39
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm. Project No: Drawn by: 1" 2" CLINICAL EXPANSION G-1.0E 2020026 --- 11.05.2021 BID SET MOUNTAIN LAUREL - CLINICAL EXPANSION --- COVER SHEET 1027 MEMORIAL DRIVE OAKLAND, MARYLAND 21550 MOUNTAIN LAUREL - CLINICAL EXPANSION QR CODE contact info P R O J E C T L O C A T I O N P R O J E C T & C O D E I N F O R M A T I O N Omni Associates - Architects, Inc. 207 Jefferson Street Fairmont, WV 26554 304.367.1417 ARCHITECTURAL SERVICES: MOUNTAIN LAUREL MEDICAL CENTER 1027 MEMORIAL DRIVE OAKLAND, MD. 21550 301.533.3300 OWNER: Civil & Environmental Consultants, Inc. 120 Genesis Boulevard Bridgeport, WV 26330 304.933.3119 SITE DESIGN: Arrow Engineering 1028 Village Drive Morgantown, WV 26505 304.435.8828 STRUCTURAL DESIGN: Barton Associates 400 Mosites Way, Suite 301 Pittsburgh, PA 15205 412.421.0145 MECHANICAL, ELECTRICAL AND PLUMBING DESIGN: GENERAL G-1.0E COVER SHEET G-1.1E CODE COMPLIANCE CIVIL C-0.0E GENERAL CIVIL-SITE NOTES C-1.0E EXISTING SITE CONDITIONS C-2.0E SITE LAYOUT AND GRADING PLAN C-2.1E SITE LAYOUT AND GRADING PLAN C-3.0E EROSION AND SEDIMENT CONTROL PLAN - PRE CONSTRUCTION C-3.1E EROSION AND SEDIMENT CONTROL PLAN - MID CONSTRUCTION C-3.2E EROSION AND SEDIMENT CONTROL PLAN - POST CONSTRUCTION C-4.0E SITE DETAILS C-4.1E SITE DETAILS C-4.2E SITE DETAILS ARCHITECTURAL AD-1.0E FIRST FLOOR DEMOLITION AD-1.1E FIRST FLOOR CEILING DEMOLITION A-1.1E OVERALL PLAN A-1.2E FLOOR PLAN A-1.3E REFLECTED CEILING PLAN A-4.0E PHARMACY ENLARGED PLAN A-4.1E PHARMACY DETAILS A-4.2E NURSE DOCUMENTATION ENLARGED PLANS A-5.1E DETAILS A-6.0E SCHEDULES A-7.1E FINISH PLAN MECHANICAL H-0.0E SYMBOLS & GENERAL NOTES - HVAC H-1.1E FIRST FLOOR PLAN - DUCTWORK H-2.1E FIRST FLOOR PLAN - PIPING H-5.1E DETAILS & SCHEDULES HD-1.0E FIRST FLOOR PLAN - DEMOLITION - HVAC PLUMBING P-0.0E SYMBOLS & GENERAL NOTES - PLUMBING P-1.1E FIRST FLOOR PLAN - DOMESTIC WATER P-2.1E FIRST FLOOR PLAN - SANITARY & VENT P-5.1E DETAILS & SCHEDULES PD-1.0E FIRST FLOOR PLAN - DEMOLITION - PLUMBING ELECTRICAL E-0.0E SYMBOLS & GENERAL NOTES - ELECTRICAL E-1.1E FIRST FLOOR PLAN - LIGHTING E-2.1E FIRST FLOOR PLAN - POWER E-6.1E LIGHTING FIXTURE SCHEDULE E-6.2E PANEL SCHEDULES & DETAILS ED-1.0E FIRST FLOOR PLAN - DEMOLITION - ELECTRICAL Applicable Life Safety Code 2018 Applicable International Building Code (IBC) 2015 Floor Area of Renovation 10,000 SF Floor Area of Addition N/A Floor Area of New Construction N/A Total Floor Area (SQ. FT.) 13,000 SF Does this building have a basement? No Number of Stories above grade 2 B None USE\ OCCUPANCY CLASSIFICATION(S): FIRE SUPRESSION: RENOVATION V(000) / Type V-B TYPE OF WORK: TYPE(S) OF CONSTRUCTION: GARRETT GARRETT OAKLAND, MD 21550 OAKLAND, MD 21550 1027 MEMORIAL DRIVE 1027 MEMORIAL DRIVE BUILDING ADDRESS: OWNER ADDRESS: P R O J E C T T E A M D R A W I N G I N D E X REVISIONS ▼ C L I N I C A L E X P A N S I O N: V O L U M E 1 OF 2

MOUNTAIN LAUREL -CLINICAL EXPANSION

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
MOUNTAIN LAUREL - CLINICAL EXPANSION
ct i
n fo
P R O J E C T L O C A T I O N P R O J E C T & C O D E I N F O R M A T I O N
Omni Associates - Architects, Inc.
ARCHITECTURAL SERVICES:
OWNER:
SITE DESIGN:
Arrow Engineering
STRUCTURAL DESIGN:
Barton Associates
MECHANICAL, ELECTRICAL AND PLUMBING DESIGN:
GENERAL
C-3.0E EROSION AND SEDIMENT CONTROL PLAN - PRE CONSTRUCTION
C-3.1E EROSION AND SEDIMENT CONTROL PLAN - MID CONSTRUCTION
C-3.2E EROSION AND SEDIMENT CONTROL PLAN - POST CONSTRUCTION
C-4.0E SITE DETAILS
C-4.1E SITE DETAILS
C-4.2E SITE DETAILS
A-1.1E OVERALL PLAN
A-1.2E FLOOR PLAN
A-5.1E DETAILS
A-6.0E SCHEDULES
H-5.1E DETAILS & SCHEDULES
PLUMBING
P-1.1E FIRST FLOOR PLAN - DOMESTIC WATER
P-2.1E FIRST FLOOR PLAN - SANITARY & VENT
P-5.1E DETAILS & SCHEDULES
ELECTRICAL
E-6.1E LIGHTING FIXTURE SCHEDULE
E-6.2E PANEL SCHEDULES & DETAILS
Applicable Life Safety Code 2018
Applicable International Building Code (IBC) 2015
Floor Area of Renovation 10,000 SF
Floor Area of Addition N/A
Floor Area of New Construction N/A
Total Floor Area (SQ. FT.) 13,000 SF
Does this building have a basement? No
Number of Stories above grade 2
B None
RENOVATION V(000) / Type V-B
GARRETT GARRETT
BUILDING ADDRESS: OWNER ADDRESS:
P R O J E C T T E A MD R A W I N G I N D E X
REVISIONS
C L I N I C A L E X P A N S I O N: V O L U M E 1 OF 2
10' DIAGONAL
SF METAL STUD FULL-HEIGHT SP METAL STUD PARTIAL-HEIGHT
A. See plans and sections for wall location and type selections. B. Wall types do not include finishes. See room finish schedule and \ or interior elevations for
finish information. C. All rated walls are to be constructed in accordance with noted assembly designs to the
standards of the applicable testing agency. All penetrations through rated walls must be sealed, firestopped, etc. So as to maintain the noted rating.
D. In all cases, the partition with the greater fire rating shall be continuous through wall intersections.
E. Provisions shall be made at all full height nonbearing walls for 1-inch vertical movement of the building structure without transfer of compressive loads to wall. Fill irregularities between top of wall land deck above with fire stopping insulation or firestopping materials as required to meet fire rating of respective walls.
F. Scribe gypsum board of walls and partitions to irregularities of deck above. Seal tightly around any penetrations.
G. Locate gypsum wallboard control joints so there are no continuous runs longer than 25'-0". Coordinate location of joints with architect.
H. Interior walls where sound batts are indicated are acoustic walls, and should be sealed accordingly. Maintain specific STC ratings where noted. Walls enclosing restrooms and private offices shall always be insulated to prevent sound transmittance.
I. Fire rated walls where sound attenuation blankets are indicated shall utilize unfaced resin and mineral-fiber blankets complying with the UL assembly and rating indicated in the contract documents.
J. Where steel stud walls do not extend to structure, provide brace at centerline of door openings.
K. Wall types do not show blocking or bracing within the wall. The contractor is responsible for anticipating where blocking and bracing will be required to meet the design intent. Certain types of blocking (such as untreated wood) may not be allowed by code to be used in all types of construction. Confirm with architect that planned blocking methods are acceptable. Locations for blocking include, but are not limited to: - wall-mounted counters and cabinets - wall-mounted accessories and equipment - door hold-open devices, closures and stops - toilet room partitions and accessories - televisions and mounting brackets - other locations as required by architect and industry standards
A10 1
ROOM TAG
MATERIAL TAG
PLAN NORTH
TRUE NORTH
ELEVATION
SHEET
GENERAL NOTES APPLY TO ALL DRAWINGS A. Do not scale the drawings. B. Verify field conditions prior to commencement of each portion of the work. C. Dimensions for door and window openings are shown nominal. Allow for 1/4-inch
(10) shimming and sealant of exterior frames. D. All dimensions are actual and are to face of studs, face of concrete walls, face of
CMU walls, face of frames, or centerline of columns, unless noted otherwise. E. All interior CMU walls shall be 8" nominal thickness, unless noted otherwise. F. All new interior partition types shall be type SF1a unless noted otherwise. G. General contractor shall coordinate all mechanical chase sizes with mechanical
subcontractor. H. See code compliance sheet for location of walls of fire-resistive construction. All walls
of fire-resistive construction shall extend to underside of floor or roof deck above. I. In all cases, the partition with the greater fire rating shall be continuous through wall
intersections. J. All penetrations through walls, floors and between curtainwall and floor shall be
sealed with firestopping material as required to achieve the respective fire-resistive rating and smoke stoppage.
K. Contractor shall coordinate installation of all imaging equipment with owners' vendor. L. A curtainwall insulation system is required behind all spandrel glass locations. M. General contractor shall coordinate sizes and locations of concrete housekeeping
pads with the mechanical and electrical equipment suppliers. Paint all edges of equipment pads safety yellow.
FLOOR
3 5/8" METAL STUDS @ 16" o.c.
5/8" TYPE X GYPSUM WALLBOARD
4 7/8"
1-HOUR U.L. DESIGN U419
5/8" GYPSUM WALLBOARD
5/8" GYPSUM WALLBOARD
E X
LIFE SAFETY:
ACCESSIBILITY:
ENERGY:
PLUMBING:
MECHANICAL:
ELECTRICAL:
1-HOUR WALL
2-HOUR WALL
EXIT ACCESS TRAVEL DISTANCE
COMMON PATH of TRAVEL
MAINTAIN LOCATION OF ALL FIRE EXTINGUISHERS DURING AND AFTER CONSTRUCITON
2645 SF ?
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
WALL TYPE DESIGNATIONS
OH OPPOSITE HAND
BLDG BUILDING
BOT BOTTOM
BRG BEARING
BTW BETWEEN
CH CHANNEL
Mark From Room To Room Length
E01 BH OFFICE 112 HALLWAY 103 58'
E02 BH OFFICE 112 LOBBY 101 84'
Applicable Life Safety Code 2018
Applicable International Building Code (IBC) 2015
Floor Area of Renovation 10,000 SF
Floor Area of Addition N/A
Floor Area of New Construction N/A
Total Floor Area (SQ. FT.) 13,000 SF
Does this building have a basement? No
Number of Stories above grade 2
B None
RENOVATION V(000) / Type V-B
GARRETT GARRETT
BUILDING ADDRESS: OWNER ADDRESS:
316-091 LAG
-- -
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
PH: (304) 848-7151 CONTACT: TOM ADAMS, P.E.
LOCATION MAP
SOILS MAP
SITE NOTES SEQUENCE OF CONSTRUCTION PROFESSIONAL CERTIFICATION I HEREBY CERTIFY THAT THESE DOCUMENTS (SHEETS C - 0.0E - C - 4.2E) WERE PREPARED OR APPROVED BY ME, AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF MARYLAND, LICENSE NO. 37637, EXPIRATION DATE JULY 19, 2023.
11/1/2021
11/1/2021
-- -
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
316-091 LAG
-- -
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
11/1/2021
316-091 LAG
-- -
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
-- -
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
-- -
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
-- -
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
-- -
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
11/1/2021
-- -
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
11/1/2021
-- -
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
MAGNETIC WARNING TAPE5
R E F .
A. Coordinate all demolition/phasing efforts with the architect, engineer and owner's representatives. Every effort shall be made to minimize disruption of adjacent operations and to ensure public safety and safe working conditions. Excessive noise or vibration shall be pre- approved and coordinated with the owner's representative.
B. Coordinate with the owner any pre-approved disruption and verification of service within the existing building so as to minimize the disruption of service.
C. Provide temporary dust partition protecting access enclosures where noted and as directed by the owner or architect around all areas of work to prevent the spread of construction debris and dust. Temporary partitions to be constructed prior to start of the demolition work. Isolate any demolition/construction work from the general public and maintain means of egress throughout the work.
D. Maintain a secure, weather-tight enclosure at the exterior of the existing building throughout the demolition/construction portion of the work in that area. Building security shall be coordinated with the owner.
E. Verify all existing conditions, dimensions, and elevations and notify the architect-engineer of any discrepancies.
F. Remove in their entirety all existing walls, doors, millwork, plumbing fixtures, etc. As required to execute the demolition/construction work described by the architect-engineer.
G. Remove all demolition materials from the site unless noted otherwise. The owner shall reserve the right to salvage any materials.
