Upload
lytuyen
View
219
Download
0
Embed Size (px)
Citation preview
www.hannainst.com 1144..11
14M
INI CO
NTRO
LLERSS E C T I O N
C O N T E N T S
N A V I G A T I O N
Introduction . . . . . . . . . . . . . . . . . . . .14.2
pH . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14.5
ORP . . . . . . . . . . . . . . . . . . . . . . . . . . . .14.7
Conductivity . . . . . . . . . . . . . . . . . . .14.9
TDS . . . . . . . . . . . . . . . . . . . . . . . . . . .14.11
Resistivity . . . . . . . . . . . . . . . . . . . . .14.14
Level . . . . . . . . . . . . . . . . . . . . . . . . . .14.15
Level Transmitter . . . . . . . . . . . . . .14.16
MIN
I CO
NTR
OLL
ERS
14
1144..1100 With Great Products, Come Great Results™
ORDERING INFORMATIONBL 983317-0 (12 Vdc) and BL 983317-1(115/230 Vac) are supplied with mounting brackets,transparent cover and instruction manual.
BL 983327-0 (12 Vdc) and BL 983327-1(115/230 Vac) are supplied with mounting brackets,transparent cover and instruction manual.
PROBESHI 7632-00 EC/TDS probe with internal
temperature sensor and 2 m cable
SOLUTIONSHI 7031L 1.41 mS/cm calibration solution,
500 mL bottleHI 7039L 5.00 mS/cm calibration solution,
500 mL bottleHI 7061L Cleaning solution, 500 mL
ACCESSORIESHI 710005 115 Vac/12 Vdc power adapterHI 710006 230 Vac/12 Vdc power adapterHI 740146 Mounting brackets
Effective Process ControlBL 983317 and BL 983327 are panelmounted mini controllers with an outputrelay that have been designed for easy, affordable installation in tightspaces—ideal for simple yet effective process control.
They are provided with automaticcompensation for variations intemperature. The probe is easy-to-cleanand requires very little maintenance. Thecalibration is performed at 1 point,through a trimmer.
All wiring and connections to externaldevices are done through the terminals onthe rear panel. The multicolor LEDcontinuously indicates if the controller isin measurement, dosing or alarm mode.
You can also choose automatic or manualdosing mode with a switch on the frontpanel. Manual control is particularlyuseful during maintenance operations,because it permits you to enable ordisable the dosing relay according to yourneed. The overtime control system advisesyou when the relay is active too long,helping to prevent overdosing.
Several models are available:
“-0” Models powered at 12 Vdc
“-1” Models powered at 115 or 230 Vac
BL 983317 • BL 983327
Conductivity Mini ControllersMeasuring in mS/cm
SPECIFICATIONS BL 983317 BL 983327
Range 0.00 to 10.00 mS/cm
Resolution 0.01 mS/cm
Accuracy (@20°C/68°F) ±2% f.s.
Probe (not included) HI 7632-00
Temperature Compensation automatic, 5 to 50°C (41 to 122°F) with ß=2%/ºC
Calibration manual, with CAL trimmer
Dosing Relay
1, max 2A (fuse protected), 250 Vac, 30 Vdc
contact closed when reading
falls below setpoint value
contact closed when reading
exceeds setpoint value
Setpoint adjustable from 0 to 10 mS/cm
Overtime adjustable, typically from 5 to approx. 30 minutes
Power Supplymodels “-0”: 12 Vdc adapter (included)
models “-1”: 115/230 Vac ±10%; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight models “-0”: 200 g (7.1 oz.) / models “-1”: 300 g (10.6 oz.)
HI 1211 Controller and Monitorin an Industrial Enclosure• NEMA protection• Simple to install
optional
These controllers will allow any system to becost effectively monitored 24 hours a day.
14M
INI CO
NTRO
LLERS
www.hannainst.com 1144..1111
ORDERING INFORMATION
BL 983315-0 (12 Vdc) and BL 983315-1 (115/230Vac) are supplied with mounting brackets, transparent cover and instruction manual.
BL 983319-0 12 Vdc) and BL 983319-1 (115/230Vac) are supplied with mounting brackets, transparent cover and instruction manual.
BL 983321-0 12 Vdc) and BL 983321-1 (115/230Vac) are supplied with mounting brackets, transparent cover and instruction manual.
BL 983329-0 12 Vdc) and BL 983329-1 (115/230Vac) are supplied with mounting brackets, transparent cover and instruction manual.
PROBESHI 7634-00 EC/TDS probe with internal
temperature sensor and 2 m cable
SOLUTIONSHI 7033L 84 μS/cm (42ppm) calibration
solution, 500 mL
HI 7032L 1382 ppm calibration sol., 500 mL
HI 70442L 1500 ppm calibration sol., 500 mL
HI 7061L Cleaning solution, 500 mL
ACCESSORIESHI 710005 115 Vac/12 Vdc power adapter
HI 710006 230 Vac/12 Vdc power adapter
HI 740146 Mounting brackets
Ideal for Hydroponics,Horticulture and WaterConditioningThese instruments have been designed forTDS control in hydroponics, horticultureand water conditioning. Compact in size,they can be mounted in confined spacesor even right next to the vat or barrelcontaining the chemicals. These meterspermit automatic control of installationspreviously checked manually.
