AIR CONDITIONING NOTES
1bullshy AC CONTRACTOR SHALL
A) VERIFY All SPACE CONDillONS AND DIMENSIONS AT JOB SITE PRIOR THE CONSTRUCTION OF DUCTWORK AND INSTALlATION OF ANY EQUIPMENTS
B) COORDINATE ALL WORK WITH OTHER TRADES (REVIEW ALL PLANS)
C) DO All WORK IN ACCORDANCE WITH STATE AND LOCAL CODES
D) DO ALL WORK IN ACCORDANCE WITH LATEST ASHRAE GUIDE AND SMACNA STANDARDS COMPLY WITH ALL RECOMMENDATIONS AND INSTRUCTIONS OF SMACNA STANDARDS AND THE EQUIPMENTS MANUFACTURERS
E) ADJUST AND BALANCE DIFFUSERS IN ACCORDANCE WITH QUANTITIES SHOWN ON PLANS (LATESTS NAnONAL ENVIRONMENTAL BALANCING BUREAU PROCEDUAL STANDARDS OR AABC NAnONAL STANDARDS
F) SUBMIT SHOP DRAWINGS TO ENGINEER FOR APPROVAL
2- GUARANnEES
A) All NEW EQUIPMENTS PARTS AND MATERIALS SHALL BE GUARANnEED FOR ONE YEAR AFnER DATE OF ACCEPTANCE
B) PROVIDE 90 DAYS FREE SERVICE
3- TYPICAL AIR CONDITIONIND DUCTWORK (READ NOTES
A) SHALL BE CONSTRUCTED OF STANDARD DUTY FIBERGLASS BOARD FLAMEshy PROOF REINFORCED ALUMINUM FACED COVER IN ACCORDANCE WITH FBC AND NFIPA LATEST GUIDES AS MANUFACTURED BY OWENS-CORNING INSTALL AIR VOLUME EXTRACTORS TURNING VANES OR AIR SCOOPS AT EACH DUCT TAP FIBERGLASS DUCT BOARD R VALUE TO BE MINIMUM 42 AT COND SPACES AND 60 AT NON CONDillONED SPACES SUCH AS ATTICS
B) All DUCTWORK SHALL BE CONSTRUCTED AND ERECTED IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST nMA CONSTRUCTION STANDARDS AND AS PER FBC-CHAPTER 6 - SECTION 603
4- EXHAUST OR VENnLAnON DUCTWORK
A) SHALL BE CONSTRUCTED AS PER FBC-CHAPTER 5 FROM GALVANIZED SHEET METAL IN ACCORDANCE WITH ASHRAE AND SMACNA STANDARDS TERMINATED OUTSIDE THE BLDG AND EQUIPPED WITH A BACKDRAFT DAMPER (THERMOFIN ALLOWED)
B) CLOTHES EXH DRYER DUCT SHALL NOT BE SCREENED (4 MIN) 8c CONSTRUCTED OF A MIN 001 6 INCHES THICK OR 26 GAUGE METAL PIPE HAVING A SMOOTH INTERIOR SURFACE WI JOINTS IN THE DIRECTION OF THE AIR FILOW NO SCREWS OR FASnENERS EXnENDED INTO THE DUCTS AS PER FMCR-M15024 1
C) BATHROOM EXHAUST DUCTS TO BE CONSTRUCTED OF A MIN 30 GAUGE (GALVANIZED) OR 26 GAUGE (ALUMINUM AND DISCHARGE TO THE OUTSIDE OF THE BLDG SHALL BE TERMINATED NOT LESS THAN 6 ABOVE THE FINISHED ROOF SURFACE AND SHALL BE SCREENED WITH A CORROSION RESISTANT MATERIAL MESH SIZE NOT LARGER THAN 12 (GOOSENECK OR RAIN CAP ON ROOF TERMINAnON)
D) A UL CERTIFIED RESIDENTIAL RECIRCULAnNG KITCHEN EXHAUST HOOD SHALL BE INSTALLED AT KITCHEN
NOnE
AI IPERFORATED VENT CAP
12MIN UNION
SLOPE 18 FT f- AIC UNIT
ll I [ J I DRAIN PAN
314 MIN_ fshy fshy -shy
_3MIN
CONDENSATE DRAIN TRAP DETAIL
FLOAT SWITCH TO SHUT-DOWN EQUIP AS PER FMC 30113 (EZ-TRAP SERIES 200) INSTALLED INSIDE OF DRAIN PAN FBC R-M 1411311
REMOVABLE CAP
~C OVERFILOWI RAIN LINE
NTS
34 AC UNIT DRAIN PAN
DRAIN LINE
AUX OVERFLOW DRAIN LINE DETAIL NTS
STEEL CAGE WACCESS DOOR FOR SECURITY OF AC COMPRESSOR
I II COND UNIT TO BE AT OR ABOVE FLOOR
I I Ill
Ill UEVELf GALVANIZED
---------- bull middotmiddotmiddotLImiddotNE COVER CBS WALL
BOLT CONDENSING UNIT TO f- f middotSUPPORTS TO WITHSTAND _____ c-j 170 MPH HURRICANE ~ 1
FORCE WINOS AS PER I I L FcBcCcbull2010______ ---shy --+-11-tl
I II 12 MIN 4 CONCRETE PAO (SEE ELEVATION ON SITE PLAN)
FINISHED GRADE
NOTE
I
I
CONDENSING UNIT SHALL BE ANCHORED TO THE CONCRETE SLAB ON THE INSIDE OF THE UNIT WrlH (1) 12f SUP-R-STUD (4 12 MIN EMBEDMENT) PER EACH CORNER (1YPICAL)NOA 10-0928-01 EXP 03-03-2016 (SEE CALCULAnONS ATIACHED)
EFRIGERANT NES-
FINISHED FLOOR
TYPICAL CONDENSING UNIT MOUNTING DETAIL NTS
UNIT NUMBER QUANTITY AHU-1 I 1
MANUFACTURER PAYNE
MODEL PF4MNB037TOO E-o NOM TONS 25z
TOTAL CAPACITY SENSIBLE 288oo 1 2o6oo~
tl TOTAL CFM 1000
z S E E R 160
~ WEIGHT (LBS) 157 ~ z VOLTAGE 240-1-60
lt MOTOR TYPE X-13= FAN MOTOR HP I FLA 12 I 41
~ KW BTUH 8o Ilt HEATER 27304
ELECTRIC DATA MIN CIRC AMPACITY 485
MAX CIRC PROTECTION 50
UNIT NUMBER (QUANTITY) CU-1 I 1
E-o MANUFACTURER PAYNE MODEL PA16NA03000Gz
~ NOMINAL TONS 25
tl VOLTAGE 240-1-60
z WEIGHT (LBS) 171
rn COfIPRESSOR RLA LRA 128 I 64z rl CONDENSER FAN MOTOR 110 PSC ~ z FUSE OR HACR MINIMUM 168
0 BREAKER MAXIfIUM 25u REFRIG LINES LIQ I SUCT 38 I 34
REFRIGERANT R-41 OA (PURON
NOTE
REQUIRE PROGRAMfIABLE THERMOSTAT SEE ENERGY CALCULATIONS amp DRAWINGS REFRIGERANT LINES SHALL BE TYPE L SEAMLESS COPPER INSULATE SUCTION LINE WITH ARMAFLEX 34 bull ABOVE 50 USE MANUFACTURERS CAPACITY fIULnPLIERS AND BALANCE LINE SIZING INSTRUCTIONS TO SUBsnTUTE AND INSTALL ANY OTHER SIMILAR OR EQUAL AC SYSTEM DIFFERENT FROM THE ABOVE SHOWN CHECK amp MATCH CALCULAnONS SEER SENSIBLE COOLING CAPACITY AND All REQUIREMENTS AS PER CHAPTER 13 FBC
M1411 6 LOCKING ACCESS PORT CAPS REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS
PROVIDE PROGRAMMABLE THERMOSTAT TO THIS AHU (SEE ENERGY CALCULAnONS)
CLOSET CEILING BE AIRnGHT -----YI
FLEXIBLE SUPPLY DUCT
I I CEILING
PERFORATED CAP 12 ABV DRAIN PAN --~f-1
--PLENUM SHALL BE MECHANICALLY ATTACHED
AUX OVERFLOW LINE W FLOAT SWITCH(SEE DETAIL)
34 CD AND PIT TRii-shyWITH CO BY PLUMBER
ISOMODE PADS----shy
METAL SUPPORTS ---shy
12 HIN lUIDEflt TI-IAN I
--RU(II REFRIG IN AmC
SPACE TO COND UNIT
INSULATE WALLS R-1
2 PVC COND DRAIN LINE ~=====r--2CD DISCHARGE6ABOVE FINISH GRADE
TYPICAL AIR HANDLING UNIT MOUNTING DETAIL NTS
CONSTRUCT AND SEAL AC SYSTEIl COMPONENTS IN ACCORDANCE WITH FBC CHAPTER 13
CONDENSATE LINE UNDERGROUND TO BE 2 MINIMUM PVC SCHEDULE 40
141305 1 1 FURNACES AND AIR HANDLERS
FURNACES AND AIR HANDLERS WITHIN COMPARTMENTS OR ALCOVES SHALL HAVE A lliNIMUM WORKING SPACE CLEARANCE OF 4 INCHES (102 MM) ALONG THE SIDES BACK AND TOP WITH A TOTAL WIDTH OF THE ENCLOSING SPACE BEING AT LEAST 12 INCHES (305 MM) WIDER THAN THE FURNACE OR AIR HANDLER FURNACES HAVING A FIREBOX OPEN TO THE ATMOSPHERE SHALL HAVE AT LEAST A 6-INCH (152 MM) WORKING SPACE ALONG THE FRONT COMBUsnON CHAMBER SIDE COMBUsnON AIR OPEtliNGS AT THE REAR OR SIDE OF THE COMPARTMENT SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 17
DIFFUS WVP BUILT-IN
~DUCT (SEE PLAN VIEW)
----Srll JOINT WITH EPO)(Y AND DUCT TAPE
TYP FLEXIBLE DUCT CONNECTION DETAIL NTS
middot=1 12 HNIGER BND CLAMP WITH WIRE IS OPIIONAI
TYPICAL FLEXIBLE DUCT SUPPORT
ROOF STRUCTURE SEE ARCHITECTURAL
I 4-16d NAILS---7 THRU PLYWOOD
BACKDRAFT----~-~ DAMPER
DuCT FROM UNIT-Ill(SEE PLAN FOR SIZE 8c TYPE)
NTS
PROVIDE WP CAP LOW PROFILE BDD AT TOP PROVIDE CORROSION RESISTANT BIRO SCREEN FOR BATHROOM CAPS ONLY amp NO BIRD SCREEN FOR DRYER CAP
6 CLEAR FROM FINISH ROOF
TYPICAL ROOF CAP DETAIL DRYER ANDOR TOILET EXH
NTS
CLOTHES EXH DRYER DUCT SHALL NOT BE SCREENED (4 MIN) amp CONSTRUCTED OF A MIN OD16 INCHES THICIlt OR 26 GAUGE METAL PIPE HAVING A SMOOTH INTERIOR SURFACE W JOINTS IN THE DIRECTION OF THE AIR FILOW NO SCREWS OR FASnENERS EXnENDED INTO THE DUCTS AS PER FMCR-MI50241
BATHROOM EXHAUST DUCTS TO BE CONSTRUCTED OF A MIN 30 GAUGE (GALVANIZED) OR 26 GAUGE (ALUMINUM) AND DISCHARGE TO THE OUTSIDE OF THE BLDG SHALL BE TERMINATED NOT LESS THAN 6 ABOVE THE FINISHED ROOF SURFACE AND SHALL BE SCREENED WITH A CORROSION RESISTANT MATERIAL MESH SIZE NOT LARGER THAN 12
AC AREA ___1505 SQ FT
HVAC DESIGN REQUIRES YES NO
DUCT SMOKE DETECTOR FIRE DAfIPER(S) SMOKE DAMPER(S)
nRE RATED ENCLOSURE FIRE RATED ROOF CEILING ASSEMBLY FIRE SlOPING SMOKE CONTROL
FLORIDA BUILDING CODE SECTION 49014(C) EXCEPTON GROUP I ONLY
~ ~ gt ~ ~ = u if)
z lt ~
FAN NO
MANUFACTURER
MODEL
CFM
SP
RPM
VOLTAGE
AMPS WATTS
DRIVE
SERVICE
LOCAnON
SONES DUCT
ACCESSORIES
REMARK
GREAT ROOcf
2 UG CD UNE
10x8 3W-CG 175 CFM
EF - 1
GREEN HECK
SP - B50
50 CFIl
0125 bull
625
120 VOLTS
050 I 378
DIRECT
BATHROOMS
CEILING
14 I 4bull
ROOF WAILL CAP
ENERGY STAR QUALIFIED
8x6 1W-CG 75 CFM
ENTRf
VENnLAnON CALCULAnONS (CFM) REQUIRED PROVIDED
fIASTER BATH (TOILET RM) 50 CFfl 50 CFfl
BATHROOM (TOILET) 50 CFfl 50 CFfl
NOTES IT IS THE INTENT OF THESE PLANS TO PROVIDE A COIlPLETE OPERAnNG SYSTEM AC CONTRACTOR SHALL FURNISH AND INSTAll All REQUIRED EQUIPMENTS MATER~ ETC EXCEPT WHERE SPECIFICAIlY NOTED AS BEING FURNISHED BY OTHERS SHOULD THERE BE ANY QUESTIONS CONCERNING RESPONSIBILITY THEY SHALL BE SETTLED BEFORE BID SUBIliSSION AND CONTRACT SIGNINGshy NO EXTRA CHARGES WILL BE AllOWIED
WIC
I
I
I
I
__ _j
u p
--shy
riASTER BEDR001
1 UD (typfor
bedrooms)
10)~--[SJ I
~~ 12x12 RAG
b
I -- _ I
L _- -cJ
(
I ~
BEDROOc1 2
1 UD (typfor
bedrooms)
1 UD (typfor
bedrooms)
BATH middot
BEDROA-1 3
10x8 1W-CG 140 CFM
REF LINES IN AmC
l
---------shy -shy -----shy
REFRIGERANT SUCTION LINE LINES TO BE INSULATED WITH INSULATION HAVING A THERMAL RESisnVITY OF AT LEAST R-4 AND HAVING AN EXTERNAL PERMEANCE NOT EXCEEDING 005 PERM WHEN TESTED IN ACCORDANCE WITH ASTM E 96------------------------- l I I I I 1
Twa ARS 1
I GARAGE I
I I I I I I r I I I I 1-shy1 I I I
MEC~ANICAL PLAN 14bull1-IZgt
I
CONC SLAB
FeEVISIONS 6Y
bulllt[
bull ill cent- bull illo
lt[ -shy1ltJ) J)
0 Cl~
tshy middot-ill )QE- -o
OCu a~ u EX~
l ~middot-u u
t- w~ rJ)J 5 J)j
~ J) 6laquo)shy-shy ltll
~---~ ltObulloill-
d) Q bull JgtS- J)~
ol lt W--ll
bull t~ lt~lt[ QJcent~I ~lt0pound0a
JltIl(l
au ltfloill
Cl J)=llJ)Il
gt~ () Eoc-OJill
lt[lt( ClQ -~ () [)~
t- N
l) J)~ ~ll
0 0
w ()Zlshylt(Zzw Ll~ (911 lt(
z9 0
-w 0(f)gt 0
J=gtw lL
Oo gtshyI fshy
gt-gtshy z J
1-1shy 0 zz ()
0 gtgt 0 0~ ~ ()~ 0 oo 0
oo DO
0 ~~ w z Olt(s 0 0 (()
A-ll 0 0 0
A-ll f-w
A-ll lt(-wltt 00
~ - (f) C) 21l00
~ ~li IN
A oil DOZ Nw
C) I 1l()2fshy
11 0gt2 0 0 -o 0 w DO
T-115 DFALUING ANgt SFECIFIATIONS COTAINS PROPRE-A~Y 11-FO~_ATION
AND ARE TI-l= PRo=Rrr CF OCTAVIO A 5ANTURIO AIAFA AND MAY NOT eE REPRODUCED COPIED OR DISTRBUTED WITI-OUT TI-l EXPRESSED WRITTE1 FERYIamp5ION AND COMFENSA TICN OF OCTAVIO C_ SANT-RIO AlA_ =A
DRAWgt
JOflN D C-IECKED
OAS gtATE
JANUARY 2121 SCALE
AS SfIOWN JOB NO
IIZS
51-EET
AC-1 I OF 1 5fIEET5
--
----
--
PLUMBING LEGEND
WH WATER HEATER SOIL OR WASTE UNE
co CLIEANOUT ---- shy VENT LINE
~VISIONS BY
GENERAL PLUMBING NOTES
1 ALL WORK SHALL CONFORM WITH ALL LOCAL STATE FEDERAL ORDINANCES AND BUILDING CODES GOVERNING THE INSTALLATION OF THE PLUMBING SYSTEM IF WORK AS LAID OUT INDICAnED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH LOCAL ORDINANCES BUILDING CODES AND REGULATIONS THE CONTRACTOR SHALL REPORT IN WRITING TO THE ARCHITECTENGINEER BEFORE SUBMITTING A BID THE ARCHinECTENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED
2 THE DRAWINGS ARE TO BE CONSIDERED DIAGRAtAMATIC NOT NECESSARILY SHOWING IN DETAIL OR TO SCALE ALL OF THE MINOR ITEMS UNUESS SPECIFIC DIMENSIONS ARE SHOWN THE STRUCTURAL ARCHITECTURAL AND SITE CONDITIONS SHALL GOVERN THE EXACT LOCATIONS CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK CHECK DRAWINGS OF ALL TRADES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED AND MAINTAIN MAXItAUtA HEAD ROOM AND SPACE CONDITIONS AT ALL POINTS WHERE HEAD ROOM OR SPACE CONDITIONS APPEAR INADEQUAnE ARCHITECTENGINEER SHALL BE NOTIFIED BEFORE PROCEEDING WITH INSTALLATION THIS CONTRACTOR SHALL WITHOUT EXTRA CHARGE MAKE FIELD MODIFICATIONS IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF VARIOUS TRADES OR FOR PROPER EXECUTION OF THE WORK
3 EXAMINE ALL DRAWINGS CAREFULLY PRIOR TO SUBtAITTING A BID CONTRACTOR WILL BE REQUIRED TO FURNISH INSTALL ANDOR CONNECT WITH APPROPRIATE SERVICES ALL PLUMBING ITEtAS SHOWN ON ANY OF THE ARCHinECTURAL AIR CONDITIONING ELECTRICAL AND SPRINKLER DRAWINGS WITHOUT ADDITIONAL EXPENshySE TO THE OWNER IF DISCREPANCIES CONFLICTS INTERFERENCES OR OMISSIONS OCCUR BETWEEN DRAWINGS NOTIFY IN WRITING THE ARCHinECTENGINEER IN AMPLE TltAE TO PERMIT REVISIONS BEFORE THE BIDS ARE SUBMITTED
4 INSTALL MAnERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT OF ITEMS OF WHICH IN HIS OPINION DO NOT PRESENT A NEAT AND WORKMANLIKE APPEARANCE REMOVAL AND REPLACEMENT IS TO BE DONE IMMEDIAnELY WHEN DIRECTIED BY THE OWNER IN WRITING AT THE SOLE EXPENSE OF THE CONTRACTOR
5 START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER TRADES OR OTHER CONTRACTORS TO RECEIVE HIS WORK THIS CONTRACTshyTOR SHALL REtAOVE AND REPLACE AT HIS EXPENSE ALL PLUMBING WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCES WITH OTHER TRADES
6 THIS CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE FEES PERMITS ASSOCIATION DUES ROYALTIES AND TAXES OF WHATEVER NATURE SHALL APPLY TO THIS WORK HE SHALL ALSO PAY ALL INSPECTION FEES AS MAY BE REQUIRED BY LAW OR ORDINANCE AND SHALL KEEP THE OWNER HARMLESS FROM ANY DAMAGE AND EXPENSE ARISING FROM ANY VIOLATION OF THE LAWS RUUES OR ORDINANCES
7 PROVIDE MEANS FURNISHED AND INSTALL
8 DO A COMPLETE JOB EVERYTHING CONNECTIED READY FOR USE
9 SHOP DRAWINGS THIS CONTRACTOR SHALL FURNISH THE ENGINEER WITH SHOP DRAWINGS OF EQUIPMENT PRIOR TO PURCHASE FOR APPROVAL
1 0 AT COMPLIETION OF JOB THE PLUMBING CONTRACTOR SHALL GIVE THE OWNER AN AS-BUILT SET OF REPRODUCIBUE SEPIAS SHOWING THE EXACT INSTALLATION
11 PLUMBING CONTRACTOR SHALL PRESSURE nEST ALL PIPING AS REQUIRED BY CODE TEST SHALL BE WITNESSED AND APPROVED BY PROPER AUTHORITIES
12 THE PLUMBING CONTRACTOR SHALL WARRANT ALL WORKtAANSHIP AND MATERIALS FOR ONE YEAR FROM THE DAnE OF FINAL WORK ACCEPTANCE BY OWNER ANY BREAKDOWN OCCURRING IN FIRST YEAR SHALL BE REPAIRED AT NO EXPENSE TO THE OWNER
13 PLUMBING FIXTURES SPECIFICATIONS TO BE SUBMITTED BY ARCHinECT AT A LAnER DAnE
14 PROVIDE SHUT-OFF VALVE FOR EACH FIXTURE
1 5 WHEREVER DISSIMILAR METALS ARE TO JOINED A DI-ELECTRIC FITTING SHALL BE PROVIDED TO CONNECT BOTH TYPES OF PIPES
16 PLUMBING CONTRACTOR SHALL PROVIDE AIR CONDITIONING CONDENSATE DRAIN AND TRAP SEE AIR CONDITIONING PLANS FOR LOCATION OF UNITS AND DRAINS
17 MATERIALSmiddot
A COLD amp HOT WATER PIPING DOWNSTREAM OF WATER METER SHALL BE CPVC
B SANITARY WASTE AND VENT LINES SHALL BE PVC
C CONDENSAnE DRAIN PIPE SHALL BE INSULAnED PVC SCHEDULE 40
v VENT COLD WATER LINE
VTR VENT-THRU-ROOF --middot-- HOT WATER UNE
IAS-R BEDRCOI1
I I
( TUB
ll~~~I I =
(5 ru) JAll
rmiddot )ii1 k--
~
~ 2
Qr I
[--1 2cw ampCD CONDENSATE DRAIN 12HW ONw WASTE
cw COLD WATER 12 HB WVACUUM BREAKER -2 VENTamp VALVE ON RAISER+FCO FLUSH CLIEANOUT -M-- GATE VALVEFU FIXTURE UNITS _
RVD RELIEF VALVE DISCHARGE PIPING TURN DOWN
CD CONDENSATE DRAIN 0 PIPING TURN DOWN
---o PIPING TURN UPJl~ VTR (VENT THRU ROOF) -o- PIPING TURN UP
3 (5 FU)
rr~~~~~12 HB WVACUU~
~---------~ BREAKER amp VALVE I 0sectshyON RISER- 1 I I
I me II
EEDROOHl______ r ~
I -12CW DN plusmn== c
I I I I
- ALL SANITARY PIPING 2 OR LESS TO HAVE 14 MIN SLOPE
3 I I - ALL SANITARY PIPING 3 TO 6 TO HAVE 18 MIN SLOPE (5 FU)
- ALL SANITARY PIPING 8 OR LARGER TO HAVE 116 MIN SLOPE KITCI-Et~
-PROVIDE ANTI-SCALDING VALVE IIOF ON ALL TUBS AND SHOWERS
-PROVIDE SHUTOFF VALVE FOR EACH FIXTURE
- PROVIDE CLEAN OUTS AT EACH SOIL B WASTE STACKS
2VTR~W FOOD GRINDER
BEDROOMGREAT ROOcl S
bull ~ - nshy
bull nrshylt - shy-~ 0
11~
I shy middot-n Cl~E- LL~OOCo middot- 4 EXlaquogt
l middot-lL 0
t- w~ I Ill cpound)~
~ ~c- gt 0 r- Oui~
~---~ o ~ ol) middot shy
d) ~ ~s- oi s
w~bull I~ rlt1-
lt Ill ltI)--1 ~()pound01L gtltIll)
au ltI)bullol) bullbull
11 -= -~$it 0 E rt----~
ol)
ltlt 11~ ~(() ru~
tshy 0 -~
0-Ie
0 Q_
w 0Zlshylt(Zzw LL2 C) a
(sectz9 -w It(fJgt 0
__jJw lL
Oo ~I gt-gtshy z
J 1-1shy 0 zz ()
0JJ It 02 ~ 02 0 oo It
oO Ill
~~0 w z Olt(
s 0 0 Ill
jiijl 0 0 Itjiijl f--w
jiijl lt(()
tljJi
~ ()lt( (J)()(f)Ott
~ 0lt(ttU IN
A f-oeslt( lllZNw
0 -I (J)()f-shy0lt11 0
~ It
-o 0 w Ill ()
TI-llS D~AWINC AND SPECIFICATIONS CCNTAINS PROPRIETARY INFOR-JATION A~D A~ TI-lE =~OFE~TI OF OCTAVIO A 3ANTURIJ AIAPA AlD MAY OT BE R~f-ROP~CI~ COF-IP OFlt PIS-RI6UTED wr--lOUT TI-lE EXPRESSED WRnEN PERM ISS ON AND C01PEI-SATION CF OCTAVIO A SANTURIO AlA FA
FIXTURE CONNECTION SCHEDULE
ITEM cw CONN
HW CONN
TRAP SIZE
FU COUNT REMARKS
LAVATORY 12 12 1 14 1 BIDET 12 12 2 2 WATER CLOSET (TANK) 12 - 3 4 SHOWER 12 12 2 2 WANTI-SCALD ttiXING VALVE BATHTUB 12 12 2 2 WANTI-SCALD VALVE
BATH GROUP 5 FU
KITCHEN SINK 12 12 1 12 2
DISHWASHER - 12 1 12 2 WASHING MACHINE 12 12 2 2
HOSE BIB 12 - - - VACUUM BREAKER amp VALVE IN THE VERTICAL
6049 WAlER ]H_E FLOW VELOCITY OF THE WATER DISTRIBUTION SYSIDt SIWL BE CONTROLLED TO REDUCE ]HE middot laquo_WATER_ HAMMER A WATER-twIIER ARRESTOR SHALL BE INSTAllED WHERE QUICK-CLOSING VALVES ARE UTILIZED WAlER HAMMER ARRESTORS SHALL BE INSTAllED IN ACCORDANCE WITH THE IIANlFACTIJRERS SPECIFICATIONS WAlER HAMMER ARRESTORS SIWL CONFORM TO ASSE 1010
12 MIN 3 I
2 UG CD LINE ~~~I bull ~~~~~V~RADE 34 UG RVD LINE
bull 1~3H RVD Ill IE-__JII~ ~~L -pound_
TO OUTSIDE amp TERMINATE 6 ABOVE RNISH ~ ---~~ct~t~ V 1_1
middot~
GRADE 3 I )(14 FU)
-J 1 ------------------34CW---------------~THE DISCHARGE PIPE SHALL I 34CWNOT HAVE ANY TRAPPED
--------------------------lI 34 CW ON_VISIBLE AIR GAP OR AIR GAP SECTIONS AND SHALL HAVE A
I TO EWH tWo CARS I FITTING LOCATED IN THE SAME GARAGE ~
IROOM AS THE WATER HEATER MASTER WATER AS PER P2803_6 1_1 FB_C I SHUT-OFF VALVE
I- IN CONC BOXI
I I 1ishyI I - ~~~ ~~~2 WAY C~ I 34CW
TABLE P29032a FCO ~ AIMAXIMUM FLOW RATES AND CONSUMPTION FOR I ~--------------~ PLUMBING FIXTURES FIXTURES FITIINGS AND APPLIANCES I
PLU~tBING FIXTURE PLUMBING FIXTURE OR OR
FIXTURE FITIING FIXTURE FITIING
LAVATORY FAUCET 15 GPM AT 60 PSI
SHOWER HEADa 15 GPM AT 80 PSI
SINK FAUCET 15 GPM AT 60 PSI
WATER CLOSET 128 GALLONS PER FLUSHING CYCLE
DISHWASHER 65 GALLONS PER CYCLE OR LESS
WASH MACHINE WATER FACTOR OF 8 OR LOWER
I I I I I
I
3 (14 FU) 12 HB WVACUUM _J
I BREAKER amp VALVE ON RISER
~34CW I
1
3 (14 FU) -SANITARY LINE 34 WATER SERVICE CONNECTED CONNECTED TO SEWER MAIN SERVICE TO WATER METER BY UTILnY CO BEFORE INSTALLATION COORDINATE BEFORE INSTALLATION COORDINATE EXACT LOCATION AT FIELD EXACT LOCATION AT FIELD SEE SITE PLAN FOR CONTINUATION SEE SITE PLAN FOR CONTINUATION
I 7-12
-
I I I I I I
Ht-57-sectI I
~
__----PATI-t
I
-
I
I
F ~ iht
11_)CJ=---lt D I I
1-4 2-8 1-4
--
~~-======If
I
_j 1-b L 3-2 1-6 2-8
~ ___J~ 101 l~dmiddot(o~)~~- ()
I itgt ilr~n~ ~lt
~_
I l ~middot-e~middot
I
FOR 51 1 GAIlON PER MtiiTE = 3785 Lrn1 POUND PER SQUARE INCH = 6895 KPa
FIXTURE CLEARENCE FLAN FIXTURE CLEARENCE FLAN Vlt4bull14 a A HANDHELD SHOWER SPRAY IS AlSO A SHOWER HEAD b A CONSUMPilON TOLIRANCES SHAll BE DEIERMINED FROMMASTER 6ATHROOM 6ATH No2 REFERENCED STANDARDS c WATER FICTOR IN GAIIONS PER CYCLE PER CUBIC FOOT PLUMBING PLAN 14=1-IZ
ALL PLUMBING FIXTURE SHALL BE EPA WATER SENSE LABELED
DRAW
JOI-lN D I-IECKEr
OA5 DATE
JANUARY 2015 SCA_E
A5 51-lOWN )06 NO
1505
51-lEET
PL-1 I OF 2 51-lEET5
50 GAL ELECTRICAL
EWH
JJW
i til
o II ) o j middot~I
bullcwl [f-z i cWvmiddotlp
~VISIONS BY
I CW amp HWSERVICE RUN ABOVE CEILING SEE FLOOR PLAN FOR ROUTING
HEAT TRAPmiddot--- MINIMUM 3
DRAIN COCK
34
34
AIR GAP
RVD RISER
_ 34 RVD LINE TO OUTSIDE amp TERMINATE 6 ABOVE GRADE
WAlER HEAlER PIPING DETAIL NTS
WATER HEATER DATA
MARK STORAGE IN US GAL INPUT MANUFACTURER
MODEL No ELECTRICAL
DATA ENERGY
EFFICIENCY
EWH 50 45KW AOSMITH
PROMAX middot ECT-52 OR
EQUAL
24()1-lO 091
WATER HEATER TYPICAL WATER RISER DIAGRAM NT5
2 VTR
T I I jx~v SHUT-OFF VALVE -Jl_
12HB WVACUUM f-CW IN CONC BOXo
BREAKER amp VALVE 1J2 ON RISER
2 VTRgt 2
l----shy~-
34 WATER SERVICE CONNECTED~ bull shyTO WATER METER BY UTIUJY CO BEFORE INSTALLATION COORDINATE _
2EXACT LOCATION AT FIELD bull ( SEE SITE PLAN FOR CONTINUATION
---
3 (14 FU SANITARY LINE CONNECTED TO SEWER MAJN SERVICE BEFORE INSTALLATION COORDINATE EXACT LOCATION AT FIELD SEE SITE PLAN FOR CONTINUATION
TYPICAL SANITARY RISER DIAGRAM Nrs
2 VTR
Ill 1-ill_ I
I tmiddot I I - I-- 2 I I - I 2
II II
2 II I I I I
2
bull ~ onshy- bull onrshy
- 0lt shy-~ 0 I-
11~ middot-U Cl~E -lt) - LL~_ 0 EX d)OCo middot-lL 0l I Ill cpound)~t-- w~ ~c- gt 0 r- Oui~
~---~ ltOoo ~ 1f middot shy
~s ~
~d) oL s
w~bull I~ rlt1-
QJ lt --1 ~()pound01L gtell)
au ltI)bullU
11 -= -~ rt----~$it ) E
1f
~(() ru~ltlt 11~
t-- -~
0 )0 -lc
Q_
w 0Zlshylt(Zzw LL2 C) a
(sect -w z9
It 0(fJgt uJw _j
OoI ~ gt-gt- J
z 1-1- 0 zz ()
JJ 0 It
02 ~ 02 0 Itoo
oO Ill
0 w ~~ z Olt(
0s 0 Ill
0jiijl 0
jiijl It f-wlt(()jiijl tljJi()lt( (J)()(f)~ Ott 0lt(ttU~ IN
A f-oeslt( lllZ
0 NwI
(J)()
11 f shy0lt 0 It~ -o 0 w Ill ()
TI-llS D~AWINC AND SPECIFICATIONS CCNTAINS FROFRIETART INFOR-JATION A~D A~ TI-lE =~OFE~TI OF OCTAVIO A 3ANTURIJ AIAPA AlD MAY OT BE R~f-ROP~C~~ COF-IP OFlt PIS-RI6UTED wr--lOUT TI-lE EXFREOSED WRr-TEN FERMIS6 ON AND C01PEI-6ATION CF OTAVIO A OANTURIO AlA FA
DRAW
JOI-lN D I-IECKEr
OA5 DATE
JANUARY 2015 6CA_E
A5 51-lOWN )06 NO
1505
51-1EET
PL-2 2 OF 2 5HEET5
~VISIONS BY
GENERAL ELECTRICAL NOTES
1 ALL WORK SHALL CONFOR~ WITH ALL LOCAL STAlE FEDERAL ORDINANCES AND BUILDING CODES GOVERNING THE INSTALLATION OF THE ELECTRICAL SYSTE~ IF WORK AS LAID OUT INDICATED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH LOCAL ORDINANCES BUILDING CODES AND REGULAshyTIONS THE CONTRACTOR SHALL REPORT IN WRITING TO THE ARCHITECT ENGINEER BEFORE SUB~ITTING A BID THE ARCHITECTENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED
2 THE DRAWING ARE TO BE CONSIDERED DIAGRAMMATIC NOT NECESSARILY SHOWING IN DETAIL OR TO SCALE ALL OF THE ~INOR ITE~S UNLESS SPECIFIC DI~ENSIONS ARE SHOWN THE STRUCTURAL ARCHITECTURAL AND SITE CONDITIONS SHALL GOVERN THE EXACT LOCATIONS CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK CHECK DRAWINGS OF ALL TRAIDES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED AND ~AINTAIN MAXI~U~ HEAD ROO~ OR SPACE CONDITIONS AT ALL POINTS WHERE HEAlD ROO~ OR SPACE CONDITIONS APPEAR INADEQUATE ARCHITECTENGINEERSHALL BE NOTIFIED BEFORE PROCEEDING WITH INSTALLATION THIS CONTRACshyTOR SHALL WITHOUT EXTRA CHARGE MAKE FIELD MODIFICATION IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF VARIOUS TRADES OR FOR PROPER EXECUTION OF THE WORK
3 EXA~INE ALL DRAWINGS CAREFULLY PRIOR TO SUB~ITTING A BID CONTRACTOR WILL BE REQUIRED TO FURNISH INSTALL ANDOR CONNECT WITH APPROPRIATE SERVICES ALL ELECTRICAL ITEMS SHOWN ON ANY OF THE ARCHITECTURAL PLU~BING AIR CONDITIONING SPRINKLER DRAWINGS WITHOUT ADDITIONAL EXPENSE TO TIHE OWNER IF DISCREPANCIES CONFLICTS INTERFERENCES OR O~ISSIONS OCCUR BETWEEN DRAWINGS NOTIFY IN WRITING THE ARCHITECT ENGINEER IN AMPLE TI~E TO PER~IT REVISIONS BEFORE TIHE BIDS ARE SUB~ITlED
4 VERIFY SERVICE CHARACTERISTICS LOCATION AND CONNECTION WI1H TELEPHONE AND ELECTRIC UTIUTY CO~PANIES PERFOR~ ALL WORK RELATED TO SERVICE IN STRICT ACCORDANCE WITH UTIUTY Co STANDARDS AND REQUIRE~ENTS
5 INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEshyMENT OF ITEM WHICH IN HIS OPINION DO NOT PRESENT A NEAT AND WORKMANshyLIKE APPEARANCE RE~OVAL AND REPLACEMENT IS TO BE DONE ~~~EDIATELY WHEN DIRECTED BY THE OWNER IN WRITING AT THE SOLE EXPENSE OF CONTRACshyTOR
6 START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER TRADES OR OTHER CONTRACTIDRS TO RECEIVE HIS WORK THIS CONTRACTOR SHALL REMOVE AND REPLACE AT HIS EXPENSE ALL ELECTRICAL WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCE WITH OTHER TRAIDES
7 THIS CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE FEES PERMITS ASSOshyCIATION DUES ROYALTIES AND TAXES OF WIHATEVER NATURE SHALL APPLY TO THIS WORK HE SHALL ALSO PAY ALL INSPECTION FEES AS MAY BE REQUIRED BY LAW OR ORDINANCE AND SHALL KEEP THE OWNER HARMLESS FROM ANY DA~E AND EXPENSE ARISING FROM ANY VIOLATION OF THE LAWS RULES OR ORDINANCES
8 ALL WIRE COPPER IN RACEWAY UNLESS OTHERWISE SPECIFIED ON DRAWINGS
9 WIRE UP COMPLElE ALL THE AC EQUIPMENT AND CONTROLS AS DIRECTED BY AC CONTRACTOR CONTROL WIRING SHALL BE SEPARAlE RACEWAY FRO~ POWER WIRING
10 PROVIDE RACEWAYS AND PREWIRE TELEPHONE SYSTEM COMPLElELY WITH lELEshyPHONE JACKS
11 PROVIDE RACEWAYS AND PREWIRE CABLE TV SYSlEIA AS DIREClED BY CABLE TV Co FIELD REPRESENTATIVE
12 PROVIDE MEANS FIURNISH AND INSTALL
13 COORDINATE WORK WITH WORK OF OTHER TRADES TO AVOID ALL CONFLICTS
14 DO A COMPLElE JOB EVERYTHING CONNEClED READY FOR USE
15 PROVIDE TE~PORARY WIRING SYSTEM FOR USE OF ALL TRAIDES ADEQUATE FOR ENTIRE NEEDS OF THIS PROJECTS
16 PROVIDE PULL WIRES WHEN EMPTY CONDUITS ARE SHOWN ON TIHE PLANS
17 PROVIDE LIGHT FIXTURES AS PER OWNER SELECTION
18 PROVIDE ALL WIRING DEVICES
19 IDENTIFY CLEARLY ON A TYPE WRITlEN FOR~ ALL CIRCUITS AND EQUIP~ENT TO CORRESPOND WITH THE PLANS AND PANELS SCHEDULE AND ATIACH INSIDE THE PERTAINING PANEL
20 RACEWAYSmiddot ALL UNDERGROUND RACEWAYS TO BE PVC INSIDE CONCRETE SLAB EIAT WITH APPROVED SET SCREW FITIING INSIDE PARTITION EIAT ENT AND ROMEX WIRE WHERE ALLOWED FOR FLOOR PENETRATION USE ONLY EIAT
21 SHOP THIS CONTRACTOR SHALL FIURNISH THE ENGINEER WITH SHOP OF EQUIP~ENT PRIOR TO PURCHASE FOR APPROVAL
23 TESTINGmiddot THE CONTRACTOR SHALL TEST ALL WORK AND EQUIPMENT AS DIREClED BY TIHE ARCHITECT AND BY AUTHORITIES HAVING JURISDICTION FURNISHING ALL EQUIPMENT AND NECESSARY PERSONNEL AND ELECTRIC POWER THE ENTIRE INSTALLATION SHALL BE TESlED FOR SHORTS GROUNDS AND OPEN CIRCUITS AND ALL DEFECTS SHALL BE DEMONSTRATED TO BE IN PROPER WORKING AND OPERATING CONDITION TO THE COMPLElE SATISFACTION OF THE ENGINEER
24 GliARANJEESmiddot ALL EQUIP~ENT AND MATERIALS SHALL BE GUARANlEED FOR ONE YEAR AFTER THE DATE OF ACCEPTANCE BY OWNER
25 AT COMPLETION OF JOB THE ELECTRICAL CONTRACTOR SHALL GIVE THE OWNER AN AS-BUILT SET OF REPRODUCIBLE SEPIAS SHOWING THE EXACT ELECTRICAL INSTALLATION
26 BEFORE BIDDING THE JOB THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS
PNL AMPS VOLTAGE CKTS WIRE PHASE MAIN MOUNT MANUFACTURER TYPE
150 120240 3040 3 1 LUGS FLUSH SIEMENS OR EO LOAD CENTER
CKT No WIRE COND
INCH
CKT BKR SERVING CKT
No WIRE COND INCH
CKT BKR SERVING
POLE AMPS POLE AMPS
1 r- shy
3 6 34 2 50 RANGE
(12KW)
2 12 12 1 20 SMALL APPL
4 12 12 1 20 SMALL APPL
5
7 6 34 2 50 AHU + ST HTR
(10KW+80KW)
6 12 12 1 20 BATH RECEPT
a 14 12 1 15 BEDROOM CKT
9
11 8 34 2 30 AIR COND UNIT
(440 KW)
10 14 12 1 15 BEDROO~ CKT
BEDROOM CKT12 14 12 1 15
13 r- shy
15 10 12 2 30
TANK WATER HEATER
(45 KW)
14 14 12 1 15 LIGHTS amp RECEPT
16 14 12 1 15 LIGHTS amp RECEPT
17 r- shy
19 10 12 2 30 DRYER
18 14 12 1 15 LIGHTS amp RECEPT
20 14 12 1 15 LIGHTS amp RECEPT
21 12 12 1 20 WASHER 22 12 12 1 20 GARAGE OPENER
23 12 12 1 20 KITCHEN HOOD 24 - - - - SPACE
25 12 12 1 20 DISH WASHER 26 - - - - SPACE
27 12 12 1 20 GARB DISPOSAL 28 - - - - SPACE
29 12 12 1 20 REFRIGERATOR 30 - - - - SPACE
NEC TABLE 220-30 ~
1990 SO FT 0 3 WATTSSO FT --~-c=-c=--- 60 TWO 20 AMP SMALL APPL CKT 0 1500 WATTS EACH___ 30 RANGE 120 TANK WATER HEATER 45 DRYER 50 WASHER 15 REFRIGERATOR 0 7 DISH WASHER 12 GARBAGE DISPOSAL 07 MICROWAVE 10 GARAGE DOOR OPENER 0 7
TOTAL WITHOUT DEMAND 363
FIRST 100 KW 0 100------------100 NEXT 263 KW 0 40 106
AHU + STRIP HEATER (10 KW + 80 KW x 100) 90
TOTAL CONNEClED LOAD 296
WATTS TO AMPS (LINE) 29600 240V = 124 AMPS
FEEDER TIHWN CU 311 amp 16 CU (GND) IN 1 12 PVC OR
THWN AL 220 amp 110 amp 16 CU (GND) IN 12 PVC (NEC 31 0-15(B)(6)
HEATING LOAD LARGER THAN COOLING LOAD
16
16
GREAT ROOM
(DihINS AREt_l
2 18
18
18
8
WIC
ltITC~EN
s
------shy1
I
I
I
I
I
I
I
I
I
I
I I I I I I
I I I I I I I I I I I I I I
- shy--F
a
II
20
TWO CARS SARASE
C I
12
10
3ATH
BEDROCi 3
~dpound0
12
1
CU-1
NEMA 3R EUCTJIIICAI MAINA lEiER COMeiNATION
bull ~ nshy- bull nrshylt - shy-~ 0
11~
I shymiddot-1()
Cl~E- LL~OOCo middot- 4 EXlaquogt
l middot-lL 0I Illt- w~ cpound)~ ~c
~ - gt 0 r- Oui~
~ o ~ 1() _
~ ~sd) shy oL s
w~bull I~ rlt1-
lt Ill ltt ltI)--1 ~()pound01L gtltIll)
au ltI)bull1()
11 -= -~$it 0 E rt----~
1()
11~ltl-ct ~(() ru~
tshy
0 ~~ 0 ~c
0 Q_
w 0Zlshylt(Zzw LL2 C) a
(sectz9 -w It(fJgt 0
_jJw lL
Oo ~I gt-gtshy z
J 1-1shy 0 zz ()
0JJ It 02 ~ 02 0 oo It
oO Ill
~~0 w z Olt(
s 0 0 Ill
jiijl 0 0 Itjiijl f--w
jiijl lt(()
tljJi
~ ()lt( (J)()(f)Ott
~ 0lt(ttU IN
A f-oeslt( lllZNw
0 I (J)()f-shy0lt11 0
~ It
-o 0 w Ill ()
TI-llS D~AWINC AND SPECIFICATIONS CCNTAINS PROPRIETARY INFOR-JATION A~D A~ TI-lE =~OFE~TI OF OCTAVIO A 3ANTURIJ AIAPA AlD MAY OT BE R~f-ROP~CI~ COF-IP OFlt PIS-RI6UTED wr--lOUT TI-lE EXPRESSED WRnEN PERM ISS ON AND C01PEI-SATION CF OCTAVIO A SANTURIO AlA FA
r- shy
r- shy
NOTES
BEFORE INSTALLATION THE ELECTRICAL CONTRACTOR SHALL VERIFY THE SIZE OF CKT BKR AND FEEDER WlTH THE AIC MANUFACTURERS REQUIREMENTS AND SHALL BE IN COMPLIANCE WITH NEG 424-3 440-22 AND 440-32
ALL 15A AND 20A BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT IN FAMILY ROOMS DINING ROOMS LIVING ROOMS PARLORS LIBRARIES DENS SUN ROOMS RECREATION ROOMS CLOSETS HALLWAYS OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED ARC FAULT CIRCUIT INTERRUPTER DEVICE OF THE COMBINATION TYPE AS REQUIRED BY NEC 210-12fBi
ALL 15A AND 20A RECEPTACLES IN AREAS SPECIFIED IN NEC 21052 SHALL BE LISTED AS TAMPER RESISTANT RECEPTACLES AS REQUIRED BY NEG 40611
THE ELECTRICAL PANEL CONNECTIONS MUST BE UL LISTED FOR 60f75 CONDUCTORS IN COMPLIANCE WITH NEC 110-14(c) THE TEMPERATURE RATING ASSOCIATED WITH THE AMPACITY OF A CONDUCTOR SHALL BE SELECTED AND COORDINATED SO AS NOT TO EXCEED THE LOWEST TEMPERATURE RATING OF ANY CONNECTED TERMINATION CONDUCTOR OR DEVICE
ELECTRICAL RISER DIAGRAM NTS
THWN CU 3(11 amp 1 6 CU (GND) IN 1 12 PVC
OR THWN AL 2120 amp 11110 amp ELECT NEMA 3R
16 CU (GND) IN 1 12 PVC PANEL i 0 ELECTRICAL INSIDE MAINMElER HOUSE COMBINATION
I 4 cu NEMA 3R 2POLE 240V 150A MAIN BKR 22000 AIC
~ 34CW PIPE ~ TO COMPLY W 25094
(
GROUND TO BLDG STEEL REINFORCING BAR W~4 BARE CU CONDUCTO
(1) 10-0L x 58t -==shy GROUND ROD --
r-
2 PVC TO FPL SERVICE ENTRANCE r COORDINATE EXACT LOCTAION WITH
FPL REPRESENTATIVE
ELECTRICAL LEGEND THE USE OF ROMEX TYPE WIRE IS ACCEPTABLE IF IT IS IN COMPLIANCE120V HALF SWITCHED DUPLEX RECEPTACLE~ 0 4-amiddot CEILING SURFACE MOUNlED FLOURECENT LIGHT FIXTURE WITH NEC TABLE 310-16 FOR 60C
120V DUPLEX RECEPTACLE BATHROOM RECIRCULATING FANreg -e 120V SINGLE RECEPTACLE 120V ACBATIERY OPERATED CEILING MOUNTED SMOKE DETECTOR INTERCONNECTIED WITH OTHER SMOKE DIETECTORS INSIDE THE HOUSE
120V GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE FOR SIMULTANEOUS OPERATION SMOKE DETECTORS SHALL BE ALARM NOTE LOCATED 36 AWAY FROM ANY AC DIFFUSER AND FROM BATH AND ALARM SYSTEM BY ALARM CONTRACTOR KITCHEN DOORS SMOKE DETECTbRS SHALL BE PHOTO-ELECTRIC UNDER SEPARATE PERMIT 120V ABOVE COUNTER GROUND FAULT INTERRUPTER~ TYPE IF IT IS LOCATED WI1HIN 20 FROM KITCHEN APPL
DUPLEX RECEPTACLE
120V ACBATIERY OPERATED CEILING MOUNTED SMOKE AND- 240V 30A DRYER RECEPTACLE CARBON ~ONOXIDE DElECTOR INTERCONNEClED WITH OTHER S~OKE amp CARBON MONOXIDE DETECTORS INSIDE THE HOUSE FOR240V 50A RANGE RECEPTACLE-reg SIMULTANEOUS OPERATION SMOKE amp CARBON ~ONOXIDE DElECTORS SHALL BE LOCATED 36 AWAY FROM ANY AC 98-30472 CARBON MONOXIDE PROTECTIONLn TOGGLE SWITCH DIFFUSER AND FROM BATH AND KITCHEN DOORS S~dKE amp CARBON ~ONOXIDE DElECTORS SHALL BE PHOTO-ELECTRIC TYPE (1) DEFINITIONS FOR PURPOSES OF THIS RULE THE FOLLOWING DEFINITIONS~ 3 WAY TOGGLE SWITCH IF IT IS LOCATED WITHIN 20 FRO~ KITCHEN APPL SHALL APPLY
SERVICE LOCATION MUST BE AIPPROVED BY UTILITY CO
(a) CARBON MONOXIDE ALARM A DEVICE FOR THE PURPOSE OFGROUND FAULT INlERRUPTER GARAGE DOOR CONTROLLERTELEPHONE OUTLET DElECTING CARBON MONOXIp~ THAT PRODUCES A DISTINCT AUDIBLE ALAR~ AND IS LISTED OR LAt1ELED WI1H THE APPROPRLTE ~ TV OUTLET
JUNCTION BOX
STANDARD EITHER ANSIUL 2034-96 STANDARD FOR SINGLE ANDDOOR CHIME
