1 UC Davis UC Davis UC Davis UC Davis Mondavi Center For the Performing Arts Mondavi Center For the Performing Arts Mondavi Center For the Performing Arts Mondavi Center For the Performing Arts Life Safety Analysis Life Safety Analysis Life Safety Analysis Life Safety Analysis Jeff Paterson Cal Poly - San Luis Obispo

Mondavi Center Life Safety Analysis - Cal Poly

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Mondavi Center Life Safety Analysis - Cal Poly

1

UC DavisUC DavisUC DavisUC DavisMondavi Center For the Performing ArtsMondavi Center For the Performing ArtsMondavi Center For the Performing ArtsMondavi Center For the Performing ArtsLife Safety AnalysisLife Safety AnalysisLife Safety AnalysisLife Safety Analysis

Jeff Paterson

Cal Poly - San Luis Obispo

Page 2: Mondavi Center Life Safety Analysis - Cal Poly

2

Overview

I. Building Description

II. Prescriptive Analysis

◦ Code Analysis

◦ Egress

◦ Detection and Alarm

◦ Suppression

III. Performance Based Analysis

Page 3: Mondavi Center Life Safety Analysis - Cal Poly

3

Building Description

• Location: UC Davis Campus

• Cost: $60,000,000• Construction began – 2000

• First performance – Oct. 2002

• Floor area: 104,000 sqft

• Height: 97.5 ft

• Theaters:• Jackson Hall – 1801 max seating

• Vanderhoef Studio Theater – Up to 250 capacity

• Automatic sprinkler system

• Automatic detection and alarm system with emergency voice alarm/communication system

• Atrium lobby with smoke management system

Page 4: Mondavi Center Life Safety Analysis - Cal Poly

4

Jackson HallStage

Lobby

Studio

Theater

Back of

House

Page 5: Mondavi Center Life Safety Analysis - Cal Poly

5

Relevant Codes

Original Codes

◦ California Building Code – 1995

◦ California Fire Code – 1995

◦ NFPA 13 – 1994

◦ NFPA 72 – 1993

Project Codes

◦ California Building Code – 2010

◦ California Fire Code - 2010

◦ NFPA 13 – 2010

◦ NFPA 72 – 2012

CODE ANALYSIS

Page 6: Mondavi Center Life Safety Analysis - Cal Poly

6

Building Occupancy

• Mixed Occupancy

• Main Occupancy Classifications

• Assembly Group A-1

• Assembly Group A-3 (Vanderhoef Studio Theater)

• Accessory Occupancies

• Business

• Storage

Separation Requirements

A-1 <-> A-3 0 hr

CODE ANALYSIS

Page 7: Mondavi Center Life Safety Analysis - Cal Poly

7

Building Height and Area

Mixed occupancy classification, most stringent requirements must be used -> A-1.

Original Construction Type: II FR

Current Construction type: IB

Allowable Actual

Building height 160+20* ft 97.5 ft

Stories 5+1* 5

Area per story Unlimited 48,000 ft2 max.

* Automatic Sprinklers

CODE ANALYSIS

Page 8: Mondavi Center Life Safety Analysis - Cal Poly

8

Structural Protection

Building Element Required Fire-Resistance

Rating (hour)

Applied Fire-Resistance

Rating (hour)

Primary structural frame 2, 1* 2, 1*

Bearing walls

Exterior

Interior

2, 1*

2

2, 1*

2

Nonbearing walls/partitions

Exterior

Interior

0, 1

0

0, 1

0

Floor construction 2 2

Roof construction 1 1

CODE ANALYSIS

Page 9: Mondavi Center Life Safety Analysis - Cal Poly

9CODE ANALYSIS

>30

>30

>30

30>x>10

Page 10: Mondavi Center Life Safety Analysis - Cal Poly

Incidental Accessory Occupancies

Egress

Special Situations

10

Separation Requirements

Room/Area Req. Separation Applied Protection

Fire Pump Room 2-hr; or 1 hr w/ fully sprinklered 2-hr fire barrier and sprinklers

