5. Let the system run for a short period.

� There must only be a slight yellow colouring on thecardboard. If oil drops out, this is an indication thattoo much oil has been used.

A further indication of excessive lubrication is the colouringor status of the exhaust silencer. A distinctly yellow colouringof the filter element or drops of oil on the silencer indicatethat the lubricator setting is too high.

3. Installation

3−7Festo P.BE−MPA−EN en 0302NH

3.2 General notes on connecting the tubing

WarningSudden unexpected movement of the connected actuatorsand uncontrolled movements of loose tubing can causeinjury to human beings or damage to property.

Before carrying out installation and maintenance work,switch off the following:

� the compressed air supply

� the operating and load voltage supplies.

Pay particular attention to the following:The components of the valve terminal contain electrostaticallysensitive elements. The components will be damaged if youtouch the contact surfaces of the plug connectors or if you donot observe the regulations for handling electrostaticallysensitive components.

3.2.1 Laying the tubing

If elbow screw connectors or multiple distributors are used,the airflow will be reduced slightly.

Connecting Proceed as follows:

1. Push the tubing as far as possible into or over the tubeconnection of the screw connector.

2. Pull the locking ring 1 over the tube connection ortighten the locking screw2.

3. For reasons of clarity, group the tubing together with:� tube straps or� multiple hose holders

3. Installation

3−8 Festo P.BE−MPA−EN en 0302NH

1

2

Fig.�3/1: Fitting the tubing

Removing Proceed as follows:

WarningIf the pneumatic tubing is under pressure when connec�tions are loosened, it may perform sudden unexpectedmovements, thereby causing injury to human beings.

· Switch off the compressed air supply before disconnect�ing the pneumatic tubing on the MPA valve terminal.

1. Loosen the locking screw or press the locking ring of thescrew connector.

2. Pull out the tubing.

3. Replace non−required screw connectors with blankingplugs 3.

3

Fig.�3/2: Disconnecting the tubing

3. Installation

3−9Festo P.BE−MPA−EN en 0302NH

3.3 Connecting the MPA valve terminal

In the case of sub−bases fitted with reserve plates, seal thework connections (2 or 4) with blanking plates or threadedblanking plugs to prevent dirt from entering.

In order to guarantee the optimum efficiency of the valve ter�minal, we recommend in the following cases that more than

one supply or exhaust line be used:

� when large volume cylinders are operated at high speeds

� when several valves are switched simultaneously to the

flow position

Connections on the following components are available forsupplying the valve terminal:

on the MPA valve terminal with CPX terminal:

� on the pneumatic interface

� on the supply unit, maximum between each sub−base(optional)

� on the supply unit next to the right−hand end plate

on the MPA valve terminal with MP connection:

� on the MP sub−base

� if necessary, on the supply unit next to the right−hand endplate

3. Installation

3−10 Festo P.BE−MPA−EN en 0302NH

3.3.1 Pilot control of the valve solenoid coils (auxiliary pilot air)

Depending on the pneumatic interface or MP sub−base fitted,pilot control of the valve solenoid coils can be carried out withinternal or external auxiliary pilot air. You can ascertain the

pilot control variant, for which your MPA valve terminal isequipped, by the following features (see table).

Variants Pneumaticinterface

MP connectionblock

Recognition features

� Pilot control with in�ternal auxiliary pilotair

� ducted exhaust

VMPA...−FB−EPL−G VMPA...−MP−EPL−G � sealed connection 12/14� exhaust plate

� Pilot control with in�ternal auxiliary pilotair

� Exhaust via large sur�face−mounted si�lencer

VMPA...−FB−EPL−GU VMPA...−MP−EPL−GU � sealed connection 12/14� large surface−mounted si�

lencer

� Pilot control with ex�ternal auxiliary pilotair

� ducted exhaust

VMPA...−FB−EPL−E VMPA...−MP−EPL−E � open connection 12/14� exhaust plate

� Pilot control with ex�ternal auxiliary pilotair

� Exhaust via large sur�face−mounted si�lencer

VMPA...−FB−EPL−EU VMPA...−MP−EPL−GU � open connection 12/14� large surface−mounted si�

lencer

Table�3/1: Variants of the pneumatic interfaces or MP sub−base

Internal auxiliary pilot air If the supply pressure lies between 3 ... 8 bar, you can oper�

ate the pilot control of the valve solenoid coils with internallybranched auxiliary pilot air. In this case, the auxiliary pilot airin the pneumatic interface or in the MP sub−base is branched

from supply channel 1. �

3. Installation

3−11Festo P.BE−MPA−EN en 0302NH

Please note· Internal auxiliary pilot air is branched centrally from sup�ply connection 1 in the pneumatic interface or MP sub−base for all valve solenoid coils. This alsoapplies if the MPA valve terminal is operated with differ�ent pressure zones (see Figs. 3/4 and 3/5).

Auxiliary pilot air If the operating pressure lies below 3 bar or above 8 bar, pilot

control of the valve solenoid coils must be operated with ex�ternal auxiliary pilot air. In this case, the auxiliary pilot air is

supplied externally via pilot connection 12/14.

Please note· Use regulated external auxiliary pilot air.(3 ... 8 bar). Reliable faultless operation of the MPA valveterminal is then possible, even with fluctuating operat�ing pressure.

· The external auxiliary pilot air is supplied centrally viapilot connection 12/14 on the pneumatic interface or MPsub−base for all valve solenoid coils. This also applies ifthe MPA valve terminal is operated with different pres�sure zones (see Figs. 3/4 and 3/5).

· Set the external auxiliary pilot air to correspond to theoperating pressure with which these valves are operated(see diagrams).

3. Installation

3−12 Festo P.BE−MPA−EN en 0302NH

1 Pressure of theexternal auxiliarypilot air at pilotconnection 12/14[bar]

2 Work range forvalves with exter�nal auxiliary pilotair

3 Operating pres�sure at connec�tion 1 [bar]

0 1 2 3 4 5 6 7 8 9 100

1

2

3

4

5

6

7

8

9

1

2

3

Fig.�3/3: Diagram: External auxiliary pilot air as a factor of the operating pressure onvalve plates with Ident. code N, K, H and D

1 Pressure of theexternal auxiliarypilot air at pilotconnection 12/14[bar]

2 Work range forvalves with exter�nal auxiliary pilotair

3 Operating pres�sure at connec�tion 1 [bar]

0 1 2 3 4 5 6 7 8 9 10

12

3

4

5

6

7

8

9

−10

1

2

3

Fig.�3/4: Diagram: External auxiliary pilot air as a factor of the operating pressure onvalve plates with Ident. code M, J, B, E, G and X

3. Installation

3−13Festo P.BE−MPA−EN en 0302NH

3.3.2 MPA valve terminal with pressure zone separation

The MPA valve terminal can be fitted with the followingnumber of pressure zones depending on the connection vari�ant:

Electrical connection variant

CPX terminal MP connection

Pressure zones 1 ... 8 1 ... 2

Table�3/2: Number of pressure zones

The pressure zones are implemented by means of special

sheet seals which separate the following channels:

� only supply channel (1)

� supply channel (1) and exhaust channels (3 and 5)

� only supply channels (3 and 5)

Please notePlease note with MPA valve terminals which are operatedwith internal auxiliary pilot air and which have severalpressure zones:

· The auxiliary pilot air is branched centrally from supplyconnection 1 of the pneumatic interface or the MP sub−base for all valve solenoid coils (see Figs. 3/4 and 3/5).

· The pressure zone which is supplied via connection 1 ofthe pneumatic interface or MP sub−base must be oper�ated with a pressure between 3 ... 8 bar.

The number of pressure zones with which your MPA valveterminal is fitted, is indicated by the marking on the seal (see

diagram.).

3. Installation

3−14 Festo P.BE−MPA−EN en 0302NH

1 2 3

5 6 7

8

4

MPA valve terminal with:

large surface−mounted silencer exhaust plates

1 Channels 1, 3 and 5 open 5 Channels 1, 3 and 5 open

2 Channels 1, 3 and 5 blocked 6 Channels 1, 3 and 5 blocked

3 Channel 1 blocked 7 Channel 1 blocked

4 Channels 3 and 5 blocked 8 Channels 3 and 5 blocked

Table�3/3: Sub−base seals, identification of the seal variants

The following diagrams show as an example the assignmentof the supply and exhaust connections to the valve plates onan MPA valve terminal with blocked channels 1, 3 and 5.

3. Installation

3−15Festo P.BE−MPA−EN en 0302NH

MPA valve terminal with CPX terminal

A pressure zone seal and a supply unit is required for eachpressure zone (see diagram).

The connections 1 or 3/5 are:

� for the pressure zone on the outside left of the pneumaticinterface.

� for all other pressure zones, on the supply unit which lieswithin the relevant pressure zones.The position of the supply unit in the pressure zone (left,centre or right) is optional, but two supply units (e.g. ofneighbouring pressure zones) must not lie next to eachother.

By fitting an additional supply unit within a pressure zone youcan supply additional supply air or extract exhaust air.

