Micrologic 6

Embed Size (px)

Citation preview

  • 7/22/2019 Micrologic 6

    1/12

  • 7/22/2019 Micrologic 6

    2/1229

    40

    100%

    %

    menu

    40

    100%

    %

    menu

    40

    100%

    %

    menu

    40

    100%

    %

    menu

    Measurements and programmable protection

    A: ammeter

    I1, I2, I3, IN, Iearth-fault, Iearth-leakage and maximeter for thesemeasurements

    fault indications

    settings in amperes and in seconds

    P: A + power meter + programmable protectionmeasurements of V, A, W, VAR, VA, Wh, VARh, VAh, Hz, V peak, Apeak, power factor and

    maximeters and minimetersIDMTL long-time protection, minimum and maximum voltage and frequency, voltage and

    current imbalance, phase sequence, reverse powerload shedding and reconnection depending on power or currentmeasurements of interrupted currents, differentiated fault indications, maintenance

    indications, event histories and time-stamping, etc.

    H: P + harmonicspower quality: fundamentals, distortion, amplitude and phase of harmonics up to the 31st

    orderwaveform capture after fault, alarm or on request

    enhanced alarm programming: thresholds and actions

    2.0 A

    5.0 A

    6.0 A

    7.0 A

    5.0 P

    6.0 P

    7.0 P

    5.0 H

    6.0 H

    7.0 H

    E46251

    E46252

    E46255

    E46255

    E46253

    E46256

    E46256

    E46253

    E46256

    E46256

  • 7/22/2019 Micrologic 6

    3/1230

    Micrologic 6.0 A

    40

    100%

    %

    menu

    .4

    .5

    .6.7

    .8.9

    .95

    .98

    1

    delay

    short timeI itsd

    (s)

    on I2t

    .2

    .3.4 .4

    .1

    .2.3

    .10off

    instantaneous

    long timealarmIr

    x In

    13

    10

    ground fault

    B

    CD

    EF

    G

    H

    J

    Ig tg(s)

    on I2t

    .2

    .3.4 .4

    .1

    .2.3

    .10off

    A

    .5

    1

    24

    812

    16

    20

    tr(s)

    @ 6 Ir24

    setting

    x Ir

    2

    2.53

    456

    8

    10

    Isd

    1.5x In

    test

    6

    3

    5

    71

    2

    12

    11

    9

    8

    2

    410

    3

    6 8

    12

    15off

    4

    kAs

    Ir=Ii=

    tr=Isd=

    Ig=

    tsd=t=

    tg=

    In= MAX

    Control unitsMicrologic A "ammeter"

    Functionsand characteristics

    Protection settings........................................................

    Protection thresholds and delays are set using the adjustment dials.

    The selected values are momentarily displayed in amperes and in seconds.

    Overload protectionTrue rms long-time protection.

    Thermal memory: thermal image before and after tripping.Setting accuracy may be enhanced by limiting the setting range using a different

    long-time rating plug.

    The long-time rating plug "OFF" enables to cancel the overload protection.

    Short-circuit protectionShort-time (rms) and instantaneous protection.

    Selection of I2t type (ON or OFF) for short-time delay.

    Earth fault protectionResidual or source ground return.Selection of I2t type (ON or OFF) for delay.

    Residual earth-leakage protection (Vigi).Operation without an external power supply.

    Protected against nuisance tripping.k DC-component withstand class A up to 10 A.

    Neutral protectionOn three-pole circuit breakers, neutral protection is not possible.

    On four-pole circuit breakers, neutral protection may be set using a three-position

    switch: neutral unprotected (4P 3d), neutral protection at 0.5 In (4P 3d + N/2),neutral protection at In (4P 4d).

    Zone selective interlocking (ZSI)A ZSI terminal block may be used to interconnect a number of control units toprovide total discrimination for short-time and earth-fault protection, without a delay

    before tripping.

    "Ammeter" measurements ...........................................menu

    Micrologic A control units measure the true rms value of currents.

    A digital LCD screen continuously displays the most heavily loaded phase (Imax)

    or displays the I1, I2, I3, IN, Ig, In, stored-current (maximeter) and setting values bysuccessively pressing the navigation button.

    The optional external power supply makes it possible to display currents < 20% In.

    Communication option

    In conjunction with the COM communication option, the control unit transmits thefollowing:

    setting values

    all "ammeter" measurementstripping causes

    maximeter reset.

    1 long-time current setting and tripping delay2 overload signal (LED) at 1.125 Ir3 short-time pick-up and tripping delay4 instantaneous pick-up5 earth-leakage or earth-fault pick-up and tripping delay6 earth-leakage or earth-fault test button7 long-time rating plug screw8 test connector9 lamp test, reset and battery test10 indication of tripping cause11 digital display12 three-phase bargraph and ammeter13 navigation buttons

    Micrologic A control units protect powercircuits.

    They also offer measurements, display,communication and current maximeters.Version 6 provides earth-fault protection,version 7 provides earth-leakageprotection.

    E46028

    Note.Micrologic A control units come with a transparent lead-seal cover as standard.

