Modal parameter estimation of low-rise building

using sine sweep vibration tests

Le Thai HoaWind Engineering Research Center

Tokyo Polytechnic University

Page 2: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Contents

1. Sine Sweep Force (Measured & Simulated)

2. Frequency Response Functions (FRF)3. Smoothing Techniques for FRF4. Modal Parameter Estimation [DX1 only]

Page 3: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Objectives

o Estimating modal parameters (natural frequencies and damping ratios) using sine sweep vibration data

o Sine sweep input force has been measured and simulated theoretically

o Identifying Frequency Response Functions (FRFs) from measured/theoretical input and measured response

Page 4: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Exciter

Exciter

o Linear sine sweep forceo Constant sweep force (Constant amplitude)o Variable frequency rangeo Starting frequency fo= 2Hzo Ending frequency fe 6Hzo Sweep rate =0.01 Hz/s

Reference (Exciter)S-ACCTABLE-ACC: Input acceleration TABLE-DISP: Input displacement

Page 5: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Sensors

Exciter

1F

2F

2F

PU4-X(CH4)

PU

4-Y

(CH

5)

X

Y

PU6-X(CH7)

PU

6-Y

(CH

8)

PU5-X(CH6)

PU1-X (CH1)

X

Y

PU3-X(CH3)

PU2-X(CH2)

Sampling rate: 100Hz

Accelerometer

Page 6: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Sine sweep excitation

Measured sweep forceSimulated sweep force

Page 7: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Measurement of sine sweep force

0 100 200 300 400 500 600 700 800-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

Time (s)

Acc

e. (

m/s

2 )

Table - Disp

Table - Disp

0 100 200 300 400 500 600 700 800-0.2

-0.15

-0.1

-0.05

0

0.05

0.1

0.15

Time (s)

Acc

e. (

m/s

2 )

Table - ACC

Table - ACC

0 2 4 6 8 10 12 14 16 18 200

0.002

0.004

0.006

0.008

0.01

0.012

Frequency (Hz)

PS

D

Table - Disp

Table - Disp

2.207Hz

2.573Hz3.013Hz

3.428Hz

3.843Hz4.283Hz

4.697Hz

5.137Hz

5.552Hz5.943Hz

0 2 4 6 8 10 12 14 16 18 200

0.5

1

1.5

2

2.5

3

3.5x 10

-3

Frequency (Hz)

PS

D

S - ACC

S - ACC3.697Hz

10.02Hz

DX1-Small Amplitude

Input displacement

Input acceleration

PSD

PSD

Page 8: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Input / Output (PSD)

0 1 2 3 4 5 6 7 8 9 1010

-10

10-8

10-6

10-4

10-2

100

Frequency (Hz)

PS

D

Segment 0-360seconds

Pu4xTable-dips2.207Hz

2.622Hz 3.452Hz

3.037Hz 3.843Hz

4.258Hz 5.088Hz

4.673Hz

3.697Hz

0 1 2 3 4 5 6 7 8 9 1010

-10

10-8

10-6

10-4

10-2

100

Frequency (Hz)

PS

D

Segment 360-720seconds

Pu4xTable-dips

3.062Hz

3.526Hz

3.672Hz3.965Hz

4.405Hz

4.844Hz

5.283Hz

5.772Hz

InputOutput

0 100 200 300 400 500 600 700 800-0.08

-0.06

-0.04

-0.02

0

0.02

0.04

0.06

0.08

Time (s)

Acce

. (m

/s2 )

PU4X - 2F

PU4X

0-360s 360-720s

InputResponse

DX1-Small Amplitude

Spectral leakage due toperiodic excitation

Page 9: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Input / Output (Wavelet)Input

Response

0 100 200 300 400 500 600 700 800-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

Time (s)

Acc

e.

(m/s

2 )

Table - Disp

Table - Disp

0 100 200 300 400 500 600 700 800-0.08

-0.06

-0.04

-0.02

0

0.02

0.04

0.06

0.08

Time (s)

Acc

e.

(m/s

2 )

PU4X - 2F

PU4X

100÷

300s

300÷

500s

500÷

700s

DX1-Small Amplitude

Page 10: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Input / Output (Wavelet)Input

Response120 140 160 180 200 220 240 260 280

-0.2

-0.1

0

0.1

0.2

0.3

Time (s)

Dis

p.