H. Provide protection for all existing building materials and equipment from damage due to any demolition or construction-related incident performed under this contract.
I. Repair or replace any walls, floors, or equipment damaged as a result of demolition or construction to match existing finish and/or condition.
J. The contractor shall coordinate with the architect-engineer any materials to be reused and will be responsible for verifying and maintaining the functional and aesthetic integrity of the materials.
K. Verify and maintain the location of existing power, communication and data cables so as not to inadvertently interrupt the continuity of their service.
L. Patch all floor and ceiling penetrations resulting from removal or rerouting of new or existing piping, ductwork, conduit, etc...as required to maintain fire separations. Finish as required for new or existing adjacent surfaces.
M. Cap all disconnected mechanical piping lines within the wall or floor. Patch and finish as required to match new or existing adjacent surfaces.
N. See MEP drawings and notes for further sequencing and scope of work. O. Avoid any disturbance of soils within the zone of influence around existing footings and floor
slabs as directed by soils engineer. P. Remove portions of existing concrete slabs as required for new mechanical, electrical and/or
plumbing work. Coordinate locations and sizes with mechanical, electrical and/or plumbing installers. Patch concrete slabs to match existing. Install vapor barrier prior to pouring slab.
Q. Contractor to remove all unnecessary or abandoned piping, conduit and wiring that is accessible without additional demolition.
R. Areas showing the removal of walls to be properly shored up, if necessary. The contractor is responsible for determining which areas are to be shored and the structural integrity of such shoring.
S. Notes showing demolished conduit, gas lines, waterlines and air lines assume demolition of entire line referenced.
T. Remove and or reinstall ceilings as required by mechanical, electrical or plumbing ceiling work in areas where no architectural demolition work or limited demolition work is being done. Reinstall ceilings and patch to match existing.
U. Any demolition work necessary on floor above or below (demolition required to install new work) shall be scheduled with the owner. Any finishes disturbed or damaged as a result of demolition or installation shall be patched or replaced to match existing finishes.
V. Salvage ceiling tiles for reuse or to turn over to owner.
96 SF
149A
PHASE III: *WORK ONLY TO BE COMPLETED ONCE ADMINISTRATION BUILDING IS OCCUPIED*
0"
D8
D8
D8
D9
D9
D9
D9
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
GENERAL DEMOLITION NOTES
KEY_FIRST FLOOR PLAN
REVISIONS
DEMO DOOR SCHEDULE
Number of
Frame
Type
Frame
Material
Frame
Finish
137C BREAKROOM 142 1 3'-0" 7'-0" F WD F A HM PT REMOVE AND SALVAGE
149A HALLWAY 103 HALLWAY 103 1 3'-0" 7'-0" F WD F A HM PT 45 MIN. (C-LABEL) REMOVE AND REINSTALL
149E HALLWAY 108 HALLWAY 108 1 3'-0" 7'-0" F WD F A HM PT REMOVE AND REINSTALL
149F BH OFFICE 112 BH OFFICE 112 1 3'-0" 7'-0" F WD F A HM PT REMOVE AND REINSTALL
149G BH TREATMENT 113 BH TREATMENT 114 1 3'-0" 7'-0" F WD F A HM PT REMOVE AND REINSTALL
150 HALLWAY 108 1 3'-0" 7'-0" F WD F A HM PT REMOVE AND REINSTALL
151 HALLWAY 108 BH TREATMENT 110 1 3'-0" 7'-0" F WD F A HM PT REMOVE AND REINSTALL
152 HALLWAY 103 PHARMACY 101 1 3'-0" 7'-0" F WD EXISTING A HM P REMOVE AND SALVAGE
157 HALLWAY 103 HALLWAY 103 1 3'-0" 7'-0" F WD F A HM PT REMOVE AND REINSTALL
158A IMAGING 102 HALLWAY 103 2 4'-0" 6'-8" FWG WD F A HM PT REMOVE AND SALVAGE
158B IMAGING 102 HALLWAY 103 2 4'-0" 6'-8" FWG WD F A HM PT REMOVE AND SALVAGE
161 3'-0" 7'-0" H MTL EXISTING TO BE RE-USED
162 3'-0" 7'-0" H MTL EXISTING TO BE RE-USED
KEYED DEMOLITION NOTES
D1.1 Demolish door in it's entirety
D1.2 Demolish window and framing as necessary to expand opening for new door and sidelight, salvage stone for infilling new jambs
D1.3 Existing door to remain
D1.4 Remove and reinstall overhead coiling door
D4 Demolish wall in it's entirety
D4.1 Demolish a portion of existing wall for placement of New Door
D5 Demolish Countertop in it's entirety
D5.1 Remove furniture for reuse
D6 Replace with insulated aluminum panel, to match existing, bottom row only
D7 Salvage appliances for re-use
D8 Remove and salvage UniWeb slat wall system for reuse, typ. in existing pharmacy
D9 Remove all drywall, vertical and horizontal, in preparation for lead lining
D3
D3
D3.1
D3.1
D3.1
D3.1
D3.1
D3
D3.1
D3.2
D3.3
D3.4
D9
D9
A. Coordinate all demolition/phasing efforts with the architect, engineer and owner's representatives. Every effort shall be made to minimize disruption of adjacent operations and to ensure public safety and safe working conditions. Excessive noise or vibration shall be pre- approved and coordinated with the owner's representative.
B. Coordinate with the owner any pre-approved disruption and verification of service within the existing building so as to minimize the disruption of service.
C. Provide temporary dust partition protecting access enclosures where noted and as directed by the owner or architect around all areas of work to prevent the spread of construction debris and dust. Temporary partitions to be constructed prior to start of the demolition work. Isolate any demolition/construction work from the general public and maintain means of egress throughout the work.
D. Maintain a secure, weather-tight enclosure at the exterior of the existing building throughout the demolition/construction portion of the work in that area. Building security shall be coordinated with the owner.
E. Verify all existing conditions, dimensions, and elevations and notify the architect-engineer of any discrepancies.
F. Remove in their entirety all existing walls, doors, millwork, plumbing fixtures, etc. As required to execute the demolition/construction work described by the architect-engineer.
G. Remove all demolition materials from the site unless noted otherwise. The owner shall reserve the right to salvage any materials.
H. Provide protection for all existing building materials and equipment from damage due to any demolition or construction-related incident performed under this contract.
I. Repair or replace any walls, floors, or equipment damaged as a result of demolition or construction to match existing finish and/or condition.
J. The contractor shall coordinate with the architect-engineer any materials to be reused and will be responsible for verifying and maintaining the functional and aesthetic integrity of the materials.
K. Verify and maintain the location of existing power, communication and data cables so as not to inadvertently interrupt the continuity of their service.
L. Patch all floor and ceiling penetrations resulting from removal or rerouting of new or existing piping, ductwork, conduit, etc...as required to maintain fire separations. Finish as required for new or existing adjacent surfaces.
M. Cap all disconnected mechanical piping lines within the wall or floor. Patch and finish as required to match new or existing adjacent surfaces.
N. See MEP drawings and notes for further sequencing and scope of work. O. Avoid any disturbance of soils within the zone of influence around existing footings and floor
slabs as directed by soils engineer. P. Remove portions of existing concrete slabs as required for new mechanical, electrical and/or
plumbing work. Coordinate locations and sizes with mechanical, electrical and/or plumbing installers. Patch concrete slabs to match existing. Install vapor barrier prior to pouring slab.
Q. Contractor to remove all unnecessary or abandoned piping, conduit and wiring that is accessible without additional demolition.
R. Areas showing the removal of walls to be properly shored up, if necessary. The contractor is responsible for determining which areas are to be shored and the structural integrity of such shoring.
S. Notes showing demolished conduit, gas lines, waterlines and air lines assume demolition of entire line referenced.
T. Remove and or reinstall ceilings as required by mechanical, electrical or plumbing ceiling work in areas where no architectural demolition work or limited demolition work is being done. Reinstall ceilings and patch to match existing.
U. Any demolition work necessary on floor above or below (demolition required to install new work) shall be scheduled with the owner. Any finishes disturbed or damaged as a result of demolition or installation shall be patched or replaced to match existing finishes.
V. Salvage ceiling tiles for reuse or to turn over to owner.
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
2 1 5 5 0
SCALE: 1/8" = 1'-0" SHEET: AD-1.1E1 01 FIRST FLOOR CEILING DEMOLITION PLAN
GENERAL DEMOLITION NOTES
D3.1 Demolish existing ceiling, including lights, diffusers, grilles, etc.
D3.2 Remove and salvage existing ceiling tile. Replace grid.
D3.3 Demo enough for new work
D3.4 Partial demo as required to tie-into new waiting area
D9 Remove all drywall, vertical and horizontal, in preparation for lead lining
REF.
UP
TIE INTO EXISTING SIDEWALK
EXISTING CONSTRUCTION
NEW CONSTRUCTION
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
SCALE: 1/8" = 1'-0" SHEET: A-1.1E1 FIRST FLOOR OVERALL
REVISIONS
AREA CAREA D
GENERAL NOTES APPLY TO ALL DRAWINGS A. Do not scale the drawings. B. Verify field conditions prior to commencement of each portion of the work. C. Dimensions for door and window openings are shown nominal. Allow for 1/4-inch
(10) shimming and sealant of exterior frames. D. All dimensions are actual and are to face of studs, face of concrete walls, face of
CMU walls, face of frames, or centerline of columns, unless noted otherwise. E. All interior CMU walls shall be 8" nominal thickness, unless noted otherwise. F. All new interior partition types shall be type SF1a unless noted otherwise. G. General contractor shall coordinate all mechanical chase sizes with mechanical
subcontractor. H. See code compliance sheet for location of walls of fire-resistive construction. All walls
of fire-resistive construction shall extend to underside of floor or roof deck above. I. In all cases, the partition with the greater fire rating shall be continuous through wall
intersections. J. All penetrations through walls, floors and between curtainwall and floor shall be
sealed with firestopping material as required to achieve the respective fire-resistive rating and smoke stoppage.
K. Contractor shall coordinate installation of all imaging equipment with owners' vendor. L. A curtainwall insulation system is required behind all spandrel glass locations. M. General contractor shall coordinate sizes and locations of concrete housekeeping
pads with the mechanical and electrical equipment suppliers. Paint all edges of equipment pads safety yellow.
EXISTING CONSTRUCTION
NEW CONSTRUCTION
8' -0
A.F.F.
GWB-2
8'-0"
CRRH
FI EL
D V
ER IF
TOP / BOTTOM CLOSURE CAP
Application Diagram
CORNER GUARD FEATURES: 1. CLASS A FIRE RATING. 2. "SURFACE MOUNT" INSTALLATION
FOLLOWS COMPLETION OF DRYWALL MOUNTING.
TOP / BOTTOM CAP
YP .
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
SCALE: 1/4" = 1'-0" SHEET: A-1.2E1 FIRST FLOOR_AREA B
SCALE: 1/4" = 1'-0" SHEET: A-1.2E3 FIRST FLOOR_AREA C
SCALE: 1/4" = 1'-0" SHEET: A-1.2E2 FIRST FLOOR_AREA D
REVISIONS
C1 Portion of temporary wall to remain, ensure finish quality
C3 Refer to Healthcare Consultant for specific layout of equipment.
C4 Align new wall with existing
C5 Coordinate with plumbing
C8 Provide blocking in wall as necessary for imaging equipment
C9 Provide blocking as necessary. Drywall work will be required.
C10 Provide 1/16" lead lined drywall
C11 5/8" Drywall with 1/16" lead lining, all walls and ceiling(s).
C12 All barrier penetrations, such as openings for doors, windows, conduits, pipes, air ducts, service boxes, etc., require the installation of either lead baffles or lead backing to restore the protective effectiveness of the barrier.
C13 Door, door frames and door bucks, unless otherwise specified, shall have the same effective shielding as the barrier into which they are inserted. The doors shall be hung such that the bottom edge is as close as possible to the finished floor with the clearance not to exceed 1/2 inch. Otherwise, a shielded barrier threshold shall be installed.
C14 Joints in lead sheets shall be constructed so that their surfaces are in contact and overlap not less than 1/2 inch.
SCALE: 1/2" = 1'-0" SHEET: A-1.2E4 IMAGING TECH COUNTER AND CHANGING
SCALE: 6" = 1'-0" SHEET: A-1.2E6 PARTITION END CORNER GUARD DETAIL
ZC
S
OS
S
OS
ZC
ZC
SD
A. All sprinklers, speakers, recessed lights, smoke or thermal detectors shall be centered in ceiling tile unless noted otherwise.
B. Ceiling subcontractor shall provide blocking and tees surrounding mechanical grilles and diffusers, and electrical fixtures in ceiling.
C. Ceiling notes apply to all reflected ceiling plan sheets. D. Ceiling heights are as noted on the reflected ceiling plans or in the room finish
schedule unless noted otherwise. E. In suspended acoustical ceilings, provide exposed tees around electrical fixtures,
mechanical grilles, diffusers, etc. F. In areas with exposed structure ceilings, coordinate exact locations of mechanical
grilles, diffusers, ductwork, and electrical fixtures with each respective contractor. G. Coordinate locations of access panels in gypsum board ceiling or bulkhead with
architect.
