13
MOL.19960716.0195 -CRWMS/M&O I Non-Q Design Analysis Cover Sheet Complete only applicable items. c;) I QA: N/A v I Page: 1 Of: 6 NORTH PORTAL - HOT WATER CIRCULATION PUMP CALCULATION - SHOP BUILDTNG #5006 3. DOCUMENT IDEflTIFIER (Including Rev. No.) Gc p& N/$ 5. TOTAL PAGES 4. REV. NO. BABBAD000-01717-0200-00144 Rev 01 Io1 6. TOTAL ATTACHMENTS 17. ATTACHMENT NUMBERS - NO. OF PAGES IN EACH 8. SYSTEM ELEMENT 9. Originator 10. Checker 11. Lead Design Engineer 12. Department Manager 13. Remarks II-5,11-2 Print Name R. Blackstone D.F. Vanica R.E. Flye G. N. Kimura I MGDS - Signature Date /a,?'#- 96 NAP.MG-013 [Effective 09/08/95) 0642 (Rev. 08/18/95)

MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

  • Upload
    vudiep

  • View
    215

  • Download
    1

Embed Size (px)

Citation preview

Page 1: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

MOL.19960716.0195

-CRWMS/M&O I Non-Q Design Analysis Cover Sheet

Complete only applicable items. c;) I QA: N/A v I Page: 1 Of: 6

NORTH PORTAL - HOT WATER CIRCULATION PUMP CALCULATION - SHOP BUILDTNG #5006 3. DOCUMENT IDEflTIFIER (Including Rev. No.)

G c p& N/$ 5. TOTAL PAGES 4. REV. NO.

BABBAD000-01717-0200-00144 Rev 01 Io1 6 . TOTAL ATTACHMENTS 17. ATTACHMENT NUMBERS - NO. OF PAGES IN EACH 8 . SYSTEM ELEMENT

9. Originator

10. Checker

11. Lead Design Engineer

12. Department Manager

13. Remarks

II-5,11-2 Print Name

R. Blackstone

D.F. Vanica

R.E. Flye

G. N. Kimura

I MGDS - Signature Date

/a,?'#- 96

NAP.MG-013 [Effective 09/08/95) 0642 (Rev. 08/18/95)

Page 2: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

CRWMS/M&O Design Analysis Revision Record

Complete only applicable items.

2. DESIGN ANALYSIS TITLE

NORTH PORTAL - HOT WATER CIRCULATION PUMP CALCULATION- SHOP BUILDING #5006 3. DOCUMENT IDENTIFIER (Including Rev. No.)

4. Revision No.

00 01

3200-00 144 REV 0 1

5. Description of Revision

Initial Issue Refonnatted per NAP-MG-013, Rev. 0 Removed Tl3V-122 Changed QA Classification from TBV to QA: NIA Revised calculations to include water film coefficient and pipe thermal conductivity Editorial Changes

Page 3: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

DI: BABBAD000-01717-0200-00144 REV 01 Title: North Portal - Hot Water Circulation Pump

Calculation - Shop Building #5006 Page: 3 of6

1. PURPOSE

The purpose of this design analysis and calculation is to size a circulating pump for the service hot water system in the Shop Building 5006, in accordance with the Uniform Plumbing Code (Section 4.4.1) and U.S. Department of Energy Order 6430.1A-1540 (Section 4.4.2).

2. QUALITY ASSU-RANCE

This arialysis is non-Q because it is for a temporary item. A Determination of Importance Evaluation (Reference 5.1) of the Shop Building has determined that no quality assurance (QA) controls are applicable within the context of this analysis.

3. METHOD

The method used for the calculation is based on Reference 5.2. This consists of determining the total heat transfer from the service hot water system piping to the surrounding environment. The heat transfer is then used to define the total pumping capacity based on a given temperature change in the circulating hot water as it flows through the closed loop piping system. The total pumping capacity is used to select a pump model from manufacturer's literature. This established the head generation for that capacity and particular pump model. The total length of all hot water supply and return piping including fittings is then estimated from the plumbing drawings which defines the pipe friction losses that must fit within the available pump head. Several iterations may be required before a pump can hie se!ei;ted that satisfies the head-capacity requirements.

4. DESIGN INPUTS

4.1 DESIGN PARAMETERS

Water temperature at most remote outlet = 110 degrees F

Ambient temperature = 70 degrees F

Velocity of flow = 5 feedsecond

Length of Pipe: '/2" = 126 feet (Attachment I) 3/4" = 80 feet

1 = 45 feet

(Reference 4.4)

(Reference 4.4)

(Reference 5.4)

(Reference 5.8) (Reference 5.8) (Reference 5.8)

I I

I I I

ni&o\analyses\bndl44.r0 1

Page 4: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

DI: BABBADOOO-01717-0200-00144 E V 01 I Title: North Portal - Hot Water Circulation Pump I

Calculation - Shop Building #5006 Page: 4 o f 6 I

I 4.2 I I I I I I 4.3 I I I I 4.4 I I I I I I I I I I I I

I I

I I 1 5.3 I I I 5.4 I I 5.5 I I I

I I 5.7 I I

I 5.1

I 5.2

I 5.6

CRTTERIA

The Plumbing Design for the Shop Building will be designed in accordance with DOE Order 6430.1A (Section 4.4.2) and appropriate state and local codes (ESF'DR Sections 3.2.1Q, 3.2. lR, and 3.2. lS, Reference 5.7).