Readings are shown on the large displayand the multicolored LED continuouslyindicates if the mini-controller is inmeasurement, dosing or alarm mode.
BL 983315 can control TDS from 0.0 to199.9 ppm, BL 983319 from 0 to 1999 ppm,BL 983321 from 0.00 to 19.99 ppm and BL 983329 from 0 to 999 ppm.
You can also choose automatic or manualdosing mode with a switch on the frontpanel. Manual control is particularlyuseful during maintenance operations,because it permits you to enable ordisable the dosing relay according to your need.
The overtime control system advises youwhen the relay is active too long, helpingto prevent over dosage.
Several models are available:
“-0” Models powered at 12 Vdc
“-1” Models powered at 115 or 230 Vac
SPECIFICATIONS BL 983315 BL 983319 BL 983321 BL 983329
Range 0.0 to 199.9 ppm 0 to 1999 ppm 0.00 to 19.99 ppm 0 to 999 ppm
Resolution 0.1 ppm 1 ppm 0.01 ppm 1 ppm
Accuracy (@20°C/68°F) ±2% f.s.
TDS Conversion Factor 0.5 0.65 0.5 0.5
Probe (not included) HI 7634-00
TemperatureCompensation
automatic, 5 to 50°C (41 to 122°F) with ß=2%/ºC
Calibration manual, with CAL trimmer
Dosing Relay
1, max 2A (fuse protected), 250 Vac, 30 Vdc
contact close when reading
exceeds setpoint falls below setpoint exceeds setpoint exceeds setpoint
Setpoint adjustable from 0 to
199.9 ppm
adjustable from 0 to
1999 ppm
adjustable from 0 to
19.99 ppm
adjustable
from 0 to 999 ppm
Overtime adjustable, typically from 5 to approx. 30 minutes
Power Supplymodels “-0”: 12 Vdc adapter (included)
models “-1”: 115/230 Vac ±10%; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight models “-0”: 200 g (7.1 oz.) / models “-1”: 300 g (10.6 oz.)
BL 983315 • BL 983319 • BL 983321 • BL 983329
TDS (Total Dissolved Solids) Mini Controllers
Combine any of HANNA’s mini controllers intothe HI 1222 for versatile monitoring and control
HI 1222 Controllers and Monitorin an Industrial Enclosure• NEMA protection• Simple to install
optional
MIN
I CO
NTR
OLL
ERS
14
1144..1122 With Great Products, Come Great Results™
ORDERING INFORMATION
BL 983318-0 (12 Vdc) and BL 983318-1(115/230 Vac) are supplied with mounting brackets,transparent cover and instruction manual.
PROBES
HI 7632-00 EC/TDS probe with internal
temperature sensor and 2 m cable
SOLUTIONSHI 7038L 6.44 ppt (6440 ppm) calibration
solution, 500 mLHI 7061L Cleaning solution, 500 mL
ACCESSORIESHI 710005 115 Vac/12 Vdc power adapterHI 710006 230 Vac/12 Vdc power adapterHI 740146 Mounting brackets
Easy, AffordableInstallationBL 983318 is a mini controller that hasbeen designed for easy, affordableinstallation in tight spaces, ideal forsimple yet effective process control.
BL 983318 features ATC (AutomaticTemperature Compensation) and simpleone point calibration is performedthrough trimmer.
The multicolored LED continuouslyindicates if the controller is inmeasurement, dosing or alarm mode.
Wiring and external device connectionsare extremely simple to perform throughthe terminals on the rear of the instrument.
You can also choose automatic or manualdosing mode with a switch on the frontpanel. Manual control is particularlyuseful during maintenance operations,because it permits you to enable ordisable the dosing relay according to your need.
The overtime control system advises youwhen the relay is active too long, helpingto prevent over-dosage.
Two models are available, with powersupply input at 115/230 Vac or 12 Vdc.
Two models are available:
BL 983318-0 powered at 12 Vdc
BL 983318-1 powered at 115 or 230 Vac
SPECIFICATIONS BL 983318-0 BL 983318-1
Range 0.00 to 10.00 ppt (0 to 10,000 ppm)
Resolution 0.01 ppt (10 ppm)
Accuracy (@20°C/68°F) ±2% f.s.
TDS Conversion Factor 0.5
Probe (not included) HI 7632-00
Temperature Compensation automatic, 5 to 50°C (41 to 122°F) with ß=2%/ºC
Calibration manual, with CAL trimmer
Dosing Relay 1, max 2A (fuse protected), 250 Vac, 30 Vdc
contact closed when reading exceeds setpoint value
Setpoint adjustable from 0 to 10 ppt (10,000 ppm)
Overtime adjustable, typically from 5 to approx. 30 minutes
Power Supply 12 Vdc adapter (included) 115/230 Vac ±10%; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight 200 g (7.1 oz.) 300 g (10.6 oz.)
