Modular cabinets XL³ 125

wor

ksho

p spe

cific

atio

ns

THE GLOBAL SPECIALIST in electrical and diGital buildinG inFrastructures

Page 2: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

22

SPECIfICATIOnS■■■ class ii insulated cabinet■■■ cabinet without door: iP 30-iK 08■■■ cabinet with optional door: iP 40-iK 09■■■ self-extinguishing: 650°c (cabinets supplied without ter-minal blocks) 750°c (cabinets supplied with terminal blocks)

■■■ conforming to current standards en 60439-3, en 60670-24, en 62208

■■■ colour of box and cover: white ral 9003 ■■■ rated operating and insulation voltage: 400 VA 50/60 Hz

■■■ short-circuit current: 10 ka ■■■ Maximum permissible current: - cat.no 4 016 11/52/53/76 = 63 a - cat.no 4 016 12/77 = 90 a - cat.no 4 016 13/14/78/79 = 125 a

Xl³ 125 cabinets are modular surface-mounting cabinets, with 1 to 4 rows of 18 modules, which can accommodate a distribution block up to 125 a.thanks to the tilting removable chassis and rails which can be taken out without tools, Xl³ 125 cabinets offer unobstructed access when connecting cables.

CHOICE Of PrOduCTSthe Xl³ 125 range consists of “fully modu-lar” cabinets with 1 to 4 rows of 18 modules as well as electrical boxes (for France only) which can take a main circuit-breaker on its own, or a circuit-breaker and a single-phase electrical energy meter.

Cabinets XL³ 125

“Fully Modular” Xl³ 125 cabinets

Xl³ 125 electrical boX

nuMber oF rows nuMber oF Modules

cabinet cat.no

supplied with terminal blocks

supplied without terminal blocks

“Modular” cabinets

1 18 4 016 11 4 016 762 36 (2 x 18) 4 016 12 4 016 773 54 (3 x 18) 4 016 13 4 016 784 72 (4 x 18) 4 016 14 4 016 79

Electrical boxes

1 incoming circuit-breaker only 4 016 52 -

1 incoming circuit-breaker + energy meter 4 016 53 -

Page 3: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

3workshop specificationsXL³ 125 cabinets

SCHEMATIC vIEw Of An XL³ 125 CABInET

dIMEnSIOnS

door Handle

Frame

Faceplates

backpiece

Modular chassis and rails

Marker-holder (only for cabinets supplied with terminal blocks)

identification strip

set of 4 plugs on a sprue

cable gland plates

Mosaic support

terminal block supports

earth terminal block(depending on the type of cabinet)

Guide ring

blanking plates

Vue de côtéavec porte

150CB

A

Entraxes de fixationet distance entre rails

260

150 B

Réf. coffret A(mm)

B(mm)

4016 11 300 2504016 12 450 3654016 13 600 5154016 14 750 6654016 50 300 2504016 51 300 250

cat.no a (mm) b (mm)c (mm)

without door with door4 016 11 4 016 76 300

450 128,2 1504 016 12 4 016 77 4504 016 13 4 016 78 6004 016 14 4 016 79 750

4 016 52/53 300

Page 4: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

4

PrEPArInG THE CABInETS fOr uSE

Xl³ 125 cabinets are supplied assembled and packed in individual boxes. these can be re-used for onward shipping.

we recommend using a 6.5 mm flat screwdriver to open and close the Xl³ 125 cabinets, and also for positioning the faceplates with a ¼ turn, for which 1 nm tightening torque is sufficient.

CapaCity of terminaL bLoCks suppLied with the Cabinets

aCCessories suppLied with the Cabinets

Xl³ 125 cabinets are supplied with an insulated earth terminal block (iP 2x), see specifications in the chart below.

CABInET CAT.nO

AuTOMATIC COnnECTIOn EArTH TErMInAL BLOCk IP 2X SCrEw TErMInAL BLOCkS

Automatic terminals

1.5 to 4 mm²

Screw terminals

6 to 25 mm²

Screw terminals

6 to 35 mm²Earth (green) neutral (blue)

4 016 11 18 (2 x 9) 5 - - -

4 016 12 27 (3 x 9) 5 - - -4 016 13 36 (4 x 9) 5 - - -4 016 14 45 (5 x 9) 5 5 - -

4 016 76 - - - 1 x 25 mm²+16 x 16 mm²

1 x 25 mm²+16 x 16 mm²

4 016 77 - - - 1 x 25 mm²+21 x 16 mm²

1 x 25 mm²+21 x 16 mm²

4 016 78 - - - 1 x 25 mm²+26 x 16 mm²

1 x 25 mm²+26 x 16 mm²

4 016 79 - - - 2 x 25 mm²+33 x 16 mm²

2 x 25 mm²+33 x 16 mm²

CABInET CAT.nO

5-MOduLE BLAnkInG

PLATESMOSAIC GrId GuIdE rInGS

SET Of 4 PLuGS On A

SPruE

18-MOduLE IdEnTIfICA-TIOn STrIPS

4 016 11 1 1 - 2 1

4 016 12 2 1 2 2 24 016 13 3 1 3 2 34 016 14 3 1 4 2 44 016 76 1 - - 2 14 016 77 2 - - 2 24 016 78 3 - - 2 34 016 79 3 - - 2 44 016 52 3 - - 2 14 016 53 1 - - 2 1

Page 5: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

5workshop specificationsXL³ 125 cabinets

doors – Cat.no 4 018 61/62/63/64/ 71/72/ 73/74the doors are reversible and come in transparent plastic or opaque white (ral 9003).

a snap connection system means the door is easily fitted without needing to hold it. For maximum safety, the grey handle (ral 7035) with two locking points can be fitted with a key-operated lock cat.no 4 018 51.