  • 7/22/2019 Micrologic 6

    4/1231

    0 I

    t

    Ir

    tr

    Isd

    Protection Micrologic 2.0 Along time

    current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

    tripping between 1.05 and 1.20 x Ir other ranges or disable by changing rating plug

    time setting tr (s) 0.5 1 2 4 8 12 16 20 24

    time delay (s) accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600

    accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24

    accuracy: 0 to -20 %) 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

    thermal memory 20 minutes before and after tripping

    (1)0 to - 40 % -(2)0 to - 60 %

    instantaneous

    pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10

    accuracy: 10 %

    time delay max resettable time: 20 ms ; max break time: 80 ms

    Ammeter Micrologic 2.0 Acontinuous current measurements

    display from 20 to 200 % of In I1 I2 I3 IN

    accuracy: 1.5% (including sensors) no auxiliary source (where I > 20 % In)

    maximeters I1 max I2 max I3 max IN max

    Protection Micrologic 5.0 / 6.0 / 7.0 Along time Micrologic 5.0 / 6.0 / 7.0 A

    current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

    tripping between 1.05 and 1.20 x Ir other ranges or disable by changing rating plug

    time setting tr (s) 0.5 1 2 4 8 12 16 20 24

    time delay (s) accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600

    accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24

    accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

    thermal memory 20 minutes before and after tripping

    (1)0 to - 40 % -(2)0 to - 60 %

    short time

    pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10

    accuracy: 10 %time setting tsd (s) settings I2t Off 0 0.1 0.2 0.3 0.4

    I2t On - 0.1 0.2 0.3 0.4

    time delay (ms) at 10 Ir tsd (max resettable time) 20 80 140 230 350

    (I2t off or I2t on) tsd (max break time) 80 140 200 320 500

    instantaneous

    pick-up (A) Ii = In x 2 3 4 6 8 10 12 15 off

    accuracy: 10 %

    time delay max resettable time: 20 ms ; max break time: 50 ms

    earth fault Micrologic 6.0 A

    pick up (A) Ig = In x A B C D E F G H J

    accuracy: 10 % In 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    400 A < In 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    In > 1200 A 500 640 720 800 880 960 1040 1120 1200

    time setting tg (s) settings I2t Off 0 0.1 0.2 0.3 0.4

    I2t On - 0.1 0.2 0.3 0.4

    time delay (ms) tg (max resettable time) 20 80 140 230 350

    at In or 1200 A (I2t off or I2t on) tg (max break time) 80 140 200 320 500

    residual earth leakage (Vigi) Micrologic 7.0 A

    sensitivity (A) In 0.5 1 2 3 5 7 10 20 30accuracy: 0 to -20 %

    time delay t (ms) settings 60 140 230 350 800

    t (max resettable time) 60 140 230 350 800

    t (max break time) 140 200 320 500 1000

    Ammeter Micrologic 5.0 / 6.0 / 7.0 Acontinuous current measurements

    display from 20 to 200 % of In I1 I2 I3 IN Ig In

    accuracy: 1.5 % (including sensors) no auxiliary source (where I > 20 % In)

    maximeters I1 max I2 max I3 max IN max Ig max In max

    E46022

    Note.All current-based protection functions require no auxiliary source.The test / reset button resets maximeters, clears the tripping indication and tests the battery.

    menu

    DB100423

    0 I

    tIn

    t

    E46243

    menu

    0 I

    t

    Ig

    tgI2t off

    I2t on

    E46024

  • 7/22/2019 Micrologic 6

    5/1232

    Micrologic 6.0 P

    .4

    .5

    .6.7

    .8.9

    .95

    .98

    1

    delay

    short timeI itsd

    (s)

    on I2t

    .2

    .3.4 .4

    .1

    .2.3

    .10off

    instantaneous

    long timealarmIr

    x In

    ground fault

    B

    CD

    EFG

    H

    J

    Ig tg(s)

    on I2t

    .2

    .3.4 .4

    .1

    .2.3

    .10off

    A

    setting

    x Ir

    2

    2.53

    456

    8

    10

    Isd

    1.5

    .5

    1

    24

    812

    16

    20

    tr(s)

    @ 6 Ir24

    x In

    test

    2

    410

    3

    6 8

    12

    15off

    I(A)

    Trip

    20 kA

    0.4s

    Off

    24s

    2000A

    13

    5

    10

    15

    166

    1

    8

    2

    7

    43

    9

    11

    12 14

    Control unitsMicrologic P "power"

    Functionsand characteristics

    Micrologic P control units include all thefunctions offered by Micrologic A.

    In addition, they measure voltages andcalculate power and energy values.They also offer new protection functionsbased on currents, voltages, frequency andpower reinforce load protection.

    Protection settings........................................................ +

    The adjustable protection functions are identical to those of Micrologic A

    (overloads, short-circuits, earth-fault and earth-leakage protection).

    Double settingWithin the range determined by the adjustment dial, fine adjustment of thresholds

    (to within one ampere) and time delays (to within one second) is possible on thekeypad or remotely using the COM option.

    IDMTL settingCoordination with fuse-type or medium-voltage protection systems is optimised byadjusting the slope of the overload-protection curve. This setting also ensures

    better operation of this protection function with certain loads.

    Neutral protectionOn three-pole circuit breakers, neutral protection may be set using the keypad or

    remotely using the COM option, to one of four positions: neutral unprotected (4P3d), neutral protection at 0.5 In (4P 3d + N/2), neutral protection at In (4P 4d) and

    neutral protection at 1,6 In (4P 3d + 1,6N). Neutral protection at 1,6 In is used whenthe neutral conductor is twice the size of the phase conductors (major load

    imbalance, high level of third order harmonics).On four-pole circuit breakers, neutral protection may be set using a three-position

    switch or the keypad: neutral unprotected (4P 3d), neutral protection at 0.5 In (4P

    3d + N/2), neutral protection at In (4P 4d). Neutral protection produces no effect ifthe long-time curve is set to one of the IDMTL protection settings.