ASSUMPTIONS

Not used.

CODES AND STANDARDS

4.4.1

4.4.2

International Association of Plumbing and Materials Officials:

UPC 1991

U.S. Department of Energy (DOE):

DOE Order 6430.1A-89

Uniform Plumbing Code (UPC)

General Design Criteria

5. REFERENCES

BABBA0000-0 17 17-2200-00007 Rev. 00 Determination of Importance Evaluation for ESF Change House Facility and Shop Building.

1991 American Society of Heating, Refi-igeration, and Air Conclitioning Engineers Handbook, HVAC Applications I-P Edition.

Michael R. Lindeburg, P.E., Mechanical Engineering Reference Manual, Eighth Edition, Professional Publications, Inc., 1990.

Crane Technical Paper No. 410, "Flow of Fluids," Crane Co., 1988.

American Society of Heating, Refrigeration, and Air Conditioning Engineers/Illuminating Engineering Society of North America Standard 90.lb, Energy Efficient Design of New Buildings Except New low-Rise Residential Buildings, 1992.

Mohinder L. Nayyar, P. E., Piping Handbook, Sixth Edition, McGraw-Hill.

Yucca Mountain Site Characterization Project Exploratory Studies Facility Design Requirements, YMP/CM-O019, REV. 1, ICN 3

m&o\ruialysa\bad 144.d 1

Page 5: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

I

i

DI: BABBADOOO-0 17 17-0200-00 144 REV 0 1 I Title: North Portal - Hot Water Circulation Pump $ 1

Calculation - Shop Building #5006 Page: 5 of6 I I

5.8 . Drawings:

5.8.1 BABBAD000-0 17 17-21 00-27400-00 Shop - Bldg 5006 Plumbing and Piping First Floor Plan

5.8.2 BABBADOOO-0 1717-2 100-2740 1-00 Shop - Bldg 5006 Plumbing and Piping Second Floor Plan

5.8.3

Grundfos Pumps Corporation Bulletin L-UP-TL-007, Dated 1/15/93

BABBADOOO-0 1717-2100-27402-00 Shop - Bldg 5006 Isometrics and Details

5.9

6. USE OF COMPUTER SOFTWARE

Not used.

7. DESIGN ANALYSIS

Th;: radial hest flow out of an insulated pipe can be expressed as follows:

4 = 2nLAT

where film coeficient, ha water = 150 (British thermal unit) BTWfeet2 - F (Reference 5.3)

(Reference 5.3)

(Reference 5.3)

(Reference 5.3)

(Derived)

(Reference 5.5)

(Reference 5.6)

h, still air = 1.65 BTWfeet2 - F

radius, ra pipe I.R. = 0.0327 feet

r,, pipe O.R. = 0.0364 feet

r,, insulation O.R. = 0.1 197 feet

thermal conductivity, k, insulation = 0.0233 BTWfee t - F

kpiF, pipe = 200 BTWfeet - F

m&ohalysesbad 144.d 1

. .

1

Page 6: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

\ ! DI: BABBAD000-0 17 17-0200-00144 FSN 0 1 I

Title: North Portal - Hot Water Circulation Pump 1 - Calculation - Shop Building #5006 Page: 6 o f 6 I

1

! length of pipe, L = 25 1 feet of 3/4 inch based on weighted average (Attachment I)

Substituting the appropriate design parameters in Equation (1) and solving for the heat loss through the insulated pipe, q = 1,119 BTUH.

The water flow rate in gaVmin to remove thk heat q is defined as:

Q = q/500 AT

where AT is the difference in temperature of the water leaving and returning to the water heater. The water flow limitation in piping systems is related to the velocity of flow and/or pressure drop which affects pumping costs. To minimize the erects of high velocities at AT in the hot water, return is limited to 1 degree which is reasonable for an insulated small diameter pipe line for service hot water. This results in a flow rate of 2.2 gallons per minute (gpm). From the UPC shown as Page 3 in Attachment I, the velocity of flow is 3 feedsecond and the friction loss is 4.5 psVlO0 feet pipe length if % inch diameter copper tubing is the minimum size used in the hot water return. However, as shown in Attachment I, the use of some '/2 inch tubing in the return results in a relatively high pressure drop. The minimum size tubing was increased to 3/4 inch which resulted in the selection of a

