Installation and Commissioning Instructions

MLS Connect Digital

Plug-in Programmable Lighting Control Module

CDW12U5

Page 2: MLS Connect Digital Plug-in Programmable Lighting …...Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 186 P C B 1 Max recommended LIVE (MAINTAINED LIVE) EARTH NEUTRAL

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

186 P

CB

1

LIVE(MAINTAINED LIVE)

EARTHNEUTRAL

MAINS POWERCONNECTIONSTHIS EQUIPMENT MUST BEEARTHEDREMOVE LINK IF A SEPARATEMAINTAINED LIVE SUPPLY ISTO BE CONNECTED.

MLS Bus 1 InMLS Bus 2 InMLS Bus 1 OutMLS Bus 2 Out

MLS BUS CONNECTIONS1.5mm² TWISTED PAIR IN AND 1.5mm² TWISTED PAIR OUT

CABLECHAMBER

Pre-InstalledRigid Link

Connections Available on each Luminaire Socket.

Switched Live - 6A max per channel, 16A max per box.

Neutral

Maintained Live - 2A max per box.

-

Dimming Control+

10 x DSI/DALI ballasts max per channel.40 x DSI/DALI ballasts max per box.Analogue 1-10V ballasts: 20mA, see details on back page.

Connecting the SwitchesThe CDW12U5 is equipped to take a set of up to five SELV switches which will typically be two way, centre-off, momentary rockers, (e.g. the MK K4900 range). The logical function of a switch can be configured from a wide range of options and its action can be associated with any combination of channels. The switch connection consists of a 3-pole pluggable terminal block comprising a common and two returns from normally open contacts. The LCM is supplied fully populated with five plugs.

MLS InterfaceCard (if fitted)

Note that if the SELV status of any one of the switches is compromised by reason of inadequate insulation or segregation of the cabling, then the SELV status of all other switches AND OF THE SENSORS will also be compromised.

Introduction

The CDW12U5 is an intelligent lighting control module (LCM) or connection box providing connections for up to twelve luminaires, up to five sensors and up to five switch inputs. The unit is designed to simplify installation whilst providing an intelligent managed lighting system, including provision for emergency lighting.

Fixing

The box should be attached to a suitable smooth, flat surface, using the two end-located fixing points. Consideration should be given to the need for access to install and maintain the lighting system when choosing a location for the box.

The box must not be distorted when fixing. If the box is to be mounted on an uneven surface it may be necessary to use packing pieces or self-adhesive stand-off feet.

When the box is to be rod-fixed, the fixing should be substantial enough to withstand the action of plugging and unplugging the connectors.

Electrical Connection

The connections to this equipment should be made only by a suitably qualified person and in accordance with current wiring regulations.

A means of disconnection must be incorporated in the fixed mains wiring to this box in accordance with current wiring regulations.

It is imperative that the MLS Bus be wired in the correct type of cable. Normally it should be 1.5mm² unscreened twisted pair. See Application Note AN4001. Do not connect Mains to the MLS Bus.

The cover of the cable chamber is removed by inserting the tip of a flat bladed screwdriver into the catch recess and exerting light pressure on the handle in an inboard direction while lifting the long outboard edge of the cover.

The cable entries, for 20mm conduit, bushes or glands are semi-pierced in the walls of the cable chamber and can easily be removed from the outside with a 20mm hole saw.

If the cables are not routed right into the box through conduit or trunking, a cable restraining gland must be fitted at the cable entry for strain relief.

Connecting the Luminaires

Separate versions of the CDW12U5 are provided to control DSI, DALI and 1-10V Ballasts. (See Part Numbers list on the back page.)

Note: Ballast types CANNOT BE MIXED on a single CDW12U5

The CDW12U5 is equipped with twelve GST 18/6 sockets for the connection of individual luminaires. These connections are equipped to take Ex-Or's Latching Plug Shells. Alternatively non-latching "Wieland style" plugs with hoods of up to 21mm depth may be fitted.

The luminaire sockets are grouped into six channels, each capable of independent control, as follows:

2 channels each controlling 3 luminaire sockets,

2 channels each controlling 2 luminaire sockets,

2 channels each controlling a single luminaire socket.

The CDW12U5 may be commissioned with configurations which allow two or more of the six channels to act together, in any combination required.

