Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
Mission Support Alliance
Page 1 of 18
Statement of Work
Title: Fire Alarm / Fire Suppression Training for Hanford Fire Department Fire Systems
Maintenance
Revision Number: 1
Date: 2/14/2017
1.0 INTRODUCTION / BACKGROUND
The Fire Systems Maintenance (FSM) group within Mission Support Alliance (MSA) maintains,
inspects, and tests fire alarm systems and fire suppression systems across the Hanford Site. Their
electricians and pipefitters who conduct this work are in need of some training to keep them
qualified to perform the work. FSM also uses firefighters from Testing & Services (T&S) group
within MSA to assist the electricians and pipefitters.
MSA is seeking one class for each of the three job classifications identified above. The T&S class,
however, will be a shorter, less detailed version of the pipefitter’s and electrician’s classes.
2.0 OBJECTIVE
It’s been several years since the electricians, pipefitters, and T&S personnel have had any training.
Previously, Oklahoma State University delivered the classes: one for electricians and one for
pipefitters. These classes are on each person’s training plan which means this is required training
with a requalification to be completed every three years.
Currently, the T&S firefighters do not have any requirement for similar training. But through this
Statement of Work (SOW) and subsequent efforts that will change.
Therefore, the objective of this SOW is to request for the Subcontractor to provide the required
training to FSM’s electricians and pipefitters, as well as a shorter class for T&S firefighters.
3.0 DESCRIPTION OF WORK – SPECIFIC
3.1 General Description of Work for All Training to Be Delivered
a. This SOW is requesting for the Subcontractor to deliver the training at the Hanford Site in Richland, Washington. The classroom portion will be held at Hanford Fire Station #2, 600
Area, 609-A building, Rm. 20. The hands-on part of the class will be held at
2721EA/shop/200E facility where fire alarm panel mockups reside. MSA is requesting the
three classes described within this SOW.
b. The Subcontractor shall submit to MSA for approval a lesson plan with learning objective and the PowerPoint to be used.
Mission Support Alliance
Page 2 of 18
c. The Subcontractor shall design, develop, and deliver a training course on Fire Suppression Systems that will include inspection, testing, and maintenance of such systems.
d. The course shall include both classroom sessions covering the various types of fire suppression systems in general use and specifically covering the systems in use at the Hanford Site, as well
as hands-on exercises working on a majority of the fire suppression systems in use at Hanford.
e. The classroom sessions shall include a brief overview of the NFPA Standard 25: Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems requirements.
f. The exercise portion of the course shall include classroom and live system hands-on exercises following the inspection, testing, and maintenance procedures applicable to the chosen
Hanford systems.
g. FSM will identify the proposed in-place live Site systems to be used as part of a field exercise to provide hands-on experience. For use in the hands-on classroom activities, the
Subcontractor shall provide mock-ups for a minimum of two (2) of the fire suppression systems
and/or their components in use at Hanford.
h. Any Subcontractor supplied classroom handouts, drawings, and classroom presentations used in delivering the course become MSA owned materials and are to remain with MSA at the
conclusion of the training.
i. The classes for the pipefitters and electricians shall be delivered in a single class format, with of a minimum of five (5) students up to twelve (12) students maximum.
j. This SOW will allow for optional years of extension as necessary to provide additional training as follows:
Initial training for NEW FSM Electricians and Pipefitters if or when new members are hired
in to replace FSM members due to attrition.
For the requalification training for the pipefitters and electricians once every three years.
For requalification training the Subcontractor shall update presentations and course materials as needed to reflect changes and updates to pertinent codes and standards.
Initial training for NEW T&S firefighters if or when new firefighters are hired in to replace firefighters due to attrition.
T&S Firefighters do not require requalification.
All subsequent training will be on an as-needed-basis only.
Mission Support Alliance
Page 3 of 18
3.2 Specific Requirements for Delivery of Fire Suppression Systems Inspection, Testing and
Maintenance Training.
Course Objective:
Intended Audience: FSM PIPEFITTER.