    Programmable alarms and other protection............................

    Depending on the thresholds and time delays set using the keypad or remotely

    using the COM option, the Micrologic P control unit monitors currents and voltage,power, frequency and the phase sequence. Each threshold overrun is signalled

    remotely via the COM option. Each threshold overrun may be combined with

    tripping (protection) or an indication carried out by an optional M2C or M6C

    programmable contact (alarm), or both (protection and alarm).

    Load shedding and reconnection........................................

    Load shedding and reconnection parameters may be set according to the power orthe current flowing through the circuit breaker. Load shedding is carr ied out by a

    supervisor via the COM option or by an M2C or M6C programmable contact.

    Measurements .......................................................................

    The Micrologic P control unit calculates in real time all the electrical values (V, A,W, VAR, VA, Wh, VARh, VAh, Hz), power factors and crest factors.

    The Micrologic P control unit also calculates demand current and demand powerover an adjustable time period. Each measurement is associated with a minimeterand a maximeter.

    In the event of tripping on a fault, the interrupted current is stored. The optional

    external power supply makes it possible to display the value with the circuit breakeropen or not supplied.

    Histories and maintenance indicators ................................

    The last ten trips and alarms are recorded in two separate history files.Maintenance indications (contact wear, operation cycles, etc.) are recorded for

    local access.

    Indication option via programmable contacts

    The M2C (two contacts) and M6C (six contacts) auxiliary contacts may be used tosignal threshold overruns or status changes. They can be programmed using the

    keypad on the Micrologic P control unit or remotely using the COM option.

    Communication option (COM)

    The communication option may be used to:remotely read and set parameters for the protection functions

    transmit all the calculated indicators and measurements

    signal the causes of tripping and alarms

    consult the history files and the maintenance-indicator register.

    maximeter reset.An event log and a maintenance register, stored in control-unit memory but notavailable locally, may be accessed in addition via the COM option.

    1 long-time current setting and tripping delay2 overload signal (LED)3 short-time pick-up and tripping delay4 instantaneous pick-up5 earth-leakage or earth-fault pick-up and tripping delay6 earth-leakage or earth-fault test button7 long-time rating plug screw8 test connector9 lamp + battery test and indications reset10 indication of tripping cause11 high-resolution screen12 measurement display13 maintenance indicators14 protection settings15 navigation buttons16 hole for settings lockout pin on cover

    E46017

    Note.Micrologic P control units come with a non-transparentlead-seal cover as standard.

  • 7/22/2019 Micrologic 6

    6/1233

    0 I/U/P/F

    t

    delay

    threshold

    delay

    threshold

    0 I

    t

    Ig

    tgI2t off

    I2t on

    Protection Micrologic 5.0 / 6.0 / 7.0 P +long time (rms) Micrologic 5.0 / 6.0 / 7.0 P

    current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

    tripping between 1.05 and 1.20 x Ir other ranges or disable by changing rating plug

    time setting tr (s) 0.5 1 2 4 8 12 16 20 24

    time delay (s) accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600

    accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24

    accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

    IDMTL setting curve slope SIT VIT EIT HVFuse DT

    thermal memory 20 minutes before and after tripping

    (1)0 to- 40 % -(2)0 to - 60 %

    short time (rms)

    pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10

    accuracy: 10 %

    time setting tsd (s) settings I2t Off 0 0.1 0.2 0.3 0.4

    I2t On 0.1 0.2 0.3 0.4

    time delay (ms) at 10 x Ir tsd(max resettable time) 20 80 140 230 350

    (I2t off or I2t on) tsd (max break time) 80 140 200 320 500

    instantaneouspick-up (A) Ii = In x 2 3 4 6 8 10 12 15 OFF

    accuracy: 10 %

    time delay max resettable time: 20 ms ; max break time: 50 ms

    earth fault Micrologic 6.0 P

    pick-up (A) Ig = In x A B C D E F G H J

    accuracy: 10 % In 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    400 A < In 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    In > 1200 A 500 640 720 800 880 960 1040 1120 1200

    time setting tg (s) settings I2t Off 0 0.1 0.2 0.3 0.4

    I2t On 0.1 0.2 0.3 0.4

    time delay (ms) tg (max resettable time) 20 80 140 230 350

    at In or 1200 A (I2t off or I2t on) tg (max break time) 80 140 200 320 500

    residual earth leakage (Vigi) Micrologic 7.0 P

    sensitivity (A) In 0.5 1 2 3 5 7 10 20 30

    accuracy: 0 to -20 %

    time delay t (ms.) settings 60 140 230 350 800

    t (max resettable time) 60 140 230 350 800

    t (max break time) 140 200 320 500 1000

    Alarms and other protection Micrologic 5.0 / 6.0 / 7.0 Pcurrent threshold time delay

    current unbalance Iunbalance 0.05 to 0.6 Iaverage 1 to 40 s.

    maximum demand current Imax demand: I1, I2, I3, IN 0.2 In to In 15 to 1500 s.

    earth fault alarm

    It 20 A to 1200 A 1 to 10 s.

    voltage

    voltage unbalance Uunbalance 0.02 to 0.3 Uaverage 1 to 40 s.

    minimum voltage Umin 100 to Umax between phases 1.2 to 5 s.

    maximum voltage Umax Umin to 1200 between phases 1.2 to 5 s.

    power

    reverse power rP 5 to 500 kW 0.2 to 20 s.

    frequency

    minimum frequency Fmin 45 to Fmax 1.2 to 5 s.

    maximum frequency Fmax Fmin to 440 Hz 1.2 to 5 s.

    phase sequence

    sequence (alarm) 1/2/3 or 1/3/2 0.3 s.