RECESSED DOWN LIGHT
HVAC SUPPLY DIFFUSER
HVAC RETURN REGISTER
HVAC EXHAUST FAN
HVAC SLOT DIFFUSER
RECESSED DOWN LIGHT CONNECTED TO EMERGENCY POWER
X-RAY IN USE LED LIGHT (WALL MOUNT)
ACT-1
SALVAGED EXISTING TILES
ACT-2
BULKHEAD @ 7'-10" A.F.F.
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
CEILING NOTES
SCALE: 1/8" = 1'-0" SHEET: A-1.3E1 01 FIRST FLOOR CEILING PLAN
REVISIONS
C6.1 New ceiling as required, tie into existing waiting room
REF.
0"
1' -6
3' -1
SLAT WALL
EXISTING WALL
3' -1
8
A-4.1E
UNIWEB SLAT WALL SYSTEM. MATCH EXISTING SPACING, COLOR, THICKNESS, ETC. CONTRACTOR SHOULD ALSO PROVIDE ALL NECESSARY ACCESSORIES INCLUDING BUT NOT LIMITED TO, END CLOSERS, CAPS, SILL, ETC. CONTRACTOR TO ASSUME 50% OF WHAT IS SHOWN IN DRAWINGS WILL BE NEW PRODUCT. (50% WILL BE SALVAGED - VERIFY AMOUNT EXISTING IN FIELD)
30 "
20 "
20 "
.
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
2 1 5 5 0
SCALE: 1/2" = 1'-0" SHEET: A-4.0E5 PHARMACY 101_WEST ELEV SCALE: 1/2" = 1'-0" SHEET: A-4.0E1 01 FIRST FLOOR_PHARMACY
REVISIONS
SCALE: 1/2" = 1'-0" SHEET: A-4.0E2 PHARMACY 101_NORTH ELEV
SCALE: 1/2" = 1'-0" SHEET: A-4.0E3 PHARMACY 101_SOUTH ELEV SCALE: 1/2" = 1'-0" SHEET: A-4.0E4 PHARMACY 101_EAST ELEV
KEYED CONSTRUCTION NOTES
C1 Portion of temporary wall to remain, ensure finish quality
0"
T. O
. C O
U N
TE R
SEE INTERIOR DESIGN DRAWINGS FOR CASEWORK AND COUNTER FINISHES, TYP.
NEW 2X SILL
PATCH AND REPAIR GYP BOARD AROUND NEW OPENING AS REQUIRED
LEDGER BOARD, PAINTED TO MATCH WALL
GLAZING FRAME BEYOND COILING DOOR
TRACK/GUIDE BEYOND
PATCH AND REPAIR GYP BOARD AROUND NEW OPENING AS REQUIRED
NEW KING STUD
CONTINUOUS 'J' BEAD, TYP.
PATCH AND REPAIR GYP BOARD AROUND NEW OPENING AS REQUIRED
GYP. WB RETURN, TYP.
REUSED COILING COUNTER DOOR
0"
CEILINGS AS SCHEDULED
UNIWEB SLAT WALL SYSTEM. MATCH EXISTING SPACING, COLOR, THICKNESS, ETC. CONTRACTOR SHOULD ALSO
PROVIDE ALL NECESSARY ACCESSORIES INCLUDING BUT NOT LIMITED TO, END CLOSERS, CAPS, SILL, ETC.
CONTRACTOR TO ASSUME 50% OF WHAT IS SHOWN IN DRAWINGS WILL BE NEW PRODUCT.
(50% WILL BE SALVAGED)
EXISTING WALL
STUD EXTENDED TO DECK/STRUCTURE ABOVE
EXISTING GLAZING PANELS TO REMAIN
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
REVISIONS
SCALE: SHEET: A-4.1E1 PHARMACY 1_3D SCALE: SHEET: A-4.1E2 PHARMACY 2_3D
SCALE: 1/2" = 1'-0" SHEET: A-4.1E3 PHARMACY WAITING
SCALE: 3/4" = 1'-0" SHEET: A-4.1E4 PHARMACY ADA COUNTER WINDOW
SCALE: 1 1/2" = 1'-0" SHEET: A-4.1E5 OH COUNTER DOOR SILL DETAIL
SCALE: 1 1/2" = 1'-0" SHEET: A-4.1E6 OH COUNTER DOOR JAMB DETAIL
SCALE: 1 1/2" = 1'-0" SHEET: A-4.1E7 OH COUNTER DOOR HEAD DETAIL NOTE: AXONOMETRIC VIEWS SHOWN FOR INFORMATIONAL PURPOSES ONLY
SCALE: 3/4" = 1'-0" SHEET: A-4.1E8 WALL SECTION - PHARMACY
A-4 .2
3'-0" 3'-10" 2'-1"
HANG RAILS
(4 )
HANG RAILS (TYP.)
SE E
EL EV
AT IO
N S
VA R
IE S
SE E
EL EV
AT IO
N S
VA R
IE S
1'-6" 3'-4 1/2" 1'-6" 3'-0"
FILE FILE
2' -0
" T YP
3'-0" 1'-6" 3'-0" 3'-0"
2'-0" 1'-6" 3'-11" 1'-6" 3'-0"
FILE FILE FILE
127
WORKSPACE
WORKSPACE
WORKSPACE
WORKSPACE
WORKSPACE
WORKSPACE
A. Field verify all dimensions prior to installation. B. Reference respective drawings and specifications for any fixtures, appliances, or
accessories associated with casework. G.C. to verify and provide all equipment specifications to fabricator for coordination.
C. G.C. is to provide sink templates to fabricator. D. Provide in-wall blocking required for installation. E. Base cabinets to be 24" deep; wall cabinets are to be 12" clear inside unless noted
otherwise. F. Architectural plastic laminate casework shall conform to the current AWI
(Architectural Woodwork Institute) standards, and shall be fabricated per AWI section 400, Custom Grade, flush overlay design, U.N.O.
G. Residential wood casework shall comply with current KCMA (Kitchen Cabinet Manufacturers Association) standards.
H. Closure panels and nailers to be provided by casework manufacturer. I. Backsplashes to be 4" high square sash with returns along all side walls to counter
depth, U.N.O. J. Knee space panels, sidewalls, and under counter bracing to be of material and finish
to match base cabinets, U.N.O. K. Interiors of cabinets to be white melamine, U.N.O. L. All exposed cabinet body edges shall be covered with matching 1mm PVC edge
banding. Doors and drawer fronts are to have 3mm PVC edge banding. M. Cabinet drawer boxes are to be white melamine, U.N.O. N. Provide electrical access panels at back walls of knee spaces. O. Toe kicks to be covered with rubber base, U.N.O. P. Provide (2) flip-top round plastic grommets at each work area (work areas are
indicated by countertop spanning an open area). Coordinate exact location with architect and owner before installing.
Q. Casework noted as "File" is intended to be casework which accommodates standard business files. Provide all necessary tracks and hardware for casework installation.
R. Countertops to be H.P. laminate on 3/4" resin particle board, U.N.O. S. Provide 3/4" x 3" web frame at top of base cabinets. T. Intermediate partitions located midway between sinks are H.P. laminate on 3/4" resin
particle board, U.N.O. U. Insulate all exposed pipes per A.D.A. guidelines.
TYPICAL HARDWARE FOR ARCHITECTURAL PLASTIC LAMINATE CABINETS: • Shelf rests shall be Blum pins. • Hinges shall be European concealed style - Blum 120deg. • Drawer pulls to match existing • Drawer slides shall be 'Accuride 3282-20' (or approved equal) at typical drawer box. • File drawer slides shall be 'Sterling nj31032' full extension (or approved equal).
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0" SHEET: A-4.2E2 NURSE DOCUMENTATION A_ELEV 02
SCALE: 1" = 1'-0" SHEET: A-4.2E11 TYP. (4) DRAWER BASE & WALL CABINETS
SCALE: 1/2" = 1'-0" SHEET: A-4.2E1 NURSE DOCUMENTATION A_ELEV 01 SCALE: 1/2" = 1'-0" SHEET: A-4.2E3 NURSE DOCUMENTATION A_ELEV 03
SCALE: SHEET: A-4.2E7 NURSE DOCUMENATION A SCALE: SHEET: A-4.2E8 NURSE DOCUMENATION A_2
SCALE: 1/2" = 1'-0" SHEET: A-4.2E4 NURSE DOCUMENTATION B_ELEV 01 SCALE: 1/2" = 1'-0" SHEET: A-4.2E5 NURSE DOCUMENTATION B_ELEV 02
SCALE: 1/2" = 1'-0" SHEET: A-4.2E6 NURSE DOCUMENTATION B_ELEV 03
SCALE: SHEET: A-4.2E10 NURSE DOCUMENATION B SCALE: SHEET: A-4.2E9 NURSE DOCUMENATION B_2
REVISIONS
"
NEW 1X CEDAR TRIM, MATCH TO EXISTING (CONTRACTOR MAY SALVAGE & REUSE IF NOT DAMAGED
EXISTING 1X TRIM
SPANDREL PANELS
EXISTING GLAZING TO REMAIN
TOOTH-IN SALVAGED STONE. INTENT IS THAT ALL EXPOSED SURFACES ARE NATURAL, UNCUT SURFACES
SHIM AS REQUIRED
CONTINUOUS SEALANT (INT. & EXT.) W/ BACKER ROD; SHIM AS REQUIRED (TYP.)
GYP. WB RETURN, TYP.
CONTINUOUS CORNER BEAD, TYP.
CONTINUOUS BEAD OF SEALANT ALONG PERIMETER
PATCH AND REPAIR GYP BOARD AROUND NEW OPENING AS REQUIRED
CEILING AS SCHEDULED
EXISTING HEADER FLASHING W/ DRIP EDGE
WRAP SELF ADHESIVE MEMBRANE INTO THE OPEING, NEW MATERIAL IS REQUIRED.
DOOR AS SCHEDULED
01 FIRST FLOOR
EXISTING BUILDING FLOOR
EXPANSION JOINT, TYP.
4" SLAB, CAST IN PLACE, SLOPE FROM BUILDING, ON COMPACTED GRAVEL BASE
STOREFRONT DOOR, AS SCHEDULED
FLOOR FINISH AS SCHEDULED
SEE INTERIOR DESIGN DRAWINGS FOR CASEWORK AND COUNTER FINISHES, TYP.
37" 27" 24" 36" 15"
D.W. N.I.C
SHIM AS REQUIRED
CONTINUOUS SEALANT (INT. & EXT.) W/ BACKER ROD; SHIM AS REQUIRED (TYP.)
GYP. WB RETURN, TYP.
CONTINUOUS CORNER BEAD, TYP.
STONE VENEER BELOW
EX IS
TI N
PATCH AND REPAIR GYP BOARD AROUND NEW OPENING AS REQUIRED
NEW KING STUD
NEW JACK/TRIM STUD
ALUMINUM SPANDREL, ALUMINUM ON BOTH SIDES OF PANEL (POLY-ISO CORE)
CONTINUOUS SEALANT (INT. & EXT.) W/ BACKER ROD; SHIM AS REQUIRED (TYP.)
GYP. WB RETURN, TYP. CONTINUOUS BEAD OF SEALANT
ALONG PERIMETER
EX IS
TI N
SHIM AS REQUIRED
CONTINUOUS CORNER BEAD, TYP. PATCH AND REPAIR GYP BOARD AROUND NEW OPENING AS REQUIRED
NEW KING STUD
NEW JACK/TRIM STUD
MATCH EXISTING
TOOTH-IN SALVAGED STONE. INTENT IS THAT ALL EXPOSED SURFACES ARE NATURAL, UNCUT SURFACES
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
SCALE: 1/4" = 1'-0" SHEET: A-5.1E1 EXTERIOR ELEVATION - SOUTH
SCALE: 1 1/2" = 1'-0" SHEET: A-5.1E2 STOREFRONT DOOR HEAD, EXTERIOR
SCALE: 1 1/2" = 1'-0" SHEET: A-5.1E3 STOREFRONT DOOR SILL, EXTERIOR
SCALE: 1/2" = 1'-0" SHEET: A-5.1E6 BREAKROOM
REVISIONS
SCALE: 1 1/2" = 1'-0" SHEET: A-5.1E4 STOREFRONT DOOR JAMB @ SIDING, EXTERIOR
SCALE: 1 1/2" = 1'-0" SHEET: A-5.1E5 STOREFRONT DOOR JAMB @ STONE, EXTERIOR
DOOR SCHEDULES MAY USE THE FOLLOWING ABBREVIATIONS:
DOOR OR FRAME MATERIALS:
PANEL TYPES: F FLUSH
SA STOREFRONT NARROW STILE SB STOREFRONT MEDIUM STILE SC STOREFRONT WIDE STILE
MODIFIERS: WG WOOD GRAIN
2" 2"
2" A. Dimensions of all openings to be field verified prior to fabrication. B. Provide 1/4" shim and sealant at all exterior openings. C. Glass types for non-rated hollow metal doors and frames to be clear
tempered glass. D. Glass type for rated hollow metal doors and frames to be wired glass. E. Frame manufacturer and security supplier shall coordinate locations of all
concealed conduit and j-boxes required for the security system prior to manufacturing of hollow metal frames.
F. For roll-up doors and counter doors, width and height dimensions shown in door and frame schedule represent clear opening size. Contractor to coordinate exact size of door with roll-up counter door manufacturer.