At the conclusion of the class, students will have an understanding of various types of fire
suppression systems and how to perform various functions necessary to the inspection, testing and
maintenance of such systems with priority given to the fire suppression systems in use at the
Hanford Site. The Subcontractor will update presentations and course materials as needed to
reflect changes and updates to pertinent codes and standards. Training shall include the following:
a. Inspection:
Fire Suppression System Inspection training shall include classroom discussions and hands
on exercises covering, as a minimum, how to perform inspections for:
Backflow devices
Fire Sprinkler Systems (wet and dry pipe, pre-action, deluge, anti-freeze and standpipe systems) including the schedule for inspections
Schedule for various inspections, i.e. annual, monthly, etc.
b. Testing:
Fire Suppression System Testing training shall include classroom discussions and hands-
on exercises that shall describe how to properly perform required tests and, as a minimum,
shall cover:
Overview of Hanford Site Fire Protection Systems including a description of the system and how the system operates.
Discussion of system hardware components, i.e. piping, valves, backflow preventers
Hydrostatic testing
System flushing
Valve trip tests
Pressure reducing valve testing
c. Maintenance:
Mission Support Alliance
Page 4 of 18
Fire Suppression System Maintenance training shall include classroom discussions and
hand on exercises that cover:
Maintenance procedures required by applicable NFPA codes and standards
Manufacturer’s required/suggested maintenance for Hanford systems
Maintenance when equipment still under manufacturer’s warranty
Specifically performing maintenance functions on the several of the Hanford systems including but not limited maintenance on valves, pressure gages, and drains.
d. Hands-On Exercises:
For inspection, testing, and maintenance shall include work on:
Wet pipe systems
Dry pipe systems
Pre-action and deluge systems
Dry chemical systems
Antifreeze systems
e. Topics to Include:
1. The NFPA and Introductory Concepts
2. Objectives of Inspection, Testing, & Maintenance
Acceptance testing
Routine inspection and testing
Preventative Maintenance & Repairs
3. Automatic Sprinklers
Types
Applications
4. Types of automatic sprinkler systems
Mission Support Alliance
Page 5 of 18
Wet
Dry
Pre-action
Deluge
Anti-freeze
Standpipe systems
5. Important Hardware Components
Piping
Indicating Control Values
Hangers
Fire Department Connections
Backflow Preventers
6. Acceptance Inspection and Testing
Comparison with approved plans
System flushing
Hydrostatic testing
Alarm and supervisory system testing
Valve tripping and resetting
7. Routine Inspection, Testing & Maintenance
Valves
Piping
Sprinklers
Mission Support Alliance
Page 6 of 18
Hangers
Occupancy Consideration
Alarm Tests
Trip tests and component testing
8. Overview of Inspection, Testing & Maintenance of any Hanford Site Fire Protection
System not covered above, including Dry Chemical Systems and Antifreeze systems.
3.3 Specific Requirements For Delivery Of Fire Alarm Systems Inspection, Testing, And
Maintenance Training:
COURSE OBJECTIVE
Intended Audience: FSM Electricians
The overall goal will be at the conclusion of the class, students will have an understanding of
various types of fire alarm systems and how to perform the functions necessary for the inspection,
testing and maintenance of such systems, with priority given to the fire alarm systems in use at the
Hanford Site. The Subcontractor will update presentations and course materials as needed to
reflect changes and updates to pertinent codes and standards. Training shall include the following:
1. Inspection: Fire Alarm System Inspection training shall include classroom discussions and hands on exercises covering, as a minimum, how to perform inspections for:
Emergency and exit lighting
Fire Alarm monitoring
Various types of detectors
Schedule for various inspections, i.e. annual, monthly, etc.