(m

)

Table - Disp

Input displacement

320 340 360 380 400 420 440 460 480

-0.2

-0.1

0

0.1

0.2

0.3

Time (s)

Dis

p. (m

)

Table - Disp

Input displacement

520 540 560 580 600 620 640 660 680

-0.2

-0.1

0

0.1

0.2

0.3

Time (s)

Dis

p. (m

)

Table - Disp

Input displacement

120 140 160 180 200 220 240 260 280-0.1

-0.05

0

0.05

0.1

Time (s)

Acce

. (m

/s2 )

PU4X - 2F

Acceleration

320 340 360 380 400 420 440 460 480-0.1

-0.05

0

0.05

0.1

Time (s)

Acce

. (m

/s2 )

PU4X - 2F

Acceleration

520 540 560 580 600 620 640 660 680-0.1

-0.05

0

0.05

0.1

Time (s)

Acce

. (m

/s2 )

PU4X - 2F

Acceleration

Page 11: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

o Sine sweep excitation:

Simulation of sine sweep force

o Linear sweep:

: Argument (rad): Amplitude (m)

: Instantaneous frequency

: Starting frequency (Hz)

: Ending frequency (Hz)

: Sweep rate (Hz/s)

o Linear argument:

o Input sweep:

Amplitude Sweep Initial frequency& phase

Page 12: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Simulation of sine sweep force

o Setting initial parameters

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

X: 0Y: -0.259

Time (s)

Dis

p.(m

)

Input: Measured

Measured displacement

0 50 100 150 200 250 300 350 400-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

Time (s)

Dis

p.(m

)

Theoretical Input

Theoretical displacement

To=0.5s0.18s

0 1 2 3 4 5 6 7 8 9 1010

-20

10-15

10-10

10-5

100

Frequency (Hz)

Mag

nitu

de

PSD

Theoretical input

2.20Hz

2.62Hz

3.03Hz

3.45Hz

3.86Hz

4.28Hz

4.69Hz

5.11Hz

5.50Hz

Simulated sine sweep input

Initial condition (phase)

Page 13: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Comparison bt. simulation & measure

0 50 100 150 200 250 300 350 400-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

Time (s)

Dis

p.(m

)

Theoretical Input

Theoretical displacement

0 1 2 3 4 5 6 7 8 9 1010

-20

10-15

10-10

10-5

100

Frequency (Hz)

Mag

nitu

de

PSD

Theoretical input

2.20Hz

2.62Hz

3.03Hz

3.45Hz

3.86Hz

4.28Hz

4.69Hz

5.11Hz

5.50Hz

0 1 2 3 4 5 6 7 8 9 10-0.4

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

0.4

Time (s)

Dis

p.(m

)

Input displacement

MeasuredTheoretical

Simulated and measured input

Simulated input

0 1 2 3 4 5 6 7 8 9 1010

-20

10-15

10-10

10-5

100

Frequency (Hz)

Mag

nitu

de

PSD

Measured inputTheoretical inputMeasured output

Phase difference happens

Page 14: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Frequency Response Function (FRF)

Measured FRFTheoretical FRFSmoothing techniques for FRF

Page 15: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

FRFo FRFs: Relationship between input forces x(t) and output responses y(t) in the frequency domain

x(t)InputsExciter

Second order FRFs:

Phase:

Coherence:

Type1: Cross spectrum

Type2: Auto spectrum

Page 16: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Measured FRFDX1-Small Amplitude

0 1 2 3 4 5 6 7 8 9 1010

-5

10-4

10-3

10-2

10-1

100

Frequency (Hz)

Mag

nitu

de

FRF

PU1X/Input

0 1 2 3 4 5 6 7 8 9 1010

-6

10-5

10-4

10-3

10-2

10-1

100

Frequency (Hz)

Mag

nitu

de

FRF

PU2X/Input

0 1 2 3 4 5 6 7 8 9 1010

-3

10-2

10-1

100

101

Frequency (Hz)

Mag

nitu

de

FRF

PU4X/Input

0 1 2 3 4 5 6 7 8 9 1010

-4

10-3

10-2

10-1

100

101

Frequency (Hz)

Mag

nitu

de

FRF

PU5X/Input

Floor 1

Floor 2

3.67Hz

3.67Hz 3.67Hz

3.67Hz

Page 17: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Measured FRF

0 1 2 3 4 5 6 7 8 9 1010

-3

10-2

10-1

100

101

Frequency (Hz)

Ma

gn

itu

de

FRF

PU4X/Input

0 1 2 3 4 5 6 7 8 9 10-10

-5

0

5

10

15

20

25

Frequency (Hz)

De

gre

e

Phase

PU4X/Input

0 1 2 3 4 5 6 7 8 9 100

0.2

0.4

0.6

0.8

1Coherence

PU4X/Input

DX1-Small Amplitude

FRF

Phase

Coherence

PU4X and Measured Input

3.67Hz

Page 18: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Theoretical FRFDX1-Small Amplitude

0 1 2 3 4 5 6 7 8 9 1010

-6

10-4

10-2

100

102

Frequency (Hz)

Mag

nitu

de

FRF

PU1X/Measured InputPU1X/Theoretical Input

Floor 2

0 1 2 3 4 5 6 7 8 9 1010

-6

10-4

10-2

100

102

Frequency (Hz)

