18
Mission Support Alliance Page 1 of 18 Statement of Work Title: Fire Alarm / Fire Suppression Training for Hanford Fire Department Fire Systems Maintenance Revision Number: 1 Date: 2/14/2017 1.0 INTRODUCTION / BACKGROUND The Fire Systems Maintenance (FSM) group within Mission Support Alliance (MSA) maintains, inspects, and tests fire alarm systems and fire suppression systems across the Hanford Site. Their electricians and pipefitters who conduct this work are in need of some training to keep them qualified to perform the work. FSM also uses firefighters from Testing & Services (T&S) group within MSA to assist the electricians and pipefitters. MSA is seeking one class for each of the three job classifications identified above. The T&S class, however, will be a shorter, less detailed version of the pipefitter’s and electrician’s classes. 2.0 OBJECTIVE It’s been several years since the electricians, pipefitters, and T&S personnel have had any training. Previously, Oklahoma State University delivered the classes: one for electricians and one for pipefitters. These classes are on each person’s training plan which means this is required training with a requalification to be completed every three years. Currently, the T&S firefighters do not have any requirement for similar training. But through this Statement of Work (SOW) and subsequent efforts that will change. Therefore, the objective of this SOW is to request for the Subcontractor to provide the required training to FSM’s electricians and pipefitters, as well as a shorter class for T&S firefighters. 3.0 DESCRIPTION OF WORK SPECIFIC 3.1 General Description of Work for All Training to Be Delivered a. This SOW is requesting for the Subcontractor to deliver the training at the Hanford Site in Richland, Washington. The classroom portion will be held at Hanford Fire Station #2, 600 Area, 609-A building, Rm. 20. The hands-on part of the class will be held at 2721EA/shop/200E facility where fire alarm panel mockups reside. MSA is requesting the three classes described within this SOW. b. The Subcontractor shall submit to MSA for approval a lesson plan with learning objective and the PowerPoint to be used.

Mission Support Alliance - Hanford Site · This course content will be a shorter and less detailed version of the classes for pipefitters and electricians. This class will combine

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

  • Mission Support Alliance

    Page 1 of 18

    Statement of Work

    Title: Fire Alarm / Fire Suppression Training for Hanford Fire Department Fire Systems

    Maintenance

    Revision Number: 1

    Date: 2/14/2017

    1.0 INTRODUCTION / BACKGROUND

    The Fire Systems Maintenance (FSM) group within Mission Support Alliance (MSA) maintains,

    inspects, and tests fire alarm systems and fire suppression systems across the Hanford Site. Their

    electricians and pipefitters who conduct this work are in need of some training to keep them

    qualified to perform the work. FSM also uses firefighters from Testing & Services (T&S) group

    within MSA to assist the electricians and pipefitters.

    MSA is seeking one class for each of the three job classifications identified above. The T&S class,

    however, will be a shorter, less detailed version of the pipefitter’s and electrician’s classes.

    2.0 OBJECTIVE

    It’s been several years since the electricians, pipefitters, and T&S personnel have had any training.

    Previously, Oklahoma State University delivered the classes: one for electricians and one for

    pipefitters. These classes are on each person’s training plan which means this is required training

    with a requalification to be completed every three years.

    Currently, the T&S firefighters do not have any requirement for similar training. But through this

    Statement of Work (SOW) and subsequent efforts that will change.

    Therefore, the objective of this SOW is to request for the Subcontractor to provide the required

    training to FSM’s electricians and pipefitters, as well as a shorter class for T&S firefighters.

    3.0 DESCRIPTION OF WORK – SPECIFIC

    3.1 General Description of Work for All Training to Be Delivered

    a. This SOW is requesting for the Subcontractor to deliver the training at the Hanford Site in Richland, Washington. The classroom portion will be held at Hanford Fire Station #2, 600

    Area, 609-A building, Rm. 20. The hands-on part of the class will be held at

    2721EA/shop/200E facility where fire alarm panel mockups reside. MSA is requesting the

    three classes described within this SOW.

    b. The Subcontractor shall submit to MSA for approval a lesson plan with learning objective and the PowerPoint to be used.