2. Testing: Fire Alarm System Testing training shall include classroom discussions and hands-on exercises that shall describe how to properly perform required tests and, as a
minimum, shall cover:
Fire Alarm and components testing
Detector (i.e. smoke and heat) system testing
Mission Support Alliance
Page 7 of 18
3. Maintenance: Fire Alarm System Maintenance training shall include classroom discussions and hand on exercises that cover:
Maintenance procedures required by applicable NFPA codes and standards
Manufacturer’s required/suggested maintenance for Hanford systems
Maintenance when equipment still under manufacturer’s warranty
Performance of maintenance functions on alarm system components
4. Hands-On Exercises shall, as a minimum, include work on:
Smoke and/or flame detectors
Notification devices
Manual pull boxes
5. Topics to include:
The NFPA and Introductory Concepts /Overview
The System Concept
Functions and Objectives of Emergency Signaling Systems
Basic Components
Basic Functional Flow
6. Basic Functional Categories of Fire Alarm and Emergency Signaling Systems
Types of Systems
7. Control Panels, Circuitry and Devices (Conventional vs Intelligent)
Wire, Fiber and RF Communication Modes vs Mechanical, Hydraulic and Pneumatic Modes
Control Panel Operation Summary
Initiating-Input and Notification-Output Circuits Operation and NFPA classification summary
Mission Support Alliance
Page 8 of 18
Classification Summary
Signal Compatibility
Alarm Signal Verification
Conventional Systems and Initiating Devices
Intelligent and Addressable Systems and Initiating Devices
Network Systems
Supervision of Circuits, Power Supplies and Devices
Power Supplies
8. Fire Alarm Initiating Device Types:
Intelligent and Conventional Initiating Devices
Manual Fire Alarm Stations/Boxes
Automatic Fire Detector Types
Heat Detectors
Smoke Detectors
Ionization Smoke Detectors
Photoelectric Smoke Detectors
Air Duct Smoke Detectors
Flame Detectors
Gas Detectors
9. Fire Alarm Notification Appliances-Alarm Signal Notification
Evacuation Signals
ADA and Evacuation Signals
Mission Support Alliance
Page 9 of 18
Signal Evacuation Audible Codes
Trouble Signals
Annunciation
Application of Notification Appliance and Structural Characteristics
10. Fire Extinguishing Systems
Sprinkler System Water Alarm and Supervisory Signals
Special Hazard Protection Systems
11. Fire Detection System Design
Design Objectives
Design Criteria
System Design
System Features and Unwanted Alarm Prevention
12. Engineering Documents
Specifications
Drawings
13. Approvals, Authorities and Acceptance
U.L. Listings and F.M. Approvals
Systems Certification
Authority Having Jurisdiction
NFPA Code Summary
14. Inspection, Testing, & Maintenance
Acceptance Testing
Systems Maintenance and Periodic Testing
Mission Support Alliance
Page 10 of 18
Detector Maintenance System Testing
Maintenance procedures-NFPA Codes & Standards
Manufacturer’s Required/Suggested Maintenance for Hanford
Manufacturer’s Warranty Maintenance
15. Hands-On Exercises
Smoke and/or flame detectors
Notification devices
Manual pull boxes
3.4 Specific Requirements for Delivery of Introduction to Fire Alarm System and Fire
Suppression Systems Training:
COURSE OBJECTIVE
Intended Audience: FSM Testing and Services (T&S) Firefighters
This course content will be a shorter and less detailed version of the classes for pipefitters and
electricians. This class will combine the basics from those two classes.
This training will consist of two (2) eight (8) hour training sessions for a total of sixteen (16) hours.
One class will be on fire suppression systems. The second class will cover fire alarms. A total of
10 (ten) students will attend each session.
3.4.a Fire Suppression class. (8 hours)
Topics to Include:
1. Introduction to inspections, testing, and maintenance of fire suppression systems. The
NFPA and Introductory Concepts
2. Objectives of Inspection, Testing, & Maintenance
Acceptance testing
Routine inspection and testing
Preventative Maintenance & Repairs
Mission Support Alliance
Page 11 of 18
3. Automatic Sprinklers
Types
Applications
4. Types of automatic sprinkler systems
Wet
Dry
Pre-action
Deluge
Anti-freeze
Standpipe systems
5. Important Hardware Components
Piping
Indicating Control Values
Hangers
Fire Department Connections
Backflow Preventers
6. Acceptance Inspection and Testing
Comparison with approved plans
System flushing
Hydrostatic testing
Alarm and supervisory system testing
Valve tripping and resetting
7. Routine Inspection, Testing & Maintenance
Mission Support Alliance
Page 12 of 18
Valves
Piping
Sprinklers
Hangers
Occupancy Consideration
Alarm Tests
Trip tests and component testing
3.4.b. Fire Alarm class. (8 hours)
Topics to include:
1. Inspection: Fire Alarm System Inspection training shall include classroom discussions and hands on exercises covering, as a minimum, how to perform inspections for:
Emergency and exit lighting
Fire Alarm monitoring
Various types of detectors
Schedule for various inspections, i.e. annual, monthly, etc.