BL 983318
TDS (Total Dissolved Solids) Mini ControllersMeasuring up to 10,000 ppm
HI 1211 Controller and Monitorin an Industrial Enclosure• NEMA protection• Simple to install
optional
These controllers will allow any system to becost effectively monitored 24 hours a day.
Combine any of HANNA’s mini controllers intothe HI 1222 for versatile monitoring and control
HI 1222 Controllers and Monitorin an Industrial Enclosure• NEMA protection• Simple to install
optional
14M
INI CO
NTRO
LLERS
www.hannainst.com 1144..1133
ORDERING INFORMATION
BL 983324-0 (12 Vdc) and BL 983324-1
(115/230 Vac) are supplied with mounting brackets,
transparent cover and instruction manual.
PROBES
HI 7634-00 EC/TDS probe with internal
temperature sensor and 2 m cable
SOLUTIONSHI 7061L Cleaning solution, 500 mL
HI 7033L 84 μS/cm (42ppm) calibration solution, 500 mL
ACCESSORIESHI 710005 115 Vac/12 Vdc power adapter
HI 710006 230 Vac/12 Vdc power adapter
HI 740146 Mounting brackets
Compact and Easy toInstallBL 983324 is a panel mounted TDScontroller, designed for easy installation,configuration and maintenance.
The meter is provided with a dosing relay,activated when the TDS reading exceedsthe setpoint value.
Measurements are compensated fortemperature variations and shown on thelarge display automatically.
A multicolored LED on the front panelcontinuously indicates if the minicontroller is in measurement, dosing oralarm mode.
Wiring and external device connectionsare extremely simple to perform through the terminals on the rear of the instrument.
You can also choose automatic or manualdosing mode with a switch on the frontpanel. Manual control is particularlyuseful during maintenance operations,because it permits you to enable ordisable the dosing relay according to your need.
The overtime control system advises youwhen the relay is active too long, helpingto prevent over dosage.
Two models are available:
BL 983324-0 powered at 12 Vdc
BL 983324-1 powered at 115 or 230 Vac
SPECIFICATIONS BL 983324-0 BL 983324-1
Range 0.0 to 49.9 ppm
Resolution 0.1 ppm
Accuracy (@20°C/68°F) ±2% f.s.
TDS Conversion Factor 0.5
Probe (not included) HI 7634-00
Temperature Compensation automatic, 5 to 50°C (41 to 122°F) with ß=2%/ºC
Calibration manual, with CAL trimmer
Dosing Relay 1, max 2A (fuse protected), 250 Vac, 30
contact closed when reading exceeds setpoint value
Setpoint adjustable from 0 to 49.9 ppm
Overtime adjustable, typically from 5 to approx. 30 minutes
Power Supply 12 Vdc adapter (included) 115/230 Vac ±10%; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight 200 g (7.1 oz.) 300 g (10.6 oz.)
BL 983324
TDS (Total Dissolved Solids) Mini ControllersMeasuring up to 49.9 ppm
MIN
I CO
NTR
OLL
ERS
14
1144..1144 With Great Products, Come Great Results™
ORDERING INFORMATIONBL 983314-0 (12 Vdc) and BL 983314-1(115/230 Vac) are supplied with mounting brackets,transparent cover and instruction manual.
PROBESHI 3314 Resistivity probe
ACCESSORIESHI 710005 115 Vac/12 Vdc power adapter
HI 710006 230 Vac/12 Vdc power adapter
HI 740146 Mounting brackets
BL 983314
Resistivity Mini Controllers
Designed for Ultra PureWater, R.O. and WaterConditioning ApplicationsBL 983314 is a simple-to-operateresistivity controller designed for ultrapure water, R.O., and water conditioningapplications. The BL 983314 resistivitycontroller is also ideal for continuousmonitoring of process solutions. Setpointand calibration are manually adjustedwith a trimmer and the alarm relay allowsfor simple control.
Readings are automatically temperaturecompensated, with three differentcoefficients (β=2.4, 3.5 or 4.5 %/°C). Thealarm contact can be used for connectionto an alarm, pump, solenoid or dosing system.
The relay contact is open when readingsare higher than the setpoint, while formeasurements lower than setpoint, therelay contact is closed. The Hysteresis istypically 0.20 MΩ/cm from the setpoint.
Measurements are displayed on the large LCD and the multicolored LEDcontinuously indicates if the controller isin measurement, dosing or alarm mode.You can also choose automatic or manualdosing mode with a switch on the frontpanel. Manual control is particularlyuseful during maintenance operations,because it permits you to enable ordisable the dosing relay according to your need.
The overtime control system advises youwhen the relay is active for too long,helping to prevent over-dosage.
Two models are available:
BL 983314-0 powered at 12 Vdc
BL 983314-1 powered at 115 or 230 Vac
SPECIFICATIONS BL 983314-0 BL 983314-1
Range 0.00 to 19.90 MΩ/cm
Resolution 0.10 MΩ/cm
Accuracy (@20°C/68°F) ±2% f.s.