Storage rooms >100 sqft 1-hr or auto fire-extinguishing system Sprinklers

Furnace Room 1-hr or auto fire-extinguishing system Sprinklers

Space Req. Separation Applied Protection

Atrium <-> Rest of building 1-hr fire barrier or horiz. assembly 1-hr constr. 20-min. doors

Proscenium wall 2-hr construction 2-hr fire barrier

Stage to adjacent spaces 2-hr fire barrier 2-hr fire barrier*

Adjacent <-> adjacent spaces 1-hr fire barrier 1-hr fire barrier

Space Req. Separation Applied Protection

Corridors 1-hr or 0-hr w/ Fully Sprinklered 1-hr fire partition

Horiz./Vert. Exit Enclosures 2-hr fire barrier 2-hr fire barrier

CODE ANALYSIS

Page 11: Mondavi Center Life Safety Analysis - Cal Poly

11CODE ANALYSIS

Page 12: Mondavi Center Life Safety Analysis - Cal Poly

12

Special Requirements

Atrium

• Approved Sprinkler system throughout building

• Fire alarm system with detection throughout atrium and emergency voice alarm/communication system

• Smoke control system

Stage

• Standpipe system

• Class III with 1-1/2” and 2-1/2” hose connections on each side of stage

• Emergency ventilation

• Roof vents >5% stage area or smoke control system

CODE ANALYSIS

Page 13: Mondavi Center Life Safety Analysis - Cal Poly

13

Egress Analysis

Assembly – Fixed seating: Number of seats + wheel chairs and non-fixed seating in accordance with Table 1004.1.1

Use Load Factor (ft2/occupant)

Assembly – Fixed See note

Assembly – Standing 5 net

Assembly – Concentrated 7 net

Assembly – Unconcetrated 15 net

Stage 15 net

Business 100 gross

Storage 300 gross

EGRESS

Page 14: Mondavi Center Life Safety Analysis - Cal Poly

14

Egress Analysis

LocationFloor Area

(ft2)

Load Factor (ft2

per person)Load

Limiting Door/Stair

Exit Capacity

Lobby

1st Floor

2nd Floor

3rd Floor

8,615

4,500

5,949

51,725

900

1,190

3,105

560

761

Jackson Hall Seating

Orchestra/Parterre

First Balcony

Second Balcony

580

580

300

# seats, 7, 1001,179

393

364

1309

400

400

Studio Theater 3,334 # seats, 7, 15 335 390

Stage 9,500 15, 300, 100 498 675

Back of House

1st Floor

2nd Floor

6,000

1,500

7, 15, 100, 300 718

96

756

329

Basement 2,700 7, 15, 100, 300 107 467

EGRESS

Page 15: Mondavi Center Life Safety Analysis - Cal Poly

15

A – Fixed

A – Concentrated

A – Unconc.

Stage

Business

Storage

Access Corridor

Exit Enclosure

Exit

Exit Access

Exit Discharge

Page 16: Mondavi Center Life Safety Analysis - Cal Poly

16

A – Fixed

A – Concentrated

A – Unconc.

Stage

Business

Storage

Access Corridor

Exit Enclosure

Exit

Exit Access

Exit Discharge

EGRESS

Page 17: Mondavi Center Life Safety Analysis - Cal Poly

17

A – Fixed

A – Concentrated

A – Unconc.

Stage

Business

Storage

Access Corridor

Exit Enclosure

Exit

Exit Access

Exit Discharge

EGRESS

Page 18: Mondavi Center Life Safety Analysis - Cal Poly

18

A – Fixed

A – Concentrated

A – Unconc.

