2
gIndustrial relays - MID System
� Microprocessor and analog based
relay system;
� Modular - Independent modules
mounted in:
� 1/2 rack (MID050) or ;
� 1 rack (MID100) of 19”.
3
g MID System - Application
� Interconnection between utilities
and consumers;
� Isolated Small Power plants (5-10 MW);
� Co-Generation Power plants;
� Protection packages for:
� Generators;
� Motors;
� Transformers;
� Shunt capacitor banks.
5
g
MFF ModuleMicroprocessor Frequency Relay
� MODELS
� MFF1000: 2 X 81;
� FEATURES
� Overfrequency & underfrequency;
� Overfrequency (2 steps);
� Underfrequency (2 steps);
� Definitive time delay operation with
acceleration of the second step.
6
g Frequency relay - MFF (cont'd)
� Front display with 3 characters to:
show current values;
set the relay;
show information of the last trip;
� Auxiliary DC voltages:
24-48 Vdc/Vac, 48-125 Vdc/Vac,
110-240 Vdc /110-220 Vac.
8
g
MID System - ModulesGenerator Protection - MGC
� MODELS
� MGC1000 (Functions: 46,49,51,51G);
� FEATURES
� Thermal image unit - 49;
� Negative sequence overcurrent unit - 46;
� Time delay (definite time)
three-phase overcurrent function - 51.
9
g Generator Protection - MGC (cont’d)
� Time delay (definite time) single-
phase overcurrent function - 51G;
� Front display with 3 characters to:
show current values;
set the relay;
show information of the last trip;
� Auxiliary DC voltages:
24-48 Vdc/Vac, 48-125 Vdc/Vac,
110-240 Vdc /110-220 Vac.
11
g
MID Systems - ModulesOvercurrent Module - MIC
� MODELS
� MIC5000 (Overcurrent single-phase
module 50/51);
� MIC7000 (Overcurrent three-phase
module 3 x 50/51);
� MIC8000 (Overcurrent three-phase &
ground 3 x 50/51 + 50N/51N);
� MIC9000 (Overcurrent two-phase &
ground 2 x 50/51 + 50N/51N).
12
g Overcurrent Module-MIC (cont'd)
� FEATURES
� Inverse time delay
(inverse, very inverse & extremely
inverse selectable curves);
� Definite time delay
(also selectable);
� Instantaneous unit
(with time delay possibility).
13
g Overcurrent Module-MIC (cont'd)
� Front display with 2 characters to:
show current values;
set the relay;
show information of the last trip;
� Auxiliary DC voltages:
24-48 Vdc/Vac, 48-125 Vdc/Vac,
110-240 Vdc /110-220 Vac.
14
g
Model MIC5000
External Connections
Overcurrent Module-MIC (cont'd)
Model MIC7000
External Connections
15
g
Model MIC8000
External Connections
Overcurrent Module-MIC (cont'd)
Model MIC9000
External Connections
16
g
MID System - ModulesSynchro Check relay -MLJ
� MODELS
� MLJ1000: Without communications;
� MLJ1005: WIth communications (RS485)
� FEATURES
� Programmable Synchronism Task;
� Programmable Line/Busbar Permission
(DLDB, DLLB, LLDB);
� Configurable Outputs;
17
g Synchro Check relay - MLJ (cont'd)
� Real Time Monitoring of Line and Busbar
magnitudes:
� Line and busbar voltage amplitude;
� Line/busbar voltage phase difference;
� Line/busbar slip frequency;
� Recording of the last event;
� Auxiliary DC voltages:
24-48 Vdc/Vac, 48-125 Vdc/Vac,
110-240 Vdc /110-220 Vac.
19
g
MID System - ModulesMotor Protection - MMC
� MODELS
� MMC1000D (Functions: 37, 46, 49,
51, 51N, 51LR, 66)
� FEATURES
� Undercurrent protection - 37;
� Current unbalance or reversal - 46;
� Thermal image - 49;
� Phase Overcurrent - 51.
20
gMotor Protection - MMC (cont'd)
� Ground Overcurrent - 51N
� Locked rotor - 51LR;
� Control of number of starts - 66.
(Relay does not allow more
starts than set for a given time
period).
21
g Motor Protection - MMC (cont'd)
� Front display with 3 characters to:
show current values;
set the relay;
show information of the last trip;
� Auxiliary DC voltages:
24-48 Vdc/Vac, 48-125 Vdc/Vac,
110-240 Vdc /110-220 Vac.
23
g
MID Systems - ModulesPower Reverse module - TCW
� MODELS:
� TCW500DA (Single-phase unit);
� FEATURES:
� Setting range 1% - 40% of In ;
� Definite time delay unit
(100 msec - 10 seconds);
� Auxiliary DC voltages:
24-48 Vdc/Vac, 48-125 Vdc/Vac,
110-240 Vdc /110-220 Vac.
25
g
MID System - ModulesVoltage module model - TOV
� MODELS
� TOV5000B
Under or Overvoltage single-phase unit 27/ 59.
3rd harmonic filter available.
� TOV4000I
Undervoltage three-phase unit - 27.
� TOV4000M
Overvoltage three-phase unit - 59.
26
g Voltage module TOV (cont'd)
� FEATURES
� Definite time delay operation;
� Time delay and instantaneous units;
� Setting ranges:
3/66 V, 20/275 V or 50/305 V in the
single-phase units and 20/275 V or
50/305 V in the three-phase units;
� Auxiliary DC voltages:
24-48 Vdc/Vac, 48-125 Vdc/Vac,
110-240 Vdc / 110-220 Vca.