Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 776
Modelling and Testing of a Numerical Pilot Distance Relay for
Compensated Transmission Lines Mohammad M. Almomani*, Seba F. Algharaibeh**
*Electrical engineering department, engineering college, Mutah university, Jordan, Email:[email protected] *Electrical engineering department, engineering college, Mutah university, Jordan
Email: [email protected],[email protected] *Corresponding Author: [email protected] , Tel.: +00-962-796515220
----------------------------------------************************----------------------------------
Abstract: Flexible AC transmission system (FACTS) technologies are wildly used in the high voltage and
extra-high voltage AC transmission systems to control the power flow. The existence of FACTS devices in
the transmission lines makes a misoperation of the traditional distance relay. In this paper, a new special
pilot distance protection scheme is presented for any compensated transmission line. This scheme is valid
for any type of FACTS device (shunt, series, and compound) and different operation points (capacitive mode
or inductive mode). The proposed scheme is modeled and tested in MATLAB 2020a/Simulink. The model
includes a fault detection algorithm, phase selection, measured impedance, and five zones mho
characteristic. The proposed scheme includes two additional reversed zones with the three traditional zones.
The model is verified under deferent fault scenarios, including single-line to ground faults, double-line
faults, double-line to ground faults, and three-phase faults. The results show the model robustness for
different FACTS devices, including Static synchronous compensator (STATCOM), static synchronous
series compensator (SSSC), and unified power flow controller (UPFC) as examples on the shunt, series, and
compound FACTS devices respectively. All results show that the relay operates correctly under different
FACTD device locations, different types of faults, different types of FACTS devices, and different operation
points.
Keywords: FACTS device, Distance Relay, compensated transmission line, modeling, UPFC.
----------------------------------------************************--------------------------------
1. INTRODUCTION
Selectivity, sensitivity, and time of tripping are
the most important criteria in any protection
system. In the high voltage and ultra high voltage
transmission system, these criteria are more
important than other systems due to the stability
limitation in addition to its thermal capability. In
the modern interconnected power systems, the
FACTS devices are widely used to achieve optimal
load flow with minimum losses and maximum
loadability. The traditional distance relay will
operate incorrectly (under/overreach) for
compensated transmission lines due to the device
impedance.
Different researchers present the performance of
the distance relay in compensated transmission
lines [1-10]. The impact of different FACTS
devices including SSSC, STATCOM, and UPFC
on the apparent impedance by the distance relay is
discussed in [1]. The results show that the apparent
impedance of the fault is highly dependent on the
presence of the FACTS device, their type, and
control parameters setting. In [2], the impact of
delta connection MMC STATCOM on the distance
protection using hardware in the loop is presented.
In this study different operation points of the
STATCOM are not considered, so only the under-
reach problem is observed. From this study, the
Impact of STATCOM on distance relay in case of
http://www.ijsred.com/mailto:[email protected],[email protected]:Author:%[email protected]
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 777
external fault is less than in the case of an internal
fault. At the certain operation point (and control
parameter setting) the under reach problem is
observed higher in three-phase fault than single-
phase fault. The impact of shunt transmission line
capacitance on distance relay for SSSC
compensated transmission line in case of single-
phase fault is presented in [9]. The result shows
that the analysis of the apparent impedance is less
accurate when the shunt transmission line
capacitance is ignored. The effect of shunt
capacitance depends on the compensation level.
So, some under reach cases may be observed if a
fault is accrued in the first zone (if the shunt
capacitance is ignored) and overreach problem in
case of a fault occurs in second and third zones. In
summary, the traditional relay still not be able to
detect the zones boundary correctly in
compensated transmission lines. The modeling of
the traditional distance relay in
MATLAB/SIMULINK is proposed in [11-15]. In
[11], a three-zone mho characteristic is modeled in
MATLAB/Simulink. The results show that the
software (MATLAB) is capable of being used to
simulate any protection relays. Researchers in [12]
presented a model of three stepped zones mho
distance relay. The model is valid for different
types of faults and different locations. The basic
principles of a digital distance relay and some
related filtering techniques are described in [13].
Three zones mho type distance relay is
implemented using the SimPowerSystem toolbox
in MATLAB in [14]. In this research, the non-pilot
distance relay for the uncompensated transmission
line is modeled and tested for different fault types
and locations.
In this paper, a new pilot distance scheme is
proposed to increase the robustness of the distance
relay in a compensated transmission line.