0 MULTIPLE STATION CO ALARMS INCORPORATED HEREIN BY REFERENCE OR UL 2075-04 GAS AND VAPOR DIETECTOR SENSOR INCORPORATEDCEILING MOUNTED LIGHT FIXTURE HERE IN BY REFERENCE IN ACCORDANCE WITH ITS APPLICATIONPUSH BUTTON (b) FOSSIL FUEL COAL KEROSENE OIL FIUEL GASES OR OTHER ALL LIGHTING amp APPLIANCESI() WALL MOUNlED OUTLET PETROLEUM OR HYDROCARBON PRODUCT THAT EMITS CARBON ELECTRICAL PLAN MONOXIDE AS A BY- PRODUCT OF COMBUSTION SHALL BE ENERGY STAR LABELED DISCONNECT SWITCH NEMA 3RIQ) WALL MOUNTED JUNCTION BOX 14=1-IZ(2) EVERY BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
INSIDE AHU FACTORY MOUNTED CIRCUIT BREAKER ISSUED ON OR AFTER 7 1 I 06 AND HAVING A FOSSIL-FIUEL BURNINGCEILING MOUNlED JUNCTION BOX WITH SPECIAL HEATER OR APPLIANCE A FIREPLACE OR AN ATIACHED GARAGE SHALL0 SUPPORT FOR CHANDELIER OR LIGHTFAN COMBINATION HAVE AN OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WI1HIN 10ELECTRICAL PANEL FEET OF EACH ROOM USED FOR SLEEPING PURPOSES
SECTION 404 ELECTRICAL POWER AND LIGHTING VAPOR PROOF CEILING LIGHT FIXTURE LIGHTOVP D (3) IN NEW CONSTRUCTION ALARMS SHALL RECEIVE THEIR PRIMARY POWER SYSTEMS
I I ELECTRICAL METERMAIN COMBINATION FROM THE BUILDING WIRING WHEN SUCH WIRING IS SERVED FRO~ THE LOCAL POWER UTILITY SUCH ALARMS SHALL HAVE BATIERY BACK UP
WEATHER PROOF 4041 LIGHTING EQUIPMENT
PADDLE CEILING FAN WITH LIGHT FIXTURE A MINIMUM OF 50 PERCENT OF THE LAMPS IN (4) COMBINATION SMOKECARBON MONOXIDE ALARMS SHALL BE LISTED ORMOTION DETECTOR OUTDOOR LIGHT FIXTURE LABELED BY A NATidNALLY RECOGNIZED TESTING LABORATORY PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS
DRAW
JOI-lN D HECKEr
OA5 DATE
JANUARY 2015 SCA_E
A5 51-lOWN )06 NO
1505
51-1EET
E = 1
I OF I 51-lEET5
--
----
--
PLUMBING LEGEND
WH WATER HEATER SOIL OR WASTE UNE
co CLIEANOUT ---- shy VENT LINE
~VISIONS BY
GENERAL PLUMBING NOTES
1 ALL WORK SHALL CONFORM WITH ALL LOCAL STATE FEDERAL ORDINANCES AND BUILDING CODES GOVERNING THE INSTALLATION OF THE PLUMBING SYSTEM IF WORK AS LAID OUT INDICAnED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH LOCAL ORDINANCES BUILDING CODES AND REGULATIONS THE CONTRACTOR SHALL REPORT IN WRITING TO THE ARCHITECTENGINEER BEFORE SUBMITTING A BID THE ARCHinECTENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED
2 THE DRAWINGS ARE TO BE CONSIDERED DIAGRAtAMATIC NOT NECESSARILY SHOWING IN DETAIL OR TO SCALE ALL OF THE MINOR ITEMS UNUESS SPECIFIC DIMENSIONS ARE SHOWN THE STRUCTURAL ARCHITECTURAL AND SITE CONDITIONS SHALL GOVERN THE EXACT LOCATIONS CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK CHECK DRAWINGS OF ALL TRADES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED AND MAINTAIN MAXItAUtA HEAD ROOM AND SPACE CONDITIONS AT ALL POINTS WHERE HEAD ROOM OR SPACE CONDITIONS APPEAR INADEQUAnE ARCHITECTENGINEER SHALL BE NOTIFIED BEFORE PROCEEDING WITH INSTALLATION THIS CONTRACTOR SHALL WITHOUT EXTRA CHARGE MAKE FIELD MODIFICATIONS IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF VARIOUS TRADES OR FOR PROPER EXECUTION OF THE WORK
3 EXAMINE ALL DRAWINGS CAREFULLY PRIOR TO SUBtAITTING A BID CONTRACTOR WILL BE REQUIRED TO FURNISH INSTALL ANDOR CONNECT WITH APPROPRIATE SERVICES ALL PLUMBING ITEtAS SHOWN ON ANY OF THE ARCHinECTURAL AIR CONDITIONING ELECTRICAL AND SPRINKLER DRAWINGS WITHOUT ADDITIONAL EXPENshySE TO THE OWNER IF DISCREPANCIES CONFLICTS INTERFERENCES OR OMISSIONS OCCUR BETWEEN DRAWINGS NOTIFY IN WRITING THE ARCHinECTENGINEER IN AMPLE TltAE TO PERMIT REVISIONS BEFORE THE BIDS ARE SUBMITTED
4 INSTALL MAnERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT OF ITEMS OF WHICH IN HIS OPINION DO NOT PRESENT A NEAT AND WORKMANLIKE APPEARANCE REMOVAL AND REPLACEMENT IS TO BE DONE IMMEDIAnELY WHEN DIRECTIED BY THE OWNER IN WRITING AT THE SOLE EXPENSE OF THE CONTRACTOR
5 START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER TRADES OR OTHER CONTRACTORS TO RECEIVE HIS WORK THIS CONTRACTshyTOR SHALL REtAOVE AND REPLACE AT HIS EXPENSE ALL PLUMBING WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCES WITH OTHER TRADES
6 THIS CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE FEES PERMITS ASSOCIATION DUES ROYALTIES AND TAXES OF WHATEVER NATURE SHALL APPLY TO THIS WORK HE SHALL ALSO PAY ALL INSPECTION FEES AS MAY BE REQUIRED BY LAW OR ORDINANCE AND SHALL KEEP THE OWNER HARMLESS FROM ANY DAMAGE AND EXPENSE ARISING FROM ANY VIOLATION OF THE LAWS RUUES OR ORDINANCES
7 PROVIDE MEANS FURNISHED AND INSTALL
8 DO A COMPLETE JOB EVERYTHING CONNECTIED READY FOR USE
9 SHOP DRAWINGS THIS CONTRACTOR SHALL FURNISH THE ENGINEER WITH SHOP DRAWINGS OF EQUIPMENT PRIOR TO PURCHASE FOR APPROVAL
1 0 AT COMPLIETION OF JOB THE PLUMBING CONTRACTOR SHALL GIVE THE OWNER AN AS-BUILT SET OF REPRODUCIBUE SEPIAS SHOWING THE EXACT INSTALLATION
11 PLUMBING CONTRACTOR SHALL PRESSURE nEST ALL PIPING AS REQUIRED BY CODE TEST SHALL BE WITNESSED AND APPROVED BY PROPER AUTHORITIES
12 THE PLUMBING CONTRACTOR SHALL WARRANT ALL WORKtAANSHIP AND MATERIALS FOR ONE YEAR FROM THE DAnE OF FINAL WORK ACCEPTANCE BY OWNER ANY BREAKDOWN OCCURRING IN FIRST YEAR SHALL BE REPAIRED AT NO EXPENSE TO THE OWNER
13 PLUMBING FIXTURES SPECIFICATIONS TO BE SUBMITTED BY ARCHinECT AT A LAnER DAnE
14 PROVIDE SHUT-OFF VALVE FOR EACH FIXTURE
1 5 WHEREVER DISSIMILAR METALS ARE TO JOINED A DI-ELECTRIC FITTING SHALL BE PROVIDED TO CONNECT BOTH TYPES OF PIPES
16 PLUMBING CONTRACTOR SHALL PROVIDE AIR CONDITIONING CONDENSATE DRAIN AND TRAP SEE AIR CONDITIONING PLANS FOR LOCATION OF UNITS AND DRAINS
17 MATERIALSmiddot
A COLD amp HOT WATER PIPING DOWNSTREAM OF WATER METER SHALL BE CPVC
B SANITARY WASTE AND VENT LINES SHALL BE PVC
C CONDENSAnE DRAIN PIPE SHALL BE INSULAnED PVC SCHEDULE 40
v VENT COLD WATER LINE
VTR VENT-THRU-ROOF --middot-- HOT WATER UNE
IAS-R BEDRCOI1
I I
( TUB
ll~~~I I =
(5 ru) JAll
rmiddot )ii1 k--
~
~ 2
Qr I
[--1 2cw ampCD CONDENSATE DRAIN 12HW ONw WASTE
cw COLD WATER 12 HB WVACUUM BREAKER -2 VENTamp VALVE ON RAISER+FCO FLUSH CLIEANOUT -M-- GATE VALVEFU FIXTURE UNITS _
RVD RELIEF VALVE DISCHARGE PIPING TURN DOWN
CD CONDENSATE DRAIN 0 PIPING TURN DOWN
---o PIPING TURN UPJl~ VTR (VENT THRU ROOF) -o- PIPING TURN UP
3 (5 FU)
rr~~~~~12 HB WVACUU~
~---------~ BREAKER amp VALVE I 0sectshyON RISER- 1 I I
I me II
EEDROOHl______ r ~
I -12CW DN plusmn== c
I I I I
- ALL SANITARY PIPING 2 OR LESS TO HAVE 14 MIN SLOPE
3 I I - ALL SANITARY PIPING 3 TO 6 TO HAVE 18 MIN SLOPE (5 FU)
- ALL SANITARY PIPING 8 OR LARGER TO HAVE 116 MIN SLOPE KITCI-Et~
-PROVIDE ANTI-SCALDING VALVE IIOF ON ALL TUBS AND SHOWERS
-PROVIDE SHUTOFF VALVE FOR EACH FIXTURE
- PROVIDE CLEAN OUTS AT EACH SOIL B WASTE STACKS
2VTR~W FOOD GRINDER
BEDROOMGREAT ROOcl S
bull ~ - nshy
bull nrshylt - shy-~ 0
11~
I shy middot-n Cl~E- LL~OOCo middot- 4 EXlaquogt
l middot-lL 0
t- w~ I Ill cpound)~
~ ~c- gt 0 r- Oui~
~---~ o ~ ol) middot shy
d) ~ ~s- oi s
w~bull I~ rlt1-
lt Ill ltI)--1 ~()pound01L gtltIll)
au ltI)bullol) bullbull
11 -= -~$it 0 E rt----~
ol)
ltlt 11~ ~(() ru~
tshy 0 -~
0-Ie
0 Q_
w 0Zlshylt(Zzw LL2 C) a
(sectz9 -w It(fJgt 0
__jJw lL
Oo ~I gt-gtshy z
J 1-1shy 0 zz ()
0JJ It 02 ~ 02 0 oo It
oO Ill
~~0 w z Olt(
s 0 0 Ill
jiijl 0 0 Itjiijl f--w
jiijl lt(()
tljJi
~ ()lt( (J)()(f)Ott
~ 0lt(ttU IN
A f-oeslt( lllZNw
0 -I (J)()f-shy0lt11 0
~ It
-o 0 w Ill ()
TI-llS D~AWINC AND SPECIFICATIONS CCNTAINS PROPRIETARY INFOR-JATION A~D A~ TI-lE =~OFE~TI OF OCTAVIO A 3ANTURIJ AIAPA AlD MAY OT BE R~f-ROP~CI~ COF-IP OFlt PIS-RI6UTED wr--lOUT TI-lE EXPRESSED WRnEN PERM ISS ON AND C01PEI-SATION CF OCTAVIO A SANTURIO AlA FA
FIXTURE CONNECTION SCHEDULE
ITEM cw CONN
HW CONN
TRAP SIZE
FU COUNT REMARKS
LAVATORY 12 12 1 14 1 BIDET 12 12 2 2 WATER CLOSET (TANK) 12 - 3 4 SHOWER 12 12 2 2 WANTI-SCALD ttiXING VALVE BATHTUB 12 12 2 2 WANTI-SCALD VALVE
BATH GROUP 5 FU
KITCHEN SINK 12 12 1 12 2
DISHWASHER - 12 1 12 2 WASHING MACHINE 12 12 2 2
HOSE BIB 12 - - - VACUUM BREAKER amp VALVE IN THE VERTICAL
6049 WAlER ]H_E FLOW VELOCITY OF THE WATER DISTRIBUTION SYSIDt SIWL BE CONTROLLED TO REDUCE ]HE middot laquo_WATER_ HAMMER A WATER-twIIER ARRESTOR SHALL BE INSTAllED WHERE QUICK-CLOSING VALVES ARE UTILIZED WAlER HAMMER ARRESTORS SHALL BE INSTAllED IN ACCORDANCE WITH THE IIANlFACTIJRERS SPECIFICATIONS WAlER HAMMER ARRESTORS SIWL CONFORM TO ASSE 1010
12 MIN 3 I
2 UG CD LINE ~~~I bull ~~~~~V~RADE 34 UG RVD LINE
bull 1~3H RVD Ill IE-__JII~ ~~L -pound_
TO OUTSIDE amp TERMINATE 6 ABOVE RNISH ~ ---~~ct~t~ V 1_1
middot~
GRADE 3 I )(14 FU)
-J 1 ------------------34CW---------------~THE DISCHARGE PIPE SHALL I 34CWNOT HAVE ANY TRAPPED
--------------------------lI 34 CW ON_VISIBLE AIR GAP OR AIR GAP SECTIONS AND SHALL HAVE A
I TO EWH tWo CARS I FITTING LOCATED IN THE SAME GARAGE ~
IROOM AS THE WATER HEATER MASTER WATER AS PER P2803_6 1_1 FB_C I SHUT-OFF VALVE
I- IN CONC BOXI
I I 1ishyI I - ~~~ ~~~2 WAY C~ I 34CW
TABLE P29032a FCO ~ AIMAXIMUM FLOW RATES AND CONSUMPTION FOR I ~--------------~ PLUMBING FIXTURES FIXTURES FITIINGS AND APPLIANCES I
PLU~tBING FIXTURE PLUMBING FIXTURE OR OR
FIXTURE FITIING FIXTURE FITIING
LAVATORY FAUCET 15 GPM AT 60 PSI
SHOWER HEADa 15 GPM AT 80 PSI
SINK FAUCET 15 GPM AT 60 PSI
WATER CLOSET 128 GALLONS PER FLUSHING CYCLE
DISHWASHER 65 GALLONS PER CYCLE OR LESS
WASH MACHINE WATER FACTOR OF 8 OR LOWER
I I I I I
I
3 (14 FU) 12 HB WVACUUM _J
I BREAKER amp VALVE ON RISER
~34CW I
1
3 (14 FU) -SANITARY LINE 34 WATER SERVICE CONNECTED CONNECTED TO SEWER MAIN SERVICE TO WATER METER BY UTILnY CO BEFORE INSTALLATION COORDINATE BEFORE INSTALLATION COORDINATE EXACT LOCATION AT FIELD EXACT LOCATION AT FIELD SEE SITE PLAN FOR CONTINUATION SEE SITE PLAN FOR CONTINUATION
I 7-12
-
I I I I I I
Ht-57-sectI I
~
__----PATI-t
I
-
I
I
F ~ iht
11_)CJ=---lt D I I
1-4 2-8 1-4
--
~~-======If
I
_j 1-b L 3-2 1-6 2-8
~ ___J~ 101 l~dmiddot(o~)~~- ()
I itgt ilr~n~ ~lt
~_
I l ~middot-e~middot
I
FOR 51 1 GAIlON PER MtiiTE = 3785 Lrn1 POUND PER SQUARE INCH = 6895 KPa
FIXTURE CLEARENCE FLAN FIXTURE CLEARENCE FLAN Vlt4bull14 a A HANDHELD SHOWER SPRAY IS AlSO A SHOWER HEAD b A CONSUMPilON TOLIRANCES SHAll BE DEIERMINED FROMMASTER 6ATHROOM 6ATH No2 REFERENCED STANDARDS c WATER FICTOR IN GAIIONS PER CYCLE PER CUBIC FOOT PLUMBING PLAN 14=1-IZ
ALL PLUMBING FIXTURE SHALL BE EPA WATER SENSE LABELED
DRAW
JOI-lN D I-IECKEr
OA5 DATE
JANUARY 2015 SCA_E
A5 51-lOWN )06 NO
1505