  • Mission Support Alliance

    Page 2 of 18

    c. The Subcontractor shall design, develop, and deliver a training course on Fire Suppression Systems that will include inspection, testing, and maintenance of such systems.

    d. The course shall include both classroom sessions covering the various types of fire suppression systems in general use and specifically covering the systems in use at the Hanford Site, as well

    as hands-on exercises working on a majority of the fire suppression systems in use at Hanford.

    e. The classroom sessions shall include a brief overview of the NFPA Standard 25: Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems requirements.

    f. The exercise portion of the course shall include classroom and live system hands-on exercises following the inspection, testing, and maintenance procedures applicable to the chosen

    Hanford systems.

    g. FSM will identify the proposed in-place live Site systems to be used as part of a field exercise to provide hands-on experience. For use in the hands-on classroom activities, the

    Subcontractor shall provide mock-ups for a minimum of two (2) of the fire suppression systems

    and/or their components in use at Hanford.

    h. Any Subcontractor supplied classroom handouts, drawings, and classroom presentations used in delivering the course become MSA owned materials and are to remain with MSA at the

    conclusion of the training.

    i. The classes for the pipefitters and electricians shall be delivered in a single class format, with of a minimum of five (5) students up to twelve (12) students maximum.

    j. This SOW will allow for optional years of extension as necessary to provide additional training as follows:

    Initial training for NEW FSM Electricians and Pipefitters if or when new members are hired

    in to replace FSM members due to attrition.

    For the requalification training for the pipefitters and electricians once every three years.

    For requalification training the Subcontractor shall update presentations and course materials as needed to reflect changes and updates to pertinent codes and standards.

    Initial training for NEW T&S firefighters if or when new firefighters are hired in to replace firefighters due to attrition.

    T&S Firefighters do not require requalification.

    All subsequent training will be on an as-needed-basis only.

  • Mission Support Alliance

    Page 3 of 18

    3.2 Specific Requirements for Delivery of Fire Suppression Systems Inspection, Testing and

    Maintenance Training.

    Course Objective:

    Intended Audience: FSM PIPEFITTER.

    At the conclusion of the class, students will have an understanding of various types of fire

    suppression systems and how to perform various functions necessary to the inspection, testing and

    maintenance of such systems with priority given to the fire suppression systems in use at the

    Hanford Site. The Subcontractor will update presentations and course materials as needed to

    reflect changes and updates to pertinent codes and standards. Training shall include the following:

    a. Inspection:

    Fire Suppression System Inspection training shall include classroom discussions and hands

    on exercises covering, as a minimum, how to perform inspections for:

    Backflow devices

    Fire Sprinkler Systems (wet and dry pipe, pre-action, deluge, anti-freeze and standpipe systems) including the schedule for inspections

    Schedule for various inspections, i.e. annual, monthly, etc.

    b. Testing:

    Fire Suppression System Testing training shall include classroom discussions and hands-

    on exercises that shall describe how to properly perform required tests and, as a minimum,

    shall cover:

    Overview of Hanford Site Fire Protection Systems including a description of the system and how the system operates.

    Discussion of system hardware components, i.e. piping, valves, backflow preventers

    Hydrostatic testing

    System flushing

    Valve trip tests

    Pressure reducing valve testing

    c. Maintenance:

  • Mission Support Alliance

    Page 4 of 18

    Fire Suppression System Maintenance training shall include classroom discussions and

    hand on exercises that cover:

    Maintenance procedures required by applicable NFPA codes and standards

    Manufacturer’s required/suggested maintenance for Hanford systems

    Maintenance when equipment still under manufacturer’s warranty

    Specifically performing maintenance functions on the several of the Hanford systems including but not limited maintenance on valves, pressure gages, and drains.

    d. Hands-On Exercises:

    For inspection, testing, and maintenance shall include work on:

    Wet pipe systems

    Dry pipe systems

    Pre-action and deluge systems

    Dry chemical systems

    Antifreeze systems

    e. Topics to Include:

    1. The NFPA and Introductory Concepts

    2. Objectives of Inspection, Testing, & Maintenance

    Acceptance testing

    Routine inspection and testing

    Preventative Maintenance & Repairs

    3. Automatic Sprinklers

    Types

    Applications

    4. Types of automatic sprinkler systems

  • Mission Support Alliance

    Page 5 of 18

    Wet

    Dry

    Pre-action

    Deluge

    Anti-freeze

    Standpipe systems

    5. Important Hardware Components

    Piping

    Indicating Control Values

    Hangers

    Fire Department Connections

    Backflow Preventers

    6. Acceptance Inspection and Testing

    Comparison with approved plans

    System flushing

    Hydrostatic testing

    Alarm and supervisory system testing

    Valve tripping and resetting

    7. Routine Inspection, Testing & Maintenance

    Valves

    Piping

    Sprinklers

  • Mission Support Alliance

    Page 6 of 18

    Hangers

    Occupancy Consideration

    Alarm Tests

    Trip tests and component testing

    8. Overview of Inspection, Testing & Maintenance of any Hanford Site Fire Protection

    System not covered above, including Dry Chemical Systems and Antifreeze systems.

    3.3 Specific Requirements For Delivery Of Fire Alarm Systems Inspection, Testing, And

    Maintenance Training:

    COURSE OBJECTIVE

    Intended Audience: FSM Electricians

    The overall goal will be at the conclusion of the class, students will have an understanding of

    various types of fire alarm systems and how to perform the functions necessary for the inspection,

    testing and maintenance of such systems, with priority given to the fire alarm systems in use at the

    Hanford Site. The Subcontractor will update presentations and course materials as needed to

    reflect changes and updates to pertinent codes and standards. Training shall include the following:

    1. Inspection: Fire Alarm System Inspection training shall include classroom discussions and hands on exercises covering, as a minimum, how to perform inspections for:

    Emergency and exit lighting

    Fire Alarm monitoring

    Various types of detectors

    Schedule for various inspections, i.e. annual, monthly, etc.

    2. Testing: Fire Alarm System Testing training shall include classroom discussions and hands-on exercises that shall describe how to properly perform required tests and, as a

    minimum, shall cover:

    Fire Alarm and components testing

    Detector (i.e. smoke and heat) system testing

  • Mission Support Alliance

    Page 7 of 18

    3. Maintenance: Fire Alarm System Maintenance training shall include classroom discussions and hand on exercises that cover:

    Maintenance procedures required by applicable NFPA codes and standards

    Manufacturer’s required/suggested maintenance for Hanford systems

    Maintenance when equipment still under manufacturer’s warranty

    Performance of maintenance functions on alarm system components

    4. Hands-On Exercises shall, as a minimum, include work on:

    Smoke and/or flame detectors

    Notification devices

    Manual pull boxes

    5. Topics to include:

    The NFPA and Introductory Concepts /Overview

    The System Concept

    Functions and Objectives of Emergency Signaling Systems

    Basic Components

    Basic Functional Flow

    6. Basic Functional Categories of Fire Alarm and Emergency Signaling Systems

    Types of Systems

    7. Control Panels, Circuitry and Devices (Conventional vs Intelligent)

    Wire, Fiber and RF Communication Modes vs Mechanical, Hydraulic and Pneumatic Modes

    Control Panel Operation Summary

    Initiating-Input and Notification-Output Circuits Operation and NFPA classification summary