Probe (included) HI 3314
Temperature Compensation automatic and linear, 5 to 50°C (41 to 122°F)
Temperature Coefficientβ=2.4 ; 3.5 ; 4.5 %/°C
selectable through jumper on the rear panel
Calibration factory calibrated
Dosing Relay 1, max 2A (fuse protected), 250 Vac, 30 Vdc
contact closed when reading falls below setpoint value
Setpoint adjustable from 0 to 19.90 MΩ/cm
Overtime adjustable, typically from 5 to approx. 30 minutes
Power Supply 12 Vdc adapter (included) 115/230 Vac ±10%; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight 200 g (7.1 oz.) 300 g (10.6 oz.)
14M
INI CO
NTRO
LLERS
www.hannainst.com 1144..1155
ORDERING INFORMATIONHI 7871/115 (115 Vac) is supplied with mountingbrackets and instructions.
HI 7871/220 (220 Vac) is supplied with mountingbrackets and instructions.
HI 7873/115 (115 Vac) is supplied with mountingbrackets and instructions.
HI 7873/220 (220 Vac) is supplied with mountingbrackets and instructions.
ACCESSORIESHI 7874 Level transmitter with internal
amplifier
HI 7164 Undecal connector
HI 731324 Stainless steel threaded measuring bars (5)
Liquid Level ControlHI 7871 and HI 7873 mini levelcontrollers are ideal for liquid levelcontrol over distances of up to 100 meters(330 feet). The are highly compact andwill fit in tight spaces.
These easy-to-use controllers are ideal fornearly any liquid level application, suchas industrial and municipal watertreatment, nutrient tank control infarming, hydroponics, aquaculture app-lications and plating rinse baths.
HI 7871 features high and low levelcontrol, while HI 7873 includes anoverflow alarm. Both instruments areconnected to a 2-wire transmitter (HI 7874), which is ideal for levelmonitoring in remote applications.
A complete liquid level measuring systemrequires:
A controller (HI 7871 or HI 7873)
A bar holder with amplifier circuitry (HI 7874)
A package of measuring bars (HI 731324)
An undecal connector (HI 7164)
HI 7871 requires 3 bars, one each for low and high levels and the third as aconsent sensor.
HI 7873 requires 4 bars with theadditional bar used for overflowmeasurement.
HI 7871 • HI 7873
Mini Level Controllers
SPECIFICATIONS HI 7871 HI 7873
Transmission max 100 meters (330 feet)
Electrical Connection HI 7164 undecal connector (not included)
Level Adjustment high and low high, low and overflow
Level Indication high and low high, low and overflow
Sensor Bars3 (not included) 4 (not included)
(HI 731324 pack of 5)
Transmitter HI 7874 (not included)
Output Contact 1 relay (2A/250 Vac, 30 Vdc) 2 relays (2A/250V, 30 Vdc)
Power Supplymodels “/115”: 110/115 Vac ±10%; 50/60Hz
models “/220”: 220/240 Vac ±10%; 50/60Hz
Environment 0 to 50°C (32 to 122°F); RH max 85% non condensing
Dimensions 83 x 53 x 95 mm (3.1 x 1.9 x 3.8’’)
Weight 250 g (8.8 oz
HI 7874 Level Transmitter with HI 731324 Stainless SteelMeasuring Bars
MIN
I CO
NTR
OLL
ERS
14
1144..1166 With Great Products, Come Great Results™
ORDERING INFORMATIONHI 7874 is supplied with mounting bracket andinstructions.
ACCESSORIESHI 731324 Stainless steel threaded
measuring bars (5)
Quick and EasyInstallationAccurate level control is critical to manyindustrial applications, especially forprocess adjustments using aggressivechemicals. Our sensor bars are built withstainless steel for long life even in harshconditions. They are easy to install andideal for monitoring tanks and waterconditioning plants.
The HI 7874 transmitter has beendesigned to be combined with the HI 7871 and HI 7873 level controllers.The transmitter is housed in a durable andwaterproof ABS body, and allows the userto easily adjust the length of the sensorbars according to the specific need.
HI 7874 is supplied with a sturdymounting bracket for quick and easy installation.
HI 7874
Level Transmitter
SPECIFICATIONS HI 7874
Transmission max 100 meters (330 feet)
Electrical Connection 2-wire terminal
Level Adjustment high, low and overflow
Sensor Bars3 or 4 (not included)
(HI 731324 pack of 5)
Power Supply from level controller
Environment 0 to 50°C (32 to 122°F); RH max 100%
Weight 550 g (1.2 lbs.)
HI 7874 Level Transmitter with HI 731324 Stainless Steel
Measuring Bars
MIN
I CO
NTR
OLL
ERS
14
1144..22 With Great Products, Come Great Results™
Accurate and Simple toInstallTraditionally, process monitoring hasrequired considerable investment insystem design, equipment, maintenanceand training. With our mini controllers,we are able to offer a solution forindustries that have to monitor a processeconomically. HANNA mini controllersare easy-to-use and allow accuratecontinuous monitoring and control ofpH, ORP, TDS, EC, Resistivity and Level.These compact, in-line instruments aredesigned to consistently perform in mostenvironments and conditions.