51-lEET
PL-1 I OF 2 51-lEET5
50 GAL ELECTRICAL
EWH
JJW
i til
o II ) o j middot~I
bullcwl [f-z i cWvmiddotlp
~VISIONS BY
I CW amp HWSERVICE RUN ABOVE CEILING SEE FLOOR PLAN FOR ROUTING
HEAT TRAPmiddot--- MINIMUM 3
DRAIN COCK
34
34
AIR GAP
RVD RISER
_ 34 RVD LINE TO OUTSIDE amp TERMINATE 6 ABOVE GRADE
WAlER HEAlER PIPING DETAIL NTS
WATER HEATER DATA
MARK STORAGE IN US GAL INPUT MANUFACTURER
MODEL No ELECTRICAL
DATA ENERGY
EFFICIENCY
EWH 50 45KW AOSMITH
PROMAX middot ECT-52 OR
EQUAL
24()1-lO 091
WATER HEATER TYPICAL WATER RISER DIAGRAM NT5
2 VTR
T I I jx~v SHUT-OFF VALVE -Jl_
12HB WVACUUM f-CW IN CONC BOXo
BREAKER amp VALVE 1J2 ON RISER
2 VTRgt 2
l----shy~-
34 WATER SERVICE CONNECTED~ bull shyTO WATER METER BY UTIUJY CO BEFORE INSTALLATION COORDINATE _
2EXACT LOCATION AT FIELD bull ( SEE SITE PLAN FOR CONTINUATION
---
3 (14 FU SANITARY LINE CONNECTED TO SEWER MAJN SERVICE BEFORE INSTALLATION COORDINATE EXACT LOCATION AT FIELD SEE SITE PLAN FOR CONTINUATION
TYPICAL SANITARY RISER DIAGRAM Nrs
2 VTR
Ill 1-ill_ I
I tmiddot I I - I-- 2 I I - I 2
II II
2 II I I I I
2
bull ~ onshy- bull onrshy
- 0lt shy-~ 0 I-
11~ middot-U Cl~E -lt) - LL~_ 0 EX d)OCo middot-lL 0l I Ill cpound)~t-- w~ ~c- gt 0 r- Oui~
~---~ ltOoo ~ 1f middot shy
~s ~
~d) oL s
w~bull I~ rlt1-
QJ lt --1 ~()pound01L gtell)
au ltI)bullU
11 -= -~ rt----~$it ) E
1f
~(() ru~ltlt 11~
t-- -~
0 )0 -lc
Q_
w 0Zlshylt(Zzw LL2 C) a
(sect -w z9
It 0(fJgt uJw _j
OoI ~ gt-gt- J
z 1-1- 0 zz ()
JJ 0 It
02 ~ 02 0 Itoo
oO Ill
0 w ~~ z Olt(
0s 0 Ill
0jiijl 0
jiijl It f-wlt(()jiijl tljJi()lt( (J)()(f)~ Ott 0lt(ttU~ IN
A f-oeslt( lllZ
0 NwI
(J)()
11 f shy0lt 0 It~ -o 0 w Ill ()
TI-llS D~AWINC AND SPECIFICATIONS CCNTAINS FROFRIETART INFOR-JATION A~D A~ TI-lE =~OFE~TI OF OCTAVIO A 3ANTURIJ AIAPA AlD MAY OT BE R~f-ROP~C~~ COF-IP OFlt PIS-RI6UTED wr--lOUT TI-lE EXFREOSED WRr-TEN FERMIS6 ON AND C01PEI-6ATION CF OTAVIO A OANTURIO AlA FA
DRAW
JOI-lN D I-IECKEr
OA5 DATE
JANUARY 2015 6CA_E
A5 51-lOWN )06 NO
1505
51-1EET
PL-2 2 OF 2 5HEET5
~VISIONS BY
GENERAL ELECTRICAL NOTES
1 ALL WORK SHALL CONFOR~ WITH ALL LOCAL STAlE FEDERAL ORDINANCES AND BUILDING CODES GOVERNING THE INSTALLATION OF THE ELECTRICAL SYSTE~ IF WORK AS LAID OUT INDICATED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH LOCAL ORDINANCES BUILDING CODES AND REGULAshyTIONS THE CONTRACTOR SHALL REPORT IN WRITING TO THE ARCHITECT ENGINEER BEFORE SUB~ITTING A BID THE ARCHITECTENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED
2 THE DRAWING ARE TO BE CONSIDERED DIAGRAMMATIC NOT NECESSARILY SHOWING IN DETAIL OR TO SCALE ALL OF THE ~INOR ITE~S UNLESS SPECIFIC DI~ENSIONS ARE SHOWN THE STRUCTURAL ARCHITECTURAL AND SITE CONDITIONS SHALL GOVERN THE EXACT LOCATIONS CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK CHECK DRAWINGS OF ALL TRAIDES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED AND ~AINTAIN MAXI~U~ HEAD ROO~ OR SPACE CONDITIONS AT ALL POINTS WHERE HEAlD ROO~ OR SPACE CONDITIONS APPEAR INADEQUATE ARCHITECTENGINEERSHALL BE NOTIFIED BEFORE PROCEEDING WITH INSTALLATION THIS CONTRACshyTOR SHALL WITHOUT EXTRA CHARGE MAKE FIELD MODIFICATION IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF VARIOUS TRADES OR FOR PROPER EXECUTION OF THE WORK
3 EXA~INE ALL DRAWINGS CAREFULLY PRIOR TO SUB~ITTING A BID CONTRACTOR WILL BE REQUIRED TO FURNISH INSTALL ANDOR CONNECT WITH APPROPRIATE SERVICES ALL ELECTRICAL ITEMS SHOWN ON ANY OF THE ARCHITECTURAL PLU~BING AIR CONDITIONING SPRINKLER DRAWINGS WITHOUT ADDITIONAL EXPENSE TO TIHE OWNER IF DISCREPANCIES CONFLICTS INTERFERENCES OR O~ISSIONS OCCUR BETWEEN DRAWINGS NOTIFY IN WRITING THE ARCHITECT ENGINEER IN AMPLE TI~E TO PER~IT REVISIONS BEFORE TIHE BIDS ARE SUB~ITlED
4 VERIFY SERVICE CHARACTERISTICS LOCATION AND CONNECTION WI1H TELEPHONE AND ELECTRIC UTIUTY CO~PANIES PERFOR~ ALL WORK RELATED TO SERVICE IN STRICT ACCORDANCE WITH UTIUTY Co STANDARDS AND REQUIRE~ENTS
5 INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEshyMENT OF ITEM WHICH IN HIS OPINION DO NOT PRESENT A NEAT AND WORKMANshyLIKE APPEARANCE RE~OVAL AND REPLACEMENT IS TO BE DONE ~~~EDIATELY WHEN DIRECTED BY THE OWNER IN WRITING AT THE SOLE EXPENSE OF CONTRACshyTOR
6 START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER TRADES OR OTHER CONTRACTIDRS TO RECEIVE HIS WORK THIS CONTRACTOR SHALL REMOVE AND REPLACE AT HIS EXPENSE ALL ELECTRICAL WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCE WITH OTHER TRAIDES
7 THIS CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE FEES PERMITS ASSOshyCIATION DUES ROYALTIES AND TAXES OF WIHATEVER NATURE SHALL APPLY TO THIS WORK HE SHALL ALSO PAY ALL INSPECTION FEES AS MAY BE REQUIRED BY LAW OR ORDINANCE AND SHALL KEEP THE OWNER HARMLESS FROM ANY DA~E AND EXPENSE ARISING FROM ANY VIOLATION OF THE LAWS RULES OR ORDINANCES
8 ALL WIRE COPPER IN RACEWAY UNLESS OTHERWISE SPECIFIED ON DRAWINGS
9 WIRE UP COMPLElE ALL THE AC EQUIPMENT AND CONTROLS AS DIRECTED BY AC CONTRACTOR CONTROL WIRING SHALL BE SEPARAlE RACEWAY FRO~ POWER WIRING
10 PROVIDE RACEWAYS AND PREWIRE TELEPHONE SYSTEM COMPLElELY WITH lELEshyPHONE JACKS
11 PROVIDE RACEWAYS AND PREWIRE CABLE TV SYSlEIA AS DIREClED BY CABLE TV Co FIELD REPRESENTATIVE
12 PROVIDE MEANS FIURNISH AND INSTALL
13 COORDINATE WORK WITH WORK OF OTHER TRADES TO AVOID ALL CONFLICTS
14 DO A COMPLElE JOB EVERYTHING CONNEClED READY FOR USE
15 PROVIDE TE~PORARY WIRING SYSTEM FOR USE OF ALL TRAIDES ADEQUATE FOR ENTIRE NEEDS OF THIS PROJECTS
16 PROVIDE PULL WIRES WHEN EMPTY CONDUITS ARE SHOWN ON TIHE PLANS
17 PROVIDE LIGHT FIXTURES AS PER OWNER SELECTION
18 PROVIDE ALL WIRING DEVICES
19 IDENTIFY CLEARLY ON A TYPE WRITlEN FOR~ ALL CIRCUITS AND EQUIP~ENT TO CORRESPOND WITH THE PLANS AND PANELS SCHEDULE AND ATIACH INSIDE THE PERTAINING PANEL
20 RACEWAYSmiddot ALL UNDERGROUND RACEWAYS TO BE PVC INSIDE CONCRETE SLAB EIAT WITH APPROVED SET SCREW FITIING INSIDE PARTITION EIAT ENT AND ROMEX WIRE WHERE ALLOWED FOR FLOOR PENETRATION USE ONLY EIAT
21 SHOP THIS CONTRACTOR SHALL FIURNISH THE ENGINEER WITH SHOP OF EQUIP~ENT PRIOR TO PURCHASE FOR APPROVAL
23 TESTINGmiddot THE CONTRACTOR SHALL TEST ALL WORK AND EQUIPMENT AS DIREClED BY TIHE ARCHITECT AND BY AUTHORITIES HAVING JURISDICTION FURNISHING ALL EQUIPMENT AND NECESSARY PERSONNEL AND ELECTRIC POWER THE ENTIRE INSTALLATION SHALL BE TESlED FOR SHORTS GROUNDS AND OPEN CIRCUITS AND ALL DEFECTS SHALL BE DEMONSTRATED TO BE IN PROPER WORKING AND OPERATING CONDITION TO THE COMPLElE SATISFACTION OF THE ENGINEER
24 GliARANJEESmiddot ALL EQUIP~ENT AND MATERIALS SHALL BE GUARANlEED FOR ONE YEAR AFTER THE DATE OF ACCEPTANCE BY OWNER
25 AT COMPLETION OF JOB THE ELECTRICAL CONTRACTOR SHALL GIVE THE OWNER AN AS-BUILT SET OF REPRODUCIBLE SEPIAS SHOWING THE EXACT ELECTRICAL INSTALLATION
26 BEFORE BIDDING THE JOB THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS
PNL AMPS VOLTAGE CKTS WIRE PHASE MAIN MOUNT MANUFACTURER TYPE
150 120240 3040 3 1 LUGS FLUSH SIEMENS OR EO LOAD CENTER
CKT No WIRE COND
INCH
CKT BKR SERVING CKT
No WIRE COND INCH
CKT BKR SERVING
POLE AMPS POLE AMPS
1 r- shy
3 6 34 2 50 RANGE
(12KW)
2 12 12 1 20 SMALL APPL
4 12 12 1 20 SMALL APPL
5
7 6 34 2 50 AHU + ST HTR
(10KW+80KW)
6 12 12 1 20 BATH RECEPT
a 14 12 1 15 BEDROOM CKT
9
11 8 34 2 30 AIR COND UNIT
(440 KW)
10 14 12 1 15 BEDROO~ CKT
BEDROOM CKT12 14 12 1 15
13 r- shy
15 10 12 2 30
TANK WATER HEATER
(45 KW)
14 14 12 1 15 LIGHTS amp RECEPT
16 14 12 1 15 LIGHTS amp RECEPT
17 r- shy
19 10 12 2 30 DRYER
18 14 12 1 15 LIGHTS amp RECEPT
20 14 12 1 15 LIGHTS amp RECEPT
21 12 12 1 20 WASHER 22 12 12 1 20 GARAGE OPENER
23 12 12 1 20 KITCHEN HOOD 24 - - - - SPACE
25 12 12 1 20 DISH WASHER 26 - - - - SPACE
27 12 12 1 20 GARB DISPOSAL 28 - - - - SPACE
29 12 12 1 20 REFRIGERATOR 30 - - - - SPACE
NEC TABLE 220-30 ~
1990 SO FT 0 3 WATTSSO FT --~-c=-c=--- 60 TWO 20 AMP SMALL APPL CKT 0 1500 WATTS EACH___ 30 RANGE 120 TANK WATER HEATER 45 DRYER 50 WASHER 15 REFRIGERATOR 0 7 DISH WASHER 12 GARBAGE DISPOSAL 07 MICROWAVE 10 GARAGE DOOR OPENER 0 7
TOTAL WITHOUT DEMAND 363
FIRST 100 KW 0 100------------100 NEXT 263 KW 0 40 106
AHU + STRIP HEATER (10 KW + 80 KW x 100) 90
TOTAL CONNEClED LOAD 296
WATTS TO AMPS (LINE) 29600 240V = 124 AMPS
FEEDER TIHWN CU 311 amp 16 CU (GND) IN 1 12 PVC OR
THWN AL 220 amp 110 amp 16 CU (GND) IN 12 PVC (NEC 31 0-15(B)(6)
HEATING LOAD LARGER THAN COOLING LOAD
16
16
GREAT ROOM
(DihINS AREt_l
2 18
18
18
8
WIC
ltITC~EN
s
------shy1
I
I
I
I
I
I
I
I
I
I
I I I I I I
I I I I I I I I I I I I I I
- shy--F
a
II
20
TWO CARS SARASE
C I
12
10
3ATH
BEDROCi 3
~dpound0
12
1
CU-1
NEMA 3R EUCTJIIICAI MAINA lEiER COMeiNATION
bull ~ nshy- bull nrshylt - shy-~ 0
11~
I shymiddot-1()
Cl~E- LL~OOCo middot- 4 EXlaquogt
l middot-lL 0I Illt- w~ cpound)~ ~c
~ - gt 0 r- Oui~
~ o ~ 1() _
~ ~sd) shy oL s
w~bull I~ rlt1-
lt Ill ltt ltI)--1 ~()pound01L gtltIll)
au ltI)bull1()
11 -= -~$it 0 E rt----~
1()
11~ltl-ct ~(() ru~
tshy
0 ~~ 0 ~c
0 Q_
w 0Zlshylt(Zzw LL2 C) a
(sectz9 -w It(fJgt 0
_jJw lL
Oo ~I gt-gtshy z
J 1-1shy 0 zz ()
0JJ It 02 ~ 02 0 oo It
oO Ill
~~0 w z Olt(
s 0 0 Ill
jiijl 0 0 Itjiijl f--w
jiijl lt(()
tljJi
~ ()lt( (J)()(f)Ott
~ 0lt(ttU IN
A f-oeslt( lllZNw
0 I (J)()f-shy0lt11 0
~ It
-o 0 w Ill ()
TI-llS D~AWINC AND SPECIFICATIONS CCNTAINS PROPRIETARY INFOR-JATION A~D A~ TI-lE =~OFE~TI OF OCTAVIO A 3ANTURIJ AIAPA AlD MAY OT BE R~f-ROP~CI~ COF-IP OFlt PIS-RI6UTED wr--lOUT TI-lE EXPRESSED WRnEN PERM ISS ON AND C01PEI-SATION CF OCTAVIO A SANTURIO AlA FA
r- shy
r- shy
NOTES
BEFORE INSTALLATION THE ELECTRICAL CONTRACTOR SHALL VERIFY THE SIZE OF CKT BKR AND FEEDER WlTH THE AIC MANUFACTURERS REQUIREMENTS AND SHALL BE IN COMPLIANCE WITH NEG 424-3 440-22 AND 440-32
ALL 15A AND 20A BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT IN FAMILY ROOMS DINING ROOMS LIVING ROOMS PARLORS LIBRARIES DENS SUN ROOMS RECREATION ROOMS CLOSETS HALLWAYS OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED ARC FAULT CIRCUIT INTERRUPTER DEVICE OF THE COMBINATION TYPE AS REQUIRED BY NEC 210-12fBi
ALL 15A AND 20A RECEPTACLES IN AREAS SPECIFIED IN NEC 21052 SHALL BE LISTED AS TAMPER RESISTANT RECEPTACLES AS REQUIRED BY NEG 40611
THE ELECTRICAL PANEL CONNECTIONS MUST BE UL LISTED FOR 60f75 CONDUCTORS IN COMPLIANCE WITH NEC 110-14(c) THE TEMPERATURE RATING ASSOCIATED WITH THE AMPACITY OF A CONDUCTOR SHALL BE SELECTED AND COORDINATED SO AS NOT TO EXCEED THE LOWEST TEMPERATURE RATING OF ANY CONNECTED TERMINATION CONDUCTOR OR DEVICE