    Load shedding and reconnection Micrologic 5.0 / 6.0 / 7.0 Pmeasured value threshold time delay

    current I 0.5 to 1 Ir per phases 20% tr to 80% tr.

    power P 200 kW to 10 MW 10 to 3600 s.

    0

    Ir

    I

    t

    tr

    Isd

    tsd

    Ii

    IDMTL

    E46

    021

    E46024

    E46015

    Note.All current-based protection functions require no auxiliary source.Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker.

    0 I

    tIn

    t

    E46243

    0 I/P

    t

    threshold

    delaydelay

    threshold

    E46016

  • 7/22/2019 Micrologic 6

    7/1234

    03/08/199912:02:36

    Trip

    IN = 53A

    I3 = 1060A

    I2 = 1430A

    I1 = 1200A

    Ir = 1000A

    Triphistory

    30/06/1999

    03/08/1999

    27/07/1999

    Ir

    Isd

    Umax

    PdemandeActive P2180 kW

    Ractive Q- 650 kVAR

    Apparente S2280 kVA

    Pdemand

    (kW)

    (kVAR)

    (kVA)

    +2180

    -650

    +2280

    P

    Q

    S

    F (Hz)

    60.0

    Pinst.

    (kW)

    (kVAR)

    (kVA)

    +2180

    -650

    +2280

    P

    Q

    S

    U12 = 400VU23 = 404V

    U31 = 401V

    inst.

    U

    U1N = 230V

    U2N = 229V

    U3N = 233V

    IN = 200A

    I3 = 4000A

    I2 = 4600A

    I1 = 4800A

    instant.Imax

    = 13AI

    Reset ( + / - )

    3850A

    N

    0

    50

    100

    1 2 3

    Control unitsMicrologic P "power"

    Functionsand characteristics

    Navigation from one display to another is intuitive. The six buttons on the keypadprovide access to the menus and easy selection of values. When the setting cover

    is closed, the keypad may no longer be used to access the protection settings, but

    still provides access to the displays for measurements, histories, indicators, etc.

    Measurements .......................................................................

    Instantaneous values

    The value displayed on the screen is refreshed every second.

    Minimum and maximum values of measurements are stored in memory(minimeters and maximeters).

    currentsI rms A 1 2 3 N

    A e-fault e-leakage

    I maxrms A 1 2 3 N

    A e-fault e-leakage

    voltagesU rms V 12 23 31

    V rms V 1N 2N 3N

    U average rms V (U12 + U23 + U31) / 3

    U unbalance %

    power, energyP active, Q reactive, S apparent W, Var, VA totals

    E active, E reactive, E apparent Wh, VARh, VAh totals consumed - supplied

    totals consumed

    totals supplied

    power factor PF total

    frequenciesF Hz

    Demand meteringThe demand is calculated over a fixed or sliding time window that may be

    programmed from 5 to 60 minutes. According to the contract signed with the powersupplier, an indicator associated with a load shedding function makes it possible to

    avoid or minimise the costs of overrunning the subscribed power. Maximum

    demand values are systematically stored and time stamped (maximeter).

    currentsI demand A 1 2 3 N

    A e-fault e-leakage

    I max demand A 1 2 3 N

    A e-fault e-leakage

    powerP, Q, S demand W, Var, VA totals

    P, Q, S max demand W, Var, VA totals

    Minimeters and maximetersOnly the current and power maximeters may be displayed on the screen.

    Histories .................................................................................

    The last ten trips and alarms are recorded in two separate history files that may bedisplayed on the screen.

    tripping history:

    v type of faultv date and timev values measured at the time of tripping (interrupted current, etc.).alarm history:v type of alarmv date and timev values measured at the time of the alarm.

    Maintenance indicators ........................................................A number of maintenance indicators may be called up on the screen:contact wear

    operation counter:

    v cumulative total

    v total since last reset

    Default display

    Display after trippingDisplay of a tripping history

    Display of a maximumcurrent

    Display of a frequency Display of a demand power

    Display of a powerDisplay of a voltage

    E46258

    E46261

    E46262

    E46263

    E47305

    E46265

    E46259

    E46260

  • 7/22/2019 Micrologic 6

    8/1235

    With the communication option

    Additional measurements, maximeters and minimetersCertain measured or calculated values are only accessible with the COM

    communication option:

    I peak / , (I1 + I2 + I3)/3, I unbalanceload level in % Ir

    total power factor

    The maximeters and minimeters are available only via the COM option for use witha supervisor.

    Event logAll events are time stamped.

    tripsbeginning and end of alarms

    modifications to settings and parameterscounter resets

    system faults:

    fallback positionthermal self-protection

    loss of timeoverrun of wear indicatorstest-kit connectionsetc.

    Maintenance registerUsed as an aid in troubleshooting and to better plan for device maintenance

    operations.

    highest current measuredoperation counter

    number of test-kit connections

    number of trips in operating mode and in test modecontact-wear indicator.

    Additional technical characteristicsSetting the display languageSystem messages may be displayed in six different languages. The desired language isselected via the keypad.