Connecting the Sensors

The following SELV sensors are designed to interface to the CDW12U5:

MLS2500CDR Corner-mount Microwave sensor with photocell, semi-flush mounted. Available surface mounted (SM suffix)

MLS2401CDR 360º Microwave sensor with photocell, flush mounted. Available surface mounted (SM suffix)

MLSM2002CDR Control Module for 360º Mini PIR with photocell used with DHS or DHW mini detector head to form integral luminaire-mounted unit

MLSM2002CDRDHPBW Mini Detector with Control Module & Plasterboard Fixing Kit

MLS3000CDR 360º PIR sensor with photocell (flush or surface mount: F or SM suffix)

MLS3003CDR 360º PIR sensor with photocell with photocell with tilting lens (flush or surface mount: F or SM suffix)

MLS3003CDRMB Mid-Bay (for mounting up 12m high) 360º PIR sensor with photocell with tilting lens (flush or surface mount: F or SM suffix)

MLS3003CDRHB Hi-Bay(for mounting up to 16m high) 360º PIR sensor with photocell with tilting lens (flush or surface mount: F or SM suffix)

All connect to the CDW12U5 by means of an Ethernet-style RJ45 connector terminated patch lead which are available ready-made in 3m, 5m and 10m lengths. Up to five detectors may be connected to a CDW12U5 box. The maximum allowable cable length from the CDW12U5 to a detector is 100m.

Positioning the Sensors (for Fixing Details see installation instructions)

The MLS2500CDR is designed to project below the ceiling and to sense a volume of space defined by an slanting cone, radiating from its flat face. Typically sited in the corner of a room ceiling diagonally opposite the door, it can then sense presence over the entire room. At the maximum sensitivity setting it can sense an area extending to 20m from its own position.

The MLS2401CDR is designed to be set in the plane of the ceiling and to sense a conical space vertically below such that its diameter at floor level is equal to 2.8 x the detector's height above floor level (typically 7m diameter with a ceiling height of 2.5m).

Note that in the above two cases microwave presence detection is not completely blocked by materials such as plasterboard, wood, and glass, so the possibility of unwanted presence detection through lightly built partitions should be considered when determining sensor positioning and sensitivity settings.

MLS3000CDR & MLS3003CDR should be positioned in the centre of the occupied space. They sense a conical space vertically below with the following aspect ratios:

Avoid mounting next to an AC unit. For details of tilting lens, see installation instructions.

None of the sensor types above should be positioned within 0.25m of a luminaire.

The MLSM2002CDR and its associated DHS or DHW mini detector head can be mounted within the structure of the luminaire with only the small oval face of the sensor showing. See installation instructions for this product. (For remote mounting in plasterboard or suspended ceilings, use MLSM2002CDRDHPBW.)

For connection of the SELV switches, multi-core cable such as 3-core 300/500V 0.75mm² cable to CMA Reference 3183Y or, for LS0H, to CMA Reference 3183B or CAT5 cable for example may be used. The maximum allowable cable length between the switch mechanism and the CDW12U5 switch terminal block is 100m. Three separate singles cables should not be used.

Aspect Ratio (diameter : height)

TypeMax recommended

mounting height

Office

Mid-Bay

Hi-Bay

Micro Detection -High Sensitivity

Macro Detection -Standard Sensitivity

3.5m

12m

16m

N/A

N/A

4:1 (10m diameter @ 2.5m height)

2:1(20m diameter @10m height)

1.9:1(27m diameter @14m height)

2.8:1(7m diameter @ 2.5m height)

Page 3: MLS Connect Digital Plug-in Programmable Lighting …...Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 186 P C B 1 Max recommended LIVE (MAINTAINED LIVE) EARTH NEUTRAL

The CDW12U5 can be commissioned using the QuickSet Pro hand-held programmer or from a dedicated programme running on a portable PC. Communication from the PC can be by means of a USB Infrared Transceiver which can signal directly to the CDW12U5's onboard infrared port over a short range or via any attached detector over longer ranges. Alternatively a specialised wired serial link can be established with the CDW12U5 itself. The main parameters available for configuration are shown below. Parameters may be re-programmed any number of times and all settings will be retained in the event of a power loss.

Commissioning

PARAMETERS OPTIONS (Defaults, where applicable, shown in bold)

Per Box Parameters:

Switches 1A-5B & 6A-7B (RF1 & 2): Mode User may choose any option for Switch A or Switch B (see section at end of table for details of SELV switch options).

