METARTEC PICO BU SERIES
The Metartec PICO BU Series is offlineUPS with the most advanced DSP controltechnology which can protect thesensitive device from utility fail, over/under voltage, surges, transients, spikesand other electrical abnormalities. Withautomatic boot voltage regulation andwide input voltage range, BU is a goodchoice to be applied to all kinds ofcomplex power environment.
Automatic booting when the utilityrecovers
Wide range of input voltage
Alarm and mute
Auto recharging
Overvoltage and circuit short protection
Optional Interface of RJ45/11 and USB
metartecpowering your future
MODEL BU600 BU800 BU1000 BU1200 BU1500
CAPACITY 600VA/360W 800VA480W 1000VA/600W 1200VA/720W 1500VA900W
INPUT
Input Voltage 110/120VAC or 220/230/240VAC
Input Voltage Range 85-150VAC/145-290VAC
Input Frequency 50/60Hz(Auto sensing)
OUTPUT
Output Voltage 110/120VAC or 220/230/240VAC
Output Voltage Range 102-132VAC/200-255VAC
Output Frequency 50/60Hz±0.5Hz
Wave Form PWM (DC mode)
Transfer Time Typical 2 – 6 ms, max ≤ 10ms
SYSTEM
QTY &Capacity of Battery 1*12V/7AH 1*12V/9AH 2*12V/7AH 2*12V/7AH 2*12V/9AH
Charging Period 4-6hr to 90% capacity
Protection Low voltage, overload and short circuit protection
Operation Temperature 0-40°C
Relative Humidity 20% - 90%(non- condensing)
Noise ≤ 40 db
Net Weight(Kg) 5.5 6 10.2 10.2 10.6
Dimension( mm) 305*85*140 335*118*190 340*110*265
Optional LED/LCD,RJ45/11 &USB
Standard ISO9001, ISO14001, CE
DE* Specifications are subject to change without further notice.L
Metartec Ltd. Solutions House Unit A19, 20 Heron Road Sydenham Business Park Belfast BT3 9LE
Tel: 0845 50 40 444
www.metartec.com
Metartec Ltd. Elm Pa rk House Elm Park Court Pinner Middlesex HA5 3NN
Tel: 0845 643 9772 www.metarteconline4ups.com
metartec powering your future
BU2000
2000VA1200W
220VAC
175-275VAC
50/60Hz
220VAC
220-240VAC
50Hz±0.5Hz
PWM (DC mode)
≤ 10ms
4*12V/7AH
10-16 hr
19
408*145*220
THE METARTEC PICO 650
The Metartec PICO 650 is the ideal UPS unit for supporting your domestic PC and MAC.
The PICO 650 is a compact line-interactive UPS which has an excellent built-in microprocessor controller, designed for fast response to power disturbances.
The PICO 650 provides a simulated sine wave incorporating boost and buck voltage stabilization which will maintain regulated nominal output without using battery power during brownouts and over voltages from 162-290V.
Other functions include ‘Auto Restart’ after extended mains failure whilst AC/utility power supply is recovering and ‘Cold Start function’ means the PICO 650 can be started directly from battery without AC utility supply.
Metartec’s PICO 650 has a RS232 communication port and RJ-11 phone protection socket fi tted as standard.
The PICO 650 offers a transfer time of 2-6ms between utility supply failure and UPS back-up; offering complete load support with practically little to no system disruption.
metartecpowering your future
PICO 650
metartecpowering your future
PICO 650 LINE INTERACTIVE UPS SELECTION GUIDE
MODEL
W 063 / AV 056 YTICAPAC
INPUT
CAV 042/032/022 egatloV
CAV 092-261 egnaR egatloV
)gnisnes otua( zH 05/06 egnaR ycneuqerF
OUTPUT
AC Voltage Regulation (Batt. Mode)
zH 1± zH 05 ro zH 06 )edoM .ttaB( egnaR ycneuqerF
xam sm01 ,sm 6-2 lacipyT emiT refsnarT
evaW eniS detalumiS )edoM .ttaB( mrofevaW
BATTERY
1 x HA 7/V 21 rebmuN & epyT yrettaB
Backup Time (One PC load @ 120 W)
yticapac %09 ot revocer sruoh 6-4 emiT egrahceR lacipyT
INDICATORS
,egatloV tupnI ,leveL yrettaB ,leveL daoL ,edoM yrettaB ,edoM CA yalpsiD DCLyrettaB woL dna ,tluaF ,daolrevO ,egatloV tuptuO
PROTECTION
noitcetorp egrahcrevo dna ,egrahcsid ,daolrevO noitcetorP lluF
ALARM
sdnoces 01 yreve gnidnuoS edoM yrettaB
dnoces yreve gnidnuoS yrettaB woL
dnoces 5.0 yreve gnidnuoS daolrevO
sdnoces 2 yreve gnidnuoS mralA tnemecalpeR yrettaB
gnidnuos ylsuounitnoC tluaF
PHYSICAL
CEI selcatpeceR tuptuO
241 x 001 x 782 )mm( h x w x d ,noisnemiD
25.4 )gk( thgieW teN
OPERATING ENVIRONMENT
)gnisnednoc-non( C°04 -0 @ HR % 09-0 ytidimuH
Bd04 naht sseL leveL esioN
MANAGEMENT
CAM/9002/atsiV/PX/3002/0002/x.4 TN/EM/ES 89 swodniW stroppuS troP 232-SR
)yreviled morf( tnemecalper raey 2 ytnarraW
* Specifi cations are subject to change without further notice.