CABInET ACCESSOrIESJoining kit – Cat.no 4 018 45the joining kit is used to join two Xl³ 125 cabinets horizontally or vertically.

two cabinets of the same height or width can be joined together, and also cabinets of different heights. electrical boxes can be joined vertically, or horizontally on a taller cabinet.

key-operated LoCk – Cat.no 4 018 51the key-operated lock is fitted on the door handles of the Xl³ 125 cabinets. the keys are eurolocks no. 850.

fiXing Lugs – Cat.no 4 018 56this catalogue number comprises four lugs for fixing Xl³ 125 cabinets from the outside. the lugs are fixed at the back of the cabinets and can be positioned verti-cally or horizontally.the various fixing centres are specified on pages 11 and 12.

Page 6: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

6

doCument hoLder – Cat.no 4 018 44this self-adhesive document holder can hold electrical diagrams, instructions, etc for the cabinet. it is attached to the cabinet low down on the front, and does not obstruct use of a door. its reposition-ing system allows the document holder to be removed in order to open the face-plate, without touching the frame of the cabinet.

bLanking pLate – Cat.no 0 016 60in addition to those already supplied in the cabinets, blanking plates can be used to close the modular windows in the Xl³ 125 cabinet faceplates. each 5-module strip of blanking plates, white ral 9003, can be separated into half-modules.it is also possible to use separable blank-ing plates cat.no 0 016 62 and 0 016 64 of 13 and 18 modules respectively, white ral 9010.

soLid faCepLate – Cat.no 4 018 55the solid faceplate is fitted in place of a modular faceplate. it is used to integrate non-modular products (osMoZ control and signalling auxiliary, etc). the faceplate useful area is 318 x 144 mm.

perforated pLate – Cat.no 4 018 53the perforated plate is fixed in place of a modular rail, on the metal uprights of Xl³ 125 cabinets with 2 or more rows, using the four screws supplied. its useful area is 342 x 144 mm, and when the plate is fixed under a solid faceplate, the space is 85 mm.

doubLe terminaL bLoCk support – Cat.no 4 018 57this terminal block support is in addition to the one already supplied with Xl³ 125 cabi-nets. it allows terminal blocks to be added with the empty support cat.no 4 048 21.

the support can be removed simply by pressing its base on the inside, without any tools.

Page 7: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

7workshop specificationsXL³ 125 cabinets

mosaiC support – Cat.no 4 018 50this accessory is used for fixing a 2-mod-ule mechanism from the Mosaic range on one side of the Xl³ 125 cabinet.the cabinets have 2 slots at the top and bottom of each side panel.

uSInG THE CABInETremovabLe Chassis and raiLthe Xl³ 125 cabinet is simple to install on-site, in one easy action and without tools, thanks to the following 3 features:■■■ removable chassis:

by unlocking all 4 corners of the chassis, the whole chassis can be removed from the Xl3-125 cabinet. you can therefore install your equipment on a work surface or fix the back of the cabinet without risk-ing damaging the installed equipment.■■■ Pivoting chassis

the chassis can be tilted by unlocking just the bottom or top corners. this makes it easy to run cables through without the various rails and installed devices getting in the way.

■■■ removable railthe rails of Xl³ 125 cabinets can be removed from the chassis individually. the rail supports have clips so there is no need to use tools. this makes it easier to access the cables running behind the rails.

CabLe entry pLateXl³ 125 cabinets have two cable entry plates, one at the top and one at the bot-tom, which can be removed and refitted manually without the need for tools. each plate has a large number of cut-outs for adapting to the different sizes of housing service duct.cut-outs can be made in the plates using wire cutters.

Page 8: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

8

CabLe runsXl³ 125 cabinets have two removable cable entry plates, one at the top and one at the bottom. in line with these plates, the back of Xl³ 125 cabinets has attachment points for securing cables or sleeves using colson cable ties.

there are also attachment points between the rails for securing the wiring, horizon-tally or vertically.

First, open up the hole using a flat screw-driver.

the cables or sleeves are then secured using colring and colson cable ties (up to 9 mm wide).

tilting the chassis makes it easier to run cables behind the equipment. this can be done without tools and in either direction.

the chassis can be pulled out completely to make it easier to fix the cabinet in place, or to install and wire up equipment on a work surface.cables can also be run down the side of the chassis using the guide rings supplied with the cabinets or with lina 25 cable ducting.