Stage

Business

Storage

Access Corridor

Exit Enclosure

Exit

Exit Access

Exit Discharge

EGRESS

Page 19: Mondavi Center Life Safety Analysis - Cal Poly

19

Fire Detection and Alarm

• Addressable Emergency Voice Alarm/Communication System

• Manual and automatic detection

• Visual/voice notification

• Proprietary Supervising Station

• UCD Police Department Communications Center

• Control Panels

• Main Fire Alarm Control Panel

• Voice Evacuation Panel

• Fire Fighter’s Control Panel

• 2 – Remote Fire Alarm Power Supply

• Smoke Control Panel

• 4 – Fire Alarm Annunciator Panel

DETECTION AND ALARM

Page 20: Mondavi Center Life Safety Analysis - Cal Poly

20

Detection

DETECTION AND ALARM

Initiating Device Location

Manual pull stations <5 ft from exits, <200 ft from any location

Photoelectric smoke detectors Throughout occupiable space, Except studio

theater/stage zone/audience chamber zone

Additional smoke detectors • Elevator lobbies

• Above automatic closing/holding doors

Heat and smoke detectors Elevator equipment rooms/boiler room

Ionization smoke detectors Supply/return air ducts

Sprinkler water flow

switches/tamper switches

Pump room/each zone riser/exterior O.S.&Y.

Valves

Beam detector Lobby atrium

Page 21: Mondavi Center Life Safety Analysis - Cal Poly

21

Page 22: Mondavi Center Life Safety Analysis - Cal Poly

22DETECTION AND ALARM

Beam detection (30%): 37 seconds

Spot type detection: 26 seconds

Page 23: Mondavi Center Life Safety Analysis - Cal Poly

23

Notification

DETECTION AND ALARM

Notification Appliance Location

Wall/ceiling mounted speakers All occupied spaces except some

small offices and some storage rooms

Wall mounted synchronized strobes All occupied spaces except some

small offices and some storage rooms

Fire sprinkler exterior bell West exterior wall

Page 24: Mondavi Center Life Safety Analysis - Cal Poly

24

Fire Sprinkler System

• Total building area >52,000 ft2

• Split into zones

Water Supply

• Campus water supply

• Static Pressure: 65 psi

• Residual Pressure: 20 psi

• Flow: 16,825 gpm

• Pump

• Flow: 750 gpm

• Net Pressure at 150% capacity: 61 psi

• Max. net pressure developed: 97 psi

SUPPRESSION

Page 25: Mondavi Center Life Safety Analysis - Cal Poly

25

Design Basis

• Density/area method

• 250 gpm required hose stream allowance

• 60 minute required water supply duration for OH with full supervision

Most hydraulically demanding

• Zone 4: Audience Chamber

• Extended coverage sprinklers

• Design for 5 sprinklers or 1,500 ft2, whichever is highest

• 20 ft spacing

SUPPRESSION

Zone Occupancy

Classification

Density

(gpm/ft2)

Area (ft2)

1 OH (GRP 1) 0.15 1500

3 OH (GRP 2) 0.20 1500

2, 4, 5, 6 Light Hazard 0.10 1500

Page 26: Mondavi Center Life Safety Analysis - Cal Poly

26

Required Flow: 406 gpm

Required Pressure: 132.2 psi

Page 27: Mondavi Center Life Safety Analysis - Cal Poly

27SUPPRESSION

Total: 721 gpm at 132.2 psi

Page 28: Mondavi Center Life Safety Analysis - Cal Poly

28

Performance Based Analysis

Available Safe Egress Time (ASET) > Required Safe Egress Time (RSET)

Time available to escape > Time needed to escape

PERFORMANCE BASED ANALYSIS

Tenability requirements:

• Visibility > 10 meters

• Temperature < 60° C

• CO conc. < 950 ppm

• Heat Flux < 2.5 kW/m2

Page 29: Mondavi Center Life Safety Analysis - Cal Poly

29

Required Safe Egress Time

PERFORMANCE BASED ANALYSIS

Detection + Alarm Time

Pre-movement Time

Movement Time Safety Factor

60 s 1.5

British Standard

PD7974-6:2004

FDS Est. +

20 s

Pathfinder Est.

