Upload
phamnga
View
254
Download
5
Embed Size (px)
Citation preview
| User Interface | Power | Data | Sensors & Switches
Methode Electronics Power Solutions
Methode Power Solutions Group, 1700 Hicks Road, Rolling Meadows, IL 60008 (847) 577-9545 www.methode.com
• HighCurrentCapacityof130
Amps
• Hot/LoadPluggable
• LowVoltageDrop
• UL1977StandardCompliant
• CSAStandardC22.2No.182.3-
M1987Compliant
• RoHSCompliant
Insulator Polyester(PBT),UL94V-0
Contact CopperBerylliumAlloy,NickelPlated
Crimp Termination CopperBerylliumAlloy,NickelPlated
Crimp Barrel Cover BrassCopperAlloy
CONNECTOR SPECIFICATIONS
Materials & Finish
Insertion Force 12N(1.2kgf)Typical
Mechanical
Maximum Operating Current 130A
Operating Current at 30°C T-Rise 105A
Insulator Voltage 600VAC/850VDC
Load Pluggable Current 105Aat24VOpenCircuit
Operating Current Through 6 AWG Wire 85Aat30°CT-Rise
Electrical Ratings
Maximum Operating Temperature 130°C
Storage Temperature -40°Cto130°C
Environmental
The OCP (Open Compute Project) Connector is a bus bar to cable power interconnection developed for use in Open Compute System applications. The connector sides are open allowing unbounded connection along bus-bar lengths. The connector is single pole and mounted in pairs to provide current loop connection. Mating lead-in is load-pluggable rated for 105 Amp current interruption using typical nickel, silver or gold surface plate.
Individualized contact bands are low resistance providing low voltage drop through the connection.
OCP Connector(MINI-MCC Bus Connector)
REGULATORY SPECIFICATIONS
SAFETY:UL1977,CSAStandardC22.2No.182.3-M1987(ULFileNumberE303434)
RoHS:IECDirective2002/95/EC
The OCP Connector (MINI-MCC Bus Connector) complies with UL safety regulatory requirements including current interruption and arcing without compromising connection reliability.
| User Interface | Power | Data | Sensors & Switches
Methode Electronics Power Solutions
Methode Power Solutions Group, 1700 Hicks Road, Rolling Meadows, IL 60008 (847) 577-9545 www.methode.com
OCP CONNECTOR DRAWING
ELECTRICAL PERFORMANCE
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
22.0
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
60 70 80 90 100 110 120 130 140
V‐Drop (m
V)
T‐Rise (°C)
Applied Current (Amps)
V-Drop (mV)
Contact T-Rise (°C)
Crimp T-Rise (°C)
Test Conditions:
Normalized graph shows OCP Connector electrical performance for temperature rise and voltage drop from 60 amps to 140 amps. The connector is mated to nickel plated copper conductor 3 mm x 38.1 mm, and the termination is through the crimp barrel to single 6 AWG stranded wire.
ORDERING INFORMATION
OCP Connector (MINI-MCC Bus Connector)Part Number: 5301-07278-00107
[email protected](847) 577-9545
22.7
3.5 16.0
20 32.2
26.8
8.4
20.0
2.1
RELIABLE MATING DEPTH
BUS-BAR
MATING BUS THICKNESS
COMPRESSION CRIMPSHOWN
FOR RELIABLE MATEMINIMUM BUS DEPTH
FROM FULL MATE
8.0MAXIMUM OFFSET
14.5
3.00±0.10BUS THICKNESS
POWERFLEXHV6-85-C STRANDED
6 AWG CABLESHOWN
INSULATOR HOUSING
CRIMP BARRELACCEPTS 6 AWG
STRANDED 7x150/36 CABLE
OCP CONNECTOR (MINI-MCC BUS CONNECTOR)Part Number: 5301-07278-00107
APPLICATION EXAMPLE
Open Compute Project Connector ModulePart Number: 5313-07450-00107Drawing is available on the Methode website or by contacting Methode at [email protected]