Our line of simple-to-operate controllershave been specially designed forhydroponics, swimming pools orapplications where space or cost are amajor concern. Thanks to their compactsize, they can be mounted in confinedspaces and right next to tanks or vats.The low cost of these meters will make itpossible for processes that weremanually maintained to be controlledautomatically, saving considerable timeand money.
Our redesigned mini controller seriesfeatures a larger LCD for easy reading,manual output control for simplemaintenance, an overtime control systemand a multicolored LED to indicate metercondition (measurement, dosing or alarm mode).
Finally, the BL 931700 and BL 932700models are provided with 4-20 mAanalog output and input for remotecontrol disabling.
• Quick-connect terminal blocks
• 2 amp built-infuse
• Fire retardant casing• Larger LCD• Selectable overdose protection
system• External disable feature• Selectable control override• Matching pin connection• 4-20 mA analog output
HANNA Mini ControllersBL Series
• Removable modulesfor easy maintenance
14M
INI CO
NTRO
LLERS
www.hannainst.com 1144..33
HANNA Mini ControllersBL Series
pH Mini ControllersMonitoring and controlling pH in waterconditioning and industrial applications isessential for water quality and maintaininginfrastructure (piping and equipment). In the case of industrial effluent, neutralization of acidic waste is vital forenvironmental safety and public health. Inindustrial applications such as boiler feedwater conditioning, a higher pH of 8.5 is necessary to prevent scaling andcorrosion of critical components.Maintaining a pH of 7.4 is fundamentalfor proper and efficient sanitization inswimming pools and spas. Theeffectiveness of sanitizers such as chlorineis dependent on a controlled pH value.
ORP Mini ControllersORP (Oxidation Reduction Potential) is themost dependable and consistent indicatorof the sanitizing effectiveness of yourpool, spa or treatment water. As oxidizerssuch as chlorine, peroxide and ozone areadded to water for the purpose ofsanitization, the ORP value increases,providing a clear indication of thecleansing power of the water. Typically, anORP value of 650 to 700 mV at a pH of 7.2indicates that your water is properlytreated and all harmful bacteria are killedin less than 1 second. ORP is also essentialin chemical processing where reducingagents are used and a negative ORP valueis an indicator of proper neutralization.
Conductivity MiniControllersIn water, an increase in conductivity indicates an increase in water hardness and a decrease in purity. Conductivity monitoring and control is essential inreducing water hardness and maintainingwater quality. For instance, water with aconductivity value in the range of 0-140 µSis considered "very soft" where as waterwith a range of 640-840 µS is considered"hard" water. An increase in conductivityindicates an increase in the amount ofdamaging dissolved solids (salts) presentin water. Conductivity monitoring and controlis essential in industrial applications suchas feed water control, blow downactivation in cooling towers and watermanagement. In these applications, highconductivity will cause scaling andcorrosion of piping and damage to criticalcomponents.
TDS Mini ControllersTDS measurement is an importantindicator of water quality. An increase inthe TDS reading indicates an increase inthe amount of dissolved solids (salts)present in the water. TDS monitoring andcontrol is imperative in industrialapplications such as feed water control,blow down activation in cooling towersand water management, in theseapplications high TDS will cause scaling
and corrosion of piping and damage tocritical components.
TDS measurement is also an importantindicator of the effectiveness of waterconditioning since an increase in TDSindicates an increase in water hardnessand a decrease in purity. This will affectthe quality of drinking water, feed waterand rinse water. TDS monitoring andcontrol is crucial in reducing waterhardness and maintaining water qualityand usability.
Resistivity MiniControllerResistivity, measured in MΩ (Ohm's), isthe optimal way to measure the quality ofwater produced by high purity systemssuch as R.O systems and waterconditioning equipment. As filter systemsbecome less effective, the resistivity valuewill decrease indicating a need formaintenance and/or replacement of filtersand critical components. Properlyfunctioning RO and water conditioningsystems will consistently produce waterwith resistivity readings in the range of 16to 18MΩ.
BlackStone mini controllers are the perfect solution for water analysis and control
Any System Can be
Cost EffectivelyMonitored
24 Hours A Day!
Front ViewFront view of the panel-mounted units.
Dimensions show the cutout size forinstallation and also the outsidedimensions of the panel.
Side ViewSide view of panel-mounted controllers.
Adjustable location brackets allow the controller to slide into thecutout and will hold the unit securely in place.
130 or 87 mm (depending on model) is the minimum amount ofroom required to install the meter with all wiring.
Rear ViewRear view of the BL 931700-1 withelectrical connections.
Rear ViewRear view of the BL 983313-1 withelectrical connections.
MIN
I CO
NTR
OLL
ERS
14
1144..44 With Great Products, Come Great Results™
HANNA Mini ControllersBL Series Mechanical Dimensions
Combine any of HANNA’s mini controllers intothe HI 1222 for versatile monitoring and control
HI 1222 Controllers and Monitorin an Industrial Enclosure• NEMA protection• Simple to install
optional
14M
INI CO
NTRO
LLERS
www.hannainst.com 1144..55
ORDERING INFORMATIONBL 981411-0 (12 Vdc) and BL 981411-1(115/230 Vac) are supplied with mountingbrackets, transparent cover and instructionmanual.