OPENINGS USE THE FOLLOWING PREFIXES:
S STOREFRONT C CURTAIN WALL
FOR ASSEMBLY DETAILS
SEE WALL TYPES
2" HOLLOW METAL FRAME
FRAME JAMB DEPTH
FOR ASSEMBLY DETAILS
SEE WALL TYPES
SEE DOOR SCHEDULE
FRAME JAMB DEPTH
2"
2"
DOUBLE STUD JAMB
S EE
D O
O R
S C
H ED
U LE
FR A
M E
JA M
B D
EP TH
DOUBLE STUD JAMB 2"
1" 34
T
ALUMINUM U-CHANNEL FRAME
ALUMINUM U-CHANNEL FRAME
SEE SCHEDULE
SE E
SC H
ED U
1/4" TEMPERED GLAZING
AP
T
X
Copyright. © All rights reserved. Reproduction in whole or in part is prohibited. This drawing is an instrument of service, is the property of the Architect and may not be used in any way without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
OPENING
RATING
HARDWARE
SETS COMMENTSFROM ROOM TO ROOM WIDTH HEIGHT TYPE MATERIAL FINISH TYPE MATERIAL FINISH JAMB HEAD
100 HALLWAY 103 STAIR/CORRIDOR 100 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 45 MIN. (C-LABEL)
EXISTING DOOR TO BE RE-USED
102A HALLWAY 103 IMAGING 102 3'-0" 7'-0" F WD STAINED TO MATCH EXISTING A HM P J2 H2 NEW
103 HALLWAY 103 HALLWAY 160 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING DOOR TO BE RE-USED
104 STORAGE 104 HALLWAY 103 3'-0" 7'-0" F WD STAINED TO MATCH EXISTING A HM P J2 H2 NEW
105A WAITING 107 PHARMACY WAITING 105 3'-0" 7'-0" N WD STAINED TO MATCH EXISTING A HM P J2 H2 NEW
105B PHARMACY WAITING 105 3'-0" 6'-9 1/2" SC AL SC A AL J2 H2 NEW
106 HALLWAY 103 FUTURE OFFICE 106 3'-0" 7'-0" F WD STAINED TO MATCH EXISTING A HM P J2 H2 NEW
109 HALLWAY 108 BH TREATMENT 109 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING DOOR TO BE RE-USED
110 HALLWAY 108 BH TREATMENT 110 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING DOOR TO BE RE-USED
111 HALLWAY 108 BH TREATMENT 111 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING DOOR TO BE RE-USED
112 HALLWAY 108 BH OFFICE 112 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING DOOR TO BE RE-USED
113 HALLWAY 108 BH TREATMENT 113 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING DOOR TO BE RE-USED
114 HALLWAY 108 BH TREATMENT 114 3'-0" 7'-0" F WD STAINED TO MATCH EXISTING A HM P J2 H2 NEW
127 HALLWAY 159 NURSE DOCUMENTATION B 152 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING TO REMAIN
139 HALLWAY 108B BREAKROOM 142 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING TO REMAIN
149B HALLWAY 108B HALLWAY 108 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING TO REMAIN
149C HALLWAY 108 HALLWAY 103 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING TO REMAIN
152 HALLWAY 103 PHARMACY 101 3'-0" 7'-0" F WD STAINED TO MATCH EXISTING A HM P J2 H2 NEW
152A 3'-0" 4'-6" H EXISTING EXISTING SEE PG A-4.1E SEE PG A-4.1E EXISTING COILING OVERHEAD SECURITY DOOR & HARDWARE TO BE SALVAGED AND RE-USED
152B 3'-0" 3'-6" H EXISITNG EXISTING SEE PG A-4.1E SEE PG A-4.1E EXISTING COILING OVERHEAD SECURITY DOOR & HARDWARE TO BE SALVAGED AND RE-USED
153 HALLWAY 158 NURSE DOCUMENTATION A 153 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING TO REMAIN
156A HALLWAY 103 PHARMACY WAITING 105 3'-0" 7'-0" F WD EXISTING A HM P J2 H2 EXISTING TO REMAIN
DOOR TYPE NOMENCLATURE SCALE: 3/8" = 1'-0"
DOOR FRAME TYPES
DOOR & FRAME NOTES
OPENING TYPE NOMENCLATURE
REVISIONS
SCALE: 3" = 1'-0" SHEET: A-6.0EH1 DOOR HEAD CASED OPENING SCALE: 3" = 1'-0" SHEET: A-6.0EH2 DOOR HEAD MTL. STUD GWB WALL
SCALE: 3" = 1'-0" SHEET: A-6.0EJ1 DOOR JAMB CASED OPENING SCALE: 3" = 1'-0" SHEET: A-6.0EJ2 DOOR JAM MTL. STUD GWB WALL
SCALE: 3/8" = 1'-0"
IMAGING ACCESSORIES
ACCESSORIES SCHEDULE
Mark Description
Room Legend
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
E M
O R
IA L
D R
IV E
O A
K LA
N D
FINISH DESCRIPTION LEGEND
LABEL MATERIAL MANUFACTURER PRODUCT LINE STYLE COLOR SIZE REMARKS
ACT-1 ACOUSTICAL CEILING TILE CERTAINTEED PERFORMA SYMPHONY M WHITE 2'x2' REVEAL FIELD PANEL 1222BB-IOF-1
CPT-1 CARPET TILE TARKETT MODERN REFINEMENT KNOT STITCH- G0057 WARM CASHMERE- 60807 18"x36" VERTICAL ASHLAR INSTALLATION
CPT-2 CARPET TILE TARKETT MODERN REFINEMENT THREAD CRAFT- 11569 WARM CASHMERE- 60807 18"x36" VERTICAL ASHLAR INSTALLATION
GWB-1 GYPSUM WALL BOARD
LAM-1 PREMIUM LAMINATE WILSONART TBD BASE CABINETS AND OVERHEAD CABINETS
LVT-1 LUXURY VINYL TILE TARKETT EVENT TBD TBD 6"X36"
PNT-1 PAINT SHERWIN WILLIAMS INTERIOR PAINT TBD TBD SATIN FINISH
PNT-2 PAINT SHERWIN WILLIAMS INTERIOR PAINT TBD TBD SATIN FINISH
PNT-3 PAINT SHERWIN WILLIAMS INTERIOR PAINT TBD TBD HIGH GLOSS FINISH
RB-1 RUBBER BASE TARKETT MILLWORK COLLECTION REVEAL TBD 6"
RB-2 RUBBER BASE TARKETT PERCEPTIONS COLLECTION REVEAL TBD 4.25"
RT-1 RUBBER TILE TARKETT STAIRWELL MANAGEMENT RUBBER STRINGERS &
RISERS
TBD
SS-1 SOLID SURFACE FORMICA TBD COUNTERTOPS AND WORKSURFACES
SV-1 SHEET VINYL TARKETT iQ- OPTIMA OPTIMA TBD ROLL SIZE: 6.5'x82' HEAT WELD SEAMS
SV-2 SHEET VINYL TARKETT iQ- OPTIMA OPTIMA TBD ROLL SIZE:6.5'x82' HEAT WELD SEAMS
VCT-1 VINYL COMPOSITION TILE TARKETT TARKETT VCT VINYL COMPOSITION TILE TBD
ROOM FINISH SCHEDULE
Number Name Area
Casework
101 PHARMACY 493 SF PNT LVT-1 WB-2 ACT-1 LAM-1 SS-1
102 IMAGING 252 SF PNT SV-2 WB-2 GWB-1
102A IMAGING TECH 36 SF PNT SV-2 WB-2 GWB-1 LAM-1 SS-1
102B IMAGING CHANGING 32 SF PNT SV-2 WB-2 GWB-1
103 HALLWAY 143 SF PNT SV-1 WB-2 ACT-1
104 STORAGE 17 SF PNT VCT-1 WB-2 ACT-2
105 PHARMACY WAITING 160 SF PNT LVT-1 WB-1 ACT-1 LAM-1 SS-1
106 FUTURE OFFICE 109 SF PNT CPT-2 WB-2 ACT-1
107 WAITING 1017 SF PNT CPT-1 WB-1 EXISTING
108 HALLWAY 157 SF PNT SV-1 WB-2 ACT-1
109 BH TREATMENT 90 SF PNT SV-2 WB-2 ACT-1
110 BH TREATMENT 88 SF PNT SV-2 WB-2 ACT-1
111 BH TREATMENT 121 SF PNT SV-2 WB-2 ACT-1
112 BH OFFICE 224 SF PNT CPT-2 WB-2 ACT-1
113 BH TREATMENT 97 SF PNT SV-2 WB-2 ACT-1
114 BH TREATMENT 97 SF PNT SV-2 WB-2 ACT-1
115 AIR LOCK 88 SF PNT LVT-1 WB-1 EXISTING
116 EXAM RM. 124 SF PNT SV-1 WB-2 EXISTING
117 EXAM RM. 122 SF PNT SV-1 WB-2 EXISTING
118 EXAM RM. 123 SF PNT SV-1 WB-2 EXISTING
119 EXAM RM. 124 SF PNT SV-1 WB-2 EXISTING
120 WORK RM. 2 122 SF PNT SV-2 WB-2 EXISTING
121 JANITOR 85 SF EXISTING EXISTING EXISTING EXISTING
122 VESTIBULE 62 SF PNT SV-1 WB-2 EXISTING
123 EXAM RM. 127 SF PNT SV-1 WB-2 EXISTING
124 EXAM RM. 116 SF PNT SV-1 WB-2 EXISTING
125 EXAM RM. 112 SF PNT SV-1 WB-2 EXISTING
126 UTILITY SUPPLY 42 SF EXISTING EXISTING EXISTING EXISTING
127 UTILITY 121 SF EXISTING EXISTING EXISTING EXISTING
128 EXAM RM. 118 SF PNT SV-1 WB-2 EXISTING
129 EXAM RM. 117 SF PNT SV-1 WB-2 EXISTING
130 EXAM RM. 118 SF PNT SV-1 WB-2 EXISTING
131 EXAM RM. 118 SF PNT SV-1 WB-2 EXISTING
132 NURSES 106 SF PNT CPT-2 WB-2 EXISTING
133 NCC 118 SF PNT CPT-2 WB-2 EXISTING
134 CHW 91 SF PNT CPT-2 WB-2 EXISTING
135 PATIENT EDUCATION 119 SF PNT CPT-2 WB-2 EXISTING
136 OFFICE 119 SF PNT CPT-2 WB-2 EXISTING
137 IT 122 SF EXISTING EXISTING EXISTING EXISTING
138 RR 41 SF PNT SV-2 WB-2 EXISTING
139 PUBLIC RR 125 SF PNT SV-2 WB-2 EXISTING
140 RR 41 SF PNT SV-2 WB-2 EXISTING
141 PUBLIC RR 125 SF PNT SV-2 WB-2 EXISTING
142 BREAKROOM 160 SF PNT LVT-1 WB-2 ACT-1 LAM-1 SS-1
143 OFFICE 71 SF PNT CPT-2 WB-2 EXISTING
144 CHECK-IN 338 SF PNT CPT-1 WB-1 EXISTING
145 OFFICE 84 SF PNT CPT-2 WB-2 EXISTING
146 TRIAGE 81 SF PNT SV-2 WB-2 EXISTING
147 LAB 213 SF PNT SV-2 WB-2 EXISTING
148 RR 48 SF PNT SV-2 WB-2 EXISTING
149 STORAGE 37 SF EXISTING EXISTING EXISTING EXISTING
150 RR 47 SF PNT SV-2 WB-2 EXISTING
151 NURSE DOCUMENTATION 287 SF PNT SV-2 WB-2 EXISTING
152 NURSE DOCUMENTATION B 125 SF PNT SV-2 WB-2 ACT-1 LAM-1 SS-1
153 NURSE DOCUMENTATION A 96 SF PNT SV-2 WB-2 ACT-1 LAM-1 SS-1
154 SHOWER 100 SF PNT EXISTING EXISTING EXISTING
155 EXAM RM. 134 SF PNT SV-1 WB-2 EXISTING
156 RR 31 SF PNT SV-2 WB-2 EXISTING
157 NURSE DOCUMENTATION 57 SF PNT SV-2 WB-2 EXISTING
158 HALLWAY 323 SF PNT SV-1 WB-2 EXISTING
159 HALLWAY 940 SF PNT SV-1 WB-2 EXISTING
160 HALLWAY 126 SF PNT SV-1 WB-2 EXISTING
SCALE: 1/8" = 1'-0" SHEET: A-7.1E1 FIRST FLOOR FINISH PLAN
REVISIONS
HWS
HWR
CHWS
CHWR
ST-?
C-?
CP
CD
MU
RL
RS
RG
FOS
FOR
FOV
FOG
CS
CR
HVAC LINETYPE KEY (APPLIES TO ALL HVAC SERVICES OR SYMBOLS)
HVAC ABBREVIATIONS
SYMBOL DESCRIPTION
HEAVY LINEWEIGHT INDICATES PIPING AND EQUIPMENT TO BE FURNISHED UNDER THIS PROJECT
THIN LINEWEIGHT INDICATES PIPING AND EQUIPMENT THAT ARE EXISTING TO REMAIN, UNLESS NOTED OTHERWISE
DASHED LINEWEIGHT INDICATES PIPING AND EQUIPMENT THAT ARE EXISTING TO BE REMOVED, UNLESS NOTED OTHERWISE
AB CL ABOVE CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
APD AIR PRESSURE DROP
ATC AUTOMATIC TEMPERATURE CONTROL
DB DRY BULB
HP HORSEPOWER
HZ HERTZ
KW KILOWATT
RPM REVOLUTIONS PER MINUTE
WPD WATER PRESSURE DROP
1. COMPLY WITH LOCAL, STATE, AND NATIONAL CODES AND REGULATIONS.
2. PLAN DOCUMENTS ARE SCHEMATIC TO CONVEY THE DESIGN INTENT. DO NOT SCALE DRAWINGS FOR EXACT PLACEMENT OF EQUIPMENT AND DISTRIBUTION SYSTEMS.