3. Installation

3−16 Festo P.BE−MPA−EN en 0302NH

ÖÖÖÖÎÎÎÎÖÖÖÖÖÖÖÖÖÖÎÎÎÎÎ

ÖÖÖÖÎÎÎÎÖÖÖÖÖÖÖÖÎÎÎÎ

ÖÖÖÖÎÎÎÎÖÖÖÖÖÖÖÖÎÎÎÎ

12 3 4

5

67

12/14

1 1 1

3/5 3/53/5

1 Pneumatic interface with supply con�nection 1 for presssure zone 1 andpilot connection 12/14 for the com�plete valve terminal

2 Pressure zone 1

3 Pressure zone 2

4 Pressure zone 3

5 Supply unit for pressure zone 3

6 Identification of the pressure zone di�viding seal (projecting flag)

7 Supply unit for pressure zone 2

Fig.�3/5: Example of MPA valve terminal with CPX terminal and 3 pressure zones

3. Installation

3−17Festo P.BE−MPA−EN en 0302NH

MPA valve terminal with MP connection

This MPA valve terminal variant can be converted to pressurezone separation with max. one seal.

Connections 1 or 3/5 are for the left−hand pressure zone on

the MP sub−base and for the right−hand pressure zone on thesupply unit on the outside right (see diagram). Pilot connec�tion 12/14 is on the MP sub−base.

ÖÖÖÖÎÎÎÎÎÎÎÎ

ÖÖÖÖÖÖÖÖÖÖÎÎÎÎÎ

ÖÖÖÖÖÎÎÎÎÎÎÎÎÎÎÖÖÖÖÖÖÖÖ

ÎÎÎÎÎ

12 3

4

5

3/5 3/5

12/14

1 1

1 MP sub−base

2 Pressure zone 1

3 Pressure zone 2

4 Supply unit

5 Identification of the pressure zone di�viding seal (projecting flag)

Fig.�3/6: Example: MPA valve terminal with MP connection and 2 pressure zones

3. Installation

3−18 Festo P.BE−MPA−EN en 0302NH

3.3.3 Vacuum/low pressure operation

Please noteValve plates with Ident. code N, K, H (2 x 3/2−way valves) andD (2 x 2/2−way valves) are not suitable for vacuum or lowpressure operation if they are supplied via connection 1.

· Operate these valves in a separate pressure zone.

· The operating pressure for this pressure zone must beset as shown in the diagram in Fig. 3/2.

The following conditions must be fulfilled before you can op�erate your MPA valve terminal at supply connection 1 with

vacuum or low pressure between �0.9 .... 3 bar:

� The pilot control of the valve solenoid coils is operatedwith regulated external auxiliary pilot air.

� The valve terminal is fitted with the following valve plates:

� 5/2−way valve, single−solenoid (Ident. code M)

� 5/2−way valve, double−solenoid (Ident. code J)

� 5/3−way valves (Ident. codes B, E and G)

3. Installation

3−19Festo P.BE−MPA−EN en 0302NH

3.3.4 Connecting the pneumatic tubing

Please note· Use blanking plugs to seal all connections not requiredfor the functioning of the MPA valve terminal.

Position of the pneumatic connections

Please noteIf the MPA valve terminals are fittted with large surface−mounted silencers, the exhaust from channels 3, 5, 82 and84 will be vented through the surface−mounted silencer.Connection 82/84 on the supply unit is then sealed with ablanking plug.

Fit the screw connector or the silencers according to the tablebelow. Then connect the pneumatic tubing.

3. Installation

3−20 Festo P.BE−MPA−EN en 0302NH

1

2

4

82/84

12/14

3/51

3/5

Fig.�3/7: Pneumatic connections on the MPA valve terminal

Tubing Connectionidentifier(ISO 5599)

Connectionsize(ISO 228)

Connection1)

Compressed airor vacuum

1 G1/4" Screw connector in the pneumatic inter�face, MP sub−base or supply unit

Pilot air (exter�nal auxiliary pilotair)

12/14 M7 Screw connector in the pneumatic inter�face or MP sub−base

Ducted exhaust 3/5 QS10 Screw connector in exhaust plate 2 )

Ductedpilot exhaust air

82/84 M7 Screw connector in supply unit 2

Work air or vacuum

2 or 4 M7 Screw connector in the sub−base

1) Depending on your order, the MPA valve terminal may already be fitted with QS screw connectors.2) Only with MPA valve terminals with exhaust plate or supply unit

Table�3/4: Assignment of connections

3. Installation

3−21Festo P.BE−MPA−EN en 0302NH

Observe the following instructions on installing the pneuma�tic components. Only then can you guarantee faultless oper�

ation.

Please noteIn the case of several systems with centrally ducted ex�haust air:

· Use non−return valves in the common exhaust lines 3/5or 82/84 in order to prevent functional impairment dueto back pressures.

1 MPA valve ter�minal 1

2 common 3/5

3 central 82/84

4 central 3/5

5 MPA valve ter�minal 2

6 common 82/84

1

2

3 4 5

6

6

2

2

Fig.�3/8: Common lines with non−return valves

3. Installation

3−22 Festo P.BE−MPA−EN en 0302NH

3.3.5 Connecting the electric cables

WarningUse only power units which guarantee reliable isolation ofthe operating voltages as per IEC 742/EN 60742/VDE 0551with at least 4 kV isolation resistance (Protected Extra LowVoltage PELV). Switch power packs are permitted, provid�ing they guarantee reliable isolation in accordance with EN60950/VDE 0805.

Please note:By the use of PELV power units, protection against electricshock (protection against direct and indirect contact) is guar�anteed with the Festo valve terminals in accordance with EN60204−1 / IEC 204. Safety transformers with the adjacentsymbol must be used for supplying PELV networks. The devi�ce must be earthed to ensure that it functions correctly (e.g.EMC).

Please noteCheck within the framework of your EMERGENCY STOPcircuit, to ascertain the measures necessary for puttingyour machine/system into a safe state in the event of anEMERGENCY Stop (e.g. switching off the operating voltagefor the valves and output modules, switching off the com�pressed air).

MPA valve terminal with CPX terminal: Instructions on connecting the operating voltage can befound in chapter 3 of the CPX system manual.Detailed instructions on connecting the CPX modules (fieldbus node, I/O modules etc.) can be found in the relevantmanuals for the CPX modules.MPA valve terminal with MP connection:Instructions on connecting the electric cables can be found inthe leaflet supplied with the product.

3. Installation

3−23Festo P.BE−MPA−EN en 0302NH

Earthing the MPA valve terminal

Please noteEarth your MPA valve terminal.

· Connect the earth connection on the left−hand end plateor on the MP sub−base (see diagram) with low impe�dance (short cable with large cross−sectional area) to theearth potential.

· Please note the supplementary instructions on the MPAvalve terminals with CPX terminal in the CPX systemmanual.

In this way you can avoid faults due to electromagneticinfluences and ensure electromagnetic compatibility inaccordance with EMC guidelines.

11

MPA valve terminal with MP connec�tion

MPA valve terminal with CPX terminal:

1 Earth/ground connection

Fig.�3/9: Earthing the MPA valve terminal

Detailed instructions on the earthing measures to be under�taken on the MPA valve terminals with CPX terminal can befound in chapter 3 in the CPX system manual.

3. Installation

3−24 Festo P.BE−MPA−EN en 0302NH

3.4 Address assignmentof the valves

MPA valve terminal with CPX terminal

� The assignment of the addresses is module−orientated

� A pneumatic module always occupies 8 addresses.

� Counting begins on the valve terminal from left to right

� Each valve location occupies 2 addresses, irrespective ofthe valve plate or blanking plate which is fitted.The following assignment applies:

� Solenoid coil 14 occupies the lower−value address,

� solenoid coil 12 occupies the higher−value address.

3. Installation

3−25Festo P.BE−MPA−EN en 0302NH

5

6

71

0 64

3

2 4

3

2

5

1 2

5

3 1 3

47

0

1

67

1 Valve plates with two solenoid coils

2 Valve plate with one solenoid coil

3 Blanking plate

4 Addresses of coil 12

5 Addresses of coil 14

6 Further pneumatic modules

7 First pneumatic module

Fig.�3/10: Example: Address assignment of a MPA valve terminal with CPX terminal and 8valve locations (top view)

Detailed instructions on addressing the pneumatic modulesof the MPA valve terminal with CPX terminal can be found inthe manual for the CPX I/O modules.

3. Installation

3−26 Festo P.BE−MPA−EN en 0302NH

MPA valve terminal with MP connection

� The addresses must be assigned in ascending order with�out gaps

� Counting begins on the valve terminal from left to right(see diagram).

� Depending on the sum of the valve locations, a valve loca�tion occupies one or two addresses (see table).The following assignment applies:

� Solenoid coil 14 occupies the lower−value address,

� solenoid coil 12 occupies the higher−value address.

Sum ofvalve loca�tions

Valve locations which occupy twoaddresses each 1)

Valve locations which occupy oneaddress each 2)

4 all valve locations −−−

8 all valve locations −−−

12 all valve locations −−−

16 valve locations 0 ... 7 valve locations 8 ... 15

20 valve locations 0 ... 3 valve locations 4 ... 19

24 −−− all valve locations

1) Two solenoid coils per valve location can be controlled. 2) One solenoid coil per valve location can be controlled.