PROBESHI 1001 pH electrode for continuous
flow-thru monitoring
SOLUTIONSHI 7004L pH 4.01 calibration solution,
500 mL
HI 7007L pH 7.01 calibration solution,500 mL
HI 7010L pH 10.01 calibration solution,500 mL
HI 70300L Electrode storage solution,500 mL
HI 7061L Electrode cleaning solution,500 mL
ACCESSORIESHI 710005 115 Vac/12 Vdc power adapterHI 710006 230 Vac/12 Vdc power adapterHI 740146 Mounting brackets
Compact pH ControllerBL 981411 pH controller has beendesigned for easy, affordable installationin tight spaces, ideal for simple andeffective process control. The unit isprovided with high inpedance pH inputand can be used with any pH electrodewith standard BNC connector.Measurements are clearly displayed on thelarge LCD, while the status LED indicatesoperating mode.
BL 981411 is also provided with a dosingrelay. Selecting acid dosing, will cause therelay to activate when the measurement ishigher than the setpoint. If the basicdosing is selected, the relay is activatedwhen the reading falls below the setpoint.
Setpoint adjustment (from 0 to 14 pH)and calibration procedures are easilyperformed with trimmers on the frontpanel. You can also choose fromautomatic or manual dosing modes with aswitch on the front panel. Manual controlis particularly useful during maintenanceoperations, because it permits you toenable or disable the dosing relayaccording to your need. An overtimecontrol system advises you when the relayis active too long, to help preventoverdosing.
Two models are available:
BL 981411-0 powered at 12 Vdc
BL 981411-1 powered at 115 or 230 Vac
BL 981411
pH Mini Controller
SPECIFICATIONS BL 981411-0 BL 981411-1
Range 0.0 to 14.0 pH
Resolution 0.1 pH
Accuracy (@20°C/68°F) ±0.1 pH
Calibration manual, with offset trimmer
Dosing Relay 1, max 2A (fuse protected), 250 Vac, 30 Vdc
Dosing Selectionacid or alkaline
contact open=acid dosage; activated when reading exceeds setpoint value
contact closed=alkaline dosage; activated when reading falls below setpoint value
Setpoint adjustable from 0.0 to 14.0 pH
Overtime adjustable, typically from 5 to approx. 30 minutes
Input Impedance 1012 Ohm
Power Supply 12 Vdc adapter (included) 115/230 Vac ±10%; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight 200 g (7.1 oz.) 300 g (10.6 oz.)
HI 1211 Controller and Monitorin an Industrial Enclosure• NEMA protection• Simple to install
MIN
I CO
NTR
OLL
ERS
14
1144..66 With Great Products, Come Great Results™
ORDERING INFORMATIONBL 931700-0 (12 Vdc) and BL 931700-1 (115/230 Vac) are supplied with mountingbrackets, transparent cover and instructionmanual.
PROBESHI 1001 pH electrode for continuous
flow-thru monitoring
SOLUTIONSHI 7004L pH 4.01 calibration solution,
500 mL
HI 7007L pH 7.01 calibration solution,500 mL
HI 7010L pH 10.01 calibration solution,500 mL
HI 70300L Electrode storage solution,500 mL
HI 7061L Electrode cleaning solution, 500 mL
ACCESSORIESHI 710005 115 Vac/12 Vdc power adapterHI 710006 230 Vac/12 Vdc power adapterHI 740146 Mounting brackets
Easy installationBL 931700 mini pH controller has beendesigned for easy, affordable installationin tight spaces to perform simple yeteffective process control. Thanks to itscompact size, BL 931700 can be installedright next to tanks or vats.
This versatile controller is ideal for a widevariety of applications, such as textiles,papers, photographic solutions, platingbaths, chemicals and water treatment.
BL 931700 is provided with a selectablesetpoint for acid or basic dosage.
Measurements are directly aquired from apH electrode in the range from 0 to 14with a 0.01 pH resolution.
Accuracy is ensured by the 2 pointcalibration, performed manually throughtrimmers on the front panel.
You can also choose automatic or manualdosing mode with a switch on the frontpanel. Manual control is particularlyuseful during maintenance operations,because it permits you to enable ordisable the dosing relay according to yourneed. The overtime control system advisesyou when the relay is active for too long,helping to prevent overdosing.
In addition, this model features a 4-20 mAanalog output for recorder connection.