    Protection functionsAll current-based protection functions require no auxiliary source. Voltage-basedprotection functions are connected to AC power via a voltage measurement input builtinto the circuit breaker.

    Measurement functionsMeasurement functions are independent of the protection functions.The high-accuracy measurement module operates independently of the protectionmodule, while remaining synchronised with protection events.

    Measurement-calculation modemeasurement functions implement the new "zero blind time" concept which consists incontinuously measuring signals at a high sampling rate. The traditional "blind window"used to process samples no longer exists. This method ensures accurate energycalculations even for highly variable loads (welding machines, robots, etc.).

    energies are calculated on the basis of the instantaneous power values, in twomanners:vthe traditional mode where only positive (consumed) energies are consideredvthe signed mode where the positive (consumed) and negative (supplied) energies areconsidered separately.

    Accuracy of measurements (including sensors)voltage (V) 1%current (A) 1.5% frequency (Hz) 0.1 Hzpower (W) and energy (Wh) 2.5%

    Stored informationThe fine setting adjustments, the last 100 events and the maintenance register remain inthe control-unit memory even when power is lost.

    Time-stampingTime-stamping is activated as soon as time is set manually or by a supervisor.No external power supply module is required (max. drift of 1 hour per year).

    ResetAn individual reset, via the keypad or remotely, acts on alarms, minimum and maximumdata, peak values, the counters and the indicators.

    Display of an event log on a supervisor

    E47070

    ModuleEventTime

    POWERLOGIC System Manager Demo

    Ready

    File Edit View Setup ToolsControl Display Reports Window Help

    ONLINE: DEMO 9:30No working system

    5 secondsSampling Mode : MANUAL

    04/21/98 08:49:06 Net Server Shutdown User : master Level : 1 PowerLogic Network04/21/98 08:49:01 User Log Out User : master User level : 1 SMS-3000 Client04/21/98 08:48:38 DB Table Change User : master TOD Event Tasks Alarm Setup04/21/98 08:48:30 DB Table Change User : master Tasks Alarm Setup04/21/98 08:46:16 DB Table Change User : master TOD Events Alarm Setup04/21/98 08:39:19 User Log In User : master User level : 1 SMS-3000 Client04/21/98 08:39:06 Security Check Key Status : Key Found PowerLogic Network04/21/98 08:39:06 Net Server Started User : master Level : 1 PowerLogic Network04/21/98 08:38:57 User Log In Event/Alarm/Network04/21/98 08:30:44 Net Server Shutdown User : master Level : 1 PowerLogic Network04/21/98 08:24:31 Security Check Key Status : Key Found PowerLogic Network04/21/98 08:24:30 Net server Started User : master Level : 1 PowerLogic Network04/21/98 08:24:15 User Log IN Event/Alarm/Network04/21/98 08:18:07 IPC Error User : NA Err : 109 SMS-3000 Client04/21/98 07:54:05 DB Table Change User : -1 Logger Template Devices Logger Setup04/21/98 07:53:55 DB Table Change User : -1 Logger Template Topics Logger Setup04/21/98 07:53:54 DB Table Change User : -1 Logger Templates Logger Setup04/21/98 07:51:46 DB Table Change User : master Analog Levels Assigned Alarm Setup04/21/98 07:51:33 DB Table Change User : master Analog Levels Template Alarm Setup04/21/98 07:51:29 DB Table Change User : master Functions Alarm Setup04/21/98 07:50:17 DB Table Change User : master Digital Levels Assigned Alarm Setup04/21/98 07:50:17 DB Table Change User : master Analog L evels Assigned Alarm Setup0 4/ 21 /9 8 0 7: 49 :1 3 S et up : D ev ic e N am e C ha ng e D ev ic e : Mi cr oL og ic Br ea ke r U se r : ma st er D ev ic e S et up0 4/ 21 /9 8 0 7: 48 :5 7 S et up : D ev ic e A dd ed D ev ic e : M ic ro Lo gi c B re ak er U se r : ma st er D ev ic e S et up0 4/ 21 /9 8 0 7: 48 :3 8 S et up : D ev ic e N am e C ha ng e D ev ic e : Tr an sf or me r Te mp U se r : ma st er D ev ic e S et up0 4/ 21 /9 8 0 7: 48 :2 2 S et up : D ev ic e A dd ed D ev ic e : Tr an sf or me r Te mp U se r : ma st er D ev ic e S et up04/21/98 07:46:54 User Log In User : master User Level : 1 SMS-3000 Client04/21/98 07:44:59 Security Check Key Status : Key Found PowerLogic Network04/21/98 07:44:59 Net Server Started User :master Level : 1 PowerLogic Network

  • 7/22/2019 Micrologic 6

    9/1236

    Micrologic 7.0 H

    .4

    .5

    .6.7

    .8.9

    .95

    .98

    1

    delay

    short timeI itsd

    (s)

    on I2t

    .2

    .3.4 .4

    .1

    .2.3

    .10off

    instantaneous

    long timealarmIr

    x In

    setting

    x Ir

    2

    2.53

    456

    8

    10

    Isd

    1.5

    .5

    1

    24

    812

    16

    20

    tr(s)

    @ 6 Ir24

    x In

    test

    I (A)

    U (V)

    P (kW)

    E (kWh)

    Harmonics

    2

    410

    3

    6 8

    12

    15off

    800

    earth leakage

    1

    23

    57

    10

    20

    30

    t(ms)

    60.5

    140

    230 350

    In(A)

    Control unitsMicrologic H "harmonics"

    Functionsand characteristics

    Micrologic H control units include all thefunctions offered by Micrologic P.

