Module 1.6Cables
1
Generation Side. Cabling.
Cables are an utmost critical component of every system, often overlooked.His correct selection, sizing and installation methods are key for the system performance.Cutting corners or being cheap on cables has dramatic financial impacts in the long term.
2
Generation Side. Cabling Sizing.
3
Generation Side. Cable Insulation.
4
Generation Side. Cable Color Code.
5
Generation Side. Cable Capacity.
6
Generation Side. Cable Loses.
Voltage Drop formula for Single Phase and DC Circuits.
VD = I × (2 × L × R / 1000)
Voltage Drop Calculation and formula for Three Phase system.
For 3 Phase 3 Wire system.VD = 0.866 × I × RVD = 0.866 × I × 2 × L× R/ 1000
For 3 Phase 4 Wire systems.VD = 0.5 × I × RVD = 0.5 × I × 2 × L× R/ 1000 Where,
VD = Voltage Drop in Volts.I = Wire Current in Amperes.R = Wire Resistance in Ohms (Ω) [Ω/km].L = wire distance in meters.