CBC 909.4.6

Page 30: Mondavi Center Life Safety Analysis - Cal Poly

30

Lobby Fire Scenario

• Location: 4 story lobby atrium

• Fuel package: Backpacks, coat rack

• Occupant load: Fully loaded lobby

• Fire protection systems:

• Full smoke detection

• Full automatic sprinklers

• Mechanical exhaust system

• Exhaust: Two 77,000 CFM exhaust fans

• Make-up air: Lobby doors, mechanical air supply

PERFORMANCE BASED ANALYSIS

Page 31: Mondavi Center Life Safety Analysis - Cal Poly

31

Lobby Fire Scenario

• Location: Coat check area

• Fire size: t2 HRR until sprinkler activation

• Smoke control activated by smoke detection or sprinkler activation

PERFORMANCE BASED ANALYSIS

Page 32: Mondavi Center Life Safety Analysis - Cal Poly

32PERFORMANCE BASED ANALYSIS

Page 33: Mondavi Center Life Safety Analysis - Cal Poly

33PERFORMANCE BASED ANALYSIS

OPEN TO

ABOVE

� =��

4���,"=

800�� 0.3

4� 2.5��/��

� = 2.8� = 9��

��� = 9�� × 2 = 18��

Page 34: Mondavi Center Life Safety Analysis - Cal Poly

34

Lobby Fire – Concerns

PERFORMANC BASED ANALYSIS

Page 35: Mondavi Center Life Safety Analysis - Cal Poly

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

0.0

10.0

20.0

30.0

40.0

50.0

60.0

70.0

80.0

90.0

100.0

0 50 100 150 200

HR

R (

kW

)

TE

MP

(°C

)

TIME (s)

Gas Temp DETACT Spr Temp

Actuation Temp FDS Spr Temp

HRR

35

Lobby Design Fire

• Sprinkler activation time:

• DETACT: 120 s

• FDS: 130 s -> HRR = 800 kW

• FDS estimated smoke detection time: 21 s

PERFORMANCE BASED ANALYSIS

800

Page 36: Mondavi Center Life Safety Analysis - Cal Poly

36

Lobby Fire – FDS Analyses

PERFORMANCE BASED ANALYSIS

Page 37: Mondavi Center Life Safety Analysis - Cal Poly

37PERFORMANCE BASED ANALYSIS

(PPM)

CO Concentration at 600s

1st Floor 2nd Floor

3rd Floor 4th Floor

Page 38: Mondavi Center Life Safety Analysis - Cal Poly

38PERFORMANCE BASED ANALYSIS

(°C)

Temperature at 600s

1st Floor 2nd Floor

3rd Floor 4th Floor

Page 39: Mondavi Center Life Safety Analysis - Cal Poly

39PERFORMANCE BASED ANALYSIS

(m)

Visibility at 600s

1st Floor 2nd Floor

3rd Floor 4th Floor

Page 40: Mondavi Center Life Safety Analysis - Cal Poly

40PERFORMANCE BASED ANALYSIS

(m)

Visibility at 225s

2nd Floor 3rd Floor

Page 41: Mondavi Center Life Safety Analysis - Cal Poly

41

Lobby Fire– Pathfinder Analysis

PERFORMANCE BASED ANALYSIS

Page 42: Mondavi Center Life Safety Analysis - Cal Poly

42

Pathfinder Simulation at 39s

PERFORMANCE BASED ANALYSIS

Page 43: Mondavi Center Life Safety Analysis - Cal Poly

43

Lobby Fire – ASET vs. RSET

PERFORMANCE BASED ANALYSIS

ScenarioDetection

and Alarm

Pre-

movementMovement

CBC

FactorRSET ASET

2nd Floor21 + 20 60

391.5

210 225

3rd Floor 39 210 225

0 200 400 600 800 1000 1200

The rest of the lobby

3rd floor balcony

2nd floor balconyRequired

Available

Page 44: Mondavi Center Life Safety Analysis - Cal Poly

44

Recommendations

• Modify make-up air flow into the 2nd floor lobby.• Double the flow showed tenable conditions