Modeling of a digital distance relay is also
presented to validate the proposed scheme. The
structure of the paper is prepared as follows:
principle operation of the digital distance relay is
proposed in section II. Section III presents the
proposed scheme. Modeling and simulation of the
proposed scheme are shown in section IV.
Validation tests for different faults at different
locations for different types of FACTS
compensated lines are presented in section V.
2. PRINCIPLE OPERATION
A distance protective relay detects the fault
based on the measuring impedance between the
current transformer point and fault location. To
apply this simple concept, it is necessary to
identify seven loops to cover all types of faults. For
all loops the basic equation is used:
𝑍𝑚 =𝑉𝑚𝐼𝑚
(1)
The measured impedance (𝑍𝑚) is based on the measured voltage (𝑉𝑚) and current (𝐼𝑚). The relation between measured impedance in the
secondary side (of the current and voltage
transformers, CT and VT) and the actual
impedance is given by:
𝑍𝑚 = 𝑍𝐿 𝐶𝑇𝑟𝑎𝑡𝑖𝑜𝑛𝑉𝑇𝑟𝑎𝑡𝑖𝑜𝑛
(2)
Where 𝑍𝐿: the actual line impedance. The difference between the loops is the definition of the
measured voltage and the measured current,
𝑉𝑚 𝑎𝑛𝑑 𝐼𝑚. The table below shows the measured voltage and current, which are used in equation (1)
for the seven loops. TABLE I
MEASURED QUANTITY DEFINITION OF THE SEVEN LOOPS.
Fault loop Measured
voltage (𝑽𝒎) Measured
current (𝑰𝒎) A-G 𝑉𝐴 𝐼𝐴 + 𝐾0𝐼0 B-G 𝑉𝐵 𝐼𝐵 + 𝐾0𝐼0 C-G 𝑉𝐶 𝐼𝐶 + 𝐾0𝐼0 A-B / A-B-G 𝑉𝐴 − 𝑉𝐵 𝐼𝐴 − 𝐼𝐵 B-C / B-C-G 𝑉𝐵 − 𝑉𝐶 𝐼𝐵 − 𝐼𝐶 C-A / C-A-G 𝑉𝐶 − 𝑉𝐴 𝐼𝐶 − 𝐼𝐴 A-B-C 𝑉𝐴 𝑜𝑟 𝑉𝐵 𝑜𝑟 𝑉𝐶 𝐼𝐴 𝑜𝑟 𝐼𝐵 𝑜𝑟 𝐼𝐶
Where 𝐾0 = 𝑍0−𝑍1
𝑍1 , 𝑍0, 𝑍1: zero and positive
sequence impedance and 𝐼0 :zero sequence current. When a fault occurs on the line, fault with
impedance, the measured impedance is given by:
𝑍𝑚 = 𝑚 𝑍𝐿 + 𝑅𝑓
Where 𝑚 =𝐿𝑓
𝐿 , 𝐿𝑓: the distance between relay
point and fault location. L: total length of the
protected line. 𝑅𝑓: Fault resistance. The measured
impedance when a fault occurs is very less than the
measured impedance at normal load. Based on this
concept, the distance relay characteristic can be
implemented. To ensure the correct fault direction,
the first quarter of the R-X plane refers to the
forwarded fault, and the third quarter refers to
reverse fault location. MHO-characteristic is one
of the most common distance relay characteristics.
http://www.ijsred.com/
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 778
Figure (1) shows the traditional three-stepped
zones mho characteristic.
Z1
Z2Z3
R
X
θ
Fig. 1. three zones MHO characteristic
Zone (1) is the main protection to the line;
typically, it covers 80-85 % of the line and trips
instantaneously. Zone (2) and (3) are the backup
for the next station and the next line. These zones
are typically set to cover 120-150% and 180-220%
of the line, respectively. The time operation of the
second and third zones may set to 0.25-0.4s and
0.35-0.45s, respectively.