Two models are available:
BL 931700-0 powered at 12 Vdc
BL 931700-1 powered at 115 or 230 Vac
BL 931700
pH Mini Controllerwith 4-20 mA Recorder Output
SPECIFICATIONS BL 931700-0 BL 931700-1
Range 0.00 to 14.00 pH
Resolution 0.01 pH
Accuracy (@20°C/68°F) ±0.02 pH
Calibration manual, 2 point, with offset and slope trimmers
Dosing Relay 1, max 2A (fuse protected), 250 Vac, 30 Vdc
Dosing Selectionacid or alkaline
contact open=acid dosage; activated when reading exceeds setpoint value
contact closed=alkaline dosage; activated when reading falls below setpoint value
Setpoint adjustable from 0.00 to 14.00 pH
Overtime adjustable, typically from 5 to approx. 30 minutes
Recorder Output 4-20 mA, accuracy ±0.20 mA, 500 Ohm max load
Input Impedance 1012 Ohm
Power Supply 12 Vdc adapter (included) 115/230 Vac ±10%; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight 200 g (7.1 oz.) 300 g (10.6 oz.)
optional
These controllers will allow any system to becost effectively monitored 24 hours a day.
14M
INI CO
NTRO
LLERS
www.hannainst.com 1144..77
ORDERING INFORMATIONBL 982411-0 (12 Vdc) and BL 982411-1(115/230 Vac) are supplied with mounting brackets,transparent cover and instruction manual.
PROBESHI 2001 ORP electrode for continuous
flow-thru monitoring
SOLUTIONSHI 7020L 200-275 mV test solution,
500 mL
HI 7022L 470 mV test solution, 500 mL
HI 7091L Reducing solution, 500 mL
HI 7092L Oxidizing solution, 500 mL
HI 70300L Electrode storage solution, 500 mL
HI 7061L Electrode cleaning solution,500 mL
ACCESSORIESHI 710005 115 Vac/12 Vdc power adapter
HI 710006 230 Vac/12 Vdc power adapter
HI 740146 Mounting brackets
Ideal for SwimmingPools and SpasBL 982411 is an ORP mini controller forpanel mounting, specially designed forswimming pools and spas. Thanks to itscompact size, BL 982411 can be installedin small spaces. BL 982411 is the idealsolution for those who have alwayschecked ORP manually. With it’s automaticdosing, this mini controller willsignificantly reduce maintenance time.
BL 982411 can be used with any ORPelectrode with standard BNC connector.The instrument measures ORP in the 0 to1000 mV range and shows the readings onthe large display. The status LEDcontinuously indicates if the controller isin measurement, dosing or alarm mode.
BL 982411 is also provided with a relayfor selecting the dosing direction,oxidizing or reducing.
You can also choose automatic or manualdosing mode with a switch on the frontpanel. Manual control is particularlyuseful during maintenance operations,because it permits you to enable ordisable the dosing relay according to your need. The overtime control systemadvises you when the relay is active fortoo long, helping to prevent over-dosage.
Two models are available:
BL 982411-0 powered at 12 Vdc
BL 982411-1 powered at 115 or 230 Vac
BL 982411
ORP Mini Controller
SPECIFICATIONS BL 982411-0 BL 982411-1
Range 0 to1000 mV
Resolution 1 mV
Accuracy (@20°C/68°F) ±5 mV
Calibration manual, with CAL trimmer
Dosing Relay 1, max 2A (fuse protected), 250 Vac, 30 Vdc
Dosing Selectionreducing or oxidizing
contact open=reducing dosage; activated when reading exceeds setpoint value
contact closed=oxidizing dosage; activated when reading falls below setpoint value
Setpoint adjustable from 0 to 1000 mV
Overtime adjustable, typically from 5 to approx. 30 minutes
Input Impedance 1012 Ohm
Power Supply 12 Vdc adapter (included) 115/230 Vac ±10%; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight 200 g (7.1 oz.) 300 g (10.6 oz.)
Combine any of HANNA’s mini controllers intothe HI 1222 for versatile monitoring and control.
HI 1222 Controllers and Monitorin an Industrial Enclosure• NEMA protection• Simple to install
optional
MIN
I CO
NTR
OLL
ERS
14
1144..88 With Great Products, Come Great Results™
ORDERING INFORMATIONBL 932700-0 (12 Vdc) and BL 932700-1(115/230 Vac) are supplied with mountingbrackets, transparent cover and instructionmanual.
PROBESHI 2001 ORP electrode for continuous
flow-thru monitoring
SOLUTIONSHI 7020L 200-275 mV test solution,
500 mL
HI 7022L 470 mV test solution, 500 mL
HI 7091L Reducing solution, 500 mL
HI 7092L Oxidizing solution, 500 mL
HI 70300L Electrode storage solution,500 mL
HI 7061L Electrode cleaning solution,500 mL
ACCESSORIESHI 710005 115 Vac/12 Vdc power adapter
HI 710006 230 Vac/12 Vdc power adapter
HI 740146 Mounting brackets
SPECIFICATIONS BL 932700-0 BL 932700-1
Range ±1000 mV
Resolution 1 mV
Accuracy (@20°C/68°F) ±5 mV
Calibration manual, with CAL trimmer
Dosing Relay 1, max 2A (fuse protected), 250 Vac, 30 Vdc
Dosing Selectionreducing or oxidizing
contact open=reducing dosage; activated when reading exceeds setpoint value
contact closed=oxidizing dosage; activated when reading falls below setpoint value
Setpoint adjustable from -1000 to 1000 mV
Overtime adjustable, typically from 5 to approx. 30 minutes
Recorder Output 4-20 mA, accuracy ±0.20 mA, 500 Ohm max load
Input Impedance 1012 Ohm
Power Supply 12 Vdc adapter (included) 115/230 Vac ±10%; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight 200 g (7.1 oz.) 300 g (10.6 oz.)