2. Testing: Fire Alarm System Testing training shall include classroom discussions and hands-on exercises that shall describe how to properly perform required tests and, as a
minimum, shall cover:
Fire Alarm and components testing
Detector (i.e. smoke and heat) system testing
3. Maintenance: Fire Alarm System Maintenance training shall include classroom discussions and hand on exercises that cover:
Maintenance procedures required by applicable NFPA codes and standards
Manufacturer’s required/suggested maintenance for Hanford systems
Mission Support Alliance
Page 13 of 18
Maintenance when equipment still under manufacturer’s warranty
Performance of maintenance functions on alarm system components
4. Hands-On Exercises shall, as a minimum, include work on:
Smoke and/or flame detectors
Notification devices
Manual pull boxes
5. Topics to include:
1. The NFPA and Introductory Concepts /Overview
2. The System Concept
3. Functions and Objectives of Emergency Signaling Systems
4. Basic Components
5. Basic Functional Flow
6. Basic Functional Categories of Fire Alarm and Emergency Signaling Systems
7. Types of Systems
8. Control Panels, Circuitry and Devices (Conventional vs Intelligent)
9. Fire Alarm Initiating Device Types:
10. Fire Alarm Notification Appliances-Alarm Signal Notification
11. Emergency Voice Alarm Communication Systems
12. Fire Extinguishing Systems
Sprinkler System Water Alarm and Supervisory Signals
Special Hazard Protection Systems
13. Approvals, Authorities and Acceptance
U.L. Listings and F.M. Approvals
Mission Support Alliance
Page 14 of 18
Systems Certification
Authority Having Jurisdiction
NFPA Code Summary
14. Inspection, Testing, & Maintenance
Acceptance Testing
Systems Maintenance and Periodic Testing
Detector Maintenance System Testing
Maintenance procedures-NFPA Codes & Standards
Manufacturer’s Required/Suggested Maintenance for Hanford
Manufacturer’s Warranty Maintenance
15. Hands-On Exercises
Smoke and/or flame detectors
Notification devices
Manual pull boxes
3.5 EQUIPMENT PURCHASE OPTION
MSA retains the right to negotiate (through the assigned Contract Specialist) an option to
purchase any of the Subcontractor provided mock-ups used in classroom presentation.
4.0 REQUIREMENTS
General
For any work performed on the Hanford Site or any MSA controlled facility, the provisions of the
On Site Services Special Provisions, will apply to Subcontractor personnel.
4.1 Engineering Requirements
None
Mission Support Alliance
Page 15 of 18
4.2 Environment, Safety, & Health (ES&H) Requirements
The Subcontractor shall exercise a degree of care commensurate with the work and the associated
hazards. The Subcontractor shall ensure that management of safety and environmental functions
and activities is an integral and visible part of the Subcontractor’s work planning and execution
processes. The Subcontractor shall flow down safety and environmental requirements to the lowest
tier Subcontractor performing work on the Hanford site commensurate with the risk and
complexity of the work.
Subcontractors and its lower-tier subcontractors shall be responsible to complete an Employee Job
Task Analysis (EJTA) in accordance with MSC-PRO-11058 for any of the following situations:
For any subcontractor employee who will be on the Hanford Site for more than 30 days
in a year.
For any subcontractor employee who may potentially be exposed to hazards (e.g.
radiological, beryllium, hazardous wastes, noise) while performing in accordance with
the subcontract statement of work.
For any subcontractor employee enrolled in a medical or exposure monitoring
program required by 10 CFR 851, and/or any other applicable federal, state or local
regulation or other obligation.
