Electrical distribution needs are continuously evolving in residentional, commercial andIndustrial sectors. Improved operational safety, continuity of service, greater convenience and operating cost have assumed a tremendous significance. Miniature circuit breakers have been designed to continuously adapt to these changing needs.
Range6A to 40A "B" Curve0.5A to 63A "C" Curve0.5A to 63A for "DC" Application
ExecutionSingle Pole (1P)Single Pole & Neutral (1P+N)Double Pole (2P)Three Pole (3P)Three Pole & Neutral (3P+N)Four Pole (4P)
SpecificationIEC/EN 60898
Feature • Precise hammer action• 15 Plates Arc Chute for effective arc quenching• Longer electrical life• Wide range• Value for money• Low power consumption, thus cost effective & energy saving
AccessoriesAuxiliary SwitchShunt trip
• UNIFORM 10KA BREAKING CAPACITY FOR "B" AND "C" CURVE
• LOW POWER CONSUMPTION, THUS COST EFFECTIVE & ENERGY SAVING
• SUITABLE FOR DC AND FOR A WIDE FREQUENCY RANGE OF 50Hz-400Hz APPLICATION
• "FINGER SAFE" TERMINALS-IP20 DEGREE OF PROTECTION
• ARC CHUTE FOR EFFECTIVE ARC QUENCHING
• SILVER GRAPHITE CONTACTS FOR ENHANCED LIFE
MINIATURE CIRCUIT BREAKER
3
HOUSING:• The housing of Decovolt MCB is Injection Moulded from special grade PBT as per international specifications.• The housing and other moulded components are fire retardant, anti-tracking and non hygroscopic.• The Housing can withstand high temperature and is impact resistant.
CONTACTS:Contacts are made of special silver inlaid into copper strip, ensuring higher life and maximum safety against contact welding and erosion. These contacts have low contact resistance resulting into low watt loss.
CURRENT LIMITING ACTION: The high speed current limiting action ensures that the MCB operate before the full prospective fault current is allowed to develop. Under fault conditions, damage can be sustained to the installation and associated equipment due to the amount of energy that passes before the current is completely interrupted. The total energy let through depends on the value of current and the time for which it flows. The high speed current limiting action of DECOVOLT MCB ensures that the energy let through and any subsequent damage is minimized. This reduced LET THROUGH ENERGY (Class 3 as per BSEN 60898) assists greatly with both back-up and discrimination considerations.
OPERATING MECHANISM: DECOVOLT MCB have a quick make and break trip free mechanism. In the event of an over current or short circuit the MCB automatically interrupts all poles even if the MCB toggle is held in ON position, the handle always indicates the correct contact position.
MODERATE OVERLOAD CONDITION: Detection of moderate Over load conditions is achieved by the use of a Bimetal Overload Relay, which deflects in response to the current passing through it The Bimetal Relay moves against the trip bar releasing the trip mechanism.
SHORT CIRCUIT CONDITIONS: When the current flowing through the MCB reaches a predeter-mined level, the solenoid in Magnetic coil directly pulls in the plunger, which releases the trip mechanism.
PERFECT CONECTIONS: The design of termi-nals makes the wiring easier. A combination box type terminal with combination head screws on both sides with deep serrations ensures sparkles and firm connections.