Versatile ORP ControllerBL 932700 is an ORP mini controller thathas been designed for easy, affordableinstallation in tight spaces, ideal forsimple yet effective process control. As aresult of its compact size, BL 932700 canbe installed right next to tanks or vats.
This versatile controller is ideal for manyapplications, such as ORP monitoringbleaching processes, waste watertreatment and swimming pools. BL 932700permits automatic control of installationspreviously checked manually.
The instrument can be set for reducing oroxidizing dosage. It measures in the±1000 mV range, with 1 mV resolution.Setpoint adjustment and calibration aresimply performed through trimmers on thefront panel. You can also chooseautomatic or manual dosing mode with aswitch on the front panel. Manual controlis particularly useful during maintenanceoperations, because it permits you toenable or disable the dosing relayaccording to your need.
The overtime control system advises youwhen the relay is active too long, helpingto prevent over dosage. In addition, thismodel features a 4-20 mA analog outputfor recorder connection.
Two models are available, with powersupply input at 115/230 Vac or 12 Vdc.
Two models are available:
BL 932700-0 powered at 12 Vdc
BL 932700-1 powered at 115 or 230 Vac
BL 932700
ORP Mini Controllerwith 4-20 mA Recorder Output
HI 1211 Controller and Monitorin an Industrial Enclosure• NEMA protection• Simple to install
optional
These controllers will allow any system to becost effectively monitored 24 hours a day.
14M
INI CO
NTRO
LLERS
www.hannainst.com 1144..99
ORDERING INFORMATIONBL 983313-0 (12 Vdc) and BL 983313-1(115/230 Vac) are supplied with mountingbrackets, transparent cover and instructionmanual.
BL 983320-0 (12 Vdc) and BL 983320-1(115/230 Vac) are supplied with mountingbrackets, transparent cover and instructionmanual.
BL 983322-0 (12 Vdc) and BL 983322-1(115/230 Vac) are supplied with mountingbrackets, transparent cover and instructionmanual.
ELECTRODESHI 7634-00 EC/TDS probe with internal
temperature sensor and 2 m cable
SOLUTIONSHI 7031L 1413 μS/cm calibration solution,
500 mL bottleHI 7033L 84 μS/cm calibration solution,
500 mL bottleHI 7061L Cleaning solution, 500 mL
ACCESSORIESHI 710005 115 Vac/12 Vdc power adapterHI 710006 230 Vac/12 Vdc power adapterHI 740146 Mounting brackets
Specially Designed forAgriculture and WaterConditioningThese HANNA mini controllers have beenspecially designed for water conditioningand growing applications. Compact insize, they can be mounted in confinedspaces or even right next to the vat orbarrel containing the chemicals. Thesemeters permit automatic control ofinstallations previously checked manually.
EC measurements are shown on the largedisplay and the multicolored LEDcontinuously indicates if the minicontroller is in measurement, dosing oralarm mode. BL 983313 measures in the 0 to 1999 µS/cm range, BL 983320measures from 0.0 to 199.9 µS/cm and BL 983322 from 0.00 to 19.99 µS/cm.
You can also choose automatic or manualdosing mode with a switch on the frontpanel. Manual control is particularlyuseful during maintenance operations,because it permits you to enable ordisable the dosing relay according to yourneed. The overtime control system advicesyou when the relay is active for too long,helping to prevent over dosage.
Several models are available:
“-0” Models powered at 12 Vdc
“-1” Models powered at 115 or 230 Vac
BL 983313 • BL 983320 • BL 983322
Conductivity Mini ControllersMeasuring in µS/cm
SPECIFICATIONS BL 983313 BL 983320 BL 983322
Range 0 to 1999 μS/cm 0.0 to 199.9 μS/cm 0.00 to 19.99 μS/cm
Resolution 1 μS/cm 0.1 μS/cm 0.01 μS/cm
Accuracy (@20°C/68°F) ±2% f.s.
Probe (not included) HI 7634-00
Temperature Compensation automatic, 5 to 50°C (41 to 122°F) with ß=2%/ºC
Calibration manual, with CAL trimmer
Dosing Relay1, max 2A (fuse protected), 250 Vac, 30 Vdc
contact closed when reading exceeds setpoint value
Setpoint adjustable
from 0 to 1999 μS/cm
adjustable
from 0 to 199.9 μS/cm
adjustable
from 0 to 19.99 μS/cm
Overtime adjustable, typically from 5 to approx. 30 minutes
Power Supplymodels “-0”: 12 Vdc adapter (included)
models “-1”: 115/230 Vac ±10%; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight models “-0”: 200 g (7.1 oz.) / models “-1”: 300 g (10.6 oz.)
Combine any of HANNA’s mini controllers intothe HI 1222 for versatile monitoring and control
HI 1222 Controllers and Monitorin an Industrial Enclosure• NEMA protection• Simple to install
optional