I circulating pump closely matching the required performance. I I I I

8. cmrcLusm1vS

I The hot water circulating pump performance requirements are approximately 7 gpm at a system head I of 5 feet. A Grundfos closed system pump Model UPS 15-42F (SFD 2) was selected as the design I basis for the hot water return in the Shop Building. The pump shown in Attachment 11 is rated at I 1/25 horsepower at 230 V. I I The minimum pipe size is 3/4 inch type L copper water tubing. The pipe is designed for a minimum I of 1 inch insulation for added energy conservation while maintaining a hot water return temperature I of 109 degrees F. I I I I

I I I

I ATTACHMENT

I I1

9. ATTACHIKENTS

TITLE

Calculations Grundfos Pump Data

m&ohnnlysesbadl44.10 1

Page 7: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

ATTACHMENT I DI: BABBAD000-01717-0200-00144 REV 01

Page: 1-1 of 5 Title: North Portal - Hot Water Circulation Pump

Calculation - Shop Building #5006 - - . "I .-

CALCULATTONS

m&o\ruialyses\bad 144.10 1

Page 8: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

ATTACHMENT1 I 1 DI: B ABBAD000-0 17 17-0200-00 144 REV 0 1

Title: North Portal - Hot Water Circulation Pump I r Calculation - Shop Building #5006

.. I CALCULATIONS (Continued)

. -

m&o\analyscs\badl44.rO 1

Page 9: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

DI: Title: North Portal - Hot Water Circulation Pump

ATTACHMENT I BABBAD000-0 1 7 17-0200-00 144 REV 0 1

Calculation - Shop Building #5006 Page: 1-3 of 5

CALCULATIONS (Con timed) (REFERENCE 5.4)

. I

m&o\anaiyses\bad 144.d 1

Page 10: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

ATTACHMENTI I I

Calculation - Shop Building #5006 Page: 1-4 of5 I

DI: B ABBAD000-0 17 17-0200-001 44 REV 0 1 Title: North Portal - Hot Water Circulation Pump I

CALCULATIONS (Con tin ued)

m&ohalyses\badl44.rO 1

Page 11: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

ATTACHMENT I DI: BABBAD000-01717-0200-00144 REV 01

Title: North Portal - Hot Water Circulation Pump Calculation - Shop Building #SO06 Page: 1-5 of 5

CALCULATIONS (Continued)

m&oh1dlyses\badl44.r0 1

Page 12: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

ATTACHMENT JI Dk BAE3BAD000-01717~-0200-00144 REV 01

I I I I Title: North Portal - Hot Water Circulation Pump

Calculation - Shop Building #5006 Page: II-1 of 2

m&o

GRUNDFOS PUMP DATA (REFERENCE 5.9)

. . . . . ,. < i .

Page 13: MOL.19960716.0195 -CRWMS/M&O I Non-Q Design …/67531/metadc873635/m2/1/high...Revised calculations to include water film coefficient and pipe thermal conductivity ... The method used

ATTACHMENT II DI: BABBADOOO-01717-0200-00144 REV 01

I Title: North Portal - Hot Water Circulation Pump Calculation - Shop Building #5006 Page: II-2of2 I

GRUNDFOS PUMP DATA (Continued)

. . . P e no m a n ce CLOSED System Models Cast iron contmdan - flange mount I . ,*hn

CLOSED System Models STAINLESS STEEL: inlet cone. bearing plate and beanng reta-iers. rotor can. ro(or cladding. shalt retainer. and impeller (UP26 L UP431 ALUMINUM: Stator housing. ALUMINUM OXlOE CSRAMIC: Shart and upoer and lower radial bearings METAL IMPREGNATED CAR80N: ThwSI beanng. CAST IRON: aurno nousing (volute). E? (Ethylene Prcpyiene Rubber): C-nng and gaskets. PES COMPOSITE. 30% Glass Filled: lmoetler (UPIS). Nary!": Terminal box.

I

,\laqi 3 IS a rrgerwea tracemark 01 General E1ec;x Company.

ALUMINUM: Volute retainer(SU L SF models) and statar housing. ALUMINUM OXlOE CERAMIC: ShaR md upper and lower radial beatings. METAL IMPREGNATE0 CARBON: Thrust bearing. E? (Ethylene Propylene 9ubber): %ring and gaskats. BFIONZE:Pumphousing(valute)lorUMlS-l085&87. UPlS-l885_ L. 37, uPi5-4285 L 87, UPZS-363F, UP26-998F. and UPd3-75ar. PES COMPOSITE. 30% Glass Filled: Impeller (UMlO & UPlS). NaryP: Terminal box.

7 1 G RU N DFOS GRUNOFOS Pumps Corp. .2555 C:ovis Ave. C!oVis. CA 93612 PmarEo IN USA

Suppon Canters: Allentown. PA Atlanta. GA I a ,

in&o\analyses\badl44.r0 1