3. COORDINATION BETWEEN DISCIPLINES IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR AND/OR CONSTRUCTION MANAGER PRIOR TO INSTALLATION.
4. THE DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY. IN A CASE OF A CONFLICT BETWEEN THE DRAWINGS AND SPECIFICATIONS, REQUEST A DOCUMENTED INTERPRETATION FROM THE ENGINEER/ARCHITECT.
5. INSTALL EQUIPMENT PER MANUFACTURER'S INSTALLATION AND INSURANCE UNDERWRITER REQUIREMENTS.
6. THE LINE-TYPE AND SYMBOLS LEGENDS SHOW ITEMS TYPICALLY INCLUDED WITH THE SPECIFIED SYSTEMS. NOT ALL SYMBOLS AND/OR LINETYPES ARE UTILIZED.
7. INCLUDE DETAILS IN THE SCOPE OF WORK FOR EVERY SITUATION TO WHICH THAT DETAIL APPLIES EXCEPT WHERE A SPECIFIC DETAIL REFERENCE IS DESIGNATED TO INDICATE OTHERWISE.
8. EXISTING HVAC EQUIPMENT, PIPING AND DUCTWORK SHALL REMAIN UNLESS NOTED OTHERWISE.
9. SCHEDULE SYSTEM MODIFICATIONS TO MINIMIZE DISRUPTIONS TO EXISTING BUILDING SERVICES. COORDINATE SHUTDOWN REQUESTS PER SPECIFICATION AND OWNER REQUIREMENTS.
10. LOCATE DUCTWORK AND PIPING AS HIGH AS POSSIBLE, UNLESS NOTED OTHERWISE.
11. SEAL PENETRATIONS THROUGH FIRE AND/OR SMOKE BARRIERS WITH AN APPROVED SYSTEM TO MAINTAIN THE INTEGRITY OF THE BARRIER.
12. INSTALL FIRE DAMPERS, FIRE/SMOKE DAMPERS AND SMOKE DAMPERS TO MAINTAIN THE INTEGRITY OF THE STRUCTURE PER NFPA REQUIREMENTS.
13. MAINTAIN DISTANCE, CONFIGURATION AND NUMBER OF ELBOWS FROM UNIT OR VAV BOXES TO FIRST DIFFUSER AS SHOWN ON PLANS FOR SOUND ATTENUATION. CONTRACTOR SHALL COORDINATE DEVIATIONS WITH THE ENGINEER OF RECORD.
14. PROVIDE TRANSITIONS REQUIRED FROM DUCT SIZE INDICATED ON PLANS TO HVAC EQUIPMENT CONNECTION SIZE. MAINTAIN 30 DEGREE MAXIMUM ANGLE FOR TRANSITION. CONTRACTOR SHALL COORDINATE DEVIATIONS WITH THE ENGINEER OF RECORD.
15. COORDINATE EXACT GRILLE/REGISTER/DIFFUSER LOCATIONS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN BEFORE ROUGH-IN.
16. COORDINATE ROOF PENETRATIONS WITH THE ROOFING CONTRACTOR OR ROOF WARRANTY UNDERWRITER TO MAINTAIN ROOFING SYSTEM INTEGRITY.
17. MINIMUM MECHANICAL PIPING SIZE SHALL BE 3/4" UNLESS NOTED OTHERWISE.
18. INSTALL FLEXIBLE CONNECTIONS BETWEEN ALL MOTORIZED EQUIPMENT AND THE CONNECTED SYSTEM. REFER TO SPECIFICATIONS FOR CONNECTION TYPE AND APPLICATION.
SYMBOLS & IDENTIFICATION OF GRILLES
NO. OF SLOTS (LD ONLY) [DEGREE OF DEFLECTION (SR ONLY)]
DESCRIPTION
SR SUPPLY REGISTER RR RETURN REGISTER ER EXHAUST REGISTER RLR RELIEF REGISTER
RG RETURN GRILLE EG EXHAUST GRILLE LFD LAMINAR FLOW DIFFUSER
CD CEILING DIFFUSER LD LINEAR DIFFUSER TG TRANSFER GRILLE
STYLE
ROUND DIFFUSER W/ ADJUSTABLE PATTERN
SIDEWALL REGISTER OR GRILLE
CEILING REGISTER OR GRILLE
LINEAR DIFFUSER FOR RETURN AIR
STYLE 5.1
STYLE 5.2
STYLE 5.3
CHECK VALVE
BALANCING VALVE
BALL VALVE
TWO WAY CONTROL VALVE
THREE WAY CONTROL VALVE
SHUT-OFF VALVE (SEE SPEC)
FLOAT & THERMOSTATIC STEAM TRAP
OUTSIDE AIR
ROUND DUCT SIZE
OVAL DUCT SIZE
FIRE DAMPER (HORIZ. RUN)
FIRE DAMPER (VERT. RISE)
SMOKE DAMPER
CONNECT TO EXISTING
POINT OF DISCONNECT
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
H-0.0E 2020026 MIT
11.05.2021 BID SET
E M
O R
MIT DCBATR2021147-00
E X
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
H-1.1E 2020026 MIT
11.05.2021 BID SET
E M
O R
MIT DCBATR2021147-00
NO SCALE
2 BALANCE DAMPER TO 100 CFM FOR EXISTING HALLWAY DIFFUSER.
3 BALANCE OPEN ENDED DUCT TO 5850 CFM.
4 PROVIDE CABLE OPERATED DAMPERS FOR DAMPERS ASSOCIATED WITH VAV-1-E.
REVISIONS
11/03/2021
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
H-2.1E 2020026 MIT
11.05.2021 BID SET
E M
O R
MIT DCBATR2021147-00
NO SCALE
H-2.1E DRAWING NOTES
REVISIONS
11/03/2021
MIN. 6" HIGH SHEET METAL PLENUM BOX FULL SIZE OF NOTED REGISTER SIZE.
RETURN / EXHAUST AIR CEILING REGISTER.
RA / EA DUCT MAIN MANUAL VOLUME DAMPER
RA / EA BRANCH DUCT.
EXTEND RA / EA BRANCH DUCT DOWN AND CONNECT TO SHEET METAL PLENUM BOX. SECURE CONNECTION WITH A MIN. OF 4 SHEET METAL SCREWS ON THE DOVETAIL TABS.
CEILING
REFER TO SPECS FOR FASTENING REQUIREMENTS, TYP
WIRE HANGER, TYP
SHEETMETAL SHIELD, MIN. 6" LONG X DIA. OF FLEXIBLE DUCT. MOUNT AT MIDPOINT OF RUNS OVER 5 FT.
CEILING DIFFUSERCEILING
FLEX DUCT TO DIFFUSER SHALL BE SAME SIZE AS DIFFUSER NECK SIZE, UNLESS NOTED OTHERWISE ON DWG (6 FT. MAX. LENGHT.)
INSULATED FLEXIBLE DUCTWORK
SQUARE TO ROUND ADAPTER OR FIELD FABRICATED PLENUM WHERE REQUIRED
S
A
HOT WATER
VAV BOX
COIL MANUAL AIR VENT VALVE WITH PLUG
AIR VENT (3/4" BALL VALVE WITH CAP) LOCATE AT HIGH POINT
SHUT-OFF VALVE
HYDRONIC COIL DRAIN (3/4" SHUTOFF VALVE WITH HOSE COUPLING)Y-STRAINER WITH
BLOWOFF VALVE P/T PORT
CLEANING/FLUSHING BYPASS WITH SHUT-OFF VALVE (MATCH SUPPLY PIPING SIZE)
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
H-5.1E 2020026 MIT
11.05.2021 BID SET
E M
O R
MIT DCBATR2021147-00
1
DESIG INLET SIZE Ø
CFM GPM
EWT (°F)DESIGN MIN
SFP-1 10 1000 785 1000 1/4 120 1 1000 3.1 1.7 61 88 °F 180
SFP-2 6 500 395 500 1/4 120 1 500 1.8 0.6 61 88 °F 180
VARIABLE AIR VOLUME UNIT SCHEDULE, HOT WATER HEAT
DESIG
LAT (°F)
VAV-1-E 545 515 515 8 0.25 25 25 13.5 1.3 2.5 180 1 55 85
VAV-2-E 150 95 95 6 0.25 25 25 3.1 0.3 2.5 180 1 55 85
11/03/2021
NOTE 8
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
HD-1.0E 2020026 MIT
11.05.2021 BID SET
E M
O R
MIT DCBATR2021147-00
- HVAC - PHASE 1
1 UNLESS NOTED OTHERWISE, ALL EXISTING EQUIPMENT, PIPING, DUCTWORK, CONTROLS, AND
APPURTENANCES SHALL REMAIN AND BE MAINTAINED IN SERVICE.
2 REMOVE EXISTING FAN POWERED BOX IN ITS ENTIRETY INCLUDING WIRING, TEMPERATURE SENSORS,
DUCTWORK, DIFFUSERS, HANGERS, SUPPORTS, AND RELATED APPURTANANCES BACK TO MAIN AND CAP.
3 PRIOR TO DEMOLITION, MEASURE AIRFLOW OF SUPPLY AIR BRANCHES AT POINTS INDICATED. ALL FANS
SHALL BE SET TO MAXIMUM SPEED AND ALL ASSOCIATED VAV AND/OR FAN POWER BOXES SHALL BE AT
MAXIMUM POSITION AT TIME OF READINGS. SUBMIT REPORT WITH FINDINGS WITHIN 30 DAYS OF AWARD OF
CONTRACT. PROVIDE PLAN INDICATING THE LOCATION OF EACH TRAVERSE READING.
4 PRIOR TO DEMOLITION, MEASURE AIRFLOW OF EXISTING TO REMAIN RETURN AIR MAIN AT POINT INDICATED.
ALL FANS SHALL BE SET TO MAXIMUM SPEED AND ALL ASSOCIATED VAV BOXES SHALL BE AT MAXIMUM
POSITION AT TIME OF READINGS. SUBMIT REPORT WITH FINDINGS WITHIN 30 DAYS OF AWARD OF CONTRACT.
AFTER COMPLETION OF WORK, REBALANCE THE EXISTING MAIN TO THE AIRFLOW READINGS TAKEN PRIOR
TO START OF DEMOLITION EXCLUDING THE AIRFLOWS TO THE DEMOED VAV AND FAN POWERED BOXES AND
INCLUDING THE AIRFLOWS TO THE ADDITIONAL VAV AND FAN POWERED BOXES. PROVIDE PLAN INDICATING
THE LOCATION OF EACH TRAVERSE READING.
5 REMOVE EXISTING VAV BOX AND SUPPLY AIR DUCTWORK, DIFFUSERS, REGISTERS, FLEXIBLE DUCT,
HANGERS, SUPPORTS AND OTHER RELATED APPURTENANCES DOWNSTREAM OF POINT INDICATED.
PERMANENTLY CAP SA DUCT TAP AT MAIN AIRTIGHT.
6 REMOVE EXISTING RETURN AIR GRILLE.
7 REMOVE EXISTING HWS & HWR PIPING MAINS TO POINT INDICATED INCLUDING ASSOCIATED SUPPORTS,
VALVES, AND APPURTENANCES. CAP EXISTING PIPING AT MAIN.
8 REMOVE EXISTING EXHAUST AIR BRANCH DUCTWORK, DIFFUSERS, REGISTERS, FLEXIBLE DUCT, HANGERS,
SUPPORTS AND OTHER RELATED APPURTENANCES DOWNSTREAM OF POINT INDICATED.
9 EXISTING 20/20 SUPPLY AIR DUCTS TO REMAIN.
REVISIONS
UP
UP
11/03/2021
1. COMPLY WITH LOCAL, STATE, AND NATIONAL CODES AND REGULATIONS.
2. PLAN DOCUMENTS ARE SCHEMATIC TO CONVEY THE DESIGN INTENT. DO NOT SCALE DRAWINGS FOR EXACT PLACEMENT OF EQUIPMENT AND DISTRIBUTION SYSTEMS.
3. COORDINATION BETWEEN DISCIPLINES IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR AND/OR CONSTRUCTION MANAGER PRIOR TO INSTALLATION.
4. THE DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY. IN A CASE OF A CONFLICT BETWEEN THE DRAWINGS AND SPECIFICATIONS, REQUEST A DOCUMENTED INTERPRETATION FROM THE ARCHITECT / ENGINEER.
5. INSTALL EQUIPMENT PER MANUFACTURER'S INSTALLATION INSTRUCTIONS AND INSURANCE UNDERWRITER REQUIREMENTS.
6. THE LINE-TYPE AND SYMBOLS LEGENDS SHOW ITEMS TYPICALLY INCLUDED WITH THE SPECIFIED SYSTEMS. NOT ALL SYMBOLS AND/OR LINE TYPES ARE UTILIZED.
7. INCLUDE DETAILS IN THE SCOPE OF WORK FOR EVERY SITUATION TO WHICH THAT DETAIL APPLIES EXCEPT WHERE A SPECIFIC DETAIL REFERENCE IS DESIGNATED TO INDICATE OTHERWISE.