    Integrating significantly enhancedcalculation and memory functions, theMicrologic H control unit offers in-depthanalysis of power quality and detailedevent diagnostics. It is intended foroperation with a supervisor.

    In addition to the Micrologic P functions, the Micrologic H control unit offers:in-depth analysis of power quality including calculation of harmonics and the

    fundamentals

    diagnostics aid and event analysis through waveform captureenhanced alarm programming to analyse and track down a disturbance on the

    AC power system

    Measurements .......................................................................

    The Micrologic H control unit offers all the measurements carried out by MicrologicP, with in addition:phase by phase measurements of:

    v power, energyv power factorscalculation of:

    v current and voltage total harmonic distortion (THD)v current, voltage and power fundamentalsv current and voltage harmonics up to the 31st order.

    Instantaneous values displayed on the screen

    currentsI rms A 1 2 3 N

    A e-fault e-leakage

    I maxrms A 1 2 3 N

    A e-fault e-leakage

    voltagesU rms V 12 23 31

    V rms V 1N 2N 3N

    U average rms V (U12 + U23 + U31) / 3

    U unbalance %

    power, energyP active, Q reactive, S apparent W, Var, VA totals 1 2 3

    E active, E reactive, E apparent Wh, VARh, VAh totals consumed - supplied

    totals consumed

    totals supplied

    power factor PF total 1 2 3

    frequenciesF Hz

    power-quality indicatorstotal fundamentals U I P Q S

    THD % U I

    U and I harmonics amplitude 3 5 7 9 11 13

    Harmonics 3, 5, 7, 9, 11 and 13, monitored by electrical utilities, are displayed on thescreen.

    Demand measurementsSimilar to the Micrologic P control unit, the demand values are calculated over afixed or sliding time window that may be set from 5 to 60 minutes.

    currentsI demand A 1 2 3 N

    A e-fault e-leakage

    I max demand A 1 2 3 N

    A e-fault e-leakage

    powerP, Q, S demand W, Var, VA totals

    P, Q, S max demand W, Var, VA totals

    MaximetersOnly the current maximeters may be displayed on the screen.

    Histories and maintenance indicators

    These functions are identical to those of the Micrologic P.

    E46257

    Note.Micrologic H control units come with a non-transparentlead-seal cover as standard.

  • 7/22/2019 Micrologic 6

    10/1237

    ModuleEventTime

    POWERLOGIC System Manager Demo

    Ready

    File Edit View Setup ToolsControl Display Reports Window Help

    ONLINE: DEMO 9:30No working system

    5 secondsSampling Mode : MANUAL

    04/21/98 08:49:06 Net Server Shutdown User : master Level : 1 PowerLogic Network04/21/98 08:49:01 User Log Out User : master User level : 1 SMS-3000 Client04/21/98 08:48:38 DB Table Change User : master TOD Event Tasks Alarm Setup04/21/98 08:48:30 DB Table Change User : master Tasks Alarm Setup04/21/98 08:46:16 DB Table Change User : master TOD Events Alarm Setup04/21/98 08:39:19 User Log In User : master User level : 1 SMS-3000 Client04/21/98 08:39:06 Security Check Key Status : Key Found PowerLogic Network04/21/98 08:39:06 Net Server Started User : master Level : 1 PowerLogic Network04/21/98 08:38:57 User Log In Event/Alarm/Network04/21/98 08:30:44 Net Server Shutdown User : master Level : 1 PowerLogic Network04/21/98 08:24:31 Security Check Key Status : Key Found PowerLogic Network04/21/98 08:24:30 Net server Started User : master Level : 1 PowerLogic Network04/21/98 08:24:15 User Log IN Event/Alarm/Network04/21/98 08:18:07 IPC Error User : NA Err : 109 SMS-3000 Client04/21/98 07:54:05 DB Table Change User : -1 Logger Template Devices Logger Setup04/21/98 07:53:55 DB Table Change User : -1 Logger Template Topics Logger Setup04/21/98 07:53:54 DB Table Change User : -1 Logger Templates Logger Setup04/21/98 07:51:46 DB Table Change User : master Analog Levels Assigned Alarm Setup04/21/98 07:51:33 DB Table Change User : master Analog Levels Template Alarm Setup04/21/98 07:51:29 DB Table Change User : master Functions Alarm Setup04/21/98 07:50:17 DB Table Change User : master Digital Levels Assigned Alarm Setup04/21/98 07:50:17 DB Table Change User : master Analog L evels Assigned Alarm Setup0 4/ 21 /9 8 0 7: 49 :1 3 S et up : D ev ic e N am e C ha ng e D ev ic e : Mi cr oL og ic Br ea ke r U se r : ma st er D ev ic e S et up0 4/ 21 /9 8 0 7: 48 :5 7 S et up : D ev ic e A dd ed D ev ic e : M ic ro Lo gi c B re ak er U se r : ma st er D ev ic e S et up0 4/ 21 /9 8 0 7: 48 :3 8 S et up : D ev ic e N am e C ha ng e D ev ic e : Tr an sf or me r Te mp U se r : ma st er D ev ic e S et up0 4/ 21 /9 8 0 7: 48 :2 2 S et up : D ev ic e A dd ed D ev ic e : T ra ns fo rm er Te mp U se r : ma st er D ev ic e S et up04/21/98 07:46:54 User Log In User : master User Level : 1 SMS-3000 Client04/21/98 07:44:59 Security Check Key Status : Key Found PowerLogic Network04/21/98 07:44:59 Net Server Started User :master Level : 1 PowerLogic Network