  • Mission Support Alliance

    Page 8 of 18

    Classification Summary

    Signal Compatibility

    Alarm Signal Verification

    Conventional Systems and Initiating Devices

    Intelligent and Addressable Systems and Initiating Devices

    Network Systems

    Supervision of Circuits, Power Supplies and Devices

    Power Supplies

    8. Fire Alarm Initiating Device Types:

    Intelligent and Conventional Initiating Devices

    Manual Fire Alarm Stations/Boxes

    Automatic Fire Detector Types

    Heat Detectors

    Smoke Detectors

    Ionization Smoke Detectors

    Photoelectric Smoke Detectors

    Air Duct Smoke Detectors

    Flame Detectors

    Gas Detectors

    9. Fire Alarm Notification Appliances-Alarm Signal Notification

    Evacuation Signals

    ADA and Evacuation Signals

  • Mission Support Alliance

    Page 9 of 18

    Signal Evacuation Audible Codes

    Trouble Signals

    Annunciation

    Application of Notification Appliance and Structural Characteristics

    10. Fire Extinguishing Systems

    Sprinkler System Water Alarm and Supervisory Signals

    Special Hazard Protection Systems

    11. Fire Detection System Design

    Design Objectives

    Design Criteria

    System Design

    System Features and Unwanted Alarm Prevention

    12. Engineering Documents

    Specifications

    Drawings

    13. Approvals, Authorities and Acceptance

    U.L. Listings and F.M. Approvals

    Systems Certification

    Authority Having Jurisdiction

    NFPA Code Summary

    14. Inspection, Testing, & Maintenance

    Acceptance Testing

    Systems Maintenance and Periodic Testing

  • Mission Support Alliance

    Page 10 of 18

    Detector Maintenance System Testing

    Maintenance procedures-NFPA Codes & Standards

    Manufacturer’s Required/Suggested Maintenance for Hanford

    Manufacturer’s Warranty Maintenance

    15. Hands-On Exercises

    Smoke and/or flame detectors

    Notification devices

    Manual pull boxes

    3.4 Specific Requirements for Delivery of Introduction to Fire Alarm System and Fire

    Suppression Systems Training:

    COURSE OBJECTIVE

    Intended Audience: FSM Testing and Services (T&S) Firefighters

    This course content will be a shorter and less detailed version of the classes for pipefitters and

    electricians. This class will combine the basics from those two classes.

    This training will consist of two (2) eight (8) hour training sessions for a total of sixteen (16) hours.

    One class will be on fire suppression systems. The second class will cover fire alarms. A total of

    10 (ten) students will attend each session.

    3.4.a Fire Suppression class. (8 hours)

    Topics to Include:

    1. Introduction to inspections, testing, and maintenance of fire suppression systems. The

    NFPA and Introductory Concepts

    2. Objectives of Inspection, Testing, & Maintenance

    Acceptance testing

    Routine inspection and testing

    Preventative Maintenance & Repairs

  • Mission Support Alliance

    Page 11 of 18

    3. Automatic Sprinklers

    Types

    Applications

    4. Types of automatic sprinkler systems

    Wet

    Dry

    Pre-action

    Deluge

    Anti-freeze

    Standpipe systems

    5. Important Hardware Components

    Piping

    Indicating Control Values

    Hangers

    Fire Department Connections

    Backflow Preventers

    6. Acceptance Inspection and Testing

    Comparison with approved plans

    System flushing

    Hydrostatic testing

    Alarm and supervisory system testing

    Valve tripping and resetting

    7. Routine Inspection, Testing & Maintenance

  • Mission Support Alliance

    Page 12 of 18

    Valves

    Piping

    Sprinklers

    Hangers

    Occupancy Consideration

    Alarm Tests

    Trip tests and component testing

    3.4.b. Fire Alarm class. (8 hours)

    Topics to include:

    1. Inspection: Fire Alarm System Inspection training shall include classroom discussions and hands on exercises covering, as a minimum, how to perform inspections for:

    Emergency and exit lighting

    Fire Alarm monitoring

    Various types of detectors

    Schedule for various inspections, i.e. annual, monthly, etc.