The existence of a series FACTS device (line
impedance compensator) on the transmission line
decreases/increases (based on its operation) the
measured impedance by the distance relay. For
example, if a series-FACTS device absorbs
reactive power, the measured impedance will be
greater than the actual impedance, and the relay
will operate under-reach. If the device delivers
reactive power, the measured impedance will be
less than the actual, and the relay will operate
overreach. In addition to that, the measured
impedance argument will change clockwise or
counterclockwise based on the operation point of
the device. For more details, the FACTS device
may be divided into:
Voltage regulators: change the magnitude of the
voltage at the sending end to control both real and
reactive power flows. e.g., STATCOM, SVC,
TCVR, SVS-based voltage regulator. These
controllers should have a shunt part to inject
current (so reactive power) to the system at a
controlled point. The shunt impedance, which is
parallel with the actual impedance, will
increase/decrease the measured impedance based
on its operation.
Line Impedance compensators: induce a
controlled capacitance or inductance in series with
the line. e.g: TCSC, SSSC. These devices should
have a series-part to inject voltage out of phase to
the line current by ±90⁰. So the measured
impedance and its angle may be greater than the
actual, or less than the actual.
Phase angle regulation (Phase shift): these types
of FACTS devices change the angle of voltage, and
the magnitude does not change. These devices
change the measured impedance argument only
positively or negatively.
Unified power flow controller (UPFC): this
special configuration may change all line
parameters to control both real and reactive power
independently. This configuration has series and
shunts VSC connected via a DC link (capacitor).
Based on the operation principle of the FACTS,
the mho characteristic is better than other
characteristics if the phase angle regulator is used.
Otherwise, all characteristics (MHO, quadratic …)
will be affected by the FACTS.
3. PROPOSED SCHEME
The proposed scheme is based on a pilot distance
relay to overcome the problem of under/overreach
of distance relay due to the FACTS device. The
proposed scheme uses a block comparison signal
(BCS) and trip communication channel:
permissive under/ over reach trip (PUTT/POTT)
and direct trip. Referring to figure (2) The
proposed scheme is summarized as follow:
RARB
FACTS
Communication channel
Fig. 2. single line diagram of the compensated transmission line protected
by a pilot distance relay.
If the FACTS device was installed at the end of
the line (behind relay RA)
BCS: if any relay (A or B) detects a fault in the
reverse region, it will send a block signal to the
other relay. If a relay receives a block signal, it
should deactivate its forward zones.
Trip scheme: if relay RB detects a fault in its
zone 1, it will send a direct trip to relay RA. If relay
RB detects a fault in its zone 2, it will send a
permissive trip to relay RA. If relay RA detects a
fault in its zone 1 or 2, it will send a permissive trip
to relay RB. Any relay receives a direct trip; it will
trip without any condition. Any relay receives a
http://www.ijsred.com/
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 779
permissive trip and feels the fault in its forward
direction; it will trip instantaneously.
If the FACTS device is installed at the middle of
the line:
BCS: same as the previous case.
Trip scheme: if any relay detects a fault in its
zone 1 or 2, it will send a permissive trip to the
other relay. If any relay receives a permissive trip
and feels the fault in its forward direction, it will
trip directly.
For both previous cases, two additional reverse
zones are needed to cover the traditional zone 2 and
zone 3. Figure 3 shows the additional zones. The
reach setting of the zone (R1) equal to the (Z2-ZL)
with tripping time equal to the traditional zone two
operation time. For zone (R2), the reach
impedance equal to (Z3-ZL) with tripping time
equal to the traditional zone three operation time.
Where Z2: reach impedance of the traditional zone
2. Z3: reach impedance of the traditional zone 3.
ZL: protected line impedance.
Fig. 3. Proposed impedance diagram
Modeling of the proposed scheme
In this section, modeling, simulation, and testing
of three zones of traditional distance relay and the
proposed scheme are presented. The model of the
distance relay consists of:
Pre-Processing Block: this block consist of a
low-frequency filter and phase-locked loop in
addition to a Fourier analyzer, which is needed to
get a fundamental signal of the measured voltage
and current.
Fault detection: detect the faulty phase during a
fault.
Phase selection: to select a faulty loop based on
fault detection technique.
Measured impedance: for a faulty loop, the
measured impedance can be calculated based on
table1.
The fault detection algorithm compares the
impedance for each phase with the impedance of
zone 3 with the margin factor. The mask
parameters and relay settings are seen in figure 5.
Figure 6 shows the faulty phase detection
algorithm. The loop selection technique (fault type
classification) is shown in figure 7. This algorithm
uses the Karnaugh-Maps technique [16]. One
faulty loop should be selected in this block (table
1).