8. EXISTING PLUMBING EQUIPMENT, PIPING, AND FIXTURES SHALL REMAIN UNLESS NOTED OTHERWISE.
9. SCHEDULE SYSTEM MODIFICATIONS TO MINIMIZE DISRUPTIONS TO EXISTING BUILDING SERVICES. COORDINATE SHUTDOWN REQUESTS PER SPECIFICATIONS AND OWNER REQUIREMENTS.
10. LOCATE PIPING AS HIGH AS POSSIBLE, UNLESS NOTED OTHERWISE.
11. SEAL PENETRATIONS THROUGH FIRE AND/OR SMOKE BARRIERS WITH AN APPROVED SYSTEM TO MAINTAIN THE INTEGRITY OF THE BARRIER AND SHALL BE MARKED APPROPRIATELY IN ACCORDANCE WITH SPECIFICATIONS.
12. INSTALL EXTERIOR FUEL GAS REGULATORS AND METERS AT LEAST 10 FT FROM DOORS, OPERABLE WINDOWS, FRESH AIR OPENINGS, ETC.
13. COORDINATE ROOF PENETRATIONS WITH THE ROOFING CONTRACTOR OR ROOF WARRANTY UNDERWRITER TO MAINTAIN ROOFING SYSTEM INTEGRITY.
14. MINIMUM PLUMBING PIPING SIZE SHALL BE 1/2" UNLESS NOTED OTHERWISE.
15. INSTALL FLEXIBLE CONNECTIONS BETWEEN ALL MOTORIZED EQUIPMENT AND THE CONNECTED SYSTEM. REFER TO SPECIFICATIONS FOR CONNECTION TYPE AND APPLICATION.
16. PROVIDE ALL FUEL GAS PIPING WITH A SHUT OFF VALVE, UNION, AND DRIP LEG AT EACH CONNECTION TO GAS FIRE EQUIPMENT.
PLUMBING LINETYPE KEY (APPLIES TO ALL PLUMBING SERVICES OR SYMBOLS)
PLUMBING ABBREVIATIONS AB CL ABOVE CEILING
AT ST AT STRUCTURE
BL GD BELOW GRADE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
CIP CAST IRON PIPE
FPM FEET PER MINUTE
GC GENERAL CONTRACTOR
RPM REVOLUTIONS PER MINUTE
SV STACK VENT
TJ THRU JOIST
TR THROUGH ROOF
SYMBOL DESCRIPTION
HEAVY LINEWEIGHT INDICATES PIPING AND EQUIPMENT TO BE FURNISHED UNDER THIS PROJECT
THIN LINEWEIGHT INDICATES PIPING AND EQUIPMENT THAT ARE EXISTING TO REMAIN, UNLESS NOTED OTHERWISE
DASHED LINEWEIGHT INDICATES PIPING AND EQUIPMENT THAT ARE EXISTING TO BE REMOVED, UNLESS NOTED OTHERWISE
PLUMBING SYMBOLS SCHEDLE
HOT WATER (deg F)
FIRE PROTECTION WATER SUPPLY
VALVE WITH TAMPER SWITCH
VALVE WITH FLOW SWITCH
UPRIGHT FIRE SPRINKLER HEAD
PENDANT FIRE SPRINKLER HEAD
IN-RACK FIRE SPRINKLER HEAD
CONNECT NEW TO EXISTING
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
P-0.0E 2020026 WLF
11.05.2021 BID SET
E M
O R
WLF RJACLP2021147-00
2", AB CL
2", AB CL
2", AB CL
3/4", AB CL
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
P-1.1E 2020026 WLF
11.05.2021 BID SET
E M
O R
WLF RJACLP2021147-00
NO SCALE
WATER
WATER
WATER
WATER
REVISIONS
1 NO PLUMBING WORK IN THIS AREA.
2 FOR CONTINUATION PLEASE REFER TO AREA B DOMESTIC WATER PLAN ON THIS SHEET.
3 PROVIDE VENTURI FLOW SPLITTER.
NOTE 1
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
P-2.1E 2020026 WLF
11.05.2021 BID SET
E M
O R
WLF RJACLP2021147-00
NO SCALE
VENT
VENT
VENT
VENT
REVISIONS
1 NO PLUMBING WORK IN THIS AREA.
2 FOR CONTINUATION PLEASE REFER TO AREA B SANITARY & VENT PLAN, ON THIS SHEET.
3 UNLESS OTHERWISE NOTED, SANITARY PIPING 2-1/2" AND SMALLER SHALL BE SLOPED AT 1/4" FALL PER
FOOT. SANITARY PIPING 3" AND LARGER SHALL BE SLOPED AT 1/8" FALL PER FOOT.
FFE=1982.9' NOTE 3
BALL VALVE (TYP)
CHECK VALVE (TYP)
1/2" TEMPERED WATER
TO FIXTURE GROUP
FROM FIXTURE GROUP
SYMBOL DESCRIPTION SERVICE
TMV-1 THERMOSTATIC MIXING VALVE; MAXIMUM FLOW: 2.0 GPM @ 10 PSI PRESSURE DROP ACROSS
VALVE. MINIMUM FLOW: 0.5 GPM. SET OUTLET TEMPERATURE @ 110° F ADDITION & RENOVATION
PLUMBING EQUIPMENT SCHEDULE
1-1/2"
1-1/2"
* SANITARY PIPING UNDERGROUND AND BENEATH SLAB ON GRADE SHALL BE NO LESS THAN 2" IN DIAMETER.
** PROVIDE THEMOSTATIC MIXING VALVE, TMV-1, BELOW SINKS TO PROVIDE A 110° HOT WATER DELIVERY TEMPERATURE TO FAUCET. REFER TO DETAIL ON THIS SHEET.
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
P-5.1E 2020026 WLF
11.05.2021 BID SET
E M
O R
WLF RJACLP2021147-00
2
**
**
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
PD-1.0E 2020026 WLF
11.05.2021 BID SET
E M
O R
WLF RJACLP2021147-00
NO SCALE
- PLUMBING - PHASE 1
PARTIAL PLAN PD-1.0E
SCALE: 1/4" = 1'-0"
- PLUMBING - PHASE 1
PARTIAL PLAN PD-1.0E
SCALE: 1/4" = 1'-0"
- PLUMBING
- PLUMBING
1 NO PLUMBING DEMOLITION WORK IN THIS AREA.
2 REMOVE EXISTING PHARMACY SINK. REMOVE EXISTING DOMESTIC COLD AND HOT WATER BACK TO POINTS
OF LOCATION SHOWN ON PLAN. REMOVE VENT PIPING BACK TO LOCATION SHOWN ON PLAN. CAP SANITARY
PIPING AT FLOOR. PATCH AND REPAIR AS REQUIRED TO MATCH EXISTING CONSTRUCTION.
3 REMOVE ICE MAKER, SINK, AND DISHWASHER. REMOVE EXISTING DOMESTIC COLD AND HOT WATER BACK TO
POINTS OF LOCATION SHOWN ON PLAN. REMOVE VENT PIPING FROM FIXTURE BACK TO ABOVE CEILING AND
CAP FOR FUTURE CONNECTION. REMOVE SANITARY PIPING BACK TO SLAB. REVISIONS
NOTE 1
NOTE 1
NOTE 1
MC METAL-CLAD CABLE EXTERIOR : NOT PERMITTED.
INTERIOR: PERMITTED ONLY IN SPECIFIC AREAS AS DEFINED IN THE
SPECIFICATIONS AND WITH WRITTEN PERMISSION OF OWNER.
RACEWAYS DESIG TYPE LOCATIONS ALLOWED
IMC INTERMEDIATE
METAL CONDUIT
EXTERIOR : EXPOSED, CONCEALED ABOVEGROUND.
INTERIOR: EXPOSED LESS THAN FOUR FEET (4') AFF, AREAS SUBJECT TO
PHYSICAL DAMAGE, UNDERGROUND BENEATH CONCRETE SLABS,
HAZARDOUS LOCATIONS.
EXTERIOR : EXPOSED, CONCEALED ABOVEGROUND.
INTERIOR: EXPOSED LESS THAN FOUR FEET (4') AFF, AREAS SUBJECT TO
PHYSICAL DAMAGE, UNDERGROUND BENEATH CONCRETE SLABS,
HAZARDOUS LOCATIONS, CABLING OVER 600V, FIRE PUMP ROOM.
FMC FLEXIBLE METAL
VOIDS IN EXISTING MASONRY WALLS.
LFMC LIQUIDTIGHT
PVC RIGID PVC CONDUIT
INTERIOR: WITHIN OR BENEATH CONCRETE SLABS; EXPOSED IN DAMP OR
WET LOCATIONS WHERE NOT SUBJECT TO PHYSICAL DAMAGE.
EMT ELECTRICAL METAL
INTERIOR: CONCEALED IN WALLS AND CEILINGS; EXPOSED MORE THAN FOUR
FEET (4') AFF; WITHIN CONCRETE SLABS ON AND ABOVE GRADE; SECONDARY
SIDE OF ISOLATION PANELS.
WIRING
CONDUCTOR
COPPER, COMPLY WITH ASTM B 3 FOR BARE COPPER AND ASTM B 8 FOR STRANDED CONDUCTORS. LISTED AND LABELED AS DEFINED BY NEC. STRANDED FOR #8 AWG AND LARGER, SOLID FOR #10 AWG AND SMALLER. ALUMINUM CONDUCTORS NOT PERMITTED.
WIRING INSULATION THW, THHN/THWN, XHHW, OR XHHW-2
MINIMUM SIZE #12 AWG FOR POWER, #14 FOR CONTROL
WIRING LEGEND SYMBOL DESCRIPTION
HATCH MARKS INDICATE QUANTITY OF #12 PHASE (SHORT HATCH) AND NEUTRAL (LONG HATCH) CONDUCTORS IN CONDUIT. PROVIDE ADDITIONAL #12G IN EACH CONDUIT. PROVIDE 2#12 AND #12G WHERE HATCH MARKS ARE NOT INDICATED, UNLESS NOTED OTHERWISE.
CONDUIT/WIRING RUN CONCEALED IN WALL OR CEILING
CONDUIT/WIRING RUN UNDERFLOOR OR UNDERGROUND
CONDUIT/WIRING RUN EXPOSED
ELECTRICAL ABBREVIATIONS
LIGHTING FIXTURE, RECESSED ARCHITECTURAL TROFFER; NORMAL
LIGHTING FIXTURE, SURFACE OR PENDANT (AS INDICATED); NORMAL
LIGHTING FIXTURE, WALL MOUNTED; NORMAL
LIGHTING FIXTURE, CEILING MOUNTED UNLESS NOTED OTHERWISE; NORMAL
LIGHTING FIXTURE, WALL MOUNTED; NORMAL
FIXTURE DESIGNATION INDICATES FIXTURE TYPE, LETTER INDICATES SWITCH ZONE WHERE APPLICABLE (APPLIES TO ALL FIXTURE TYPES)
LIGHTING FIXTURE; HALF SHADED INDICATES NORMAL AND EMERGENCY (APPLIES TO ALL FIXTURE TYPES)
EMERGENCY LIGHTING BATTERY UNIT, NUMBER OF HEADS AS INDICATED
WALL MOUNTED EXIT SIGN, ILLUMINATED; SHADED PORTION INDICATES LIGHTED FACE; DIRECTIONAL ARROWS AS INDICATED
CEILING MOUNTED EXIT SIGN, ILLUMINATED; SHADED PORTION INDICATES LIGHTED FACE; DIRECTIONAL ARROWS AS INDICATED
SINGLE POLE SWITCH
THREE WAY SWITCH
RECEPTACLE, SINGLE NEMA 5-20R
RECEPTACLE, DUPLEX NEMA 5-20R
RECEPTACLES, TWO DUPLEX MOUNTED IN A DOUBLE GANG BOX (APPLIES TO ALL RECEPTACLE TYPES)
INDICATES RECEPTACLE TO BE MOUNTED ABOVE COUNTER
INDICATES GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE
INDICATES TAMPER-RESISTANT RECEPTACLE
INDICATES MOUNTING HEIGHT OF RECEPTACLE, 18" AFF IF NOT NOTED
NUMBER INDICATES SOURCE PANEL AND BREAKER. CONNECT ADJACENT DEVICES INDICATED ON SAME CIRCUIT. PROVIDE BRANCH CIRCUIT FROM DEVICE NEAREST PANEL TO PANELBOARD (APPLIES TO ALL RECEPTACLES AND JUNCTION BOXES)
ELECTRICAL LINETYPE KEY
SYMBOL DESCRIPTION
HEAVY LINEWEIGHT INDICATES WIRING, DEVICES, FIXTURES AND EQUIPMENT TO BE FURNISHED UNDER THIS PROJECT
THIN LINEWEIGHT INDICATES WIRING, DEVICES, FIXTURES AND EQUIPMENT THAT ARE EXISTING TO REMAIN, UNLESS NOTED OTHERWISE
DASHED LINEWEIGHT INDICATES WIRING, DEVICES, FIXTURES AND EQUIPMENT THAT ARE EXISTING TO BE REMOVED, UNLESS NOTED OTHERWISE
POWER POLE, WIRING DEVICES AS INDICATED
MOTOR STARTER, MANUAL WITH OVERLOADS; "X" INDICATES NUMBER OF POLES, NO NUMBER INDICATES ONE POLE
MOTOR STARTER, MANUAL WITHOUT OVERLOADS; "X" INDICATES NUMBER OF POLES, NO NUMBER INDICATES ONE POLE
DISCONNECT SWITCH, RATINGS AS INDICATED ON SCHEDULE, FUSED UNLESS NOTED OTHERWISE
JUNCTION BOX, WALL MOUNTED, RECESSED UNLESS NOTED
JUNCTION BOX
FIRE ALARM VISUAL UNIT, WALL MOUNTED
FIRE ALARM PULL STATION
FIRE ALARM SMOKE DETECTOR
SYMBOL DESCRIPTION
WALL OUTLET, DATA - 'Y' INDICATES QUANTITY OF JACKS, NO NUMBER INDICATES ONE JACK.