    2. Testing: Fire Alarm System Testing training shall include classroom discussions and hands-on exercises that shall describe how to properly perform required tests and, as a

    minimum, shall cover:

    Fire Alarm and components testing

    Detector (i.e. smoke and heat) system testing

    3. Maintenance: Fire Alarm System Maintenance training shall include classroom discussions and hand on exercises that cover:

    Maintenance procedures required by applicable NFPA codes and standards

    Manufacturer’s required/suggested maintenance for Hanford systems

  • Mission Support Alliance

    Page 13 of 18

    Maintenance when equipment still under manufacturer’s warranty

    Performance of maintenance functions on alarm system components

    4. Hands-On Exercises shall, as a minimum, include work on:

    Smoke and/or flame detectors

    Notification devices

    Manual pull boxes

    5. Topics to include:

    1. The NFPA and Introductory Concepts /Overview

    2. The System Concept

    3. Functions and Objectives of Emergency Signaling Systems

    4. Basic Components

    5. Basic Functional Flow

    6. Basic Functional Categories of Fire Alarm and Emergency Signaling Systems

    7. Types of Systems

    8. Control Panels, Circuitry and Devices (Conventional vs Intelligent)

    9. Fire Alarm Initiating Device Types:

    10. Fire Alarm Notification Appliances-Alarm Signal Notification

    11. Emergency Voice Alarm Communication Systems

    12. Fire Extinguishing Systems

    Sprinkler System Water Alarm and Supervisory Signals

    Special Hazard Protection Systems

    13. Approvals, Authorities and Acceptance

    U.L. Listings and F.M. Approvals

  • Mission Support Alliance

    Page 14 of 18

    Systems Certification

    Authority Having Jurisdiction

    NFPA Code Summary

    14. Inspection, Testing, & Maintenance

    Acceptance Testing

    Systems Maintenance and Periodic Testing

    Detector Maintenance System Testing

    Maintenance procedures-NFPA Codes & Standards

    Manufacturer’s Required/Suggested Maintenance for Hanford

    Manufacturer’s Warranty Maintenance

    15. Hands-On Exercises

    Smoke and/or flame detectors

    Notification devices

    Manual pull boxes

    3.5 EQUIPMENT PURCHASE OPTION

    MSA retains the right to negotiate (through the assigned Contract Specialist) an option to

    purchase any of the Subcontractor provided mock-ups used in classroom presentation.

    4.0 REQUIREMENTS

    General

    For any work performed on the Hanford Site or any MSA controlled facility, the provisions of the

    On Site Services Special Provisions, will apply to Subcontractor personnel.

    4.1 Engineering Requirements

    None

  • Mission Support Alliance

    Page 15 of 18

    4.2 Environment, Safety, & Health (ES&H) Requirements

    The Subcontractor shall exercise a degree of care commensurate with the work and the associated

    hazards. The Subcontractor shall ensure that management of safety and environmental functions

    and activities is an integral and visible part of the Subcontractor’s work planning and execution

    processes. The Subcontractor shall flow down safety and environmental requirements to the lowest

    tier Subcontractor performing work on the Hanford site commensurate with the risk and

    complexity of the work.

    Subcontractors and its lower-tier subcontractors shall be responsible to complete an Employee Job

    Task Analysis (EJTA) in accordance with MSC-PRO-11058 for any of the following situations:

    For any subcontractor employee who will be on the Hanford Site for more than 30 days

    in a year.

    For any subcontractor employee who may potentially be exposed to hazards (e.g.

    radiological, beryllium, hazardous wastes, noise) while performing in accordance with

    the subcontract statement of work.

    For any subcontractor employee enrolled in a medical or exposure monitoring

    program required by 10 CFR 851, and/or any other applicable federal, state or local

    regulation or other obligation.

    If any of the above conditions are met, the subcontractor and its lower-tier subcontractor employee

    is to have a current approved EJTA prior to that employee beginning work on the Hanford Site.