ELECTRICAL RISER DIAGRAM NTS
THWN CU 3(11 amp 1 6 CU (GND) IN 1 12 PVC
OR THWN AL 2120 amp 11110 amp ELECT NEMA 3R
16 CU (GND) IN 1 12 PVC PANEL i 0 ELECTRICAL INSIDE MAINMElER HOUSE COMBINATION
I 4 cu NEMA 3R 2POLE 240V 150A MAIN BKR 22000 AIC
~ 34CW PIPE ~ TO COMPLY W 25094
(
GROUND TO BLDG STEEL REINFORCING BAR W~4 BARE CU CONDUCTO
(1) 10-0L x 58t -==shy GROUND ROD --
r-
2 PVC TO FPL SERVICE ENTRANCE r COORDINATE EXACT LOCTAION WITH
FPL REPRESENTATIVE
ELECTRICAL LEGEND THE USE OF ROMEX TYPE WIRE IS ACCEPTABLE IF IT IS IN COMPLIANCE120V HALF SWITCHED DUPLEX RECEPTACLE~ 0 4-amiddot CEILING SURFACE MOUNlED FLOURECENT LIGHT FIXTURE WITH NEC TABLE 310-16 FOR 60C
120V DUPLEX RECEPTACLE BATHROOM RECIRCULATING FANreg -e 120V SINGLE RECEPTACLE 120V ACBATIERY OPERATED CEILING MOUNTED SMOKE DETECTOR INTERCONNECTIED WITH OTHER SMOKE DIETECTORS INSIDE THE HOUSE
120V GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE FOR SIMULTANEOUS OPERATION SMOKE DETECTORS SHALL BE ALARM NOTE LOCATED 36 AWAY FROM ANY AC DIFFUSER AND FROM BATH AND ALARM SYSTEM BY ALARM CONTRACTOR KITCHEN DOORS SMOKE DETECTbRS SHALL BE PHOTO-ELECTRIC UNDER SEPARATE PERMIT 120V ABOVE COUNTER GROUND FAULT INTERRUPTER~ TYPE IF IT IS LOCATED WI1HIN 20 FROM KITCHEN APPL
DUPLEX RECEPTACLE
120V ACBATIERY OPERATED CEILING MOUNTED SMOKE AND- 240V 30A DRYER RECEPTACLE CARBON ~ONOXIDE DElECTOR INTERCONNEClED WITH OTHER S~OKE amp CARBON MONOXIDE DETECTORS INSIDE THE HOUSE FOR240V 50A RANGE RECEPTACLE-reg SIMULTANEOUS OPERATION SMOKE amp CARBON ~ONOXIDE DElECTORS SHALL BE LOCATED 36 AWAY FROM ANY AC 98-30472 CARBON MONOXIDE PROTECTIONLn TOGGLE SWITCH DIFFUSER AND FROM BATH AND KITCHEN DOORS S~dKE amp CARBON ~ONOXIDE DElECTORS SHALL BE PHOTO-ELECTRIC TYPE (1) DEFINITIONS FOR PURPOSES OF THIS RULE THE FOLLOWING DEFINITIONS~ 3 WAY TOGGLE SWITCH IF IT IS LOCATED WITHIN 20 FRO~ KITCHEN APPL SHALL APPLY
SERVICE LOCATION MUST BE AIPPROVED BY UTILITY CO
(a) CARBON MONOXIDE ALARM A DEVICE FOR THE PURPOSE OFGROUND FAULT INlERRUPTER GARAGE DOOR CONTROLLERTELEPHONE OUTLET DElECTING CARBON MONOXIp~ THAT PRODUCES A DISTINCT AUDIBLE ALAR~ AND IS LISTED OR LAt1ELED WI1H THE APPROPRLTE ~ TV OUTLET
JUNCTION BOX
STANDARD EITHER ANSIUL 2034-96 STANDARD FOR SINGLE ANDDOOR CHIME
0 MULTIPLE STATION CO ALARMS INCORPORATED HEREIN BY REFERENCE OR UL 2075-04 GAS AND VAPOR DIETECTOR SENSOR INCORPORATEDCEILING MOUNTED LIGHT FIXTURE HERE IN BY REFERENCE IN ACCORDANCE WITH ITS APPLICATIONPUSH BUTTON (b) FOSSIL FUEL COAL KEROSENE OIL FIUEL GASES OR OTHER ALL LIGHTING amp APPLIANCESI() WALL MOUNlED OUTLET PETROLEUM OR HYDROCARBON PRODUCT THAT EMITS CARBON ELECTRICAL PLAN MONOXIDE AS A BY- PRODUCT OF COMBUSTION SHALL BE ENERGY STAR LABELED DISCONNECT SWITCH NEMA 3RIQ) WALL MOUNTED JUNCTION BOX 14=1-IZ(2) EVERY BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
INSIDE AHU FACTORY MOUNTED CIRCUIT BREAKER ISSUED ON OR AFTER 7 1 I 06 AND HAVING A FOSSIL-FIUEL BURNINGCEILING MOUNlED JUNCTION BOX WITH SPECIAL HEATER OR APPLIANCE A FIREPLACE OR AN ATIACHED GARAGE SHALL0 SUPPORT FOR CHANDELIER OR LIGHTFAN COMBINATION HAVE AN OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WI1HIN 10ELECTRICAL PANEL FEET OF EACH ROOM USED FOR SLEEPING PURPOSES
SECTION 404 ELECTRICAL POWER AND LIGHTING VAPOR PROOF CEILING LIGHT FIXTURE LIGHTOVP D (3) IN NEW CONSTRUCTION ALARMS SHALL RECEIVE THEIR PRIMARY POWER SYSTEMS
I I ELECTRICAL METERMAIN COMBINATION FROM THE BUILDING WIRING WHEN SUCH WIRING IS SERVED FRO~ THE LOCAL POWER UTILITY SUCH ALARMS SHALL HAVE BATIERY BACK UP
WEATHER PROOF 4041 LIGHTING EQUIPMENT
PADDLE CEILING FAN WITH LIGHT FIXTURE A MINIMUM OF 50 PERCENT OF THE LAMPS IN (4) COMBINATION SMOKECARBON MONOXIDE ALARMS SHALL BE LISTED ORMOTION DETECTOR OUTDOOR LIGHT FIXTURE LABELED BY A NATidNALLY RECOGNIZED TESTING LABORATORY PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS
DRAW
JOI-lN D HECKEr
OA5 DATE
JANUARY 2015 SCA_E
A5 51-lOWN )06 NO
1505
51-1EET
E = 1
I OF I 51-lEET5
50 GAL ELECTRICAL
EWH
JJW
i til
o II ) o j middot~I
bullcwl [f-z i cWvmiddotlp
~VISIONS BY
I CW amp HWSERVICE RUN ABOVE CEILING SEE FLOOR PLAN FOR ROUTING
HEAT TRAPmiddot--- MINIMUM 3
DRAIN COCK
34
34
AIR GAP
RVD RISER
_ 34 RVD LINE TO OUTSIDE amp TERMINATE 6 ABOVE GRADE
WAlER HEAlER PIPING DETAIL NTS
WATER HEATER DATA
MARK STORAGE IN US GAL INPUT MANUFACTURER
MODEL No ELECTRICAL
DATA ENERGY
EFFICIENCY
EWH 50 45KW AOSMITH
PROMAX middot ECT-52 OR
EQUAL
24()1-lO 091
WATER HEATER TYPICAL WATER RISER DIAGRAM NT5
2 VTR
T I I jx~v SHUT-OFF VALVE -Jl_
12HB WVACUUM f-CW IN CONC BOXo
BREAKER amp VALVE 1J2 ON RISER
2 VTRgt 2
l----shy~-
34 WATER SERVICE CONNECTED~ bull shyTO WATER METER BY UTIUJY CO BEFORE INSTALLATION COORDINATE _
2EXACT LOCATION AT FIELD bull ( SEE SITE PLAN FOR CONTINUATION
---
3 (14 FU SANITARY LINE CONNECTED TO SEWER MAJN SERVICE BEFORE INSTALLATION COORDINATE EXACT LOCATION AT FIELD SEE SITE PLAN FOR CONTINUATION
TYPICAL SANITARY RISER DIAGRAM Nrs
2 VTR
Ill 1-ill_ I
I tmiddot I I - I-- 2 I I - I 2
II II
2 II I I I I
2
bull ~ onshy- bull onrshy
- 0lt shy-~ 0 I-
11~ middot-U Cl~E -lt) - LL~_ 0 EX d)OCo middot-lL 0l I Ill cpound)~t-- w~ ~c- gt 0 r- Oui~
~---~ ltOoo ~ 1f middot shy
~s ~
~d) oL s
w~bull I~ rlt1-
QJ lt --1 ~()pound01L gtell)
au ltI)bullU
11 -= -~ rt----~$it ) E
1f
~(() ru~ltlt 11~
t-- -~
0 )0 -lc
Q_
w 0Zlshylt(Zzw LL2 C) a
(sect -w z9
It 0(fJgt uJw _j
OoI ~ gt-gt- J
z 1-1- 0 zz ()
JJ 0 It
02 ~ 02 0 Itoo
oO Ill
0 w ~~ z Olt(
0s 0 Ill
0jiijl 0
jiijl It f-wlt(()jiijl tljJi()lt( (J)()(f)~ Ott 0lt(ttU~ IN
A f-oeslt( lllZ
0 NwI
(J)()
11 f shy0lt 0 It~ -o 0 w Ill ()
TI-llS D~AWINC AND SPECIFICATIONS CCNTAINS FROFRIETART INFOR-JATION A~D A~ TI-lE =~OFE~TI OF OCTAVIO A 3ANTURIJ AIAPA AlD MAY OT BE R~f-ROP~C~~ COF-IP OFlt PIS-RI6UTED wr--lOUT TI-lE EXFREOSED WRr-TEN FERMIS6 ON AND C01PEI-6ATION CF OTAVIO A OANTURIO AlA FA
DRAW
JOI-lN D I-IECKEr
OA5 DATE
JANUARY 2015 6CA_E
A5 51-lOWN )06 NO
1505
51-1EET
PL-2 2 OF 2 5HEET5
~VISIONS BY
GENERAL ELECTRICAL NOTES
1 ALL WORK SHALL CONFOR~ WITH ALL LOCAL STAlE FEDERAL ORDINANCES AND BUILDING CODES GOVERNING THE INSTALLATION OF THE ELECTRICAL SYSTE~ IF WORK AS LAID OUT INDICATED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH LOCAL ORDINANCES BUILDING CODES AND REGULAshyTIONS THE CONTRACTOR SHALL REPORT IN WRITING TO THE ARCHITECT ENGINEER BEFORE SUB~ITTING A BID THE ARCHITECTENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED
2 THE DRAWING ARE TO BE CONSIDERED DIAGRAMMATIC NOT NECESSARILY SHOWING IN DETAIL OR TO SCALE ALL OF THE ~INOR ITE~S UNLESS SPECIFIC DI~ENSIONS ARE SHOWN THE STRUCTURAL ARCHITECTURAL AND SITE CONDITIONS SHALL GOVERN THE EXACT LOCATIONS CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK CHECK DRAWINGS OF ALL TRAIDES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED AND ~AINTAIN MAXI~U~ HEAD ROO~ OR SPACE CONDITIONS AT ALL POINTS WHERE HEAlD ROO~ OR SPACE CONDITIONS APPEAR INADEQUATE ARCHITECTENGINEERSHALL BE NOTIFIED BEFORE PROCEEDING WITH INSTALLATION THIS CONTRACshyTOR SHALL WITHOUT EXTRA CHARGE MAKE FIELD MODIFICATION IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF VARIOUS TRADES OR FOR PROPER EXECUTION OF THE WORK
3 EXA~INE ALL DRAWINGS CAREFULLY PRIOR TO SUB~ITTING A BID CONTRACTOR WILL BE REQUIRED TO FURNISH INSTALL ANDOR CONNECT WITH APPROPRIATE SERVICES ALL ELECTRICAL ITEMS SHOWN ON ANY OF THE ARCHITECTURAL PLU~BING AIR CONDITIONING SPRINKLER DRAWINGS WITHOUT ADDITIONAL EXPENSE TO TIHE OWNER IF DISCREPANCIES CONFLICTS INTERFERENCES OR O~ISSIONS OCCUR BETWEEN DRAWINGS NOTIFY IN WRITING THE ARCHITECT ENGINEER IN AMPLE TI~E TO PER~IT REVISIONS BEFORE TIHE BIDS ARE SUB~ITlED
4 VERIFY SERVICE CHARACTERISTICS LOCATION AND CONNECTION WI1H TELEPHONE AND ELECTRIC UTIUTY CO~PANIES PERFOR~ ALL WORK RELATED TO SERVICE IN STRICT ACCORDANCE WITH UTIUTY Co STANDARDS AND REQUIRE~ENTS
5 INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEshyMENT OF ITEM WHICH IN HIS OPINION DO NOT PRESENT A NEAT AND WORKMANshyLIKE APPEARANCE RE~OVAL AND REPLACEMENT IS TO BE DONE ~~~EDIATELY WHEN DIRECTED BY THE OWNER IN WRITING AT THE SOLE EXPENSE OF CONTRACshyTOR
6 START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER TRADES OR OTHER CONTRACTIDRS TO RECEIVE HIS WORK THIS CONTRACTOR SHALL REMOVE AND REPLACE AT HIS EXPENSE ALL ELECTRICAL WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCE WITH OTHER TRAIDES
7 THIS CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE FEES PERMITS ASSOshyCIATION DUES ROYALTIES AND TAXES OF WIHATEVER NATURE SHALL APPLY TO THIS WORK HE SHALL ALSO PAY ALL INSPECTION FEES AS MAY BE REQUIRED BY LAW OR ORDINANCE AND SHALL KEEP THE OWNER HARMLESS FROM ANY DA~E AND EXPENSE ARISING FROM ANY VIOLATION OF THE LAWS RULES OR ORDINANCES
8 ALL WIRE COPPER IN RACEWAY UNLESS OTHERWISE SPECIFIED ON DRAWINGS
9 WIRE UP COMPLElE ALL THE AC EQUIPMENT AND CONTROLS AS DIRECTED BY AC CONTRACTOR CONTROL WIRING SHALL BE SEPARAlE RACEWAY FRO~ POWER WIRING
10 PROVIDE RACEWAYS AND PREWIRE TELEPHONE SYSTEM COMPLElELY WITH lELEshyPHONE JACKS
11 PROVIDE RACEWAYS AND PREWIRE CABLE TV SYSlEIA AS DIREClED BY CABLE TV Co FIELD REPRESENTATIVE
12 PROVIDE MEANS FIURNISH AND INSTALL
13 COORDINATE WORK WITH WORK OF OTHER TRADES TO AVOID ALL CONFLICTS
14 DO A COMPLElE JOB EVERYTHING CONNEClED READY FOR USE
15 PROVIDE TE~PORARY WIRING SYSTEM FOR USE OF ALL TRAIDES ADEQUATE FOR ENTIRE NEEDS OF THIS PROJECTS
16 PROVIDE PULL WIRES WHEN EMPTY CONDUITS ARE SHOWN ON TIHE PLANS
17 PROVIDE LIGHT FIXTURES AS PER OWNER SELECTION
18 PROVIDE ALL WIRING DEVICES
19 IDENTIFY CLEARLY ON A TYPE WRITlEN FOR~ ALL CIRCUITS AND EQUIP~ENT TO CORRESPOND WITH THE PLANS AND PANELS SCHEDULE AND ATIACH INSIDE THE PERTAINING PANEL
20 RACEWAYSmiddot ALL UNDERGROUND RACEWAYS TO BE PVC INSIDE CONCRETE SLAB EIAT WITH APPROVED SET SCREW FITIING INSIDE PARTITION EIAT ENT AND ROMEX WIRE WHERE ALLOWED FOR FLOOR PENETRATION USE ONLY EIAT
21 SHOP THIS CONTRACTOR SHALL FIURNISH THE ENGINEER WITH SHOP OF EQUIP~ENT PRIOR TO PURCHASE FOR APPROVAL