The measured impedance block of loop A-G and
the trip algorithm block are shown in Figures 8 and
9. Figure 8 applied the equations in table 1. Each
faulty loop has its measured impedance block. The
proposed tripping characteristic, figure 3, is used
in figure 9. It can be easily seen in figure 9 all
tripping zones (Z1, Z2, Z3, R1, and R2). The
permissive receive signal is an effect on the
operation time of the second and third zones, it is
seen in the figure. Finlay from this figure, it can be
seen the block algorithm, when a fault is observed
in the reverse direction. The seven-loop blocks are
shown in figure 10. This model is tested for non-
compensated transmission lines at all fault types
and different locations in each zone and the edge
of each zone. The result in table 2 shows that the
relay works correctly in all zones for any type of
fault. Where Z1, Z2, and Z3 refer to zone 1, 2, and
3 operate respectively. N/O: not operate. The relay
setting is shown in figure 5.
Fig. 4. System understudy
http://www.ijsred.com/
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 780
Fig. 5. Parameter setting of the relay mask
Fig. 6. The faulty phase detection block
Fig. 7. Fault type classification
Fig. 8. Measured impedance block (A-G loop)
Fig. 9. Tripping algorithm block (loop A-G)
Fig. 10. Seven loops block diagram
Fig. 11. Measured impedance in zone one.
The measured impedance is drowned in the R-X
plan in Figure 11. This figure shows the measured
impedance in zone 1 without the FACTS device.
The effect of a FACTS device in the line may
increase or decrease the measured impedance by
the relay based on its operation. TABLE III
Test results of the proposed model
Fault
type
Fault Location
79% 80% 119% 120% 149% 150%
A-G Z1 Z2 Z2 Z3 Z3 N/O
B-G Z1 Z2 Z2 Z3 Z3 N/O
C-G Z1 Z2 Z2 Z3 Z3 N/O
A-B Z1 Z2 Z2 Z3 Z3 N/O
A-B-G Z1 Z2 Z2 Z3 Z3 N/O
B-C Z1 Z2 Z2 Z3 Z3 N/O
B-C-G Z1 Z2 Z2 Z3 Z3 N/O
C-A Z1 Z2 Z2 Z3 Z3 N/O
C-A-G Z1 Z2 Z2 Z3 Z3 N/O
A-B-C Z1 Z2 Z2 Z3 Z3 N/O
http://www.ijsred.com/
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 781
4. MODEL VALIDATION AND RESULTS
In this section, UPFC, SSSC, and STATCOM
are selected to validate the proposed scheme. Two
Different locations of the FACTS device are
studied; at the line end and in the middle of the line.
Figures 12 shows the single line diagram of the
first scenario. F1, F2, F3, F4, and F5 are different
fault locations. The relays RA and RB have the
same setting: zone 1 reach = 80 km, zone 2 reach
=120 km, zone 3 reach =150 km. zone 2 time
operation= 400ms Zone 3 time operation= 800ms.
For different fault types, this study is conducting
using traditional distance relay and proposed
schemes at different operation points of the
FACTS. Table 3 shows the power flow in two
different operation cases. Tables 4, 5, 6, and 7
show the results of different scenarios.
Tables 4 and 5 show the misoperation of the
traditional three zones mho characteristic relays
(yellow labels). All these misoperations are solved
by the proposed scheme (tables 5-6). The results
show that the proposed scheme can solve any
under/overreach in the relay for any FACTS
device. From tables 5 and 6, Z2P and Z3P are the
permissive zone 2 and 3 respectively. The trip time
of the permissive forward zones are instantaneous,
so it is similar to the first zone time operation. The
corrections in the proposed scheme, tables 5 and6,
are shown in the green label. Some of these
corrections are improved the traditional relay
operation for the uncompensated transmission
lines. This scheme can handle the faults with
resistance better than the traditional relays
RAFACTS RB
0
40
70
90
100
130
30
Distance (Km)
F1
F2 F3 F4
F5
Fig. 12. Single line diagram of the first scenario.
Table III power flow for two different operation points.
Case Operation point
Without FACTS S= 100 MW+ j 50 MVAR
UPFC case 1 S= 130 MW+ j25 MVAR
UPFC case 2 S= 80 MW+ j 75 MVAR
STATCOM case 1 Q= 25 MVAR
STATCOM case 2 Q= 75 MVAR
SSSC case 1 Injection voltage = +0.1 Pu
SSSC case 2 Injection voltage =-0.1 Pu
Table IV
Traditional Relay operation zones, operation point 1.