Detector 1-5: Range (On & Off Sensitivity) Max: 100%, 75% or 50% / High: 100%, 75% or 50% / Med: 100%, 75% or 50% / Low: 100%, 75% or 50% / Min: 100% or 75%

Detector 1-5: Sensitivity Fine Mode A, Mode B or Mode C - Applies when Sensitivity is set to Max and during occupancy only (Mode A = Normal, B & C = More Sensitive)

Common: Address 0-127 - MLS address for DALI Emergency test. Default = 0

Common: Switch Map Normal / Direct / Direct 2 / Zero Off Dly / Modes 04-07 (for future use) - Pre-set switch mappings (except Zero Off Dly - instant off option)

Common: LED Inhibit Yes / No - Enables or disables the detector’s LEDs.

Common: Inhibit DALI Init Yes / No - Prevents the DALI ballasts from being initialised every time the box powers up.

Common: Missing Detector Normal / On Full - Puts all outputs on if there’s a detector assigned to a channel and that detector isn’t present.

Common: Slow Dim (mins) 0-254 - Fade time setting, for use with Slow Dim and Slow Brighten switch functions. Default = 0

Common: Bus Absent All On Yes / No - All lights default to ON in the event of a bus failure.

Assigned Detectors Detector 1 - Detector 5 Assigned or Not Assigned to this Channel.

Pcell Source None (--), 1,2,3,4,5 - Photocell 1-5 (in Detectors 1-5) Assigned or Not Assigned to this channel.

Assigned Switches Switch 1A - Switch 5B & Switch 6A - 7B (RF) Assigned or Not Assigned to this channel.

Power Up On / Off

Occ Trigger Mode Presence / Absence / Manual

Low Lux Level (Auto Absence) 0-254 (0 = feature disabled) - Used in manual modes: When it is dark, lights respond to movement automatically without requiring switch press.

Sw Auto Detect Yes / No - Used in manual modes: If set to Yes, presence detection is automatic until a switch press is detected.

Manual I/P Local / Share (Local = Obey locally only; Share = Obey locally and trasmit command on MLS bus)

Occupied Scene Scene 1-6 Scene1

Alt. Occ. Scene A & B Scene 1-6 or -- (feature disabled) - Determines different actions on entry dependent on time of day.

Start Lamps Max / Min

Occupied Timer 10 seconds to 96 hours, Disabled. 20 mins

Photocell Regulate (100%, 90%, 80%, 70%, 60%, 50%) / Passive / Active / Disabled

Bright Out Yes / No

Set-Point Low / High Photocell Lower and Upper Thresholds: 0-1023 (used in Regulating Scene 1). Low = 350; High = 450

Scene 2-6 Output 0-100% or -- (no change) Scene 2 = 80%; 3 = 40%; 4 = 20%; 5 = 10%; 6 = 5%

Transition Scene Scene 1-6 or -- (feature disabled) - Scene interposed between 'Occ Timer' & 'Background Level' to allow movement to restore lights at existing level.

Transition Timer 10 seconds to 96 hours - Determines length of transition scene. 10 secs

Background Level Off

Minimum, 25% or Scene 6 (these options show XTN suffix) for 3 x Occupied Timer, then Off.

Minimum, 25% or Scene 6, 5, 4, 3 or 2 (these options show BLD suffix) until the building has been vacated.

Minimum, 25% or Scene 6, 5, 4, 3 or 2 (Background Timer parameter applies to these options which have no suffix).

Alt. Background Scene A & B Scene 1-6 or -- (no scene) - Determines different actions when the area is vacant dependent on time of day.

Background Tmr 10 seconds to 96 hours or -- (none) - Applies to 'Alt Exit Scenes' and some 'Background Level' scenes (i.e. not XTN and BLD options). When Background Timer

expires, channel's output turns off.

Fade to Off Yes / No

Bus Connect Yes / No

Zones 1-4 None (--), Zone number 1-100 / Common 1,2,3

Zones 1-4 TRX Tx Rx / Tx Only / Rx Only - Determines how zone parameters 1-4 behave with respect to bus commands.

Corridor 1-2: Begin / End None (--), Zone number 1-100 / Bld

Corridor Scene Scene 1-6 or -- (no scene) - Movement within an area's Corridor Begin/End span will cause that area to go to the chosen scene. Direct movement within zones 1-4

will override this and the channel will go to its Entry Scene.

Global 1-2 Rx Yes / No

Ballast 1% DSI, 3% DSI, 10% DSI, 1% DALI, 3% DALI, 10% DALI (Non-Dimming - use default i.e. 1% DSI)

Lamp Max 100%, 90%, 80%, 70%, 50%, 45%, 40%, 35%, 30%, 25%, 20%, 15%, 10%

Burn-In Hrs Burn-in 100 hrs / Cancel / Resume (See Application Note AN4028 - limited functionality via QuickSet Pro)

Quick Burn-In Yes / No - If set to Yes, output remains on until 100-hr burn-in is completed.