Xl³ 125 cabinets can accommodate lina 25 cable ducting with maximum dimensions of 40 x 60 mm (cat.no 0 362 07).

Page 9: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

9workshop specificationsXL³ 125 cabinets

MOunTInG MOduLAr PrOduCTS And MOuLdEd CASESwith a space of 150 mm between the rail fixing centres, any modular product can be installed.

the 2-position rail allows a dPX³ Mccb to be integrated in Xl³ 125 cabinets.

with the height spacer cat.no 0 262 99, dPX³ 125 moulded case products and modular products can be installed on the same rail.

ELECTrICAL BOX ACCESSOrIES (for france only)electrical boxes take plates for main circuit-breakers used on the French market (eg: baco incoming circuit-break-er). they can be added to Xl³ 125 cabinets vertically or horizontally and are reversible.

electrical box cat.no 4 016 52 is used to connect a subscriber Mcb. this cabinet is supplied with plate cat.no 4 011 91, on which the 2-pole or 4-pole “blue tariff” circuit-breaker is fixed (government-regu-lated French electricity tariff).

electrical box cat.no 4 016 53 is used to connect a subscriber Mcb and a cbe or linKy single-phase electronic meter. this cabinet is supplied with plate cat.no 4 011 81, on which the “blue tariff” cir-cuit-breaker is fixed.

up to 4 modules can be added to this elec-trical box, on the modular rail.

Page 10: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

10

dISTrIBuTIOn SySTEMSall standard optimised distribution sys-tems with a cabinet size up to 125 a can be fitted in Xl³ 125 cabinets.

ip 2X insuLated terminaL bLoCksiP 2X insulated terminal blocks can be fixed directly on the rails of the Xl³ 125 cabinet, or on a 12 x 2 bar.

moduLar distribution bLoCks Modular distribution blocks: single-pole, 2-pole or 4-pole; with a voltage up to 500 V; 40 a to 125 a can easily be used in Xl³ 125 cabinets.

ConventionaL hX³ prong type suppLy busbars for sCrew terminaLsconventional HX³ busbars supply power to a row or a group of modular devices with screw terminals. only devices with 1 pole per module and without an add-on module can be connected to these busbars.

vX³ vertiCaL suppLy busbar phase + neutraL up to 63 asingle-phase 4-pole vertical supply bus-bars with 150 mm fixing centres are ideal for installation in Xl³ 125 cabinets. their optimised dimensions free up space for fast, reliable connection from one row to the next.

vX³ 4-poLe vertiCaL suppLy busbar up to 63 athe 4-pole supply busbar is equipped with automatic output terminals. distribution is possible via flexible wires, with or without ferrules. this busbar can be supplied with power via the top or bottom screw termi-nals. their dimensions and fixing system free up the maximum amount of space on the modular rails or at the back of the cabinet.

do not work on the 4-pole vertical supply busbar when it is live.

Page 11: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

11workshop specificationsXL³ 125 cabinets

XL³ 125 a b c d

1 row 4 016 11 260 250 250 1302 rows 4 016 12 260 365 365 1303 rows 4 016 13 260 515 515 1304 rows 4 016 14 260 665 665 130

“Blue tariff”4 016 52 260 250 250 130

4 016 53 260 250 250 130

XL³ 125 a b c d

1 row 4 016 11 406 355 505 2132 rows 4 016 12 406 505 505 3633 rows 4 016 13 406 655 505 5134 rows 4 016 14 406 805 505 663

“Blue tariff”4 016 52 406 355 505 213

4 016 53 406 355 505 213

A

B C

D

CA

BD

Cabinets only

Cabinets only with fixing lugs

InSTALLATIOn And fIXInGall Xl³ 125 cabinets have 2 fixing methods via the inside of the cabinet:- Fixing from a central point: this hanging method is used to obtain a vertical cabinet thanks to a single central point at the top and 2 points at the bottom - Fixing with 4 adjustable points For each fixing point, the maximum screw diameter is 6 mm.all cabinets are supplied with two sets of 4 plugs on a sprue. once the cabinet has been fixed to the wall, fitting these plugs maintains the cabinet iP and class ii pro-tection.

Page 12: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

12

Joined cabinets

Joined cabinets with fixing lugs

B

C

A D

A

B

XL³ 125 a b c d

All Cat.no 50 190 450 50

XL³ 125 a b

All Cat.no 44 87

Page 13: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed
Page 14: Modular cabinets XL³ 125 worKsHoP sPeciFications...Xl125 cabinets with 2 or more rows, ³ using the four screws supplied. its useful area is 342x144mm, and when the plate is fixed

eXb1

4055

- o

ctob

er 2

014

Head officeand international department87045 limoges cedex - Francetel: + 33 (0) 5 55 06 87 87Fax: + 33 (0) 5 55 06 74 55

foLLow us on

www.legrand.com

www.youtube.com/legrand

twitter.com/legrand_news