Fault location Fault
type
Without FACTS UPFC SSSC STATCOM
RA RB RA RB RA RB RA RB
F1(30km) A-G N/O Z3 N/O N/O N/O N/O N/O Z3
B-C N/O Z3 N/O N/O N/O N/O N/O Z3
A-C-G N/O Z3 N/O N/O N/O N/O N/O Z3
A-B-C N/O Z3 N/O N/O N/O N/O N/O Z3
F2(40 km) A-G Z1 Z1 N/O Z1 N/O Z1 Z1 Z1
B-C Z1 Z1 Z2 Z1 Z2 Z1 Z1 Z1
A-C-G Z1 Z1 Z2 Z1 Z2 Z1 Z1 Z1
A-B-C Z1 Z1 Z2 Z1 Z2 Z1 Z1 Z1
F3(70 km) A-G Z1 Z1 N/O Z1 N/O Z1 Z1 Z1
B-C Z1 Z1 Z3 Z1 Z3 Z1 Z1 Z1
A-C-G Z1 Z1 Z3 Z1 Z3 Z1 Z1 Z1
A-B-C Z1 Z1 Z2 Z1 Z3 Z1 Z1 Z1
F4(90km) A-G Z2 Z1 N/O Z1 N/O Z1 Z2 Z1
B-C Z2 Z1 Z3 Z1 Z3 Z1 Z2 Z1
A-C-G Z2 Z1 Z3 Z1 Z3 Z1 Z2 Z1
A-B-C Z2 Z1 Z3 Z1 Z3 Z1 Z2 Z1
F5(130km) A-G Z3 N/O N/O N/O N/O N/O Z3 N/O
B-C Z3 N/O N/O N/O N/O N/O Z3 N/O
A-C-G Z3 N/O N/O N/O N/O N/O Z3 N/O
A-B-C Z3 N/O N/O N/O N/O N/O Z3 N/O Table V
Traditional Relay operation zones, operation point 2.
Fault location Fault
type
Without FACTS UPFC SSSC STATCOM
RA RB RA RB RA RB RA RB
F1(-30km) A-G N/O Z3 N/O N/O N/O N/O N/O Z3
B-C N/O Z3 N/O N/O N/O N/O N/O Z3
A-C-G N/O Z3 N/O N/O N/O N/O N/O Z3
A-B-C N/O Z3 N/O N/O N/O N/O N/O Z3
F2(40 km) A-G Z1 Z1 Z3 Z1 Z2 Z1 Z1 Z1
http://www.ijsred.com/
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 782
Fault location Fault
type
Without FACTS UPFC SSSC STATCOM
RA RB RA RB RA RB RA RB
B-C Z1 Z1 Z2 Z1 Z3 Z1 Z1 Z1
A-C-G Z1 Z1 Z2 Z1 Z3 Z1 Z1 Z1
A-B-C Z1 Z1 Z2 Z1 Z3 Z1 Z1 Z1
F3(70 km) A-G Z1 Z1 Z3 Z1 Z2 Z1 Z1 Z1
B-C Z1 Z1 Z3 Z1 Z3 Z1 Z1 Z1
A-C-G Z1 Z1 Z3 Z1 Z3 Z1 Z1 Z1
A-B-C Z1 Z1 Z3 Z1 Z3 Z1 Z1 Z1
F4(90km) A-G Z2 Z1 Z3 Z1 Z3 Z1 Z2 Z1
B-C Z2 Z1 Z3 Z1 Z3 Z1 Z2 Z1
A-C-G Z2 Z1 Z3 Z1 Z3 Z1 Z2 Z1
A-B-C Z2 Z1 Z3 Z1 Z2 Z1 Z2 Z1
F5(130km) A-G Z3 N/O N/O N/O N/O N/O Z3 N/O
B-C Z3 N/O N/O N/O N/O N/O Z3 N/O
A-C-G Z3 N/O N/O N/O N/O N/O Z3 N/O
A-B-C Z3 N/O N/O N/O N/O N/O Z3 N/O Table VI
proposed scheme Relay operation zones. (operation point 1)
Fault location Fault
type
Without FACTS UPFC SSSC STATCOM
RA RB RA RB RA RB RA RB
F1(-30km) A-G R3 N/O R3 N/O R3 N/O R3 N/O
B-C R3 N/O R3 N/O R3 N/O R3 N/O
A-C-G R3 N/O R3 N/O R3 N/O R3 N/O
A-B-C R3 N/O R3 N/O R3 N/O R3 N/O
F2(40 km) A-G Z1 Z1 Z3P Z1 Z3P Z1 Z1 Z1
B-C Z1 Z1 Z2P Z1 Z2P Z1 Z1 Z1
A-C-G Z1 Z1 Z2P Z1 Z2P Z1 Z1 Z1
A-B-C Z1 Z1 Z2P Z1 Z2P Z1 Z1 Z1