Outgoing Terminal
Body
Latch
Arc-chutes Holder
Solenoid
Arc-chutes
Arc-runner
Arc-chutes Holder
Fixed Contact
Moving Contact Arm
Incoming Terminal(Dual Termination)
MINIATURE CIRCUIT BREAKER
Internal View of MCB
4
MINIATURE CIRCUIT BREAKER
TECHNICAL INFORMATION
STANDARD CONFORMITY IEC 60898:2002 IEC 60947-3:2001TYPE/SERIES CB B
Nos of Poles (Execution)RATED SHORT CIRCUITBREAKING CAPACITY Ka
1P,1P+N,2P,3P,3P+N,4P1P,1P+N,2P,3P,3P+N,4P 1P,1P+N,2P,3P,3P+N,4P
UTILIZATION CATEGORY
(3-5) InMAGNETIC RELEASESETTING (3-5) In (3-5) In
660RATED INSULATIONVOLTAGE(Ui) 660 660
4RATED IMPULSEVOLTAGE (Uimp)ELECTRICAL / MECHANICALENDURANCE
4 4
RATED FREQUENCY (f) 5050 50
1010 10
RATED VOLTAGE (AC) (Ue) 240/415240/415 240/415RATED CURRENT (In) 6-40*6-40* 6-40*
LESS THAN 32 Amps 2000020000 20000MORE THAN 32 Amps 1000010000 10000AMBIENT TEMPERATURE - 5 to + 55- 5 to + 55 - 5 to + 55
VIBERATION g 33 3SHOCK 40MM FREE FALL40MM FREE FALL 40MM FREE FALLPROTECTION CLASS IP 20IP 20 IP 20INSTALLATION POSITION VERTICAL/ HORIZONTALVERTICAL/ HORIZONTAL VERTICAL/ HORIZONTALMOUNTING CLIP ON DIN RAILCLIP ON DIN RAIL CLIP ON DIN RAILCASE & COVER MOULDED, FLAME RETARDANT THERMOPLASTIC MATERIAL
TERMINAL CAPACITY(MAX) sq.mm 2525 25
MCB ISOLATORTITLE
1P SINGLE POLE1P+N SINGLE POLE NEUTRAL2P DOUBLE POLE3P THREE POLE3P+N THREE POLE NEUTRAL4P FOUR POLE
*** CURRENT RATINGS - 0.5, 1,2,3,4,5,6,8,10,16,20,25,32,40,50,63"B" CURVE MCB's ARE AVAILABLE ON REQUEST
5
MINIATURE CIRCUIT BREAKER
SELECTION
SELECTION OF MCB FOR MOTOR PROTECTION
S.NO KW HP
3017 51- 51 63125-38- 38 63125-32- 32 50125-27- 27 4063100-21- 21 325050-
14.4125 14.4 2540404711.280 11.2 163225268.280 8.2 102020246.363 6.3 101616204.450 - --1017.53.532 - --1011.82.625 - --68.7220 - --36.2
1.816 - --34.81.210 - --23.51.210 - --23.20.910 - --22.8
C DCC
221618.515151410137.5125.5113.7510
392.281.571.16
1.011.472.012.954.025.037.3710.0513.420.1124.829.4940.21
0.7550.740.5540.50.3730.340.2520.240.181
FULL LOADCURRENT
FULL LOADCURRENT
3 PHASE 400V ASSISTEDSTARTING STAR DELTA
"B" SERIES"B" SERIES
"B" SERIES"B" SERIES
"C" SERIES"C" SERIES
TYPE OFMCB
LampWatt
No oflamps
Rating(A)
20W 812
11.5
40W 21012
0.52
2.5
100W 124
11.52.5
60W 148
12
0.51.534
80W 1258
12
0.51245
CURRENTRATING OF MCB
CAPACITY/WATT(Load)(240V-1pH)APPLIANCES
Fresh hold application
"B" SERIES"B" SERIES
"B" SERIES"B" SERIES"B" SERIES"B" SERIES
"B" SERIES"B" SERIES"B" SERIES"B" SERIES"C" SERIES
"C" SERIES
WASHING MACHINEWASHING MACHINEWITH HEATER
"C" SERIES"C" SERIES"C" SERIES
8A10A
32A10A
3A4A
6A8A
6A10A16A32A
6A10A6A10A2A
8A
10A16A20A
1200W1500W
4500 W1750 W
165 litres350 litres
750W1250W
1000W2000W3000W6000W
AUTO TOASTER ( 2 SLICES)ELECTRIC KETTLE
" B " series MCB is used forlighting applications
ELECTRIC IRON
WATER HEATERSTORAGE / INSTANT
750W2000W1000W2000W300W
1300W
1.0 tonnes1.5 tonnes2.0 tonnes
OVEN/GRILLER
REFRIGATOR
OVEN/GRILLERHOT PLATE ONLYROOM HEATER
AIR CONDITIONER
MCBSELECTION
MCBSELECTION
1 PHASE 230V DOLSTARTING
FULL LOADCURRENT
MCBSELECTION
3 PHASE 400V DOLSTARTING
NOTE: One lighting circuit can have up to 800W or up to 10 lighting pointsOne power circuit can have up to 2000W or 1 power point