Burn-In Dimming Yes / No - If set to Yes, allows temporary (30 secs) dimming in response to manual inputs, even though in 100-hr burn-in mode.

Offset Dimming None (--) to 100% in 10% increments. Allows selected channels to be configured to be brighter than a reference channel according to chosen 'output weightings'

(e.g. Ref Ch = 0% (window row), Ch2 = 10% brighter (adjacent to window row), Ch3 = 30% brighter (furthest from windows) - all would work together to achieve

chosen lux level, maintaining respective percentage differences in output).

Per Channel Parameters:

SELV Switch Options Description

Sustain Imitates movement seen, as a result output of Channel remains ON till the assigned switch with 'SUSTAIN' is active.

Brighten Raises the light level. Works only with dimmable ballasts.

Dim Lowers the light level. Works only with dimmable ballasts.

Off Turns lamp OFF.

Scene 1-6 Recalls Scene assigned (any Scene 1 to 6 as configured).

On Turns lamp ON.

Partition Initiates logical partition of a room. Refer to Application Notes AN4002 & AN4004 for more details.

OneSwitch Simple momentary push-to-make wallswitch that can be used to raise or lower the lighting level or toggle the output of the unit ON or OFF. Short press toggles

output level between ON & OFF, long press will ramp the light level Up or Down.

On-Dim Short Press will turn the output ON, long press will lower the light level.

Off-Brighten Short Press will turn the output OFF, long press will raise the light level.

On / Brighten Short Press will turn the output ON, long press will raise the light level.

Off / Dim Short Press will turn the output OFF, long press will lower the light level.

Emergency Tst Imitates manual test of emergency luminaire by turning OFF the Maintained Live.

Emergency End Restores Maintained Live to end the Emergency Test.

Last Out "Last man out" switch, reduces the Occupied Timer to 10 seconds for a fast time-out when leaving the building.

Door Open / Door Closed Connected to switches detecting whether door is open or closed. Choice depends on type of operation (normally contact would be closed when door is closed).

Keycard In / Keycard Out Connected to switches detecting whether keycard is inserted or not. Choice depends on type of operation.

Edge: On, Off, Scene 1-6 Edge-triggered commands as above - sent only once as the switch is pressed.

Edge: Brighten / Dim Each press increments or decrements the DALI output.

Last Out-On Short press = fast time-out for "last man out"; Long press = turns on at Entry Scene for "first man in".

Time of Day A & B Cause the channels to use Alt. Occupied Scenes A or B and Alt. Background Scenes A or B.

Unoccupied 10% Sends a 'Time Out Now, Go to DALI 10%' message on the MLS bus.

Partition Open / Closed Initiates logical partition of a room - for use with EnOcean reed switch transmitters.

Slow Brighten / Dim Switch input held causes slow ramp / slow fade. Fade time adjustable in Common menu, 1 min to 254 mins.

Page 4: MLS Connect Digital Plug-in Programmable Lighting …...Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 186 P C B 1 Max recommended LIVE (MAINTAINED LIVE) EARTH NEUTRAL

W

D

H

F

D2

An Example Configuration

SW1

SW2

SW3

, (Channels 2 & 4)

, (Channel 3)

, (Channels 4 & 5), (Channels 1, 2 & 6)

123

, (All Channels, 1-6)