Table�3/5: Address assignment on the MPA valve terminal with MP connection

3. Installation

3−27Festo P.BE−MPA−EN en 0302NH

1 3 5 7 9

0 2 4 6 8 10 12 14 16 17 18 19 20 21 22 23

11 13 15

1 2

5

6

3 4

1 Valve plates on valve locations whichoccupy two addresses each.

2 Blanking plate on a valve locationwhich occupies two addresses.

3 Valve plates on valve locations whichoccupy one address each.

4 Blanking plate on a valve locationwhich occupies one address

5 Addresses of coil 12

6 Addresses of coil 14

Fig.�3/11: Example: Address assignment of an MPA valve terminal with MP connectionand 16 valve locations (top view)

3. Installation

3−28 Festo P.BE−MPA−EN en 0302NH

Commissioning

4−1Festo P.BE−MPA−EN en 0302NH

Chapter 4

4. Commissioning

4−2 Festo P.BE−MPA−EN en 0302NH

Contents

4. Commissioning 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1 General instructions 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.1 Before commissioning 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1.2 Pressure increase in the complete supply 4−4 . . . . . . . . . . . . . . . . . . . .

4.2 Manual override 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3 Checking the valves and the valve−actuator combination 4−8 . . . . . . . . . . . . . . .

4.4 LED display of the valves 4−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.5 Eliminating faults 4−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.5.1 Impairment of function 4−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.5.2 Operating states of the pneumatic system 4−18 . . . . . . . . . . . . . . . . . . .

4. Commissioning

4−3Festo P.BE−MPA−EN en 0302NH

Contents of this chapter This chapter describes the commissioning of the MPA valveterminal. The following in particular belong here:

� Checking the valve functions

� Operating the manual override

� Checking the valve−actuator combination

� Eliminating faults

� The assignment of the LEDs

Further information Commissioning the CPX terminal is described in the appropri�ate manual for the CPX field bus node.

4. Commissioning

4−4 Festo P.BE−MPA−EN en 0302NH

4.1 General instructions

4.1.1 Before commissioning

· Switch off the power supply before connecting or discon�necting plugs (otherwise this could lead to functionaldamage).

· Commission only a valve terminal which has been fittedand wired completely.

· Make sure that there is a sufficient supply of fresh air(cooling) for the following operating conditions: � when the maximum number of valves are fitted� when the maximum operating voltage is applied�when the solenoid coil is constantly under stress

· Please observe the following instructions for building uppressure in the complete supply.

4.1.2 Pressure increase in the complete supply

WarningIf the build−up in pressure of the auxiliary pilot air is tooslow or delayed, this may cause the actuators to performsudden unexpected movements under the following condi�tions:

� If the compressed air is switched on with a safetystart−up valve (slow build up of pressure) and

� when there are electric signals (e.g. after EMERGENCYSTOP).

This can cause damage to the machine or system and eveninjury to human beings.

· Operate the valve terminal with external auxiliary pilotair (3 ... 8 bar). Branch the auxiliary pilot air in front ofthe safety start−up valve (see diagram).

4. Commissioning

4−5Festo P.BE−MPA−EN en 0302NH

The auxiliary pilot air must reach a pressure of 3 ... 8 bar assoon as it is switched on, Otherwise, there is no guarantee

that the valve will switch directly (see diagram). If the pressure is less than 3 bar, there may be a delay beforethe valve is switched, in spite of an electric signal being pres�

ent. The slow increase in pressure of the complete supplydoes not then affect the actuator. The actuator would reactsuddenly (e.g. a cylinder would extend or retract, depending

on the valve function).

1

4 2

5 3

14 12

1

2

1

12/14

12/14

3

82/84

2

1 Externally supplied auxiliary pilot air (3 to 8 bar),branched in front of the safety start−up valve

2 Safety start−up valve (slow build up of pressure of com�plete supply)

Fig.�4/1: Example of valve−cylinder combination with slowincrease in pressure of the complete supply

4. Commissioning

4−6 Festo P.BE−MPA−EN en 0302NH

The table below shows the effects of slow start−up pressuriza�tion when there are electric signals.

External auxi�liary pilot air

Pressure in�crease in com�plete supply

Pressure in�crease in theauxiliary pilotair (12/14)

Time pointwhen a valveswitches

Movement ofthe cylinder

Branched after thesafety start−upvalve

slow slow after pressure in�crease at (1)

fast

Branched in frontof the safety start−up valve

slow fast before pressureincrease at (1)

slow

Table�4/1: Effects of slow start−up pressurization

4.2 Manual override

You should use the manual override especially when commis�sioning the pneumatic system, in order to check the function

and operation of the valve or the valve−actuator combination.

By actuating the manual override, you can switch the valve

without an electric signal. You only need to switch on thecompressed air supply.

The manual override has been designed to be used as fol�lows:

Method of actuation Method of operation

non−locking After actuation the manual over�ride is reset by a spring.

manual override, locking The manual override remains ac�tuated until it is reset by hand.

Table�4/2: Actuation methods of the manual override

4. Commissioning

4−7Festo P.BE−MPA−EN en 0302NH

The locking/non−locking function of the manual override canbe modified to only non−locking actuation if a cap is fitted inthe manual override.

The assignment of the manual override actuations to thevalve solenoid coils is as follows:

1 3 5 7 9

0 2 4 6 8 10 12 14 16 17 18 19 20 21 22 23

11 13 151

2

1 Manual override for valve solenoidcoils 12

2 Manual override for valve solenoidcoils 14

Fig.�4/2: Position of the manual overrides (top view)

4. Commissioning

4−8 Festo P.BE−MPA−EN en 0302NH

4.3 Checking the valves and the valve−actuator combination

Please noteBefore commissioning the MPA valve terminal, note thespecifications concerning the medium, see section � Pilotcontrol of the valve solenoid coils (auxiliary pilot air)" inthe chapter �Installation."

The MPA valve terminal should be commissioned as follows:

Commissioning variants Activity

Preliminary test of the pneuma�tic tubing

Testing the valve−actuator com�bination by means of the manualoverride

Complete commissioning of thecomplete system

Installing and connecting thecomplete system.Program control via PLC/indu�strial PC

Table�4/3: Commissioning variants

Commissioning the pneumatic components by means of themanual override is described below.

Commissioning of the CPX terminal is described in the ap�propriate manual for the CPX field bus node.

4. Commissioning

4−9Festo P.BE−MPA−EN en 0302NH

WarningBefore actuating the manual override:

Uncontrolled actuation of the valve solenoid coils cancause the actuators to perform sudden unexpected move�ments which may cause injury to human beings and dam�age to property.

· Disconnect the power supply for the valve solenoid coilsfrom the relevant connections on the MPA valve ter�minal.

You will thereby avoid undesired actuation of the valvesolenoid coils.

Before switching on the power supply:

During commissioning, manual override functions whichare in the switched state can cause actuators to performsudden unexpected movements. These movements cancause injury to human beings and damage to property.

· Make sure that all manual override actuations are intheir basic positions.

You will thereby avoid undefined switching states of thevalves.

Proceed as follows:

WarningBefore checking the valve−actuator combination:

� Make sure that nobody is in the danger zone.

1. Switch on the compressed air supply.

2. Check the functioning and operation of each individual

valve−actuator combination by actuating the manual overrideas shown in the following diagrams.

4. Commissioning

4−10 Festo P.BE−MPA−EN en 0302NH

Please noteIncorrect actuation of the non−locking manual override canlead to malfunctioning or damage to the manual override.

· Use a screwdriver (blade width max. 2.5 mm) for actuat�ing the manual override.

· Actuate the manual override with only max 25 N.

3. With the locking function of the manual override, make

sure, after testing the valves, that all manual overrideactuations are in their basic positions.

4. Switch off the compressed air supply after checking thevalves.

4. Commissioning

4−11Festo P.BE−MPA−EN en 0302NH

Before actuating the manual override: (automatic reset)

Operation Reaction of the valve

· Use a screwdriver (max. bladewidth 2.5 mm) to press down theplunger of the manual overrideuntil the valve switches.

Please noteIn the case of manual overrides with−out a cap, do not turn the pressed−down plunger as otherwise the ma�nual override will lock.

The valve:� moves to the switching position

Hold the plunger of the manual over�ride pressed down.

� remains in the switch position

· Release the plunger (the springresets the plunger of the manualoverride to the starting position).

� moves back to the basic position(not with double−solenoid valve,Ident. code J))

Table�4/4: Operating the non−locking manual override

Please noteA valve which has been switched by an electric signal (inswitch position), cannot be reset to the basic positionwhen the manual override is actuated. The electric signalis dominant in this case.

· Reset the electric signal before actuating the manualoverride.

4. Commissioning

4−12 Festo P.BE−MPA−EN en 0302NH

Please noteThe locking actuation of the manual override is only poss�ible if a manual override cap is not fitted.

Locking actuation of the manual override (reset manually)

Operation Reaction of the valve

· Use a screwdriver (max. bladewidth 2.5 mm) to press down theplunger of the manual overrideuntil the valve switches.

· Then turn the plunger in a clock�wise direction as far as possible.

The valve:� moves to the switching position

· Leave the plunger in position. � remains in the switch position

· Then turn the plunger in an anti−clockwise direction as far as poss�ible.