6
1000050003600
1000
100
10
11.131.45 2 2.55 3 5 10 14 20 28 50
1
0.1
0.01
Tim
e in
Sec
onds
Multiple of Rated Current
Limit Specified in IEC-60898-1-2002In : Rated Current B Type - 0.5A to 100A C Type - 0.5A to 100A
Reference Calibration Temp-30˚C
Lower Limit as per Standard
In > 32A
In < 32A
B-Type C-Type
Upper Limit as per Standard
1000050003600
1000
100
10
11.131.45 2 2.55 3 5 10 14 20 28 50
1
0.1
0.01
Tim
e in
Sec
onds
Multiple of Rated Current
Limit Specified inIEC-60898-1-2002In : Rated CurrentB Type - 0.5A to 100AC Type - 0.5A to 100A
Reference Calibration Temp-30˚C
Lower Limit as per Standard
In > 32A
In < 32A
B-Type
C-Type
Upper Limit as per Standard
60
CurrentLimiting
MCB
Zero pointExtinguishingMCB
Un = Mains VoltageID = Let - through short circuit current
UB = Arc VoltageIp = Prospective short circuit current
U/V
U/V
U/V
50
40
30
20
10
0.7 0.6 0.9 1.0 1.1 1.2 1.3 1.4
-10
0
Correction FactorReference Calibration Temp. 30˚C
Am
bien
t Tem
p.˚C
Temperature Compensation GraphDecovolt MCB Vs Zero Point
Extinguishing MCB
Tripping Characterstics CurveDC MCB Type B & C
Tripping Characterstics CurveType B & C
TRIPPING CHARACTERSTICS CURVES
MINIATURE CIRCUIT BREAKER
7
CURRENT RATING (A)0.5123456
1016202532405063
CURRENT RATING (A)0.5123456
1016202532405063
CURRENT RATING (A)0.5123456
1016202532405063
"B CURVE" CAT NODVBDP105
DVBDP1001DVBDP1002DVBDP1003DVBDP1004DVBDP1005DVBDP1006DVBDP1010DVBDP1016DVBDP1020DVBDP1025DVBDP1032DVBDP1040DVBDP1050DVBDP1063
"C" CURVE CAT NODVCDP105
DVCDP1001DVCDP1002DVCDP1003DVCDP1004DVCDP1005DVCDP1006DVCDP1010DVCDP1016DVCDP1020DVCDP1025DVCDP1032DVCDP1040DVCDP1050DVCDP1063
"C" CURVE CAT NODVASP105
DVASP1001DVASP1002DVASP1003DVASP1004DVASP1005DVASP1006DVASP1010DVASP1016DVASP1020DVASP1025DVASP1032DVASP1040DVASP1050DVASP1063
"B CURVE" CAT NODVBSP105
DVBSP1001DVBSP1002DVBSP1003DVBSP1004DVBSP1005DVBSP1006DVBSP1010DVBSP1016DVBSP1020DVBSP1025DVBSP1032DVBSP1040DVBSP1050DVBSP1063
"C" CURVE CAT NODVCSP105
DVCSP1001DVCSP1002DVCSP1003DVCSP1004DVCSP1005DVCSP1006DVCSP1010DVCSP1016DVCSP1020DVCSP1025DVCSP1032DVCSP1040DVCSP1050DVCSP1063
SINGLE POLE
SINGLE POLE - N
DOUBLE POLE
MINIATURE CIRCUIT BREAKER
8
CURRENT RATING (A)0.5123456
1016202532405063
CURRENT RATING (A)0.5123456
1016202532405063
CURRENT RATING (A)0.5123456
1016202532405063
"B CURVE" CAT NODVBFP105
DVBFP1001DVBFP1002DVBFP1003DVBFP1004DVBFP1005DVBFP1006DVBFP1010DVBFP1016DVBFP1020DVBFP1025DVBFP1032DVBFP1040DVBFP1050DVBFP1063
"C" CURVE CAT NODVCFP105
DVCFP1001DVCFP1002DVCFP1003DVCFP1004DVCFP1005DVCFP1006DVCFP1010DVCFP1016DVCFP1020DVCFP1025DVCFP1032DVCFP1040DVCFP1050DVCFP1063
"C" CURVE CAT NODVATP105
DVATP1001DVATP1002DVATP1003DVATP1004DVATP1005DVATP1006DVATP1010DVATP1016DVATP1020DVATP1025DVATP1032DVATP1040DVATP1050DVATP1063
"B CURVE" CAT NODVBTP105
DVBTP1001DVBTP1002DVBTP1003DVBTP1004DVBTP1005DVBTP1006DVBTP1010DVBTP1016DVBTP1020DVBTP1025DVBTP1032DVBTP1040DVBTP1050DVBTP1063
"C" CURVE CAT NODVCTP105
DVCTP1001DVCTP1002DVCTP1003DVCTP1004DVCTP1005DVCTP1006DVCTP1010DVCTP1016DVCTP1020DVCTP1025DVCTP1032DVCTP1040DVCTP1050DVCTP1063
THREEE POLE
THREEE POLE - N
DOUBLE POLE
MINIATURE CIRCUIT BREAKER
9