F3(70 km) A-G Z1 Z1 Z2P Z1 Z2P Z1 Z1 Z1
B-C Z1 Z1 Z3P Z1 Z3P Z1 Z1 Z1
A-C-G Z1 Z1 Z3P Z1 Z3P Z1 Z1 Z1
A-B-C Z1 Z1 Z2P Z1 Z3P Z1 Z1 Z1
F4(90km) A-G Z2P Z1 Z3P Z1 Z3P Z1 Z2 Z1
B-C Z2P Z1 Z3P Z1 Z3P Z1 Z2 Z1
A-C-G Z2P Z1 Z3P Z1 Z3P Z1 Z2 Z1
A-B-C Z2P Z1 Z3P Z1 Z3P Z1 Z2 Z1
F5(130km) A-G N/O R3 N/O R3 N/O R3 N/O R3
B-C N/O R3 N/O R3 N/O R3 N/O R3
A-C-G N/O R3 N/O R3 N/O R3 N/O R3
A-B-C N/O R3 N/O R3 N/O R3 N/O R3 Table VII
proposed scheme Relay operation zones. (operation point 2)
Fault location Fault
type
Without FACTS UPFC SSSC STATCOM
RA RB RA RB RA RB RA RB
F1(-30km) A-G R3 N/O R3 N/O R3 N/O R3 N/O
B-C R3 N/O R3 N/O R3 N/O R3 N/O
A-C-G R3 N/O R3 N/O R3 N/O R3 N/O
A-B-C R3 N/O R3 N/O R3 N/O R3 N/O
F2(40 km) A-G Z1 Z1 Z3P Z1 Z2P Z1 Z1 Z1
B-C Z1 Z1 Z2P Z1 Z3P Z1 Z1 Z1
A-C-G Z1 Z1 Z2P Z1 Z3P Z1 Z1 Z1
A-B-C Z1 Z1 Z2P Z1 Z3P Z1 Z1 Z1
F3(70 km) A-G Z1 Z1 Z3P Z1 Z2P Z1 Z1 Z1
B-C Z1 Z1 Z3P Z1 Z3P Z1 Z1 Z1
A-C-G Z1 Z1 Z3P Z1 Z3P Z1 Z1 Z1
A-B-C Z1 Z1 Z3P Z1 Z3P Z1 Z1 Z1
F4(90km) A-G Z2P Z1 Z3P Z1 Z3P Z1 Z2P Z1
B-C Z2P Z1 Z3P Z1 Z3P Z1 Z2P Z1
A-C-G Z2P Z1 Z3P Z1 Z3P Z1 Z2P Z1
A-B-C Z2P Z1 Z3P Z1 Z2P Z1 Z2P Z1
F5(130km) A-G N/O R3 N/O R3 N/O R3 N/O R3
B-C N/O R3 N/O R3 N/O R3 N/O R3
A-C-G N/O R3 N/O R3 N/O R3 N/O R3
A-B-C N/O R3 N/O R3 N/O R3 N/O R3
http://www.ijsred.com/
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 783
(a) (b)
(c) (d)
(e) (f)
(g) (h)
(i) (j)
Fig. 13. The measured impedance at different locations (F1, F2, F3, F4, F5)
of the Double phase-to-ground fault which seen by relay A and relay B for
the non-compensated transmission line.
Figures 13-16 show the measured impedance of
different fault locations of the non-compensated,
UPFC compensated, SSSC compensated and
STATCOM compensated transmission line,
respectively. Figure 13 shows the measured
impedance by local (RA) and remote (RB) relays
for different fault locations of Double phase to
ground (A-C-G) fault. From the figures, it can be
seen that the correct operation of both A (left) and
B (right) relays at different fault locations based on
the measured impedance. This figure validates the
operation of the modeled distance relay for all five
zones faults.