· Then release the plunger.

� moves back to the basic position(not with double−solenoid valve,Ident. code J))

Table�4/5: Operating the non−locking manual override

4. Commissioning

4−13Festo P.BE−MPA−EN en 0302NH

CautionDuring commissioning, manual override functions whichare in the switched state can cause actuators to performsudden unexpected movements. These movements cancause injury to human beings and damage to property.

· Before commissioning, bring the �manual override actua�tions into the basic position again.

4. Commissioning

4−14 Festo P.BE−MPA−EN en 0302NH

4.4 LED display of the valves

There is an LED for every valve solenoid coil. The diagrambelow shows the position of the LED and the manual override

for the relevant valve solenoid coil.

1 LED and manualoverride for valvesolenoid coil 12

2 LED and manualoverride for valvesolenoid coil 14

12 1212 12 12 12 12 12

14 14 14 14 14 14 14 14 14 14 14 14

21

2

1

Fig.�4/3: Assignment of LEDs and manual override to thevalve solenoid coils

4. Commissioning

4−15Festo P.BE−MPA−EN en 0302NH

MPA valve terminal with CPX terminal

The LEDs have a double function.

� When yellow the LEDs indicate the switching status of thevalve solenoid coils.

� When red the LEDs indicate a fault in the electronic mo�dule. All the LEDs of a pneumatic module then light upred.

LED Switching position of thevalve

Meaning

out Basic position logical 0 (no signal)

yellow alight � switch positionor

� basic position

logical 1 (signal present)

logical 1 but:� compressed air supply not OK

or� pilot exhaust blocked

or� servicing required

lights up red � in the starting phase for ap�prox.

2 seconds

� during operation

� Test phase when power supply has beenswitched on

� Operating voltage of the valves lies belowthe permitted tolerance range (18 ... 30 V DC)

� Module fault e.g. undervoltage of the electronic module (see manual for CPX I/O modules)

Table�4/6: Meaning of the LED display (MPA valve terminal with CPX terminal)

Further instructions on commissioning and diagnosing theMPA pneumatic modules can be found in the manual for theCPX I/O modules.

4. Commissioning

4−16 Festo P.BE−MPA−EN en 0302NH

MPA valve terminal with MP connection

The LEDs indicate the switching status of the valve solenoidcoils..

LED Switching position of thevalve

Meaning

out basic position logical 0 (no signal)

yellow alight � switch positionor

� basic position

logical 1 (signal present)

logical 1 but:� load voltage of the valves lies below the per�

mitted tolerance range (18 V ... 30 V DC)

� compressed air supply not OKor

� pilot exhaust blockedor

� servicing required

Table�4/7: Meaning of the LED display (MPA valve terminal with MP connection)

4. Commissioning

4−17Festo P.BE−MPA−EN en 0302NH

4.5 Eliminating faults

4.5.1 Impairment of function

After switching on the compressed air supply or when subse�quently testing the individual valves, you can learn the following

about the operating status of the pneumatic system:

Operating status ofthe pneumatic system

Fault treatment when the compressed airsupply has been switched off

Air escapes from ...� common line or work line connections · Check the tubing fitting

The valve or the pneumatic systemdoes ...� not react as expected

� not react

· Check the tubing· Check the electric cables

· Bring the locking manual override into thebasic position�

· After switching on again check the operatingpressure (if necessary for each pressure zone)Set operating pressure in accordance with in�structions in chapter 3.

· In the case of valve terminals which are oper�ated with regulated external auxiliary pilot air,check the pilot pressure after switching onagain (if necessary set as a factor of the operat�ing pressure, see chapter 3)

· servicing required

Table�4/8: Operating status of the pneumatic system

4. Commissioning

4−18 Festo P.BE−MPA−EN en 0302NH

4.5.2 Operating states of the pneumatic system

The following conditions should be fulfilled, in order that thedesired pneumatic operating states listed below can be

achieved:

Desired pneuma�tic operating sta�tus

Prerequisites Remarks

free of leakage � tubing connected with care� regulated auxiliary pilot air

fast reaction sufficient pressure supply via pres�sure supply points

· Exhaust the MPA valve terminal viaall the exhaust plates or via thelarge surface−mounted silencer

faultless non−return valves in common ex�haust line

This applies when several systemswith centrally ducted exhaust areused

two or more pressurezones

limiting the pressure zones by meansof sheet seals with blocked channels

subsequent conversion possible (seechapter 5)

vacuum or low−pres�sure operation

externally supplied regulated auxi�liary pilot air (3 ... 8 bar)

� controller can only be operatedwith pressure (between 3 ... 8 bar)

� vacuum/low−pressure operationnot with 3/2−way valves

EMERGENCY STOP ofpressure zones

guaranteeing the controller functionfor the auxiliary pilot air despite thecomplete supply being switched off

The controller regulates the auxiliarypilot air of all the valve plates on anMPA valve terminal

slow start−up afterEMERGENCY STOP

If there are control signals, the auxi�liary pilot air must have a pressure of3 ... 8 bar immediately after beingswitched on

Table�4/9: Pneumatic operating states

Maintenance and conversion

5−1Festo P.BE−MPA−EN en 0302NH

Chapter 5

5. Maintenance and conversion

5−2 Festo P.BE−MPA−EN en 0302NH

Contents

5. Maintenance and conversion 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.1 General precautionary measures 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.2 Dismantling the MPA valve terminal 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3 Servicing the MPA valve terminal 5−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.1 Cleaning the large surface−mounted silencer 5−7 . . . . . . . . . . . . . . . . .

5.4 Replacing MPA valve terminal components 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . .

5.4.1 Replacing valve plates or blanking plates 5−8 . . . . . . . . . . . . . . . . . . . .

5.4.2 Replacing the electronic modules 5−11 . . . . . . . . . . . . . . . . . . . . . . . . . .

5.4.3 Fitting/removing the large surface−mounted silencer or the exhaust plate 5−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.4.4 Replacing the sub−base 5−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.5 Converting the MPA valve terminal 5−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.5.1 Conversion to internal or external pilot air 5−18 . . . . . . . . . . . . . . . . . . . .

5.5.2 Converting the MPA valve terminal to different pressure zones 5−21 . . .

5.5.3 Adding valve locations 5−27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5. Maintenance and conversion

5−3Festo P.BE−MPA−EN en 0302NH

Contents of this chapter This chapter explains how you should fit and remove the fol�lowing components for maintenance work and conversion:

� valve plates or blanking plates

� electronic modules

� exhaust plate or large surface−mounted silencer

� sub−bases

The following activities are also described:

� adding pressure zones

� converting the valve terminal to internal or external auxili�ary pilot air

Further information MPA valve terminal with CPX terminal: Information on fitting /removing components and on the elec�trical connections can be found in the CPX system manual.

MPA valve terminal with multipin connection:Instructions on connecting the electric components can befound in the leaflet supplied with the product.

5. Maintenance and conversion

5−4 Festo P.BE−MPA−EN en 0302NH

5.1 General precautionary measures

WarningSudden unexpected movement of the connected actuatorsand uncontrolled movements of loose tubing can causeinjury to human beings or damage to property.

Before carrying out installation and maintenance work,switch off the following:

· the compressed air supply

· the operating and load voltage supplies.

Please noteHandle all modules and components of the valve terminalwith great care. Note especially the following when fittingcomponents:

· Screws must be fitted accurately (otherwise threads willbe damaged).

· Screws must be screwed in only by hand. Place thescrews so that the self−cutting threads are used.

· The specified torques must be observed.

· Screw connections must be fitted free of offset andmechanical tension.

· Check the seals for damage (IP 65).

· The contact surfaces must be dry and clean (sealingeffect, avoid leakage and contact faults).

5. Maintenance and conversion

5−5Festo P.BE−MPA−EN en 0302NH

5.2 Dismantling the MPA valve terminal

Providing the MPA valve terminal is easily accessible, it neednot be dismantled when the following components are re�placed or removed:

� valve plates or blanking plates

� electronic modules

� exhaust plates or large surface−mounted silencer

Loosening the electrical connections

Connecting variants Procedure

CPX terminal · Instructions on loosening the electrical connections can be found inthe CPX system manual.

MP connection · Loosen and remove the fastening screws of the sub−D multipin plug.

Table�5/1: Loosening the electrical connections

5. Maintenance and conversion

5−6 Festo P.BE−MPA−EN en 0302NH

Loosening the pneumatic connections

WarningIf the pneumatic tubing is under pressure when connec�tions are loosened, it may perform sudden unexpectedmovements, thereby causing injury to human beings.

· Switch off the compressed air supply before disconnect�ing the pneumatic tubing on the MPA valve terminal.

Proceed as follows:

1. Mark all pneumatic tubing.

2. Press down the blue clamping ring 1 of the screw con�nector, e.g. with a screwdriver.

3. Pull the pneumatic tubing away from the screw connector.

1

Fig.�5/1: Removing the tubing

Dismantling the MPA valve terminal

The procedure for dismantling the MPA valve terminal is de�scribed in chapter 2.