    POWERLOGIC System Manager Demo

    Ready

    File Edit View Setup ToolsControl Display Reports Window Help

    ONLINE: DEMO 9:30No working system

    5 secondsSampling Mode : MANUAL

    -167

    -83

    0

    83

    167

    Phase A-N Voltage

    17 33 50 66

    Phase B-N Voltage

    -642

    -321

    0

    321

    642

    Phase A Current

    6617 33 50

    -167

    -83

    0

    83

    167

    17 33 50

    Your Specific Device - Phase A-N Voltage

    Harmonics(RMS)

    H2: 0.01H3: 0.45H4: 0.03H5: 0.45H6: 0.04H7: 1.27H8: 0.05H9: 0.42H10: 0.01H11: 1.03H12: 0.07

    H1: 118.09Fundamental : 118.08

    RMS: 118.11

    RMS-H: 2.38

    Peak: 166.86

    CF: 1.41

    THD: 2.02

    OK

    ModuleEventTime

    POWERLOGIC System Manager Demo

    Ready

    File Edit View Setup ToolsControl Display Reports Window Help

    ONLINE: DEMO 9:30No working system

    5 secondsSampling Mode : MANUAL

    0,00

    0,20

    0,40

    0,60

    0,80

    1,00

    1,20

    H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12

    %F

    undamental

    Harmonics

    Phase A-N Voltage - Harmonics Analysis

    Phase 1-N

    Harmonics(RMS)

    H2: 0.01H3: 0.45H4: 0.03H5: 0.45H6: 0.04H7: 1.27H8: 0.05H9: 0.42H10: 0.01H11: 1.03H12: 0.07

    H1: 118.09

    OK

    Fundamental:

    RMS:

    RMS-H:

    Peak:

    CF:

    THD:

    With the communication option

    Additional measurements, maximeters and minimetersCertain measured or calculated values are only accessible with the COMcommunication option:

    I peak / , (I1 + I2 + I3)/3, I unbalanceload level in % Irpower factor (total and per phase)

    voltage and current THD

    K factors of currents and average K factorcrest factors of currents and voltages

    all the fundamentals per phasefundamental current and voltage phase displacementdistortion power and distortion factor phase by phase

    amplitude and displacement of current and voltage harmonics 3 to 31.

    The maximeters and minimeters are available only via the COM option for use with

    a supervisor.

    Waveform captureThe Micrologic H control unit stores the last 4 cycles of each instantaneous current

    or voltage measurement. On request or automatically on programmed events, thecontrol unit stores the waveforms. The waveforms may be displayed in the form of

    oscillograms by a supervisor via the COM option. Definition is 64 points per cycle.

    Enhanced alarm programmingEach instantaneous value can be compared to user-set high and low thresholds.Overrun of a threshold generates an alarm. An alarm or combinations of alarmscan be linked to programmable actions, including circuit-breaker opening,

    activation of a M2C or M6C contact, selective recording of measurements in a log,

    waveform capture, etc.

    Event log and maintenance registersThe Micrologic H offers the same event log and maintenance register functions as

    the Micrologic P.

    Additional technical characteristicsSetting the display languageSystem messages may be displayed in six different languages. The desired language isselected via the keypad.

    Protection functionsAll current-based protection functions require no auxiliary source. Voltage-basedprotection functions are connected to AC power via a voltage measurement input builtinto the circuit breaker.

    Measurement functionsMeasurement functions are independent of the protection functions.The high-accuracy measurement module operates independently of the protectionmodule, while remaining synchronised with protection events.

    Measurement-calculation mode

    An analogue calculation function dedicated to measurements enhances the accuracy ofharmonic calculations and the power-quality indicators. The Micrologic H control unitcalculates electrical magnitudes using 1.5 x In dynamics (20 x In for Micrologic P).Measurement functions implement the new "zero blind time" conceptEnergies are calculated on the basis of the instantaneous power values, in the traditionaland signed modes.Harmonic components are calculated using the discrete Fourier transform (DFT).

    Accuracy of measurements (including sensors)voltage (V) 1%current (A) 1.5%frequency (Hz) 0.1 Hzpower (W) and energy (Wh) 2.5%total harmonic distortion 1%

    Stored informationThe fine-setting adjustments, the last 100 events and the maintenance register remain inthe control-unit memory even when power is lost.

    Time-stampingTime-stamping is activated as soon as time is set manually or by a supervisor no

    external power supply module is required (max. drift of 1 hour per year).ResetAn individual reset, via the keypad or remotely, acts on alarms, minimum and maximumdata, peak values, the counters and the indicators.

    Waveform capture

    Display of harmonics up to 12th order.

    Log

    E47071

    E47072

    E47070

  • 7/22/2019 Micrologic 6

    11/1238

    External sensorsExternal sensor for earth-fault and neutral protectionThe sensors, used with the 3P circuit breakers, are installed on the neutral

    conductor for:neutral protection (with Micrologic P and H)residual type earth-fault protection (with Micrologic A, P and H)..

    The rating of the sensor (CT) must be compatible with the rating of the circuit breaker:NT06 to NT16: TC 400/1600NW08 to NW20: TC 400/2000NW25 to NW40: TC 1000/4000NW40b to NW63: TC 2000/6300.