23 TESTINGmiddot THE CONTRACTOR SHALL TEST ALL WORK AND EQUIPMENT AS DIREClED BY TIHE ARCHITECT AND BY AUTHORITIES HAVING JURISDICTION FURNISHING ALL EQUIPMENT AND NECESSARY PERSONNEL AND ELECTRIC POWER THE ENTIRE INSTALLATION SHALL BE TESlED FOR SHORTS GROUNDS AND OPEN CIRCUITS AND ALL DEFECTS SHALL BE DEMONSTRATED TO BE IN PROPER WORKING AND OPERATING CONDITION TO THE COMPLElE SATISFACTION OF THE ENGINEER
24 GliARANJEESmiddot ALL EQUIP~ENT AND MATERIALS SHALL BE GUARANlEED FOR ONE YEAR AFTER THE DATE OF ACCEPTANCE BY OWNER
25 AT COMPLETION OF JOB THE ELECTRICAL CONTRACTOR SHALL GIVE THE OWNER AN AS-BUILT SET OF REPRODUCIBLE SEPIAS SHOWING THE EXACT ELECTRICAL INSTALLATION
26 BEFORE BIDDING THE JOB THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS
PNL AMPS VOLTAGE CKTS WIRE PHASE MAIN MOUNT MANUFACTURER TYPE
150 120240 3040 3 1 LUGS FLUSH SIEMENS OR EO LOAD CENTER
CKT No WIRE COND
INCH
CKT BKR SERVING CKT
No WIRE COND INCH
CKT BKR SERVING
POLE AMPS POLE AMPS
1 r- shy
3 6 34 2 50 RANGE
(12KW)
2 12 12 1 20 SMALL APPL
4 12 12 1 20 SMALL APPL
5
7 6 34 2 50 AHU + ST HTR
(10KW+80KW)
6 12 12 1 20 BATH RECEPT
a 14 12 1 15 BEDROOM CKT
9
11 8 34 2 30 AIR COND UNIT
(440 KW)
10 14 12 1 15 BEDROO~ CKT
BEDROOM CKT12 14 12 1 15
13 r- shy
15 10 12 2 30
TANK WATER HEATER
(45 KW)
14 14 12 1 15 LIGHTS amp RECEPT
16 14 12 1 15 LIGHTS amp RECEPT
17 r- shy
19 10 12 2 30 DRYER
18 14 12 1 15 LIGHTS amp RECEPT
20 14 12 1 15 LIGHTS amp RECEPT
21 12 12 1 20 WASHER 22 12 12 1 20 GARAGE OPENER
23 12 12 1 20 KITCHEN HOOD 24 - - - - SPACE
25 12 12 1 20 DISH WASHER 26 - - - - SPACE
27 12 12 1 20 GARB DISPOSAL 28 - - - - SPACE
29 12 12 1 20 REFRIGERATOR 30 - - - - SPACE
NEC TABLE 220-30 ~
1990 SO FT 0 3 WATTSSO FT --~-c=-c=--- 60 TWO 20 AMP SMALL APPL CKT 0 1500 WATTS EACH___ 30 RANGE 120 TANK WATER HEATER 45 DRYER 50 WASHER 15 REFRIGERATOR 0 7 DISH WASHER 12 GARBAGE DISPOSAL 07 MICROWAVE 10 GARAGE DOOR OPENER 0 7
TOTAL WITHOUT DEMAND 363
FIRST 100 KW 0 100------------100 NEXT 263 KW 0 40 106
AHU + STRIP HEATER (10 KW + 80 KW x 100) 90
TOTAL CONNEClED LOAD 296
WATTS TO AMPS (LINE) 29600 240V = 124 AMPS
FEEDER TIHWN CU 311 amp 16 CU (GND) IN 1 12 PVC OR
THWN AL 220 amp 110 amp 16 CU (GND) IN 12 PVC (NEC 31 0-15(B)(6)
HEATING LOAD LARGER THAN COOLING LOAD
16
16
GREAT ROOM
(DihINS AREt_l
2 18
18
18
8
WIC
ltITC~EN
s
------shy1
I
I
I
I
I
I
I
I
I
I
I I I I I I
I I I I I I I I I I I I I I
- shy--F
a
II
20
TWO CARS SARASE
C I
12
10
3ATH
BEDROCi 3
~dpound0
12
1
CU-1
NEMA 3R EUCTJIIICAI MAINA lEiER COMeiNATION
bull ~ nshy- bull nrshylt - shy-~ 0
11~
I shymiddot-1()
Cl~E- LL~OOCo middot- 4 EXlaquogt
l middot-lL 0I Illt- w~ cpound)~ ~c
~ - gt 0 r- Oui~
~ o ~ 1() _
~ ~sd) shy oL s
w~bull I~ rlt1-
lt Ill ltt ltI)--1 ~()pound01L gtltIll)
au ltI)bull1()
11 -= -~$it 0 E rt----~
1()
11~ltl-ct ~(() ru~
tshy
0 ~~ 0 ~c
0 Q_
w 0Zlshylt(Zzw LL2 C) a
(sectz9 -w It(fJgt 0
_jJw lL
Oo ~I gt-gtshy z
J 1-1shy 0 zz ()
0JJ It 02 ~ 02 0 oo It
oO Ill
~~0 w z Olt(
s 0 0 Ill
jiijl 0 0 Itjiijl f--w
jiijl lt(()
tljJi
~ ()lt( (J)()(f)Ott
~ 0lt(ttU IN
A f-oeslt( lllZNw
0 I (J)()f-shy0lt11 0
~ It
-o 0 w Ill ()
TI-llS D~AWINC AND SPECIFICATIONS CCNTAINS PROPRIETARY INFOR-JATION A~D A~ TI-lE =~OFE~TI OF OCTAVIO A 3ANTURIJ AIAPA AlD MAY OT BE R~f-ROP~CI~ COF-IP OFlt PIS-RI6UTED wr--lOUT TI-lE EXPRESSED WRnEN PERM ISS ON AND C01PEI-SATION CF OCTAVIO A SANTURIO AlA FA
r- shy
r- shy
NOTES
BEFORE INSTALLATION THE ELECTRICAL CONTRACTOR SHALL VERIFY THE SIZE OF CKT BKR AND FEEDER WlTH THE AIC MANUFACTURERS REQUIREMENTS AND SHALL BE IN COMPLIANCE WITH NEG 424-3 440-22 AND 440-32
ALL 15A AND 20A BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT IN FAMILY ROOMS DINING ROOMS LIVING ROOMS PARLORS LIBRARIES DENS SUN ROOMS RECREATION ROOMS CLOSETS HALLWAYS OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED ARC FAULT CIRCUIT INTERRUPTER DEVICE OF THE COMBINATION TYPE AS REQUIRED BY NEC 210-12fBi
ALL 15A AND 20A RECEPTACLES IN AREAS SPECIFIED IN NEC 21052 SHALL BE LISTED AS TAMPER RESISTANT RECEPTACLES AS REQUIRED BY NEG 40611
THE ELECTRICAL PANEL CONNECTIONS MUST BE UL LISTED FOR 60f75 CONDUCTORS IN COMPLIANCE WITH NEC 110-14(c) THE TEMPERATURE RATING ASSOCIATED WITH THE AMPACITY OF A CONDUCTOR SHALL BE SELECTED AND COORDINATED SO AS NOT TO EXCEED THE LOWEST TEMPERATURE RATING OF ANY CONNECTED TERMINATION CONDUCTOR OR DEVICE
ELECTRICAL RISER DIAGRAM NTS
THWN CU 3(11 amp 1 6 CU (GND) IN 1 12 PVC
OR THWN AL 2120 amp 11110 amp ELECT NEMA 3R
16 CU (GND) IN 1 12 PVC PANEL i 0 ELECTRICAL INSIDE MAINMElER HOUSE COMBINATION
I 4 cu NEMA 3R 2POLE 240V 150A MAIN BKR 22000 AIC
~ 34CW PIPE ~ TO COMPLY W 25094
(
GROUND TO BLDG STEEL REINFORCING BAR W~4 BARE CU CONDUCTO
(1) 10-0L x 58t -==shy GROUND ROD --
r-
2 PVC TO FPL SERVICE ENTRANCE r COORDINATE EXACT LOCTAION WITH
FPL REPRESENTATIVE
ELECTRICAL LEGEND THE USE OF ROMEX TYPE WIRE IS ACCEPTABLE IF IT IS IN COMPLIANCE120V HALF SWITCHED DUPLEX RECEPTACLE~ 0 4-amiddot CEILING SURFACE MOUNlED FLOURECENT LIGHT FIXTURE WITH NEC TABLE 310-16 FOR 60C
120V DUPLEX RECEPTACLE BATHROOM RECIRCULATING FANreg -e 120V SINGLE RECEPTACLE 120V ACBATIERY OPERATED CEILING MOUNTED SMOKE DETECTOR INTERCONNECTIED WITH OTHER SMOKE DIETECTORS INSIDE THE HOUSE
120V GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE FOR SIMULTANEOUS OPERATION SMOKE DETECTORS SHALL BE ALARM NOTE LOCATED 36 AWAY FROM ANY AC DIFFUSER AND FROM BATH AND ALARM SYSTEM BY ALARM CONTRACTOR KITCHEN DOORS SMOKE DETECTbRS SHALL BE PHOTO-ELECTRIC UNDER SEPARATE PERMIT 120V ABOVE COUNTER GROUND FAULT INTERRUPTER~ TYPE IF IT IS LOCATED WI1HIN 20 FROM KITCHEN APPL
DUPLEX RECEPTACLE
120V ACBATIERY OPERATED CEILING MOUNTED SMOKE AND- 240V 30A DRYER RECEPTACLE CARBON ~ONOXIDE DElECTOR INTERCONNEClED WITH OTHER S~OKE amp CARBON MONOXIDE DETECTORS INSIDE THE HOUSE FOR240V 50A RANGE RECEPTACLE-reg SIMULTANEOUS OPERATION SMOKE amp CARBON ~ONOXIDE DElECTORS SHALL BE LOCATED 36 AWAY FROM ANY AC 98-30472 CARBON MONOXIDE PROTECTIONLn TOGGLE SWITCH DIFFUSER AND FROM BATH AND KITCHEN DOORS S~dKE amp CARBON ~ONOXIDE DElECTORS SHALL BE PHOTO-ELECTRIC TYPE (1) DEFINITIONS FOR PURPOSES OF THIS RULE THE FOLLOWING DEFINITIONS~ 3 WAY TOGGLE SWITCH IF IT IS LOCATED WITHIN 20 FRO~ KITCHEN APPL SHALL APPLY
SERVICE LOCATION MUST BE AIPPROVED BY UTILITY CO
(a) CARBON MONOXIDE ALARM A DEVICE FOR THE PURPOSE OFGROUND FAULT INlERRUPTER GARAGE DOOR CONTROLLERTELEPHONE OUTLET DElECTING CARBON MONOXIp~ THAT PRODUCES A DISTINCT AUDIBLE ALAR~ AND IS LISTED OR LAt1ELED WI1H THE APPROPRLTE ~ TV OUTLET
JUNCTION BOX
STANDARD EITHER ANSIUL 2034-96 STANDARD FOR SINGLE ANDDOOR CHIME
0 MULTIPLE STATION CO ALARMS INCORPORATED HEREIN BY REFERENCE OR UL 2075-04 GAS AND VAPOR DIETECTOR SENSOR INCORPORATEDCEILING MOUNTED LIGHT FIXTURE HERE IN BY REFERENCE IN ACCORDANCE WITH ITS APPLICATIONPUSH BUTTON (b) FOSSIL FUEL COAL KEROSENE OIL FIUEL GASES OR OTHER ALL LIGHTING amp APPLIANCESI() WALL MOUNlED OUTLET PETROLEUM OR HYDROCARBON PRODUCT THAT EMITS CARBON ELECTRICAL PLAN MONOXIDE AS A BY- PRODUCT OF COMBUSTION SHALL BE ENERGY STAR LABELED DISCONNECT SWITCH NEMA 3RIQ) WALL MOUNTED JUNCTION BOX 14=1-IZ(2) EVERY BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
INSIDE AHU FACTORY MOUNTED CIRCUIT BREAKER ISSUED ON OR AFTER 7 1 I 06 AND HAVING A FOSSIL-FIUEL BURNINGCEILING MOUNlED JUNCTION BOX WITH SPECIAL HEATER OR APPLIANCE A FIREPLACE OR AN ATIACHED GARAGE SHALL0 SUPPORT FOR CHANDELIER OR LIGHTFAN COMBINATION HAVE AN OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WI1HIN 10ELECTRICAL PANEL FEET OF EACH ROOM USED FOR SLEEPING PURPOSES
SECTION 404 ELECTRICAL POWER AND LIGHTING VAPOR PROOF CEILING LIGHT FIXTURE LIGHTOVP D (3) IN NEW CONSTRUCTION ALARMS SHALL RECEIVE THEIR PRIMARY POWER SYSTEMS
I I ELECTRICAL METERMAIN COMBINATION FROM THE BUILDING WIRING WHEN SUCH WIRING IS SERVED FRO~ THE LOCAL POWER UTILITY SUCH ALARMS SHALL HAVE BATIERY BACK UP
WEATHER PROOF 4041 LIGHTING EQUIPMENT
PADDLE CEILING FAN WITH LIGHT FIXTURE A MINIMUM OF 50 PERCENT OF THE LAMPS IN (4) COMBINATION SMOKECARBON MONOXIDE ALARMS SHALL BE LISTED ORMOTION DETECTOR OUTDOOR LIGHT FIXTURE LABELED BY A NATidNALLY RECOGNIZED TESTING LABORATORY PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS
DRAW
JOI-lN D HECKEr
OA5 DATE
JANUARY 2015 SCA_E
A5 51-lOWN )06 NO
1505
51-1EET
E = 1
I OF I 51-lEET5
~VISIONS BY
GENERAL ELECTRICAL NOTES
1 ALL WORK SHALL CONFOR~ WITH ALL LOCAL STAlE FEDERAL ORDINANCES AND BUILDING CODES GOVERNING THE INSTALLATION OF THE ELECTRICAL SYSTE~ IF WORK AS LAID OUT INDICATED OR SPECIFIED IS CONTRARY TO OR CONFLICTS WITH LOCAL ORDINANCES BUILDING CODES AND REGULAshyTIONS THE CONTRACTOR SHALL REPORT IN WRITING TO THE ARCHITECT ENGINEER BEFORE SUB~ITTING A BID THE ARCHITECTENGINEER WILL THEN ISSUE INSTRUCTIONS AS HOW TO PROCEED
2 THE DRAWING ARE TO BE CONSIDERED DIAGRAMMATIC NOT NECESSARILY SHOWING IN DETAIL OR TO SCALE ALL OF THE ~INOR ITE~S UNLESS SPECIFIC DI~ENSIONS ARE SHOWN THE STRUCTURAL ARCHITECTURAL AND SITE CONDITIONS SHALL GOVERN THE EXACT LOCATIONS CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK CHECK DRAWINGS OF ALL TRAIDES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED AND ~AINTAIN MAXI~U~ HEAD ROO~ OR SPACE CONDITIONS AT ALL POINTS WHERE HEAlD ROO~ OR SPACE CONDITIONS APPEAR INADEQUATE ARCHITECTENGINEERSHALL BE NOTIFIED BEFORE PROCEEDING WITH INSTALLATION THIS CONTRACshyTOR SHALL WITHOUT EXTRA CHARGE MAKE FIELD MODIFICATION IN LAYOUT AS NEEDED TO PREVENT CONFLICT WITH WORK OF VARIOUS TRADES OR FOR PROPER EXECUTION OF THE WORK
3 EXA~INE ALL DRAWINGS CAREFULLY PRIOR TO SUB~ITTING A BID CONTRACTOR WILL BE REQUIRED TO FURNISH INSTALL ANDOR CONNECT WITH APPROPRIATE SERVICES ALL ELECTRICAL ITEMS SHOWN ON ANY OF THE ARCHITECTURAL PLU~BING AIR CONDITIONING SPRINKLER DRAWINGS WITHOUT ADDITIONAL EXPENSE TO TIHE OWNER IF DISCREPANCIES CONFLICTS INTERFERENCES OR O~ISSIONS OCCUR BETWEEN DRAWINGS NOTIFY IN WRITING THE ARCHITECT ENGINEER IN AMPLE TI~E TO PER~IT REVISIONS BEFORE TIHE BIDS ARE SUB~ITlED
4 VERIFY SERVICE CHARACTERISTICS LOCATION AND CONNECTION WI1H TELEPHONE AND ELECTRIC UTIUTY CO~PANIES PERFOR~ ALL WORK RELATED TO SERVICE IN STRICT ACCORDANCE WITH UTIUTY Co STANDARDS AND REQUIRE~ENTS
5 INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEshyMENT OF ITEM WHICH IN HIS OPINION DO NOT PRESENT A NEAT AND WORKMANshyLIKE APPEARANCE RE~OVAL AND REPLACEMENT IS TO BE DONE ~~~EDIATELY WHEN DIRECTED BY THE OWNER IN WRITING AT THE SOLE EXPENSE OF CONTRACshyTOR