5. Maintenance and conversion

5−7Festo P.BE−MPA−EN en 0302NH

5.3 Servicing the MPA valve terminal

5.3.1 Cleaning the large surface−mounted silencer

CautionDirt in the large surface−mounted silencer can cause anincrease in pressure in exhaust channels 3 and 5.

· Clean the silencer insert if it is yellow/black or a darkcolour, or replace it by a new insert.

· Do not use TRI for cleaning, but benzine or paraffin.

· Observe the safety regulations for easily inflammablecleaning agents.

In this way you can ensure that the large surface−mountedsilencer functions correctly and that the valves operatecorrectly.

Proceed as follows:

1. Loosen the 6 fastening screws of the surface−mounted

silencer and remove it from the basis components.

2. Clean the surface−mounted silencer with benzine or paraf�

fin.

3. Check the seal between the basis component and the

surface−mounted silencer for damage. Replace the seal ifit is damaged.

4. Fasten the silencer only with the original screws. Tightenthe screws in diagonally opposite sequence

with 1.0 Nm.

5. Maintenance and conversion

5−8 Festo P.BE−MPA−EN en 0302NH

5.4 Replacing MPA valve terminal components

The components on the sub−bases of the MPA valve terminalcan easily be removed for maintenance and conversion work.

5.4.1 Replacing valve plates or blanking plates

Please noteThe sub−bases of the MPA valve terminal with MP connec�tion support the control of one or two solenoid coils, de�pending on the equipment fitted (total number of valvelocations) (see chapter 3, table 3/5).

Dismantling Proceed as follows:

· Use a narrow screwdriver to loosen the fastening screwsand remove the components from the sub−bases (seediagram).

5. Maintenance and conversion

5−9Festo P.BE−MPA−EN en 0302NH

Fig.�5/2: Removing valve plates or blanking plates

Fitting Proceed as follows:

1. Make sure the seal is not damaged.

2. Replace the seal if it is damaged.

3. Make sure that the seal is seated correctly. The cord seal between the sub−base and the componentmust be seated in the groove in the component sitzen.

The ring seals between the electronic module and thecomponent are conical. They must be fitted onto the

guide pin of the component, so that the cone fits easilyinto the appropriate recess in the electronic module whenit is mounted (alignment see

Fig. 5/3).

5. Maintenance and conversion

5−10 Festo P.BE−MPA−EN en 0302NH

1 Fastening screwsof the valve plateor blanking plate

2 Valve plate orblanking plate

3 Cord seal

4 2 conical sealsper valve plate orblanking plate(observe thealignment)

5 Sub−base

6 Electronic module

1

2

3

4

5

6

Fig.�5/3: Fitting valve plates or blanking plates

4. Place the component on the sub−base.

5. Screw the component at first only slightly and thentighten with 0.25 Nm (− 20%).

5. Maintenance and conversion

5−11Festo P.BE−MPA−EN en 0302NH

5.4.2 Replacing the electronic modules

The MPA valve terminal is fitted with one electronic moduleper sub−base. It provides for 4 valve locations the contactbetween the electrical linking and the solenoid coils. TheLEDs (function see chapter 4) and further electronic compo�nents are an integral part of the electronic module.

CautionThe electronic modules may be damaged if they are nothandled correctly.

· Switch off the power supply before removing the elec�tronic modules.

· Do not therefore touch any contact surfaces.

· Observe the regulations for handling electrostaticallysensitive components.

· Discharge yourself electrostatically before fitting or re�moving components in order to protect the componentsagainst discharges of static electricity.

Before removing the electronic module, you must first removeall valve plates or blanking plates on the relevant electronicmodule (see section �Removing valve plates or blankingplates�).

Dismantling Proceed as follows:

1. Loosen the screws with which the electronic module isfastened to the sub−base.

2. Pull the electronic module upwards out of the body of thesub−base.

5. Maintenance and conversion

5−12 Festo P.BE−MPA−EN en 0302NH

Before fitting the electronic module

There are different designs of the electronic module depend�ing on the connection variant.

MPA valve terminal with CPX terminal

Please noteFeatures of the MPA valve terminal with CPX terminal de�pend on the type of electronic module fitted, e.g.:

� Electromagnetic compatibility (EMC)

� Switching off the valve power supply at all poles

You must observe the instructions in the manual for theCPX I/O modules if you wish to fit an electronic module ofa different type.

Recommendation:

Replace only with electronic modules of the same type.

The following types are available:

� Type VMPA1−FB−EMG−8: electronic module with 8 outputsand electrical isolation of the supply voltages.

� Type VMPA1−FB−EMS−8: electronic module with 8 outputswithout electrical isolation of the supply voltages.

The electronic modules type VMPA1−FB−... support the controlof two valve solenoid coils per valve location.

5. Maintenance and conversion

5−13Festo P.BE−MPA−EN en 0302NH

Fitting Proceed as follows:

Please noteBefore fitting, check the condition and position of the fol�lowing seals:

� the seal of the electronic module

� the ring seal of the electrical contact

� the cord seal of the valve plates or blanking plates

1. Place the electronic module in the sub−base.

2. Tighten the screws of the electronic module with with 0.25 Nm.

3. Then fit the valve plates or blanking plates (see section�Fitting valve plates or blanking plates").

MPA valve terminal with MP connection

CautionReplace an electronic module only by an electronic moduleof the same type.

� You can then avoid problems in controlling the valvesolenoid coils and damage to the electrical contacts.

The following types are available:

� type VMPA1−MP−EMS−4: Electronic module with 4 out�puts. One valve solenoid coil can be controlled per valvelocation.

� type VMPA1−MP−EMS−8: Electronic module with 8 outputs.Two valve solenoid coils can be controlled per valve loca�tion.

5. Maintenance and conversion

5−14 Festo P.BE−MPA−EN en 0302NH

5.4.3 Fitting/removing the large surface−mounted silencer or the exhaustplate

Proceed as follows:

1. Loosen the 6 fastening screws of the large surface−

mounted silencer or exhaust plate and remove it from thebasis components.

2. Check the seal between the basis component and thesurface−mounted silencer or exhaust plate for damage.

Replace the seal if it is damaged.

3. Make sure that the seal is seated correctly. The seating is

determined by guides in the large surface−mounted si�lencer or exhaust plate.

4. Fasten the large surface−mounted silencer or exhaustplate only with the original screws. Tighten these screwsin diagonally opposite sequence with max. 0.65 Nm (ex�

haust plate) or 1.0 Nm (large surface−mounted silencer).

5.4.4 Replacing the sub−base

Dismantling Proceed as follows:

1. Loosen the electrical and pneumatic connections and re�move the MPA valve terminal from its fastening surface(see this chapter, �Dismantling the MPA valve terminal").

2. Place the MPA valve terminal on a flat working surface.

Please noteMPA valve terminal with MP connection:

Before dismantling the sub−bases, you must remove allcomponents (valve plates, blanking plates and electronicmodules) from all sub−bases.

5. Maintenance and conversion

5−15Festo P.BE−MPA−EN en 0302NH

3. Loosen and remove the screws of the sub−bases whichyou wish to dismantle. The sub−bases are now held to�

gether only by the electrical linking or by the bus.

ÖÖÖÖ

ÖÖÖÖ

Fig.�5/4: Position of the screw connectors of the sub−basesand the right−hand end plate

4. Pull the relevant sub−base away from the neighbouringsub−bases.

5. Maintenance and conversion

5−16 Festo P.BE−MPA−EN en 0302NH

Fitting Proceed as follows:

1. Make sure the seals are not damaged. Replace the seals ifthey are damaged. Place the flat seal onto the guide pinof the sub−base.

1 Guide pins

2 Sheet seal (op�tional with pres�sure zone separ�ation)

2

1

1

Fig.�5/5: Fitting the sub−base

2. Place the new sub−base onto the sheet seal.

5. Maintenance and conversion

5−17Festo P.BE−MPA−EN en 0302NH

3. Screw the sub−bases together. Tighten the screw con�nectors in the sequence 1, 2, 3as shown in the dia�

gram at first slightly and then with 1.3 Nm.

1

2

2

1

3

Fig.�5/6: Screw connectors of the sub−bases

4. Mount the MPA valve terminals onto the fastening surface

(see chapter 2 �Fitting onto a wall" or �Fitting onto a hatrail").

5. Then fit the pneumatic and electrical connections (seechapter 3� Installation, connecting the MPA valve ter�minal").

5. Maintenance and conversion

5−18 Festo P.BE−MPA−EN en 0302NH

5.5 Converting the MPA valve terminal

The following conversion work can be undertaken on the MPAvalve terminal:

� conversion of the MPA valve terminal to internal or exter�nal auxiliary pilot air

� conversion of the MPA valve terminal to different pressurezones

� Adding valve locations (sub−bases)

5.5.1 conversion to internal or external pilot air

Depending on the pneumatic interface or multipin sub−basefitted, pilot control of the valve solenoid coils can be carried

out with internal or external auxiliary pilot air.

Please noteMixed operation of the MPA valve terminal with internaland external auxiliary pilot air is not intended. Irrespectiveof the available pressure zones, all valve solenoid coils ofthe MPA valve terminal are supplied with the same auxili�ary pilot air.

5. Maintenance and conversion

5−19Festo P.BE−MPA−EN en 0302NH

You can ascertain the pilot control variant, for which yourMPA valve terminal is equipped, by the following features

(see table).

