MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL
FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT
GARY MESSENGER (626) 674-3478 EMAIL| [email protected]
FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM
Protected by US PATENT NO 9,163,450
626|674|3478
Waterproofing Systems
STEP 1: FUTURE FLASH SEALANT
APPLY A 1/2” BEAD OF FUTURE FLASH SEALANT AS SHOWN ON ISOMETRIC DRAWING PRIOR TO INSTALLING STEP #2, FUTURE FLASH SILL DIVERTER SHEETS.
FLASHING SYSTEM: METHOD #2.1 @ SILL STEP: 1FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL
STE
P 1
DATE: APR 2018 PAGE: 1 OF 6
SECURE BUTTERFLY TAPE WITH JT-21 STAPLES ADD BEAD OF FUTURE FLASH SEALANT
6”x 6” BUTTERFLY TAPE
MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL
FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT
GARY MESSENGER (626) 674-3478 EMAIL| [email protected]
FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM
Protected by US PATENT NO 9,163,450
626|674|3478
Waterproofing Systems
STEP 2: FUTURE FLASH - 40
RUN 12” 40mil. FUTURE FLASH DIVERTER SHEET ALONG ENTIRE LENGTH OF SILL. LENGTH OF SHEET SHOULD BE THE WIDTH OF RECESS PLUS 12” TO ALLOW FOR 6” OVERLAP ON BOTH SIDES.
NOTES: - SEE NOTE IN UPPER LEFTCORNER TO ENSURE UTILIZINGAPPROPRIATE MATERIAL WIDTH.
FLASHING SYSTEM: METHOD #2.1 @ SILL STEP: 2FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL
ATTACH WITH JT-21 STAPLES
STE
P 2
DATE: APR 2018 PAGE: 2 OF 6
FUTURE FLASH COMES IN 12", 18", 24" OR 36" WIDE ROLLS. USE WIDTH APPROPRIATE TO COVER H (HEIGHT) + S (SLOPE) + 6" min.
MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL
FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT
GARY MESSENGER (626) 674-3478 EMAIL| [email protected]
FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM
Protected by US PATENT NO 9,163,450
626|674|3478
Waterproofing Systems
STEP 3: FUTURE FLASH - 25
RUN 12” 25mil FUTURE FLASH DIVERTER SHEET ALONG RIGHT AND LEFT JAMB. MEASURE HEIGHT OF RECESS AND ADD 12” TO ALLOW FOR 6” OVERLAP ON EACH SIDE.
NOTE:
- MAKE SURE TO PRE-MEASURE
RECESS AND RISE TO ENSUREAPPROPRIATE MATERIALWIDTH.
FLASHING SYSTEM: METHOD #2.1 @ JAMBSTEP: 3 FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL
STE
P 3
DATE: APR 2018 PAGE: 3 OF 6
JT-21 STAPLES
PLACE STAPLES IN RETURN ON SILLTO HOLD UNTIL FUTURE FLASH SEALANT HAS CURED
MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL
FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT
GARY MESSENGER (626) 674-3478 EMAIL| [email protected]
FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM
Protected by US PATENT NO 9,163,450
626|674|3478
Waterproofing Systems
INS
TALL
WIN
DO
W
INSTALL WINDOW
AFTER STEP#3 AND BEFORE STEP #4 WINDOW IS INSTALLED. APPLY A 1/2” BEAD OF FUTURE FLASH SEALANT TO INSIDE FLANGE OF WINDOW. SET WINDOW IN OPENING, LEVEL WINDOW, AND FASTEN. APPLY ANOTHER 1/2” BEAD OF FUTURE FLASH SEALANT TO THE OUTSIDE FLANGE, TOOL SEALANT OVER OUTSIDE OF THE WINDOW FLANGE TO COVER ANY VOIDS BETWEEN WINDOW FLANGE AND FLASHING.
INSTALL WINDOW PER MANUFACTURER’S INSTRUCTIONS.
FLASHING SYSTEM: METHOD #2.1 STEP: BETWEEN STEP 3 AND 4FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL
DATE: APR 2018 PAGE: 4 OF 6
MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL
FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT
GARY MESSENGER (626) 674-3478 EMAIL| [email protected]
FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM
Protected by US PATENT NO 9,163,450
626|674|3478
Waterproofing Systems
STEP 4: FUTURE FLASH SEALANT
APPLY A 1/2” BEAD OF FUTURE FLASH SEALANT AS SHOWN IN THE ISOMETRIC PRIOR TO THE INSTALLATION OF STEP 5, FUTURE FLASH HEADER DIVERTER SHEET.
FLASHING SYSTEM: METHOD #2.1 @ HEADERSTEP: 4FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL
USE JT-21 STAPLE TO HOLD FLASHING IN PLACE WHILE SEALANT CURES
3”x3” BEAD OF FUTURE FLASH SEALANT
STE
P 4
DATE: APR 2018 PAGE: 5 OF 6
BEAD OF FUTURE FLASH SEALANT
MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL
FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT
GARY MESSENGER (626) 674-3478 EMAIL| [email protected]
FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM
Protected by US PATENT NO 9,163,450
626|674|3478
Waterproofing Systems
STEP 5: FUTURE FLASH - 25
RUN 12” 25mil FUTURE FLASH DIVERTER SHEET ALONG HEADER, OVERLAPING TOP OF NAIL FIN ON WINDOW. MEASURE 12” BEYOND OPENING TO ALLOW FOR 6” OVERLAY ON EACH SIDE.
PLACE STAPLE TO HOLD FLASHING IN PLACE UNTIL FUTURE FLASH SEALANT HAS CURED.
FLASHING SYSTEM: METHOD #2.1 @ HEADERSTEP: 5FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL
JT-21 STAPLES
STE
P 5
DATE: APR 2018 PAGE: 6 OF 6