COMBINATION TELEPHONE/DATA OUTLET, WALL MOUNTED- 'X' INDICATES NUMBER OF TELEPHONE JACKS, 'Y' INDICATES NUMBER OF DATA JACKS. (TYPICAL FOR ALL TELECOMMUNICATIONS SYMBOLS)
WIRELESS ACCESS POINT OUTLET, CEILING MOUNTED
SERVICE OUTLET, COMBINATION TELEPHONE/DATA AND POWER, FLOOR MOUNTED
SYMBOL SCHEDULE - SECURITY
SYMBOL SCHEDULE - MULTI MEDIA
A AMPERE
EX EXISTING TO REMAIN
FMC FLEXIBLE METAL CONDUIT
G GROUND
LSI LONG TIME, SHORT TIME AND
INSTANTANEOUS (CIRCUIT BREAKER TRIP
AND GROUND FAULT (CIRCUIT BREAKER
TRIP FUNCTIONS)
NL NIGHT LIGHT
NC NORMALLY CLOSED
OC ON CENTER
OE OVERHEAD ELECTRIC
OT OVERHEAD TELECOMMUNICATIONS
TYP TYPICAL
GENERAL ELECTRICAL NOTES
A. COMPLY WITH APPLICABLE LOCAL, STATE, NATIONAL, AND INTERNATIONAL CODES AND REGULATIONS.
B. PLAN DOCUMENTS ARE SCHEMATIC TO CONVEY DESIGN INTENT. DO NOT SCALE DRAWINGS FOR EXACT PLACEMENT OF EQUIPMENT AND DEVICES.
C. COORDINATION BETWEEN DIVISIONS IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR AND/OR CONSTRUCTION MANAGER PRIOR TO INSTALLATION.
D. THE DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY. IN A CASE OF A CONFLICT BETWEEN THE DRAWINGS AND SPECIFICATIONS, REQUEST T A DOCUMENTED INTERPRETATION FROM THE ARCHITECT / ENGINEER.
E. INSTALL EQUIPMENT PER MANUFACTURER'S INSTALLATION INSTRUCTIONS AND INSURANCE UNDERWRITER'S REQUIREMENTS.
F. THE LINE-TYPE AND SYMBOLS LEGENDS SHOW ITEMS TYPICALLY INCLUDED WITH THE SPECIFIED SYSTEMS. NOT ALL SYMBOLS AND/OR LINETYPES ARE NECESSARILY UTILIZED.
G. INCLUDE DETAILS IN THE SCOPE OF WORK FOR EVERY SITUATION TO WHICH THAT DETAIL APPLIES EXCEPT WHERE A SPECIFIC DETAIL REFERENCE IS DESIGNATED TO INDICATE OTHERWISE.
H. PROVIDE INCREASED WIRE SIZE WHERE REQUIRED TO LIMIT VOLTAGE DROP FOR BRANCH CIRCUITS TO THREE PERCENT AND TOTAL VOLTAGE DROP FOR ENTIRE CIRCUIT (FEEDERS AND BRANCH CIRCUITS) TO FIVE PERCENT.
I. REFER TO TYPICAL RECESSED LUMINAIRE INSTALLATION DETAILS FOR INSTALLATION REQUIREMENTS OF RECESSED FIXTURES.
J. CONNECT LIGHTING FIXTURES IN EACH ROOM TO INDICATED NORMAL LIGHTING CIRCUIT IN THAT SPACE. PROVIDE SWITCHING AS INDICATED AND SWITCH WIRING AS REQUIRED. WHERE NO SWITCH LEGS ARE INDICATED, LOCAL SWITCHING SHALL CONTROL ALL FIXTURES IN ROOM. WHERE SWITCH LEGS ARE INDICATED, SWITCHES SHALL CONTROL ONLY THOSE FIXTURES NOTED WITH SAME LABEL AS SWITCH.
K. PROVIDE 0-10V CONTROL CABLING TO LIGHTING FIXTURES INDICATED WITH DIMMABLE CONTROLS.
L. COORDINATE EXACT FIXTURE MOUNTING HEIGHTS OF WALL-MOUNTED AND SUSPENDED FIXTURES WITH ARCHITECTURAL BUILDING ELEVATIONS BEFORE ROUGH-IN.
M. COORDINATE EXACT MOUNTING LOCATION OF SERVICE RECEPTACLES, DISCONNECTS, AND STARTERS FOR MECHANICAL AND OWNER FURNISHED EQUIPMENT IN FIELD WITH EQUIPMENT INSTALLER BEFORE ROUGH-IN. DO NOT INSTALL DEVICES WHERE LOCATION IMPEDES REQUIRED EQUIPMENT CLEARANCES AND SERVICE ACCESS POINTS.
N. MECHANICAL EQUIPMENT IS INDICATED ON POWER PLANS FOR LOCATION REFERENCE ONLY. REFER TO MECHANICAL EQUIPMENT SCHEDULE FOR SPECIFIC WIRING, DISCONNECT, AND CONTROLS REQUIREMENTS.
O. AMPERE INTERRUPTING CAPACITY (AIC), WITHSTAND CLOSE RATINGS (WCR), AND SHORT CIRCUIT CURRENT RATINGS (SCCR) SHOWN ON DRAWINGS ARE SYMMETRICAL, MINIMUM VALUES AT VOLTAGE OF THE RESPECTIVE EQUIPMENT. PROVIDE EQUIPMENT WITH FINAL RATINGS THAT MEET OR EXCEED VALUE NOTED ON DRAWINGS.
P. PROVIDE PULL STRING IN EMPTY CONDUITS/INNERDUCT.
Q. FIELD VERIFY EXISTING CIRCUITS BEING REUSED OR MODIFIED. WHERE BRANCH CIRCUIT IS INDICATED TO BE WIRED TO EXISTING BREAKER THAT IS IN USE, CONNECT CIRCUIT TO NEXT AVAILABLE BREAKER. WHERE NECESSARY, PROVIDE COMPATIBLE CIRCUIT BREAKER WITH AMPERE RATING AS INDICATED AND AIC RATING TO MATCH EXISTING PANELBOARD. UPDATE EXISTING PANELBOARD DIRECTORY TO REFLECT ANY PANEL REVISIONS AND NOTE CHANGES ON RECORD DRAWINGS.
GENERAL ELECTRICAL DEMOLITION NOTES
A. EXISTING ELECTRICAL ITEMS SHALL REMAIN AND BE MAINTAINED IN SERVICE, UNLESS NOTED OTHERWISE.
B. VERIFY EXISTING CONDITIONS IN FIELD. DOCUMENT DISCREPANCIES BETWEEN INFORMATION SHOWN ON DRAWINGS AND ACTUAL FIELD CONDITIONS AND SUBMIT TO DESIGN PROFESSIONAL BEFORE COMMENCING WITH WORK.
C. DEMOLITION DRAWINGS INDICATE GENERAL DEMOLITION SCOPE AND INTENT OF DEMOLITION WORK REQUIRED. DEMOLITION DRAWINGS DO NOT PROVIDE EXACT QUANTITIES AND SPECIFIC TYPES OF MATERIALS AND EQUIPMENT TO BE REMOVED.
D. DISCONNECT AND MAKE SAFE FOR REMOVAL ELECTRICAL DEVICES IN WALLS SCHEDULED TO BE DEMOLISHED BY GENERAL CONTRACTOR. WHERE ELECTRICAL DEVICES ARE INDICATED TO BE REMOVED IN WALLS THAT ARE SCHEDULED TO REMAIN, BACKBOX AND CONDUIT SHALL REMAIN AND BE REUSED WHERE POSSIBLE. WHERE NO DEVICES ARE INDICATED TO BE INSTALLED IN SAME LOCATION AS REMOVED DEVICES, PROVIDE BLANK COVER PLATE.
E. REFER TO DEMOLITION AND CONSTRUCTION DRAWINGS OF OTHER TRADES FOR ADDITIONAL CLARIFICATION OF DEMOLITION SCOPE. DISCONNECT AND MAKE SAFE ANY POWERED EQUIPMENT SCHEDULED FOR REMOVAL BY OTHER TRADES. REMOVE LINE VOLTAGE CONTROLS, WIRING, CONDUIT, AND ASSOCIATED ELECTRICAL ITEMS.
F. ONLY TRADE RESPONSIBLE FOR WORK OF DIVISIONS 26-28 SHALL PERFORM ELECTRICAL DEMOLITION WORK.
G. TRACE ENTIRETY OF ANY EXISTING CIRCUIT TO BE PARTIALLY REMOVED. BEFORE REMOVAL, MARK, LABEL OR TAG REMAINING PORTIONS OF THAT CIRCUIT INDICATING TYPE OF CIRCUIT (NORMAL, EMERGENCY, ETC.) AND AREA OR ITEMS SERVED.
H. EXISTING CONDUITS REMAINING IN PLACE MAY BE REUSED, PROVIDED CONDUIT IS IN SATISFACTORY CONDITION AND IS RUN IN DIRECT MANNER BETWEEN INTENDED SOURCE AND LOAD. THOROUGHLY CLEAN EXISTING CONDUITS BEFORE INSTALLATION OF WIRE.
I. DO NOT REUSE REMOVED CONDUIT AND WIRE.
J. WHERE EXISTING ELECTRICAL ITEM TO BE REMOVED IS LOCATED IN THE MIDDLE OF EXISTING CIRCUIT WITH OTHER EXISTING ITEMS ON THAT CIRCUIT TO REMAIN, MAKE REMAINING EXISTING CIRCUIT CONTINUOUS.
K. WHERE EXISTING ELECTRICAL ITEM TO BE REMOVED IS LOCATED AT THE END OF EXISTING CIRCUIT, REMOVE EXISTING WIRE AND EXPOSED CONDUIT BACK TO THE NEXT ACTIVE ITEM ON THAT CIRCUIT.
L. WHERE EXISTING ELECTRICAL ITEM TO BE REMOVED IS THE ONLY ITEM ON EXISTING CIRCUIT, REMOVE EXISTING WIRE AND EXPOSED CONDUIT BACK TO EXISTING PANELBOARD. LABEL ABANDONED EXISTING BREAKER AS SPARE AND REVISE EXISTING PANEL SCHEDULE ACCORDINGLY.
M. WHERE EXISTING CONDUIT RUN, OR PORTION OF AN EXISTING CONDUIT RUN, TO BE REMOVED IS PARTIALLY EXPOSED AND PARTIALLY CONCEALED, REMOVE EXPOSED PORTION TO CONCEALED POINT BEYOND THE SURFACE (WALL, CEILING, FLOOR, ETC), PATCH ADJACENT SURFACE, AND REFINISH TO MATCH SURROUNDINGS.
N. REQUIREMENTS FOR EXPOSED CONDUITS ALSO APPLY TO CONDUIT RUNS LOCATED ABOVE EXISTING ACCESSIBLE CEILINGS OR EXISTING CONDUIT RUNS THAT WILL BE LOCATED ABOVE ACCESSIBLE CEILINGS.
O. WHERE REMOVAL OF EXISTING WIRING, OR EXISTING ASSOCIATED WIRING, IS INDICATED ON THE DRAWINGS, INCLUDE REMOVAL OF ASSOCIATED RACEWAYS.
P. IN AREAS OF WORK (INCLUDING AREAS WHERE CEILINGS WILL BE REMOVED), REMOVE EXISTING EXPOSED UNUSED SYSTEMS CABLES IN THEIR ENTIRETY IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. VERIFY WITH OWNER THAT CABLES ARE UNUSED AND OBTAIN OWNER'S WRITTEN APPROVAL PRIOR TO REMOVAL.
Q. SALVAGE AND TURN OVER ITEMS OF VALUE AS IDENTIFIED BY OWNER. LEGALLY DISPOSE OF EQUIPMENT AND MATERIAL THAT OWNER DOES NOT WISH TO RETAIN.
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
E-0.0E 2020026 JES
11.05.2021 BID SET
E M
O R
JES YDUJMS2021147-00
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
E-1.1E 2020026 JES
11.05.2021 BID SET
E M
O R
JES YDUJMS2021147-00
NO SCALE
E-1.1E DRAWING NOTES
1 INTERCEPT EXISTING BRANCH CIRCUIT HOMERUN AT ACCESSIBLE LOCATION, EXTEND CONDUCTORS AS
NECESSARY, AND CONNECT TO DEVICES INDICATED.
2 X-RAY, IN-USE SIGN. COORDINATE INSTALLATION WITH X-RAY EQUIPMENT MANUFACTURER. REFER TO DETAIL
3/E-6.2E FOR ADDITIONAL INFORMATION.