6 START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS OR QUESTIONS AS TO SUITABILITY OF THE WORK OF OTHER TRADES OR OTHER CONTRACTIDRS TO RECEIVE HIS WORK THIS CONTRACTOR SHALL REMOVE AND REPLACE AT HIS EXPENSE ALL ELECTRICAL WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCE WITH OTHER TRAIDES
7 THIS CONTRACTOR SHALL OBTAIN AND PAY ALL INSURANCE FEES PERMITS ASSOshyCIATION DUES ROYALTIES AND TAXES OF WIHATEVER NATURE SHALL APPLY TO THIS WORK HE SHALL ALSO PAY ALL INSPECTION FEES AS MAY BE REQUIRED BY LAW OR ORDINANCE AND SHALL KEEP THE OWNER HARMLESS FROM ANY DA~E AND EXPENSE ARISING FROM ANY VIOLATION OF THE LAWS RULES OR ORDINANCES
8 ALL WIRE COPPER IN RACEWAY UNLESS OTHERWISE SPECIFIED ON DRAWINGS
9 WIRE UP COMPLElE ALL THE AC EQUIPMENT AND CONTROLS AS DIRECTED BY AC CONTRACTOR CONTROL WIRING SHALL BE SEPARAlE RACEWAY FRO~ POWER WIRING
10 PROVIDE RACEWAYS AND PREWIRE TELEPHONE SYSTEM COMPLElELY WITH lELEshyPHONE JACKS
11 PROVIDE RACEWAYS AND PREWIRE CABLE TV SYSlEIA AS DIREClED BY CABLE TV Co FIELD REPRESENTATIVE
12 PROVIDE MEANS FIURNISH AND INSTALL
13 COORDINATE WORK WITH WORK OF OTHER TRADES TO AVOID ALL CONFLICTS
14 DO A COMPLElE JOB EVERYTHING CONNEClED READY FOR USE
15 PROVIDE TE~PORARY WIRING SYSTEM FOR USE OF ALL TRAIDES ADEQUATE FOR ENTIRE NEEDS OF THIS PROJECTS
16 PROVIDE PULL WIRES WHEN EMPTY CONDUITS ARE SHOWN ON TIHE PLANS
17 PROVIDE LIGHT FIXTURES AS PER OWNER SELECTION
18 PROVIDE ALL WIRING DEVICES
19 IDENTIFY CLEARLY ON A TYPE WRITlEN FOR~ ALL CIRCUITS AND EQUIP~ENT TO CORRESPOND WITH THE PLANS AND PANELS SCHEDULE AND ATIACH INSIDE THE PERTAINING PANEL
20 RACEWAYSmiddot ALL UNDERGROUND RACEWAYS TO BE PVC INSIDE CONCRETE SLAB EIAT WITH APPROVED SET SCREW FITIING INSIDE PARTITION EIAT ENT AND ROMEX WIRE WHERE ALLOWED FOR FLOOR PENETRATION USE ONLY EIAT
21 SHOP THIS CONTRACTOR SHALL FIURNISH THE ENGINEER WITH SHOP OF EQUIP~ENT PRIOR TO PURCHASE FOR APPROVAL
23 TESTINGmiddot THE CONTRACTOR SHALL TEST ALL WORK AND EQUIPMENT AS DIREClED BY TIHE ARCHITECT AND BY AUTHORITIES HAVING JURISDICTION FURNISHING ALL EQUIPMENT AND NECESSARY PERSONNEL AND ELECTRIC POWER THE ENTIRE INSTALLATION SHALL BE TESlED FOR SHORTS GROUNDS AND OPEN CIRCUITS AND ALL DEFECTS SHALL BE DEMONSTRATED TO BE IN PROPER WORKING AND OPERATING CONDITION TO THE COMPLElE SATISFACTION OF THE ENGINEER
24 GliARANJEESmiddot ALL EQUIP~ENT AND MATERIALS SHALL BE GUARANlEED FOR ONE YEAR AFTER THE DATE OF ACCEPTANCE BY OWNER
25 AT COMPLETION OF JOB THE ELECTRICAL CONTRACTOR SHALL GIVE THE OWNER AN AS-BUILT SET OF REPRODUCIBLE SEPIAS SHOWING THE EXACT ELECTRICAL INSTALLATION
26 BEFORE BIDDING THE JOB THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS
PNL AMPS VOLTAGE CKTS WIRE PHASE MAIN MOUNT MANUFACTURER TYPE
150 120240 3040 3 1 LUGS FLUSH SIEMENS OR EO LOAD CENTER
CKT No WIRE COND
INCH
CKT BKR SERVING CKT
No WIRE COND INCH
CKT BKR SERVING
POLE AMPS POLE AMPS
1 r- shy
3 6 34 2 50 RANGE
(12KW)
2 12 12 1 20 SMALL APPL
4 12 12 1 20 SMALL APPL
5
7 6 34 2 50 AHU + ST HTR
(10KW+80KW)
6 12 12 1 20 BATH RECEPT
a 14 12 1 15 BEDROOM CKT
9
11 8 34 2 30 AIR COND UNIT
(440 KW)
10 14 12 1 15 BEDROO~ CKT
BEDROOM CKT12 14 12 1 15
13 r- shy
15 10 12 2 30
TANK WATER HEATER
(45 KW)
14 14 12 1 15 LIGHTS amp RECEPT
16 14 12 1 15 LIGHTS amp RECEPT
17 r- shy
19 10 12 2 30 DRYER
18 14 12 1 15 LIGHTS amp RECEPT
20 14 12 1 15 LIGHTS amp RECEPT
21 12 12 1 20 WASHER 22 12 12 1 20 GARAGE OPENER
23 12 12 1 20 KITCHEN HOOD 24 - - - - SPACE
25 12 12 1 20 DISH WASHER 26 - - - - SPACE
27 12 12 1 20 GARB DISPOSAL 28 - - - - SPACE
29 12 12 1 20 REFRIGERATOR 30 - - - - SPACE
NEC TABLE 220-30 ~
1990 SO FT 0 3 WATTSSO FT --~-c=-c=--- 60 TWO 20 AMP SMALL APPL CKT 0 1500 WATTS EACH___ 30 RANGE 120 TANK WATER HEATER 45 DRYER 50 WASHER 15 REFRIGERATOR 0 7 DISH WASHER 12 GARBAGE DISPOSAL 07 MICROWAVE 10 GARAGE DOOR OPENER 0 7
TOTAL WITHOUT DEMAND 363
FIRST 100 KW 0 100------------100 NEXT 263 KW 0 40 106
AHU + STRIP HEATER (10 KW + 80 KW x 100) 90
TOTAL CONNEClED LOAD 296
WATTS TO AMPS (LINE) 29600 240V = 124 AMPS
FEEDER TIHWN CU 311 amp 16 CU (GND) IN 1 12 PVC OR
THWN AL 220 amp 110 amp 16 CU (GND) IN 12 PVC (NEC 31 0-15(B)(6)
HEATING LOAD LARGER THAN COOLING LOAD
16
16
GREAT ROOM
(DihINS AREt_l
2 18
18
18
8
WIC
ltITC~EN
s
------shy1
I
I
I
I
I
I
I
I
I
I
I I I I I I
I I I I I I I I I I I I I I
- shy--F
a
II
20
TWO CARS SARASE
C I
12
10
3ATH
BEDROCi 3
~dpound0
12
1
CU-1
NEMA 3R EUCTJIIICAI MAINA lEiER COMeiNATION
bull ~ nshy- bull nrshylt - shy-~ 0
11~
I shymiddot-1()
Cl~E- LL~OOCo middot- 4 EXlaquogt
l middot-lL 0I Illt- w~ cpound)~ ~c
~ - gt 0 r- Oui~
~ o ~ 1() _
~ ~sd) shy oL s
w~bull I~ rlt1-
lt Ill ltt ltI)--1 ~()pound01L gtltIll)
au ltI)bull1()
11 -= -~$it 0 E rt----~
1()
11~ltl-ct ~(() ru~
tshy
0 ~~ 0 ~c
0 Q_
w 0Zlshylt(Zzw LL2 C) a
(sectz9 -w It(fJgt 0
_jJw lL
Oo ~I gt-gtshy z
J 1-1shy 0 zz ()
0JJ It 02 ~ 02 0 oo It
oO Ill
~~0 w z Olt(
s 0 0 Ill
jiijl 0 0 Itjiijl f--w
jiijl lt(()
tljJi
~ ()lt( (J)()(f)Ott
~ 0lt(ttU IN
A f-oeslt( lllZNw
0 I (J)()f-shy0lt11 0
~ It
-o 0 w Ill ()
TI-llS D~AWINC AND SPECIFICATIONS CCNTAINS PROPRIETARY INFOR-JATION A~D A~ TI-lE =~OFE~TI OF OCTAVIO A 3ANTURIJ AIAPA AlD MAY OT BE R~f-ROP~CI~ COF-IP OFlt PIS-RI6UTED wr--lOUT TI-lE EXPRESSED WRnEN PERM ISS ON AND C01PEI-SATION CF OCTAVIO A SANTURIO AlA FA
r- shy
r- shy
NOTES
BEFORE INSTALLATION THE ELECTRICAL CONTRACTOR SHALL VERIFY THE SIZE OF CKT BKR AND FEEDER WlTH THE AIC MANUFACTURERS REQUIREMENTS AND SHALL BE IN COMPLIANCE WITH NEG 424-3 440-22 AND 440-32
ALL 15A AND 20A BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT IN FAMILY ROOMS DINING ROOMS LIVING ROOMS PARLORS LIBRARIES DENS SUN ROOMS RECREATION ROOMS CLOSETS HALLWAYS OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED ARC FAULT CIRCUIT INTERRUPTER DEVICE OF THE COMBINATION TYPE AS REQUIRED BY NEC 210-12fBi
ALL 15A AND 20A RECEPTACLES IN AREAS SPECIFIED IN NEC 21052 SHALL BE LISTED AS TAMPER RESISTANT RECEPTACLES AS REQUIRED BY NEG 40611
THE ELECTRICAL PANEL CONNECTIONS MUST BE UL LISTED FOR 60f75 CONDUCTORS IN COMPLIANCE WITH NEC 110-14(c) THE TEMPERATURE RATING ASSOCIATED WITH THE AMPACITY OF A CONDUCTOR SHALL BE SELECTED AND COORDINATED SO AS NOT TO EXCEED THE LOWEST TEMPERATURE RATING OF ANY CONNECTED TERMINATION CONDUCTOR OR DEVICE
ELECTRICAL RISER DIAGRAM NTS
THWN CU 3(11 amp 1 6 CU (GND) IN 1 12 PVC
OR THWN AL 2120 amp 11110 amp ELECT NEMA 3R
16 CU (GND) IN 1 12 PVC PANEL i 0 ELECTRICAL INSIDE MAINMElER HOUSE COMBINATION
I 4 cu NEMA 3R 2POLE 240V 150A MAIN BKR 22000 AIC
~ 34CW PIPE ~ TO COMPLY W 25094
(
GROUND TO BLDG STEEL REINFORCING BAR W~4 BARE CU CONDUCTO
(1) 10-0L x 58t -==shy GROUND ROD --
r-
2 PVC TO FPL SERVICE ENTRANCE r COORDINATE EXACT LOCTAION WITH
FPL REPRESENTATIVE
ELECTRICAL LEGEND THE USE OF ROMEX TYPE WIRE IS ACCEPTABLE IF IT IS IN COMPLIANCE120V HALF SWITCHED DUPLEX RECEPTACLE~ 0 4-amiddot CEILING SURFACE MOUNlED FLOURECENT LIGHT FIXTURE WITH NEC TABLE 310-16 FOR 60C
120V DUPLEX RECEPTACLE BATHROOM RECIRCULATING FANreg -e 120V SINGLE RECEPTACLE 120V ACBATIERY OPERATED CEILING MOUNTED SMOKE DETECTOR INTERCONNECTIED WITH OTHER SMOKE DIETECTORS INSIDE THE HOUSE
120V GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE FOR SIMULTANEOUS OPERATION SMOKE DETECTORS SHALL BE ALARM NOTE LOCATED 36 AWAY FROM ANY AC DIFFUSER AND FROM BATH AND ALARM SYSTEM BY ALARM CONTRACTOR KITCHEN DOORS SMOKE DETECTbRS SHALL BE PHOTO-ELECTRIC UNDER SEPARATE PERMIT 120V ABOVE COUNTER GROUND FAULT INTERRUPTER~ TYPE IF IT IS LOCATED WI1HIN 20 FROM KITCHEN APPL
DUPLEX RECEPTACLE
120V ACBATIERY OPERATED CEILING MOUNTED SMOKE AND- 240V 30A DRYER RECEPTACLE CARBON ~ONOXIDE DElECTOR INTERCONNEClED WITH OTHER S~OKE amp CARBON MONOXIDE DETECTORS INSIDE THE HOUSE FOR240V 50A RANGE RECEPTACLE-reg SIMULTANEOUS OPERATION SMOKE amp CARBON ~ONOXIDE DElECTORS SHALL BE LOCATED 36 AWAY FROM ANY AC 98-30472 CARBON MONOXIDE PROTECTIONLn TOGGLE SWITCH DIFFUSER AND FROM BATH AND KITCHEN DOORS S~dKE amp CARBON ~ONOXIDE DElECTORS SHALL BE PHOTO-ELECTRIC TYPE (1) DEFINITIONS FOR PURPOSES OF THIS RULE THE FOLLOWING DEFINITIONS~ 3 WAY TOGGLE SWITCH IF IT IS LOCATED WITHIN 20 FRO~ KITCHEN APPL SHALL APPLY
SERVICE LOCATION MUST BE AIPPROVED BY UTILITY CO
(a) CARBON MONOXIDE ALARM A DEVICE FOR THE PURPOSE OFGROUND FAULT INlERRUPTER GARAGE DOOR CONTROLLERTELEPHONE OUTLET DElECTING CARBON MONOXIp~ THAT PRODUCES A DISTINCT AUDIBLE ALAR~ AND IS LISTED OR LAt1ELED WI1H THE APPROPRLTE ~ TV OUTLET
JUNCTION BOX
STANDARD EITHER ANSIUL 2034-96 STANDARD FOR SINGLE ANDDOOR CHIME
0 MULTIPLE STATION CO ALARMS INCORPORATED HEREIN BY REFERENCE OR UL 2075-04 GAS AND VAPOR DIETECTOR SENSOR INCORPORATEDCEILING MOUNTED LIGHT FIXTURE HERE IN BY REFERENCE IN ACCORDANCE WITH ITS APPLICATIONPUSH BUTTON (b) FOSSIL FUEL COAL KEROSENE OIL FIUEL GASES OR OTHER ALL LIGHTING amp APPLIANCESI() WALL MOUNlED OUTLET PETROLEUM OR HYDROCARBON PRODUCT THAT EMITS CARBON ELECTRICAL PLAN MONOXIDE AS A BY- PRODUCT OF COMBUSTION SHALL BE ENERGY STAR LABELED DISCONNECT SWITCH NEMA 3RIQ) WALL MOUNTED JUNCTION BOX 14=1-IZ(2) EVERY BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
INSIDE AHU FACTORY MOUNTED CIRCUIT BREAKER ISSUED ON OR AFTER 7 1 I 06 AND HAVING A FOSSIL-FIUEL BURNINGCEILING MOUNlED JUNCTION BOX WITH SPECIAL HEATER OR APPLIANCE A FIREPLACE OR AN ATIACHED GARAGE SHALL0 SUPPORT FOR CHANDELIER OR LIGHTFAN COMBINATION HAVE AN OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WI1HIN 10ELECTRICAL PANEL FEET OF EACH ROOM USED FOR SLEEPING PURPOSES
SECTION 404 ELECTRICAL POWER AND LIGHTING VAPOR PROOF CEILING LIGHT FIXTURE LIGHTOVP D (3) IN NEW CONSTRUCTION ALARMS SHALL RECEIVE THEIR PRIMARY POWER SYSTEMS
I I ELECTRICAL METERMAIN COMBINATION FROM THE BUILDING WIRING WHEN SUCH WIRING IS SERVED FRO~ THE LOCAL POWER UTILITY SUCH ALARMS SHALL HAVE BATIERY BACK UP
WEATHER PROOF 4041 LIGHTING EQUIPMENT
PADDLE CEILING FAN WITH LIGHT FIXTURE A MINIMUM OF 50 PERCENT OF THE LAMPS IN (4) COMBINATION SMOKECARBON MONOXIDE ALARMS SHALL BE LISTED ORMOTION DETECTOR OUTDOOR LIGHT FIXTURE LABELED BY A NATidNALLY RECOGNIZED TESTING LABORATORY PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS
DRAW
JOI-lN D HECKEr
OA5 DATE
JANUARY 2015 SCA_E
A5 51-lOWN )06 NO
1505
51-1EET
E = 1
I OF I 51-lEET5