4
a T Pipe system installation Only for installation by authorised specialists! 500 ø 6 mm Uponor PEX 9,9 T a 80 60 100 70 140 90 Optimal loop length: L = 50 m ≈ 500 Uponor plaster system for ceiling and wall cooling/heating MOUNTING INSTRUCTIONS

Mi plaster ceiling cooling system 1048014

Embed Size (px)

DESCRIPTION

https://www.uponor.com/~/media/countryspecific/international/download-centre/indoor_climate/underfloor-heating/brochures/mi_plaster-ceiling-cooling-system-1048014.pdf?version=1

Citation preview

Page 1: Mi plaster ceiling cooling system 1048014

aT

Pipe system installation

Only for installation by authorised specialists!

500ø 6 mm

UponorPEX 9,9

T a

80 60

100 70

140 90Optimal loop length:L = 50 m

≈ 500

Uponor plaster system for ceiling and wall cooling/heating

M O U N T I N G I N S T R U C T I O N S

Page 2: Mi plaster ceiling cooling system 1048014

2 1 0 4 8 0 1 4 0 3 / 2 0 1 0

Supply pipe installation

Fill pipes/Pressure test

After 2 h leak test

2 h max. 6 barM O N T A G E A N L E I T U N GM O U N T I N G I N S T R U C T I O N S

D F

G B I

N L C Z

DIN 1264-4

Mounting/operating instructionsfor the Uponor manifolds

Follow the additional instruction:

Uponor Q&E Installation

PE-Xa Installationssystem mitQuick & Easy Verbindungstechnik

INSTALLATIONSSYSTEME

T E C H N I S C H EI N F O R M A T I O N E N

Q&E 20

Q&E 9,9

ø 6 mm

Page 3: Mi plaster ceiling cooling system 1048014

31 0 4 8 0 1 4 0 3 / 2 0 1 0

Plaster work

e.g. Knauf MP75 G/F-Light

≈10 14

≈10

14

e.g. Knauf NP75 Diamant

While plastering, all circuits have to beheld under operating pressure.The system has to be kept frostfree.

Operational check

The system function has to be tested with the heating function process. For documentation use the Uponor heating function form.

The waiting period after palstering should beCement-bonded plaster: > 21 daysGypsum-bonded plaster: > 7 days

Observe also the plaster manufacturer's instructions.

Page 4: Mi plaster ceiling cooling system 1048014

1048

014

– 03

/201

0 M

E –

Subj

ect

to m

odifi

catio

ns

Operation

ϑSupply 16 – 40° C 16 – 50° C

ϑSurface < 35° C < 40° C

The buildingmanagement must beinformed of thelocation of the systempipes.