EM- 10
B- 22
EM- 12
B- 24
NOTE 6
NOTE 6
NOTE 6
NOTE 6
NOTE 6
NOTE 6
EX MDP-2,4
EX PANEL A - SECTION 2 EX PANEL A - SECTION 1
EX FACP
Copyright. © All rights reserved. Reproduction in whole or in
part is prohibited. This drawing is an instrument of service, is
the property of the Architect and may not be used in any way
without written permission of this firm.
Project No: Drawn by:
E-2.1E 2020026 JES
11.05.2021 BID SET
E M
O R
JES YDUJMS2021147-00
E-2.1E DRAWING NOTES
1 6” x 6” x 4” JUNCTION BOX. FLUSH MOUNT IN WALL, 18” AFF TO CENTER. PROVIDE COVER PLATE WITH 2” SQUEEZE CONNECTOR.
2 6” x 6” x 4” JUNCTION BOX. FLUSH MOUNTED IN FLOOR. PROVIDE COVER PLATE.
3 4” x 4” x 4” JUNCTION BOX, FLUSH MOUNTED IN FLOOR. PROVIDE COVER PLATE WITH 2” SQUEEZE CONNECTOR.
4 24" x 24" x 4" JUNCTION BOX, FLUSH MOUNT IN WALL, 24” AFF TO CENTER. PROVIDE COVER PLATE AND 3” x 8” GROMMETED CABLE ACCESS OPENING IN FRONT COVER.
5 2” x 4” x 4” JUNCTION BOX, FLUSH MOUNT IN WALL, 48” AFF TO CENTER.
6 INTERCEPT EXISTING BRANCH CIRCUIT HOMERUN AT ACCESSIBLE LOCATION, EXTEND CONDUCTORS AS NECESSARY, AND CONNECT TO DEVICES INDICATED.
7 REFER TO DETAIL 3/E-6.2E FOR X-RAY WIRING DIAGRAM.
8 SAW CUT EXISTING FLOOR SLAB, THIS AREA, FOR IN FLOOR POWER AND DATA CONDUITS. PROVIDE MINIMUM OF 2" OF COVER OVER CONDUITS, GRIND PATCHING FLUSH WITH EXISTING FLOOR SLAB AND PREP FOR FLOOR FINISHES.
9 ONE (1) 1"C FOR BRANCH CIRCUIT WIRING AND ONE (1) 2"C FOR DATA/VOICE WITH INSULATING BUSHINGS AND PULL WIRES. RISE UP CONCEALED IN WALLS, STUB CONDUITS 6" ABOVE FINISHED CEILING. ROUTE POWER AND DATA/VOICE WIRING VIA CONDUIT TO MILLWORK.
10 ONE (1) 1"C FOR BRANCH CIRCUIT WIRING AND ONE (1) 2"C FOR DATA/VOICE WITH INSULATING BUSHINGS AND PULL WIRES. RISE UP CONCEALED IN HALF-WALL. COORDINATE EXACT LOCATION WITH ARCHITECT PRIOR TO ROUGH-IN, STUB CONDUITS 6" ABOVE FINISHED FLOOR. ROUTE POWER AND DATA/VOICE WIRING VIA FLUSH MOUNTED PULLBOXES THROUGH MILLWORK TO DEVICES INDICATED. COORDINATE ROUTING WITH MILLWORK VENDOR.
11 COORDINATE WIRING AND RECONNECTION RELOCATED SECURITY GRILLE RAISE/LOWER SWITCH WITH GRILL MANUFACTURER’S RECOMMENDATIONS.
12 RELOCATED PHARMACY SECURITY CONTROL PANEL AND COMMUNICATOR, COORDINATE RELOCATION AND WIRING OF EQUIPMENT WITH OWNER’S VENDOR, STANLEY SECURITY.
13 REFER TO SPECIFICATION SECTION 26 32 16 GASEOUS ENGINE GENERATORS FOR EMERGENCY GENERATOR REQUIREMENTS. THE EMERGENCY GENERATOR SHALL BE PURCHASED AS PART OF THE CLINICAL EXPANSION PROJECT AND INSTALLED UNDER THE FUTURE ADDITION PROJECT.
REVISIONS
LIGHTING FIXTURE SCHEDULE NOTES:
A. PRODUCT INFORMATION LISTED IS FOR THE FIRST NAMED MANUFACTURER. THIS MANUFACTURER & FIXTURE CONSTITUTES THE 'BASIS OF DESIGN'. LISTING OF ALTERNATE MANUFACTURER'S NAMES DOES NOT IMPLY ACCEPTANCE OF THEIR STANDARD PRODUCT. MANUFACTURERS ARE RESPONSIBLE FOR PROVIDING FIXTURES THAT ARE EQUAL IN ALL RESPECTS TO THE 'BASIS OF DESIGN' FIXTURE.
B. SUBSTITUTIONS OR FIXTURES PROVIDED BY MANUFACTURES NOT USED IN THE SCHEDULE ARE NOT ACCEPTABLE.
C. LIGHTING FIXTURES SUBMITTALS SHALL INCLUDE, AS A MINIMUM - 1) FIXTURE TYPE, DIMENSIONS, MATERIALS, & FINISH; 2) LED DATA FOR EACH FIXTURE TYPE INCLUDING TYPE, QUANTITY, WATTAGE, LUMEN OUTPUT,, COLOR RENDERING PROPERTIES; 3)DRIVER DATA FOR EACH FIXTURE TYPE.
D. VERIFY FIXTURE VOLTAGES & CEILING TRIM COMPATIBILITY PRIOR TO ORDERING FIXTURES.
E. PROVIDE LABOR & EQUIPMENT FOR FOCUSING OF ADJUSTABLE FIXTURES & PRESETTING OF LIGHTING CONTROL SYSTEMS. FOCUSING & PRESETTING SHALL BE DONE IN THE PRESENCE OF THE OWNER & DESIGN PROFESSIONAL.
F. IN ORDER TO CREATE A CONTROLLED, COMPETITIVE BIDDING CLIMATE, THE LIGHTING FIXTURE SCHEDULE WAS DEVELOPED AROUND 'THREE OR MORE' NAMES WHEREVER POSSIBLE.
GENERAL NOTES:
A. MATRIX INDICATES DESIRED CONTROL SCHEME AND PROGRAMMING FOR EACH SPACE. REFER TO LIGHTING FLOOR PLANS FOR LOCATIONS, TYPES, AND QUANTITIES OF FIXTURES AND CONTROL DEVICES.
B. BASIS OF DESIGN: nLIGHT BY ACUITY LIGHTING CONTROLS OR APPROVED EQUAL BY LEGRAND WATTSTOPPER 'DLM' DIGITAL LIGHTING CONTROL SYSTEM, HUBBLE NX. LIGHTING CONTROL SYSTEMS BY APPROVED ALTERNATIVE MANUFACTURERS SHALL PROVIDE ALL FUNCTIONS OF BASIS OF DESIGN SYSTEM AND SHALL BE SUBJECT TO FINAL REVIEW AND APPROVAL BY ENGINEER.
C. COORDINATE AND CONDUCT A LIGHTING CONTROL SYSTEM PRE-INSTALLATION MEETING WITH THE APPROVED SYSTEM MANUFACTURER REPRESENTATIVE(S), OWNER'S REPRESENTATIVE(S), GENERAL CONTRACTOR, AND THE DESIGN TEAM TO REVIEW THE SEQUENCE OF OPERATIONS MATRIX, COMPONENT LAYOUTS, AND MANUAL CONTROL STATION DETAILS PRIOR TO THE START OF SYSTEM INSTALLATION.
D. DURING CONTROLS SYSTEM PROGRAMMING AND COMMISSIONING, COORDINATE AND CONDUCT A WALK-THROUGH OF THE BUILDING WITH THE SYSTEM PROGRAMMING TECHNICIAN/INTEGRATOR, OWNER'S REPRESENTATIVE(S), GENERAL CONTRACTOR, AND THE DESIGN TEAM TO CONFIRM PREFERRED CONTROL PROGRAMMING AND ADJUST LIGHTING LEVELS AS REQUESTED FOR EACH SPACE. LIGHTING LEVEL PERCENTAGES LISTED IN THIS MATRIX SHALL BE CONSIDERED AS A STARTING POINT FOR INITIAL PROGRAMMING. PROVIDE MINIMUM 10 DAYS NOTICE PRIOR TO WALK-THROUGH.
E. LIGHTING CONTROL SYSTEM START-UP, COMMISSIONING, AND OWNER-TRAINING SHALL BE PROVIDED BY A MANUFACTURER-TRAINED REPRESENTATIVE.
F. PROVIDE FUNCTIONAL TESTING OF THE LIGHTING CONTROL SYSTEM AS DEFINED BY THE APPLICABLE ENERGY CODE(S). FUNCTIONAL TESTING SHALL INCLUDE BUT NOT LIMITED TO THE FOLLOWING: DAYLIGHT SENSORS, OCCUPANCY/VACANCY SENSORS, BAS INTERFACE, DIMMERS, ELAPSED TIMER SWITCHES, EMERGENCY RELAYS, EMERGENCY LIGHTING TRANSFER SWITCHES, AND NETWORKED/NON-NETWORKED DIGITAL CONTROL SYSTEM COMPONENTS. SUBMIT TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO FINAL CODE INSPECTION, ASSOCIATED DOCUMENTATION CERTIFYING THE INSTALLED CONTROLS MEET THE PERFORMANCE STANDARDS AS DEFINED BY THE REQUIREMENTS FOUND IN THE PROJECT'S SEQUENCE OF OPERATION MATRIX, AND APPLICABLE ENERGY CODE. SUBMIT TO THE OWNER[ AND COMMISSIONING AGENT] WITHIN 90 DAYS OF RECEIPT OF CERTIFICATE OF OCCUPANCY AND INCLUDE IN FACILITY'S O&M MANUAL, THE APPROVED TESTING DOCUMENTATION.
G. LIGHTING FIXTURES AND DEVICES PROVIDED AS PART OF THIS PROJECT SHALL BE COMPATIBLE WITH AND WIRED TO ACCEPT THE APPROVED DIGITAL LIGHTING CONTROL SYSTEM.
H. PROVIDE MANUFACTURER ENGRAVED PUSH-BUTTON STATIONS. DIRECTION ON WORDING OF ENGRAVINGS SHALL BE PROVIDED BY OWNER.
I. UNLESS OTHERWISE NOTED, ANY ZONE THAT IS DIMMABLE AND TO BE CONTROLLED VIA OCCUPANCY SENSOR OR VACANCY SENSOR SHALL FADE DOWN OVER 3 SECOND PERIOD AFTER TIMEOUT SETTING IS REACHED.
J. ASSUME INDICATED TARGET LIGHTING LEVELS MEASURED AT 30" AFF, UNLESS NOTED OTHERWISE.
K. UNLESS NOTED OTHERWISE, TAKE A SIMILAR APPROACH TO LOCATING ZONE CONTROLLERS, LOCAL NETWORK BRIDGES, AND OTHER SIMILAR "BACK OF HOUSE" DEVICES WITHIN ROOMS/SPACES THROUGHOUT THE PROJECT. WHERE ROOMS HAVE ACCESSIBLE CEILING, INSTALL ZONE CONTROLLERS CONCEALED ABOVE THE CEILING RIGHT INSIDE THE DOORWAY OF THE ROOM THAT THEY SERVE. WHERE NETWORK DEVICES ARE REQUIRED, INSTALL ADJACENT TO ROOM CONTROLLERS THAT THEY SERVE. IF DEVICE LOCATION IS REQUIRED IN AN UNCOMMON OR SPECIAL PLACE, PROVIDE LAMINATED TYPED LABEL ON GRID NOTING EQUIPMENT LOCATED ABOVE. COORDINATE DESIRED LABELING CHARACTERISTICS WITH ARCHITECT PRIOR TO INSTALLATION.
L. PROVIDE LABELING OF ALL LINE VOLTAGE CONDUCTOR BRANCH CIRCUITRY AT THE LIGHTING CONTROL EQUIPMENT TERMINALS. LABEL SHALL INDICATE PANELBOARD AND CIRCUIT NUMBER SERVING DEVICE.
M. PROVIDE MANUFACTURER-APPROVED LIGHTING CONTROL SYSTEM DEVICE LAYOUT PLANS AND WIRING DETAILS (TYPICAL DETAILS FOR SIMILAR SPACE TYPES ARE ACCEPTABLE) AS PART OF THE LIGHTING CONTROL SYSTEM SHOP DRAWING SUBMISSION. ADJUSTMENTS TO DEVICE QUANTITY OR DEVICE LOCATIONS SHOWN ON THE CONSTRUCTION DOCUMENTS THAT ARE NEEDED TO MEET MANUFACTURER-SPECIFIC CONTROL SYSTEM REQUIREMENTS OR OVERCOME SYSTEM LIMITATIONS WILL BE AT NO ADDITIONAL COST TO THE PROJECT.
N. COORDINATE CEILING OCCUPANCY SENSOR LOCATION TO MOUNT AT LEAST MANUFACTURER-RECOMMENDED MINIMUM DISTANCE TO SUPPLY AIR DIFFUSERS IN AN EFFORT TO AVOID FALSE TRIGGERING OF SENSOR. SENSORS WITH ULTRASONIC TECHNOLOGY WILL NOT BE PERMITTED TO BE 'PROGRAMMED OFF' WHERE SENSOR INSTALLATION IS NOT PER MANUFACTURER RECOMMENDATIONS. RELOCATION OF DETECTORS DUE TO NON-