Pneumatic interface or MP sub−base

Description

For operating the pilot control withexternal auxiliary pilot air

� Pilot connection 12/14 is marked on the pneumaticinterface or on the MP sub−base and is open.

� The auxiliary pilot air is supplied externally via pilotconnection 12/14.

� Pressure zone separation is permitted.� Unused connections must be sealed.

For operating the pilot control withinternal auxiliary pilot air

� Pilot connection 12/14 is not marked on the pneumaticinterface or on the MP sub−base and is closed.

� The auxiliary pilot air is branched internally from con�nection 1.

� Pressure zone separation is permitted.� Unused connections must be sealed.

Table�5/2: Components for operating the pilot control with internal or external auxiliarypilot air

5. Maintenance and conversion

5−20 Festo P.BE−MPA−EN en 0302NH

Variants Pneumaticinterface

MP connectionblock

Recognition features

� Pilot control with in�ternal auxiliary pilotair

� Ducted exhaust

VMPA...−FB−EPL−G VMPA...−MP−EPL−G � connection 12/14 sealed� exhaust plate

� Pilot control with in�ternal auxiliary pilotair

� Exhausting via largesurface−mounted si�lencer

VMPA...−FB−EPL−GU VMPA...−MP−EPL−GU � connection 12/14 sealed� Large surface−mounted si�

lencer

� Pilot control with ex�ternal auxiliary pilotair

� Ducted exhaust

VMPA...−FB−EPL−E VMPA...−MP−EPL−E � connection 12/14 open� exhaust plate

� Pilot control with ex�ternal auxiliary pilotair

� Exhausting via largesurface−mounted si�lencer

VMPA...−FB−EPL−EU VMPA...−MP−EPL−EU � connection 12/14 open� Large surface−mounted si�

lencer

Table�5/3: Variants of the pneumatic interface or MP sub−base

5. Maintenance and conversion

5−21Festo P.BE−MPA−EN en 0302NH

5.5.2 Converting the MPA valve terminal to different pressure zones

The MPA valve terminal can be fitted with the followingnumber of pressure zones depending on the connecting vari�ant:

Electrical connection variant

CPX terminal MP connection

Pressure zones 1 ... 8 1 ... 2

Table�5/4: Number of pressure zones

The pressure zones are implemented by means of special

sheet seals which separate the following channels:

� only the supply channel (1)

� supply channel (1) and exhaust channels (3 and 5)

� only exhaust channels (3 and 5)

5. Maintenance and conversion

5−22 Festo P.BE−MPA−EN en 0302NH

You can recognize by the marking on the seal, whether yourMPA valve terminal is fitted with pressure zones (see dia�

gram).

1 2 3

5 6 7

8

4

MPA valve terminal with:

large surface−mounted silencer exhaust plates

1 Channels 1, 3 and 5 open 5 Channels 1, 3 and 5 open

2 Channels 1, 3 and 5 blocked 6 Channels 1, 3 and 5 blocked

3 Channel 1 blocked 7 Channel 1 blocked

4 Channels 3 and 5 blocked 8 Channels 3 and 5 blocked

Table�5/5: Sub−base seals, identification of the seal variants

5. Maintenance and conversion

5−23Festo P.BE−MPA−EN en 0302NH

Conversion of the MPA valve terminal with CPX ter�minal

In order to convert the MPA valve terminal with CPX terminal

to 3 ... 8 pressure zones, you will require the following com�ponents for each pressure zone:

� sheet seal with pressure zone separation VMPA..−DP−...

� A supply plate with exhaust plate or large surface−

mounted silencer VMPA..−FB−SP or VMPA..−FB−SPU

Dismantling Proceed as follows:

1. Loosen the electrical and pneumatic connections and re�move the MPA valve terminal from the fastening surface(see section �Dismantling the MPA valve terminal" in thischapter).

2. Place the MPA valve terminal on a flat working surface.

3. Loosen the sub−base at the point where you wish to insertthe sheet seal for the pressure zone separation (see sec�tion �Dismantling sub−bases").

5. Maintenance and conversion

5−24 Festo P.BE−MPA−EN en 0302NH

Fitting Proceed as follows:

1. Insert the sheet seal for the pressure zone separation.

2. Fit the sub−base (see section �Fitting sub−bases").

3. Mount the MPA valve terminals onto the fastening surface(see chapter 2 �Fitting onto a wall" or �Fitting onto a hat

rail").

4. Then fit the pneumatic and electrical connections (see

chapter 3� Installation, connecting the MPA valve ter�minal").

The following diagram shows the layout of pressure zones

using as an example an MPA valve terminal with CPX ter�minal.

5. Maintenance and conversion

5−25Festo P.BE−MPA−EN en 0302NH

1 2 3

4567 5

1 Valve plates of the 1st. pressure zone

2 Valve plates of the 2nd. pressure zone

3 Valve plates of the 3rd. pressure zone

4 Supply unit with connection 1 for supplying compressed air to the 3rd. pressurezone

5 Identifying the sheet seal with pressure zone separation

6 Supply unit with connection 1 for supplying compressed air to the 2nd. pres�sure zone

7 Pneumatic interface with connection 1 for supplying compressed air to the 1st.pressure zone

Fig.�5/7: Example of MPA valve terminal with CPX terminal and 3 pressure zones

5. Maintenance and conversion

5−26 Festo P.BE−MPA−EN en 0302NH

Conversion of the MPA valve terminal with MP con�nection

In order to convert the MPA valve terminal to two pressure

zones, you will require the following components:

� one sheet seal with pressure zone separation MPA−DP−...

� one supply unit if the MPA valve terminal is not yet fittedwith this.

Please noteThe MPA valve terminal with MP connection can be fittedwith max. one seal for pressure zone separation. The left−hand pressure zone is supplied via the MP sub−base; theright−hand pressure zone via a supply plate which is situ�ated next to the right−hand end plate.

Dismantling Proceed as follows:

1. Loosen the electrical and pneumatic connections and re�move the MPA valve terminal from the fastening surface(see section �Dismantling the MPA valve terminal" in thischapter).

2. Place the MPA valve terminal on a flat working surface.

3. Remove all valve plates and blanking plates and then allelectronic modules (see section �Dismantling valve platesor blanking plates")

4. Loosen the sub−base at the point where you wish to insertthe sheet seal for the pressure zone separation (see sec�tion �Dismantling sub−bases").

Fitting Proceed as follows:

1. Insert the sheet seal for the pressure zone separation.

2. Fit the sub−base (see section �Fitting sub−bases").

5. Maintenance and conversion

5−27Festo P.BE−MPA−EN en 0302NH

3. Fit all the electronic modules again the Sub−base (seesection �Fitting the electronic modules").

4. Fit all the valve plates and blanking plates again (see sec�tion �Fitting valve plates or blanking plates").

5. Mount the MPA valve terminals onto the fastening surface(see chapter 2 �Fitting onto a wall" or �Fitting onto a hat

rail").

6. Then fit the pneumatic and electrical connections (see

chapter 3� Installation, connecting the MPA valve ter�minal").

5.5.3 Adding valve locations

The MPA valve terminal with MP connection is available with4, 8, 12, 16, 20 or 24 valve locations. With this valve terminalvariant it is not intended that the number of valve locationsbe increased or reduced.

Adding valve locations

You can easily adapt the MPA valve terminal with CPX terminal

to the demands of your machine or system by adding valvelocations.

The smallest extension unit is a sub−base with 4 valve loca�tions.

For extension you will require:

5. Maintenance and conversion

5−28 Festo P.BE−MPA−EN en 0302NH

Components Type

1 sub−base per 4 valve locations VMPA..−FB−AP−...

1 electronic module per sub−base VMPA..−FB−EM−...

4 valve plates or blanking plates per sub−base VMPA..−M1H−...

Table�5/6: Valve location extension

Dismantling Proceed as follows:

1. Loosen the MPA valve terminal from the fastening surface(see section �Dismantling the MPA valve terminal").

2. Dismantle the sub−base or the supply plate at the pointwhere you wish to extend the valve terminal (see section�Dismantling sub−bases").

5. Maintenance and conversion

5−29Festo P.BE−MPA−EN en 0302NH

Fitting Proceed as follows:

1. Fit the new sub−base and, if necessary, a further supplyunit (see section �Fitting sub−bases").

2. Fit the valve plates or blanking plates onto the emptyvalve locations (see section �Fitting valve plates or blank�ing plates").

3. Fit the MPA valve terminal onto the fastening surface (seechapter 2 �Fitting onto a wall" or �Fitting onto a hat rail").

4. Then fit the pneumatic and electrical connections (see

chapter 3� Installation, connecting the MPA valve ter�minal").

Please noteIf a sub−base is inserted between existing sub−bases, theaddress assignment of all the valves to the right of theinserted sub−base will be modified.