    For oversized neutral protection the sensor rating must be compatible with themeasurement range: 1,6 x IN (available up to NW 40 and NT 16).

    Rectangular sensor for earth-leakage protectionThe sensor is installed around the busbars (phases + neutral) to detect the zero-phase sequence current required for the earth-leakage protection. Rectangularsensors are available in two sizes.Inside dimensions (mm)

    280 x 115 up to 1600 A for Masterpact NT and NW470 x 160 up to 4000 A for Masterpact NW.

    External sensor for source ground return protectionThe sensor is installed around the connection of the transformer neutral point toearth and connects to the Micrologic 6.0 control unit via an MDGF module toprovide the source ground return (SGR) protection.

    Voltage measurement inputsVoltage measurement inputs are required for power measurements (Micrologic Por H) and for earth-leakage protection (Micrologic 7...).As standard, the control unit is supplied by internal voltage measurement inputsplaced downstream of the pole for voltages between 100 and 690 V AC. Onrequest, it is possible to replace the internal voltage measurement inputs by anexternal voltage input (PTE option) which enables the control unit to draw powerdirectly from the distribution system upstream of the circuit breaker. An 3 m cablewith ferrite comes with this PTE option.

    Long-time rating plugFour interchangeable plugs may be used to limit the long-time threshold settingrange for higher accuracy.The time delay settings indicated on the plugs are for an overload of 6 Ir (for furtherdetails, see the characteristics on pages 19 and 21).As standard, control units are equipped with the 0.4 to 1 plug.

    Setting rangesstandard Ir = In x 0,4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1

    low-setting option Ir = In x 0.4 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.8

    high-setting option Ir = In x 0.80 0.82 0.85 0.88 0.90 0.92 0.95 0.98 1

    off plug no long-time protection (Ir = In for Isd setting)

    Important: Long-time rating plugs must always be removed before carrying outinsulation or dielectric withstand tests.

    External power-supply moduleThe external power-supply module makes it possible to use the display even if thecircuit breaker is open or not supplied (for the exact conditions of use, see the"electrical diagrams" part of this catalogue).

    This module powers both the control unit (100 mA) and the M2C and M6Cprogrammable contacts (100 mA).

    With the Micrologic A control unit, this module makes it possible to display currentsof less than 20% of In.With the Micrologic P and H, it can be used to display fault currents after tripping.

    Characteristicspower supply:v 110/130, 200/240, 380/415 V AC (+ 10% - 15%), consumption 10 VAv 24/30, 48/60, 100/125 V DC (+20% -20%), consumption 10 Woutput voltage: 24 V DC; power delivered: 5 W / 5 VAripple < 5%Dielectric withstand : 3 kV rms between input/output.

    Battery moduleThe battery module makes it possible to use the display even if the power supply tothe Micrologic control unit is interrupted and still commucating with the supervisor.

    Characteristics:battery run-time: 12 hours (approximately)mounted on vertical backplate or symmetrical rail.

    External sensor for source ground return protection

    056467

    056412

    External sensor (CT)

    Functionsand characteristics

    Micrologic control unitsAccessories and test equipment

    E47477

    0251

    73

    Rectangular sensor

    059476

    025

    171

  • 7/22/2019 Micrologic 6

    12/12

    M2C, M6C programmable contactsThese contacts are optional equipment for the Micrologic P and H control units.

    They are described with the indication contacts for the circuit breakers.characteristics M2C/M6C

    minimum load 10mA/24V

    breaking V AC 240 5

    capacity (A) 380 3

    p.f.: 0.7 V DC 24 1.8

    48 1.5

    125 0.4

    250 0.15

    M2C: 24 V DC power supplied by control unit (consumption 100 mA).

    M6C: external 24 V DC power supply required (consumption 100 mA).

    Spare parts

    Lead-seal coversA lead-seal cover controls access to the adjustment dials.

    When the cover is closed:it is impossible to modify settings using the keypad unless the settings lockout

    pin on the cover is removed.

    the test connector remains accessible.the test button for the earth-fault and earth-leakage protection function remains

    accessible.

    Characteristicstransparent cover for basic Micrologic and Micrologic A control units

    non-transparent cover for Micrologic P and H control units.

    Spare batteryA battery supplies power to the LEDs identifying the tripping causes. Batteryservice life is approximately ten years.A test button on the front of the control unit is used to check the battery condition.

    The battery may be replaced on site when discharged.

    Test equipment

    Mini test kitThe autonomous hand-held mini test kit may be used to:check operation of the control unit and the tripping and pole-opening system by

    sending a signal simulating a short-circuit

    supply power to the control units for settings via the keypad when the circuit-

    breaker is open (Micrologic P and H control units).

    Power source: standard LR6-AA battery.

    Portable test kitThe portable test kit can be used alone or with a suppor ting personal computer.

    The portable test kit without PC may be used to check:

    the mechanical operation of the circuit breaker

    the electrical continuity of the connection between the circuit breaker and thecontrol unit

    operation of the control unit:v display of settingsv automatic and manual tests on protection functionsv test on the zone-selective interlocking (ZSI) functionv inhibition of the earth-fault protectionv inhibition of the thermal memory.

    The portable test kit with PC offers in addition:comparison of the real tripping curve with the catalogue curves available on the

    PC

    reset of the M2C / M6C contacts and indicationsreading and modification of settings and countersreading of histories and logs

    waveform captureanalysis of harmonics.

    Portable test kit

    056466

    056429

    Lead-seal cover

    056413

    M2C

    M6C

    056430