If any of the above conditions are met, the subcontractor and its lower-tier subcontractor employee
is to have a current approved EJTA prior to that employee beginning work on the Hanford Site.
Buyer’s Safety and Health Procedures are available on the internet at
http://www.hanford.gov/pmm/page.cfm/Construction. The documents on this site are kept current
and are available for Subcontractors and lower-tier Subcontractor use.
4.3 Quality Assurance (QA) Requirements
The work activities for this statement of work shall be performed in accordance with the following
MSA Quality Assurance Program and Procedures:
4.4 Government Property
The Subcontractor will be responsible for managing the Government-owned property as required
in the Subcontract Provisions: None
http://www.hanford.gov/pmm/page.cfm/Construction
Mission Support Alliance
Page 16 of 18
5.0 PERSONNEL REQUIREMENTS
5.1 Training and Qualifications
Subcontractor shall ensure that its personnel meet and maintain the appropriate training,
qualification and certification requirements.
The following types of training qualifications are required:
Required Qualifications:
A. Ten years’ experience training on fire alarms and fire suppression systems.
B. Ten years’ experience in the fire protection industry.
C. National Institute for the Certification of Engineering Technicians (NICET) certifications in the following areas:
Inspection & Testing of Water-Based Fire Protection Systems—Level III
Fire Alarm Systems—Level II
Suppression Systems—Level II
5.2 Security and Badging Requirements
For any on site work, see Special Provisions – On Site Services for details.
Subcontractor employees will be required to submit to vehicle searches and not personally carry
or transport certain prohibited articles.
Will the Subcontractor require an access authorization (security clearance)? No
5.3 Work Location / Potential Access Requirements
Work will be performed at the 2721EA/shop/200E facility, Building 609J Training Room, and
may require entry into MO-286//200E building to meet with FSM Engineering staff.
Mission Support Alliance
Page 17 of 18
5.4 Site Access and Work Hours
Hanford personnel at the Hanford Site work a standard 4/10 schedule. The standard work week
consist of ten (10) hours of work between 6:00 am and 4:30 pm, with one-half hour designated as
an unpaid period for lunch, Monday through Thursday.
Work performed outside normal operating hours shall be coordinated and/or approved through the
BTR and/or the Contract Specialist prior to performing the work.
6.0 MEETINGS
Subcontractor shall participate in all meetings as required by the Buyer’s Technical Representative
(BTR).
7.0 DELIVERABLES AND PERFORMANCE SCHEDULE REQUIREMENTS
7.1 Deliverables
The Subcontractor shall submit to BTR for approval:
1. Lesson plan with learning objectives in PDF format
2. PowerPoint to be used.
Subcontractor will submit above items 15 days before training begins. BTR will have 3 days to
approve or reject.
Subcontractor shall deliver training as defined within this SOW.
7.2.1 Schedule
Start Date: Anticipated start date is April 1, 2017
Completion Date: September 29, 2019
8.0 SPECIAL REQUIREMENTS
Reporting Administration Meetings
General purpose of meetings is for the coordination, control, and direction of the Work. In addition
to meetings addressed by this Section, Subcontractor may be required by other Sections and other
Subcontract documents to conduct special-purpose meetings and various safety meetings and
briefings.
Mission Support Alliance
Page 18 of 18
MSA will issue meeting notices and prepare an agenda and minutes for each meeting addressed in
this Section. When applicable, minutes will identify action items, assigned actionees, and due
dates.
KICKOFF MEETING - Before start of the Work, MSA will conduct a conference at a time and Hanford Site location agreed to by Subcontractor and MSA. Invited attendees will
include MSA, Subcontractor, key lower tier subcontractors and others having an interest
in the Work. Purpose of the conference is the coordination of Work start up and
familiarization of project participants with the Work and worksite.
PROGRESS MEETINGS - At the end of every class, MSA may conduct a maximum one hour progress meeting at time and Hanford Site location determined by MSA. Invited
attendees will include MSA, Subcontractor and interested parties to review the class and
determine changes that need to be made.