5. Maintenance and conversion

5−30 Festo P.BE−MPA−EN en 0302NH

Technical appendix

A−1Festo P.BE−MPA−EN en 0302NH

Appendix A

A. Technical appendix

A−2 Festo P.BE−MPA−EN en 0302NH

Contents

A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.1 Technical specifications A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2 Festo accessories A−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A. Technical appendix

A−3Festo P.BE−MPA−EN en 0302NH

A.1 Technical specifications

General information Type MPA1

Permitted temperature range� long−time storage� operation� medium

− 20 ... + 40 oC − 5 ... + 50 oC − 5 ... + 50 oC

Protection class as per EN 60 529 IP 65 (with cable from Festo accessories)

Relative humidity 90 % at 40 oC

Protection against corrosion KBK1 (as per FN940070)

Mounting position as desired

Torques� Components on the sub−bases� Exhaust plate on supply unit� Large surface−mounted silencer on supply unit� Fastening of the sub−base� Multipin connection� Support bracket on the supply unit

0.25 Nm (± 20%)0.65 Nm

1.0 Nm1.3 Nm0.65 Nm1 Nm

Materials� Sub−base, supply unit

valve and end plates� electronic modules� MP connection� seals

AlPOM/polycarbonatePolyamide 6elastomer, NBR

Weight (in g):� basic weight� per pneumatic module (4 valve plates)� per supply plate with exhaust plate or large

surface−mounted silencer� per complete CPX module� left−hand end plate

approx. 400 gapprox. 255 g

approx. 120 gapprox. 210 gapprox. 80 g

Table�A/1: General technical specifications

A. Technical appendix

A−4 Festo P.BE−MPA−EN en 0302NH

General information Type MPA1

Vibration and shock 3)

� Vibration1)

� Shock1)

� Continual shock

tested as per DIN/IEC68 / EN60068 part 2−6,With hat rail fitting: severity class 1With wall fitting: 2)

tested as per DIN/IEC68 / EN60068 part 2 − 27,With hat rail fitting: severity class 1With wall fitting: 2)

tested as per DIN/IEC68 / EN60068 part 2 − 29,With wall and hat rail fitting:severity class 1

1)Specifications on vibration and shock of the CPX terminal can be found in the manual for the CPX system.

2) MPA valve terminal with MP connection and more than 5 sub−bases: severity class 1MPA valve terminal with CPX terminal and − up to 5 sub−bases: severity class 2− up to 6 sub−bases with additional fastenings (wall bracket) on every 2nd. ... 4th. supply unit: severity class 2

− 6 or more sub−bases without additional fastenings: severity class 13) Explanations on the severity classes see following table.

Table�A/2: Vibration and shock

Severityclass

Vibration Shock Continual shock

1 0.15 mm path at 10−58 Hz2 g acceleration at 58−150 Hz

±15 g at 11 ms duration; 5 shocks in each direction

±15 g at 6�ms duration;1000 shocks in eachdirection

2 0.35 mm path at 10−60 Hz5 g acceleration at 60−150 Hz

±30 g at 11 ms duration; 5 shocks in each direction

−−−−−

Table�A/3: Values for vibration and shock as per DIN/IEC68

A. Technical appendix

A−5Festo P.BE−MPA−EN en 0302NH

Please noteThe valves can be used at temperatures down to −5 oC. Inorder to prevent the condensate and the humidity fromfreezing, we recommend that you fit a dryer with whichcondensate and humidity can be removed.

Pneumatics Type MPA1

Medium compressed air, filtered (< 40 µm), lubricated (oil: VG 32)or non−lubricated/vacuum

Design Valve plates with piston spool valves

Pilot control� with auxiliary pilot air branched inter�

nally from connection 1

� with external auxiliary pilot air

Pressure rangeValve location Ident. code D, N, K, H, X, M, J, B, G, E):at connection 1; 12/14: 3 ... 8 bar

Valve location Ident. code B, E, G, J, M and Xat connection 1: −0,9 ... 10 barValve location Ident. code D, H, N, K at connection 1: 3 ... 10 bar All valve plates:at connection 12/14: see relevant diagrams

Manual override locking or non−locking

Table�A/4: Medium and pressure range

A. Technical appendix

A−6 Festo P.BE−MPA−EN en 0302NH

1 Pilot pressure 12bar [14 bar]

2 Work range forvalves with exter�nal auxiliary pilotair

3 Work pressure P1[bar]

0 1 2 3 4 5 6 7 8 9 100

1

2

3

4

5

6

7

8

9

1

2

3

Fig.�A/1: Diagram: Pilot pressure with external auxiliary pilot air for valve plates withIdent. code N, K, H and D

1 Pilot pressure12/14 [bar]

2 Work range forvalves with exter�nal auxiliary pilotair

3 Work pressure P1[bar]

0 1 2 3 4 5 6 7 8 9 10

12

3

4

5

6

7

8

9

−10

1

2

3

Fig.�A/2: Diagram: Pilot pressure with external auxiliary pilot air for valve plates withIdent. code M, J, B, E, G and X

A. Technical appendix

A−7Festo P.BE−MPA−EN en 0302NH

Please noteThe screw connectors of the pneumatic connections causea reduction in the flow rate of the valves.

Pneumatics Type MPA1

Ident. code ofthevalve plate

Valve Rated flow [l/min] �(always without screw connector)Values of the mid−position in brackets

DNKHXMJBGE

2 x 2/2 way valves2 x 3/2−way valves2 x 3/2−way valves2 x 3/2−way valves1 x 3/2−way valve, closed,5/2−way valve (single−solenoid)5/2−way valve (double−solenoid)5/3−way valve, pressurized5/3−way valve, closed5/3−way valve, exhausted

1 ⇒ 2 or 1 ⇒ 4230300230280255360360

300 (195)320240

2 ⇒ 3/5 or 4 ⇒ 3/5230300310305295360360270320

240 (180)

Valve switching times in [ms](measuring method 0�10 %) (as perFN942032)

On, switch over Off

DN, K, HXMJB, G, E

2 x 2/2−way valvesall 2 x 3/2−way valves1 x 3/2−way valve, closed,5/2−way valve (single−solenoid)5/2−way valve (double−solenoid)5/3−way valves

101010101010

202020202035

Table�A/5: Rated flows and valve switching times

A. Technical appendix

A−8 Festo P.BE−MPA−EN en 0302NH

Electric components

Electromagnetic compatibility (EMC)MPA valve terminal� Interference emitted� Immunity to interference 2)

tested as per EN 61000−6−4 (industry) 1)

tested as per EN 61000−6−2 (industry)

Protection against electric shock(protection against direct and indirect con�tact as per EN 60204−1/IEC 204)

by connection to a PELV power unit (Protected ExtraLow Voltage)

Power supply� Rated voltage� Residual ripple

MPA valve terminal with MP connection:24 V DC ± 25 %4 Vpp

Operating voltage supply for electronics(VEL/SEN) � Rated voltage� Internal current consumption at 24 V (in�

ternal electronics, all valves switched off )

Load voltage supply for valves (VVEN)� Rated voltage� Internal current consumption at 24 V

(internal electronics)

� Diagnostic message undervoltage VOFF,load voltage outside function range

MPA valve terminal with CPX terminal:

24 V DC ± 25 %

typ. 13 ... 20 mA

24 V DC ± 25 %typ. 8 mA (not electrically isolated, electronicmodule type: VMPA1−FB−EMS−8))typ. 25 mA (electrically isolated, electronic moduletype: VMPA1−FB−EMG−8))

17,5 ... 16 V

Current consumption per solenoid coil MPA valve terminal

with CPX terminal with MP connection

� Rated starting current (up to 20 ms) 60 mAat 18 V60 mA

at 24 V80 mA

at 30 V100 mA

� Rated current at current reduction(after 20 ms switch−on time)

25 mA 20 mA

1) The MPA valve terminal is intended for industrial usage.2) The maximum signal cable length for MPA valve terminals with MP connection is 10 m

Table�A/6: Technical specifications for the electric components

A. Technical appendix

A−9Festo P.BE−MPA−EN en 0302NH

Technical specifications for the electric components of theMPA valve terminal with MP connection are enclosed with theproduct.Technical specifications for the electronic module of the MPAvalve terminal with CPX terminal can be found in the manualfor the CPX I/O modules.

A. Technical appendix

A−10 Festo P.BE−MPA−EN en 0302NH

A.2 Festo accessories

Accessories Type designation

General information� Manual override cover (manual override not access�

ible)� Manual override cap (only non−locking function of

manual override accessible)� Hat rail fitting kit� Inscription label holder� Additional fastening bracket for wall fitting

VMPA1−HBVVMPA1−HBTCPX10/14−BG−NRHVMPA1−ST−1−4VMPA−BG−RW

MPA valve terminal with MP connection� Ready−to−use multipin cable

for terminals with 4 valve locationsfor terminals with 8 ... 24 valve locations

� Multipin socket

VMPA−KMS1−8−...VMPA−KMS1−24???

Table�A/7: Accessories for the MPA valve terminal

Supplementary overview of components

B−1Festo P.BE−MPA−EN en 0302NH

Appendix B

B. Supplementary overview of components

B−2 Festo P.BE−MPA−EN en 0302NH

Contents

B. Supplementary overview of components B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.1 Overview of valve plates B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B.2 Separating the MPA valve terminal from the CPX terminal B−7 . . . . . . . . . . . . . .