W4400O

SW1 SW2

SW

3Part NumbersCDW12U5 Programmable LCM with 12 luminaire sockets, 5 sensor and 5 override socketsCDW12U5-B with MLS Bus operation cardCDW12U5-A c/w Analogue 1-10V dimmingCDW12U5-BA with MLS Bus card c/w Analogue 1-10V dimmingCDW12U5-BAWL with MLS Bus card and wireless switch cardCDW12U5-DALI c/w Digital DALI dimmingCDW12U5-BDALI with MLS Bus card c/w Digital DALI dimmingCDW12U5-BDALIWL with MLS Bus card & wireless switch card c/w Digital DALI dimmingCDW12U5-D c/w DSI dimmingCDW12U5-BD with MLS Bus operation card c/w Digital DSI dimmingCDW12U5-BDWL with MLS Bus & wireless switch card c/w Digital DSI dimmingCDWDC Plug-in Digital Dimming CardCDWAC Plug-in Analogue Dimming CardCDWBC Replacement MLS Bus InterfaceSensors with photocell:MLS2500CDR Corner-mount Microwave, semi-flush mounted MLS2500CDRSM As above - surface mountedMLS2401CDR 360° Microwave, flush mountedMLS2401CDRSM As above - surface mountedMLS3000CDRF 360° PIR, flush mountedMLS300CDRSM As above - surface mountedMLS3003CDRF 360° PIR with tilting lens, flush mountedMLS3003CDRSM As above - surface mountedMLS3003CDRMBF 360° Mid-Bay PIR with tilting lens, flush mountedMLS3003CDRMBSM As above - surface mountedMLS3003CDRHBF 360° Hi-Bay PIR with tilting lens, flush mountedMLS3003CDRHBSM As above - surface mountedMLSM2002CDR Control module for integration within luminaire DHS 360° Mini detector head for use with MLSM2002CDR - silver bezelDHW 360° Mini detector head for use with MLSM2002CDR - white bezelMLSM2002CDRDHPBW Mini Detector c/w Control Module & Plasterboard Mounting KitSensor Patch Leads:BT5E030GY 3m Patch LeadBT5E050GY 5m Patch LeadBT5E100GY 10m Patch LeadLuminaire Leads:CPWL633 3m, 3-core, 6-pole GST 18/6 Plug & Ex-Or Latching ShellCPWL635 5m, 3-core, 6-pole GST 18/6 Plug & Ex-Or Latching ShellCPWL653 3m, 5-core, 6-pole GST 18/6 Plug & Ex-Or Latching ShellCPWL655 5m, 5-core, 6-pole GST 18/6 Plug & Ex-Or Latching ShellCPWL663MF 3m Luminaire Extenstion Cable - 6-pole, 6-core male/female GST 18/6Emergency Luminaire Leads:CPWL643 3m, 4-core, 6-pole GST 18/6 Plug & Ex-Or Latching ShellCPWL645 5m, 4-core, 6-pole GST 18/6 Plug & Ex-Or Latching ShellCPWL663 3m, 6-core, 6-pole GST 18/6 Plug & Ex-Or Latching ShellCPWL665 5m, 6-core, 6-pole GST 18/6 Plug & Ex-Or Latching ShellPlugsCPWL6 GST18/6 Plug & Ex-Or Latching ShellCPWL6S GST-6 Ex-Or Plug-locking mechanism (shell only)CDWIP Switch Input Plugs (set of 5)

Technical Data

Operational Supply: 230V ~ 50Hz

Power Consumption: 18W maximum

Product Rating & Recommended Circuit Protection: 16A

Max Switched Live Load per Channel: 6A

Max Total Switched Live Load: 16A

Digital Dimming Ballasts per Channel: 10 maximum

Digital Dimming Ballasts per LCM: 40 maximum

1-10V Dimming Ballasts per Channel: 20mA (SINKING only). See manufacturer’s specification: worst case 10 ballasts but Philips HF-R, for example, 20 ballasts. Observe Switched Live Load limits above.

Maintained Live Output: 2A total per LCM

Mains Supply Terminal Capacity: 1x2.5mm² or 1x4.0mm²

Override Switch Input Connector: 2.5mm²

MLS Bus Connector: 2.5mm²

MLS Bus Cable: 1.5mm² unscreened twisted pair - see Application Note AN4001

Case Material: Polycarbonate

Case Finish: Lightly textured charcoal grey RAL7016

Height (H) = 50mm (108mm including plug and lead)Width (W) = 315mm (361mm including mounting feet)Depth (D) = 205mm Fixing Centres (F) = 340mm Weight = 1.55 kg

A school classroom, where a sophisticated blend of manual and automatic control is required, with overall manual control by staff augmented by automatic dimming control of luminaires adjacent to large windows and the automatic switch-off of the lights following an often ragged quitting of the room at the end of a teaching session, where staff typically will not be the last to leave.

At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.

W

D

H

F

D2

Ex-Or operates a genuine policy of continuous improvement. You may expect the specification to be regularly enhanced. For the latest technical information please visit www.ex-or.com

Important Additional Notes

1. The CDW12U5 must be earthed as it provides the only path to earth for luminaires connected through it.

2. A dimming control output should be connected only to the control inputs of ballasts, never to another channel's dimming output and never to other types of equipment.

3. Although nominally 12V, the dimming control outputs are not to be treated as SELV, due to their passage through multiple luminaire enclosures and therefore should be treated with the same respect as mains with regard to wiring practice.

4. This equipment switches lights no more frequently than would a responsible human occupant. However, manufacturers of some particular lighting types (e.g. '2D' luminaires) may specify a maximum number of switching cycles and/or a minimum on-time in order to achieve a predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic controls in this respect.