• Remove make-up air flow showed tenable conditions

• Move coat check

• Mondavi already has plans

PERFORMANCE BASED ANALYSIS

Page 45: Mondavi Center Life Safety Analysis - Cal Poly

45

Stage Fire Scenario

• Location: 45 ft tall storage area behind 87 ft tall stage

• Occupant load: Fully loaded theater seating and stage

• Fire protection systems:

• Fully sprinklered

• Heat activated ceiling vents

• Manual/heat activated proscenium curtain

PERFORMANCE BASED ANALYSIS

Page 46: Mondavi Center Life Safety Analysis - Cal Poly

46PERFORMANCE BASED ANALYSIS

Page 47: Mondavi Center Life Safety Analysis - Cal Poly

47PERFORMANCE BASED ANALYSIS

Page 48: Mondavi Center Life Safety Analysis - Cal Poly

48

Stage Fire - Design Fire

• Location: Storage area at the back of the stage

• Fire size: t2 HRR until calculated maximum HRR

• Heat activated sprinklers, roof vents, proscenium curtain

• Smoke detection above storage room door

• Minimum tenable distance:

� =��

4���,"=

4000�� 0.3

4� 2.5��/��

� = 6.2� = 20��

��� = 20�� × 2 = 40��

PERFORMANCE BASED ANALYSIS

Page 49: Mondavi Center Life Safety Analysis - Cal Poly

49

Stage Fire - Fuel Package• Stored rack full of electrical

cables for stage equipment

• HRR calculated from correlations provided by Lee for cable trays.

PERFORMANCE BASED ANALYSIS

�� ! = 0.45��"!" #

�� ! = 0.45 589��

��15��

$�� = 4000��

Page 50: Mondavi Center Life Safety Analysis - Cal Poly

50

Stage Fire – FDS Analyses

• Sprinklers do not activate

• Roof vent fusible links do not activate

• Proscenium fusible links do not activate

• Smoke detection at 160s

PERFORMANCE BASED ANALYSIS

Page 51: Mondavi Center Life Safety Analysis - Cal Poly

51PERFORMANCE BASED ANALYSIS

(PPM)

CO Concentration at 1200s

Stage Floor

2nd Floor Balcony

Page 52: Mondavi Center Life Safety Analysis - Cal Poly

52PERFORMANCE BASED ANALYSIS

(°C)

Temperature at 1200s

Stage Floor

2nd Floor Balcony

Page 53: Mondavi Center Life Safety Analysis - Cal Poly

53PERFORMANCE BASED ANALYSIS

(m)

Visibility

Stage Floor

2nd Floor Balcony

750 s 800 s

415 s 445 s

Page 54: Mondavi Center Life Safety Analysis - Cal Poly

54

Stage Fire – Pathfinder Analysis

Last occupant enters exit at 404 seconds.

PERFORMANCE BASED ANALYSIS

Page 55: Mondavi Center Life Safety Analysis - Cal Poly

55

Stage Fire – Pathfinder Analysis

PERFORMANCE BASED ANALYSIS

Last occupant exits the space at 234 seconds.

Page 56: Mondavi Center Life Safety Analysis - Cal Poly

56

Stage Fire – ASET vs. RSET

PERFORMANCE BASED ANALYSIS

0 200 400 600 800 1000 1200

2nd Balcony

StageRequired

Available

LocationDetection

and Alarm

Pre-

movementMovement

CBC

FactorRSET ASET

Stage160 + 20 60

2341.5

711 750

Seating 404 966 415

Page 57: Mondavi Center Life Safety Analysis - Cal Poly

57

Recommendations

• Improve stage smoke detection

• Stage ceiling smoke detectors reduced activation time by about 50%

• Detection time reduced from 160 to 77 seconds

• Optimized travel time using Pathfinder:

• Optimized seating egress: 25% travel time reduction

• 1st Floor Balcony egress through atrium: 30% further travel time reduction

• Travel time reduced from 404 to 210 seconds

• Total RSET reduced from 966 to 550 seconds

• Do not use shell storage space as miscellaneous storage

PERFORMANCE BASED ANALYSIS

Page 58: Mondavi Center Life Safety Analysis - Cal Poly

58