    Buyer’s Safety and Health Procedures are available on the internet at

    http://www.hanford.gov/pmm/page.cfm/Construction. The documents on this site are kept current

    and are available for Subcontractors and lower-tier Subcontractor use.

    4.3 Quality Assurance (QA) Requirements

    The work activities for this statement of work shall be performed in accordance with the following

    MSA Quality Assurance Program and Procedures:

    4.4 Government Property

    The Subcontractor will be responsible for managing the Government-owned property as required

    in the Subcontract Provisions: None

    http://www.hanford.gov/pmm/page.cfm/Construction

  • Mission Support Alliance

    Page 16 of 18

    5.0 PERSONNEL REQUIREMENTS

    5.1 Training and Qualifications

    Subcontractor shall ensure that its personnel meet and maintain the appropriate training,

    qualification and certification requirements.

    The following types of training qualifications are required:

    Required Qualifications:

    A. Ten years’ experience training on fire alarms and fire suppression systems.

    B. Ten years’ experience in the fire protection industry.

    C. National Institute for the Certification of Engineering Technicians (NICET) certifications in the following areas:

    Inspection & Testing of Water-Based Fire Protection Systems—Level III

    Fire Alarm Systems—Level II

    Suppression Systems—Level II

    5.2 Security and Badging Requirements

    For any on site work, see Special Provisions – On Site Services for details.

    Subcontractor employees will be required to submit to vehicle searches and not personally carry

    or transport certain prohibited articles.

    Will the Subcontractor require an access authorization (security clearance)? No

    5.3 Work Location / Potential Access Requirements

    Work will be performed at the 2721EA/shop/200E facility, Building 609J Training Room, and

    may require entry into MO-286//200E building to meet with FSM Engineering staff.

  • Mission Support Alliance

    Page 17 of 18

    5.4 Site Access and Work Hours

    Hanford personnel at the Hanford Site work a standard 4/10 schedule. The standard work week

    consist of ten (10) hours of work between 6:00 am and 4:30 pm, with one-half hour designated as

    an unpaid period for lunch, Monday through Thursday.

    Work performed outside normal operating hours shall be coordinated and/or approved through the

    BTR and/or the Contract Specialist prior to performing the work.

    6.0 MEETINGS

    Subcontractor shall participate in all meetings as required by the Buyer’s Technical Representative

    (BTR).

    7.0 DELIVERABLES AND PERFORMANCE SCHEDULE REQUIREMENTS

    7.1 Deliverables

    The Subcontractor shall submit to BTR for approval:

    1. Lesson plan with learning objectives in PDF format

    2. PowerPoint to be used.

    Subcontractor will submit above items 15 days before training begins. BTR will have 3 days to

    approve or reject.

    Subcontractor shall deliver training as defined within this SOW.

    7.2.1 Schedule

    Start Date: Anticipated start date is April 1, 2017

    Completion Date: September 29, 2019

    8.0 SPECIAL REQUIREMENTS

    Reporting Administration Meetings

    General purpose of meetings is for the coordination, control, and direction of the Work. In addition

    to meetings addressed by this Section, Subcontractor may be required by other Sections and other

    Subcontract documents to conduct special-purpose meetings and various safety meetings and

    briefings.

  • Mission Support Alliance

    Page 18 of 18

    MSA will issue meeting notices and prepare an agenda and minutes for each meeting addressed in

    this Section. When applicable, minutes will identify action items, assigned actionees, and due

    dates.

    KICKOFF MEETING - Before start of the Work, MSA will conduct a conference at a time and Hanford Site location agreed to by Subcontractor and MSA. Invited attendees will

    include MSA, Subcontractor, key lower tier subcontractors and others having an interest

    in the Work. Purpose of the conference is the coordination of Work start up and

    familiarization of project participants with the Work and worksite.

    PROGRESS MEETINGS - At the end of every class, MSA may conduct a maximum one hour progress meeting at time and Hanford Site location determined by MSA. Invited

    attendees will include MSA, Subcontractor and interested parties to review the class and

    determine changes that need to be made.