Mag

nitu

de

FRF

PU2X/Measured InputPU2X/Theoretical Input

0 1 2 3 4 5 6 7 8 9 1010

-6

10-4

10-2

100

102

104

Frequency (Hz)

Mag

nitu

de

FRF

PU4X/Measured InputPU4X/Theoretical Input

0 1 2 3 4 5 6 7 8 9 1010

-6

10-4

10-2

100

102

104

Frequency (Hz)

Mag

nitu

de

FRF

PU5X/Measured InputPU5X/Theoretical Input

3.67Hz 3.67Hz

3.67Hz 3.67Hz

Floor 1

Page 19: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Theoretical FRF

0 1 2 3 4 5 6 7 8 9 1010

-6

10-4

10-2

100

102

104

Frequency (Hz)

Magn

itude

FRF

PU4X/Measured InputPU4X/Theoretical Input

DX1-Small Amplitude

FRF

Phase

Coherence

0 1 2 3 4 5 6 7 8 9 10-30

-20

-10

0

10

20

30

40

50

Frequency (Hz)

De

gre

e

Phase

PU4X/Measured InputPU4X/Theoretical Input

0 1 2 3 4 5 6 7 8 9 100

0.2

0.4

0.6

0.8

1

Frequency (Hz)

Coherence

PU4X/Measured InputPU4X/Theoretical Input

PU4X and Measured Input

3.67Hz

Page 20: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Smoothing techniques for FRFo Single Block Technique (SBT): One blocko Block Overlapping Technique (BOT): Many blockso Frequency Averaging Technique (FAT): Many blocks

0 50 100 150 200 250 300 350 400-0.06

-0.04

-0.02

0

0.02

0.04

0.06

Time (s)

Acc

e. (

m/s

2 )

PU4X - 2F

PU4X

BOT

FAT

SBT

2N data blocks

1 data blocks

Block=4096 samplesTotal 10 blocksFrequency resolution

Blo

ck 1

Blo

ck 2

nfft nfft samples

No overlappingnfft nfft samples

50% overlapping

Page 21: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Smoothing FRF

0 1 2 3 4 5 6 7 8 9 1010

-4

10-3

10-2

10-1

100

101

Frequency (Hz)

Mag

nitu

de

FRF: PU4X/Input

Single blockNo overlapping50% overlapping

0 1 2 3 4 5 6 7 8 9 1010

-4

10-3

10-2

10-1

100

Frequency (Hz)

Mag

nitu

de

FRF: PU4X/Input

50% block overlapping

DX1-Small Amplitude DX1-Medium Amplitude

0 1 2 3 4 5 6 7 8 9 1010

-4

10-3

10-2

10-1

100

101

Frequency (Hz)

Mag

nitu

de

FRF: PU4X/Input

Single blockNo overlapping50% overlapping

0 1 2 3 4 5 6 7 8 9 1010

-3

10-2

10-1

100

Frequency (Hz)

Mag

nitu

de

FRF: PU4X/Input

50% block overlapping

Effects of smoothing techniques on frequencies and damping

(DX1 - Small amplitude)

Smoothing techniques

Natural frequency

[Hz]

Damping ratio[%]

Single block 3.67 0.27Block overlapping (No overlapping)

3.67 0.28

Block overlapping (50%overlapping)

3.67 0.57

Page 22: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Natural frequencies & Damping ratio estimation

Half-power bandwidth method (HPB) Least-squares complex frequency domain method (LSCF)

Page 23: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Half power bandwidth (SDOF system)

2 2.5 3 3.5 4 4.5 5 5.5 60

0.2

0.4

0.6

0.8

1

1.2

1.4FRF: Input/Output

Frequency (Hz)

Mag

nitu

de

3.67Hz

1.32Hz

0.93Hz

2 2.5 3 3.5 4 4.5 5 5.5 60

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6FRF: Input/Output

Frequency (Hz)

Mag

nitu

de

1.54Hz

1.09Hz

3.67Hz

DX1-Small Amplitude

DX1-Medium amplitude

Amplitude f [Hz] [%]Small 3.67 0.27Medium 3.67 0.26Large no data no data

Page 24: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Lease squares complex frequency domain (MDOF system)

o Relationship bt. input force and output response: Complex value FRF matrix

m: Number of measured pointsn: Number of excited pointsf: Frequency variable

o Least squares solution

o FRF matrix identified by measured inputs/ outputs

Min

Page 25: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Further work

• Natural frequencies can be estimated using identified FRFs. Smoothing should be applied to reduce noise

• Both theoretical or measured inputs can be used to identified FRFs

• Damping estimation of the first mode can be obtained by the half power method, however, comprehensive approach via LSCF should be used

• Next work will be based on the LSCF method for estimating damping ratios

Page 26: Modal parameter estimation of low-rise building using sine sweep vibration tests Le Thai Hoa Wind Engineering Research Center Tokyo Polytechnic University

Thank you for your attention