(a) (b)
(c) (d)
(e) (f)
(g) (h)
(i) (j)
Fig. 14. The measured impedance at different locations (F1, F2, F3, F4, F5)
of Double phase fault seen by relay A and relay B for a UPFC-compensated
transmission line at operation point 1.
Figure 14 shows the measured impedance of the
UPFC- Compensated transmission line. Different
fault locations of double phase (B-C) fault are
presented. From this figure, the impact of the
UPFC on the measured impedance is seen in
subfigures b, c, e, g, i. Based on these subfigures,
we can observe some notes:
http://www.ijsred.com/
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 784
(a) (b)
(c) (d)
(e) (f)
(g) (h)
(i) (j)
Fig. 15. The measured impedance at different locations (F1, F2, F3, F4, F5) of Single phase to ground fault seen by relay A and relay B for an SSSC-
compensated transmission line at operation point 2.
o Relay A in 14-a and relay B in 14-i do not affect by the UPFC, because the location of
the relay is between the device and the fault.
So, we can observe that the UPFC doesn’t
impact the relay if it isn’t in the path of the
fault. Refer to this comment, if a fault
occurred between the relay and the UPFC,
the relay should not be affected, see
subfigures d, f, and h.
o The underreach problem is seen in 14-b and 14-i. in the first case relay, B didn’t feel the
fault in its zones due to the UPFC.
o Overreach problems with a significant change in the impedance angle are seen in
14-c, 14-e, and 14-g.
o The overreach problem and the underreach problem may be seen if the fault is near or far
from the relay location respectively. It is very
important to mention here that the relay may
not operate in the first zone while the
overreach problem in the measured
impedance is observed. That happens
because of the significant change in the
measured impedance makes it out of the first
zone. This note is not observed in the
previous tables 4-7. The same general
comments are observed in the second
scenario, UPFC in the middle of the line.
The SSSC-Compensated transmission line
measured impedance of single-phase to ground
faults at different locations is presented in figure
15. From the figure, we can observe some other
comments:
• The main problem in the SSC compensated transmission line is the underreach problem.
No overreach problem is observed.
• The SSSC impacts the measured impedance either if it is between the relay and the fault or
not. From a, d, f, and h, we can see that the pre-
fault impedance angle is changed.
Figure 16 shows the measured impedance at
different locations of three-phase fault in a
STATCOM-Compensated transmission line. From
the figure, we can say that the effect on the
STATCOM on the distance relay can be ignored.
This result is matched with the previous tables 4,5.
For this fault case (three-phase fault), no difference
can be observed between the STATCOM
compensated transmission line and the non-
compensated transmission line. For other faults,
single-phase, or double-phase faults, a small
difference can be observed, but still can be ignored.
The second scenario, STATCOM in the middle of
the transmission line, has small difference
observations, but these observations were not
affected on the relay operations.
http://www.ijsred.com/
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 785
(a) (b)
(c) (d)
(e) (f)
(g) (h)
(i) (j)
Fig. 16. The measured impedance at different locations (F1, F2, F3, F4, F5)
of the Three-phase fault seen by relay A and relay B for the STATCOM-
compensated transmission line at operation point 1.
The impact of the STATCOM compensated
transmission line on the distance operation is very
effected by the fault resistance. The effect of the
fault resistance on the other FACTS compensated
transmission line is less than the STATCOM.
The second scenario, FACTS in the middle, is
simulated for the three FACTS devices in both
operation cases. The same general comments are
observed in the second scenario. For the SSSC
compensated transmission line, an adaptive
directional relay block may be generated based on
the operation point of the FACTS device to
overcome the directional issue. This scheme is also
tested for different fault resistance at locations, the
results show that the proposed scheme is better
than the traditional for the non-compensated
transmission line also.
5. CONCLUSION
In this paper, the impact of FACTS devices
(UPFC, STATCOM, and SSSC) on the distance
relay operation is clarified. A lot of general
comments on the operation point of the FACTS
device is cleared. A new pilot distance scheme is
presented to overcome the problems of under or
overreach in the distance relay for the compensated
transmission line. The proposed scheme can be
used for non-compensated transmission lines also.
The problem of fault resistance should be covered
in this scheme. The modeling of a numerical
distance relay in MATLAB/ Simulink is presented
in this paper.
The model is tested for different types of fault at
different locations. The results show that the
MATLAB/ Simulink is a very good environment
to model different protective relays. In this project,
the relay is modeled in both the discrete mode
solver and the phasor model. Both modes give
good accuracy for the zones' reach. Different
FACTS devices (UPFC, STATCOM, and SSSC)
are considered as examples of FACTS devices.