B. Supplementary overview of components

B−3Festo P.BE−MPA−EN en 0302NH

B.1 Overview of valve plates

Please noteThe numbers on the following switching symbols are thedesignations of the connections, coils and manual over�rides; e.g. designation 14 stands for manual override 14 orcoil 14. They are not logic designations.

Valve plates with 2/2−way valves

82/84

12/14 1

4 2

1214

Ident. code: DFunction:� Two single−solenoid 2/2−way valves,

basic position closed

Table�B/1: Valve plates with 2/2−way valves

Valve plates with 3/2−way valves

82/84

12/14 53

1

4 2

1214

Ident. code: KFunction:� Two single−solenoid 3/2−way valves,

basic position closed

82/84

12/14 53

1

4 2

1214

Ident. code: NFunction:� Two single−solenoid 3/2−way valves,

basic position open

B. Supplementary overview of components

B−4 Festo P.BE−MPA−EN en 0302NH

Valve plates with 3/2−way valves

82/84

12/14 5 31

4 2

1214

Ident. code: HFunction:� On control side 14 a single−solenoid 3/2−way

valve (basic position closed) and on controlside 12 a single−solenoid 3/2−way valve (basicposition open).

82/84

12/14 3

2

4

14

Ident. code: XFunction:Valve plate, 3/2−way, single−solenoid, basic posi�tion closed, external pressure supplyPlease noteNumber of assigned outputs on an MPA valveterminal with MP connection:The number of outputs, which are assigned tothis valve, depends on the valve location (seetable 3/3).

Table�B/2: Valve plates with 3/2−way valves

B. Supplementary overview of components

B−5Festo P.BE−MPA−EN en 0302NH

Valve plates with 5/2−way valves

82/84

12/145 31

4 2

14

Ident. code: MFunction:One single−solenoid 5/2−way valvePlease noteNumber of assigned outputs on an MPA valveterminal with MP connection:The number of outputs, which are assigned tothis valve, depends on the valve location (seetable 3/3).

82/84

12/145 31

4 2

1214

Ident. code: JFunction:� One 5/2−way valve, double−solenoid

Table�B/3: Valve plates with 5/2−way valves

B. Supplementary overview of components

B−6 Festo P.BE−MPA−EN en 0302NH

Valve plates with 5/3−way valves

82/84

12/145 31

4 2

1214

Ident. code: BFunction:� 5/3−way valve, mid position pressurized

82/84

12/14 5 31

4 2

1214

Ident. code: GFunction:� 5/3−way valve in mid−position blocked

82/84

12/145 3

1

4 2

1214

Ident. code: EFunction:� 5/3−way valve, in mid position exhausted

Table�B/4: Valve plates with 5/3−way valves

B. Supplementary overview of components

B−7Festo P.BE−MPA−EN en 0302NH

B.2 Separating the MPA valve terminal from the CPX terminal

The MPA valve terminal is connected to the CPX terminal bymeans of a pneumatic interface (see following diagram).

1 CPX terminal

2 Pneumatic inter�face

3 MPA valve ter�minal

1 2 3

Fig.�B/1: Pneumatic interface

Dismantling Proceed as follows:

1. Loosen the electrical and pneumatic connections and re�move the MPA valve terminal from its fastening surface(see chapter 5, �Dismantling the MPA valve terminal").

2. Loosen the fastening screws between the pneumatic inter�face and the MPA sub−base in the sequence 1 2 3(see Fig. B/2).

3. Then loosen the fastening screws.

B. Supplementary overview of components

B−8 Festo P.BE−MPA−EN en 0302NH

2

1

3

Fig.�B/2: Fastening the MPA valve terminal to the pneumaticinterface

Information on replacing the pneumatic interface can befound in the CPX system manual.

Fitting Proceed as follows:

1. Check the seal between the pneumatic interface and the

MPA valve terminal for damage. If necessary, use a newseal.

2. Push the MPA valve terminal together with the CPX ter�minal. Make sure that the seal and the MPA valve ter�minal are correctly positioned in relationship to the CPX

terminal.

3. Insert the fastening screws in the appropriate holes.Tighten the screws in the sequence specified in Fig. B/2 atfirst slightly and then with 1.3 Nm.

B. Supplementary overview of components

B−9Festo P.BE−MPA−EN en 0302NH

4. Fasten the CPX terminal onto the mounting surface (seeCPX system manual).

5. Carry out the electrical and pneumatic connections of theCPX terminal. Information on this can be found

� in the electrics section of the CPX system manual

� in the pneumatics section in chapter 3 of this manual.

B. Supplementary overview of components

B−10 Festo P.BE−MPA−EN en 0302NH

Index

C−1Festo P.BE−MPA−EN en 0302NH

Appendix C

C. Index

C−2 Festo P.BE−MPA−EN en 0302NH

Contents

C. Index C−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C.1 Index C−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C. Index

C−3Festo P.BE−MPA−EN en 0302NH

C.1 Index

A

Abbreviations, product−specific XIII . . . . . . . . . . . . . . . . . . .

Accessories A−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Address assignment, Outputs 3−24 . . . . . . . . . . . . . . . . . . . . .

Auxiliary pilot airbranched internally 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . supplied externally 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C

Common tubing 3−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Compressed air, requirements 3−4 . . . . . . . . . . . . . . . . . . . . .

Connectionselectrical (MPA valve terminal with CPX terminal) 1−12 . . . electrical (terminal with multipin connection) 1−13 . . . . . . identifier 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pneumatic 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . size 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Current consumption A−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

D

Designated use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Disconnecting the tubing 3−8 . . . . . . . . . . . . . . . . . . . . . . . . . .

Display elementsMPA valve terminal with CPX terminal 1−12 . . . . . . . . . . . . MPA valve terminal with multipin connection 1−13 . . . . . . .

C. Index

C−4 Festo P.BE−MPA−EN en 0302NH

E

EMERGENCY STOP 4−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Exhaust, central 3−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

exhaust plate, fitting/removing 5−14 . . . . . . . . . . . . . . . . . . . .

External pilot air 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . conversion 5−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F

Fastening accessories, Hat rail 2−7 . . . . . . . . . . . . . . . . . . . . .

Fitting onto a wall 2−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fitting tubing 3−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fitting variantsfitting onto a hat rail 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . fitting onto a wall 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Flow rates A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

H

Hat railclamping unit 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fitting 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

I

Impairment of function 4−17 . . . . . . . . . . . . . . . . . . . . . . . . . .

Important user instructions XI . . . . . . . . . . . . . . . . . . . . . . . . .

Internal pilot air 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . conversion 5−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C. Index

C−5Festo P.BE−MPA−EN en 0302NH

L

Large surface−mounted silencercleaning 5−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . fitting/removing 5−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

LEDFault display 4−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switching status display 4−15 , 4−16 . . . . . . . . . . . . . . . . . .

Low−pressure operation 4−18 . . . . . . . . . . . . . . . . . . . . . . . . . .

M

Manual override 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . locking 4−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . non−locking 4−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . types 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Manuals on the MPA valve terminal with CPX terminal IX . . .

Micro valves 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Mounting kit, for hat rail fitting 2−6 . . . . . . . . . . . . . . . . . . . . .

MP connection 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MPA valve terminalAddress assignment of the outputs 3−24 . . . . . . . . . . . . . . components 1−7 , 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . earthing the valve terminal 3−23 . . . . . . . . . . . . . . . . . . . . . loosen the CPX terminal B−7 . . . . . . . . . . . . . . . . . . . . . . . . . overview of variants 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . sizes 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Valve plates X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

N

Non−return valve 3−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Notes on the use of this manual VIII . . . . . . . . . . . . . . . . . . . .

C. Index

C−6 Festo P.BE−MPA−EN en 0302NH

O

Operating elements, pneumatic 1−11 . . . . . . . . . . . . . . . . . . .

Operating states 4−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Overview of variants 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

P

Pictograms XII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Position of the LEDs 4−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power supplyload voltage supply for the valves A−8 . . . . . . . . . . . . . . . . . operating voltage supply for the electronics A−8 . . . . . . . .

Pressure range A−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pressure zones 3−13 , 4−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . common pneumatic line 3−13 . . . . . . . . . . . . . . . . . . . . . . . . conversion 5−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Protection class A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

R

Removing the blanking plate 5−8 . . . . . . . . . . . . . . . . . . . . . . .

Removing the exhaust plate 5−8 . . . . . . . . . . . . . . . . . . . . . . .

Replacing the sub−base 5−14 . . . . . . . . . . . . . . . . . . . . . . . . . .

Replacing valve plates 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C. Index

C−7Festo P.BE−MPA−EN en 0302NH

S

Service VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Size of the pneumatic screw connectors 3−19 . . . . . . . . . . . .

Start−up pressurization 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . .

Supply pressureExternal pilot air 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . external pilot air 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . internal pilot air 3−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Support rail 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

T

Target group VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Text markings XII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Tightening torques A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Tubing variants 5−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

V

Vacuum operation 3−18 , 4−18 . . . . . . . . . . . . . . . . . . . . . . . . .

Valve locations, adding 5−27 . . . . . . . . . . . . . . . . . . . . . . . . . .

Valve locations 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Valve plates X , 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Identification code 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . overview B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Valve switching times A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Vibration A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

C. Index

C−8 Festo P.BE−MPA−EN en 0302NH