The results show that the proposed scheme is a
comprehensive solution for the under/overreach
problems in distance relays. The proposed scheme
is tested for different FACTS- Compensated
transmission line. The problem of under/overreach
may occur for non-compensated transmission lines
in case of high resistance fault. This scheme is
primness for this case in addition to the
compensated transmission lines.
REFERENCES [1] Sadhu, Rajib, and P. S. Bhowmik. "Different Setting of Unified Power
Flow Controller (UPFC) and Its Effect on Performance of Distance
Relay." International Conference on Modelling and Simulation.
Springer, Cham, 2017. [2] Guan, Rui, Ying Xue, and Xiao-Ping Zhang. "Advanced RTDS-based
studies of the impact of STATCOM on feeder distance protection."
The Journal of Engineering 2018.15 (2018): 1038-1042.
http://www.ijsred.com/
International Journal of Scientific Research and Engineering Development-– Volume 3 Issue 6, 2020
Available at www.ijsred.com
ISSN : 2581-7175 ©IJSRED: All Rights are Reserved Page 786
[3] W.H. Zhang, S.J. Lee, M.S. Choi, S. Oda, Considerations on distance relay setting for a transmission line with STATCOM, in IEEE Power
and Energy Society General Meeting, July 2010 [4] K. El-Arroudi, G. Joos, D.T. McGillis, Operation of impedance
protection relays with the STATCOM. IEEE Trans. Power Delivery
17(2), 381–387 (2002) [5] T.S. Sidhu, R.K. Varma, P.K. Gangadharan, F.A. Albasri, G.R. Ortiz,
Performance of distance relays on shunt—FACTS compensated
transmission lines. IEEE Trans. Power Delivery 20(3), 1837–1845 (2005)
[6] F.A. Albasri, T.S. Sidhu, R.K. Varma, Performance comparison of distance protection schemes for shunt-FACTS compensated transmission lines. IEEE Trans. Power Delivery 22(4), 2116–2125
(2007)
[7] M. Khederzadeh, The impact of FACTS device on digital multifunctional protective relays, in Proceedings of IEEE/PES
Transmission and Distribution Conference and Exhibition 2002, vol.
3 (Asia Pacific, 2002), pp. 2043–2048 [8] A. Kazemi, S. Jamali, H. Shateri, Comparing impacts of SSSC and
STATCOM on measured impedance at relaying point, in IEEE Power
and Energy Society General Meeting, 2009
[9] H. Abdollahzadeh, B. Mozafari, A. Tavighi, J. Marti, Impact of shunt capacitance of an SSSCcompensated transmission line on the
performance of distance relays, in IEEE Power and Energy Society General Meeting, 2013
[10] M. Khederzadeh, A. Ghorbani, A. Salemnia, Impact of SSSC on the digital distance relaying, IEEE Power and Energy Society General
Meeting, 2009. [11] Lin, Ohn Zin, and Han Su Yin. "Modelling and Simulation of Mho
type Distance Relay for High Voltage Transmission Line Protection
Using MATLAB Software." JAREE (Journal on Advanced Research in Electrical Engineering) 3.2 (2019).
[12] Rai, J. N., Aquib Jahangir, and Ilam Hoque. "Digital simulation of distance relay for long transmission line." 2017 4th IEEE Uttar Pradesh Section International Conference on Electrical, Computer and
Electronics (UPCON). IEEE, 2017.
[13] Wu, Li-Cheng, Chih-Wen Liu, and Ching-Shan Chen. "Modeling and testing of a digital distance relay
MATLAB/SIMULINK." Proceedings of the 37th Annual North
American Power Symposium, 2005.. IEEE, 2005. [14] Mrehel, Omar G., Hassan B. Elfetori, and AbdAllah O. Hawal.
"Implementation and Evaluation a SIMULINK Model of a Distance
Relay in MATLAB/SIMULINK." SDIWC 132 (2013). [15] Rambabu, M., et al. "Three zone protection by using distance relays
in simulink/matlab." International Research Journal of Engineering
and Technology (IRJET) 2.05 (2015).
[16] Allan R. Hambley, Electrical Engineering Principles and Applications, 2nd ed. New Jersey, United States of America: prentice
http://www.ijsred.com/