Metartec Ltd. Solutions House Unit A19, 20 Heron Road Sydenham Business Park Belfast BT3 9LE
Tel: 0845 50 40 444www.metartec.com
Metartec Ltd.Elm Park House Elm Park Court PinnerMiddlesex HA5 3NN
Tel: 0845 643 9772www.metarteconline4ups.com
10min
±10%
THE METARTEC PICO 850
The Metartec PICO 850 is the ideal UPS unit for supporting your domestic PC and MAC.
The PICO 850 is a compact line-interactive UPS which has an excellent built-in microprocessor controller, designed for fast response to power disturbances.
The PICO 850 provides a simulated sine wave incorporating boost and buck voltage stabilization which will maintain regulated nominal output without using battery power during brownouts and over voltages from 162-290V.
Other functions include ‘Auto Restart’ after extended mains failure whilst AC/utility power supply is recovering and ‘Cold Start function’ means the PICO 850 can be started directly from battery without AC utility supply.
Metartec’s PICO 850 has a RS232 communication port and RJ-11 phone protection socket fi tted as standard.
The PICO 850 offers a transfer time of 2-6ms between utility supply failure and UPS back-up; offering complete load support with practically little to no system disruption.
metartecpowering your future
PICO 850
metartecpowering your future
PICO 650 LINE INTERACTIVE UPS SELECTION GUIDE
MODEL
W 084 / AV 058 YTICAPAC
INPUT
CAV 042/032/022 egatloV
CAV 092-261 egnaR egatloV
)gnisnes otua( zH 05/06 egnaR ycneuqerF
OUTPUT
AC Voltage Regulation (Batt. Mode) ±10%
zH 1± zH 05 ro zH 06 )edoM .ttaB( egnaR ycneuqerF
xam sm01 ,sm 6-2 lacipyT emiT refsnarT
evaW eniS detalumiS )edoM .ttaB( mrofevaW
BATTERY
1 x HA 9/V 21 rebmuN & epyT yrettaB
Backup Time (One PC load @ 120 W)
yticapac %09 ot revocer sruoh 6-4 emiT egrahceR lacipyT
INDICATORS
,egatloV tupnI ,leveL yrettaB ,leveL daoL ,edoM yrettaB ,edoM CA yalpsiD DCLyrettaB woL dna ,tluaF ,daolrevO ,egatloV tuptuO
PROTECTION
noitcetorp egrahcrevo dna ,egrahcsid ,daolrevO noitcetorP lluF
ALARM
sdnoces 01 yreve gnidnuoS edoM yrettaB
dnoces yreve gnidnuoS yrettaB woL
dnoces 5.0 yreve gnidnuoS daolrevO
sdnoces 2 yreve gnidnuoS mralA tnemecalpeR yrettaB
gnidnuos ylsuounitnoC tluaF
PHYSICAL
CEI selcatpeceR tuptuO
241 x 001 x 782 )mm( h x w x d ,noisnemiD
9.4 )gk( thgieW teN
OPERATING ENVIRONMENT
)gnisnednoc-non( C°04 -0 @ HR % 09-0 ytidimuH
Bd04 naht sseL leveL esioN
MANAGEMENT
CAM/9002/atsiV/PX/3002/0002/x.4 TN/EM/ES 89 swodniW stroppuS troP 232-SR
)yreviled morf( tnemecalper raey 2 ytnarraW
* Specifi cations are subject to change without further notice.
Metartec Ltd. Solutions House Unit A19, 20 Heron Road Sydenham Business Park Belfast BT3 9LE
Tel: 0845 50 40 444www.metartec.com
Metartec Ltd.Elm Park House Elm Park Court PinnerMiddlesex HA5 3NN
Tel: 0845 643 9772www.metarteconline4ups.com
10min
METARTEC’S DECI HT - KVA STANDALONE
Metartec’s DECI HT 1:1 Phase system Compatible of V, 50/60 Hz.
metartec
metartec powering your future
Metartec Ltd. Solutions House Unit A19, 20 Heron Road Sydenham Business Park Belfast BT3 9LE
Tel: 0845 50 40 444 www.metartec.com
Metartec Ltd. Elm Park House Elm Park Court Pinner Middlesex HA5 3NN
Tel: 0845 643 9772 www.metarteconline4ups.com
MODEL HT1101S HT1101L HT1102S HT1102L HT1103S HT1103L Capacity 1KVA/900W 2KVA/1800W 3KVA/2700W
INPUT
Acceptable Voltage
110VAC ~ 288VAC 100% Load@>176VAC 80% Load@>154VAC 70% Load@>132VAC 50% Load@>110VAC
Current 5.5A Max 11A Max 16A Max
Frequency 50/60 Hz (40 – 70Hz Adjustable)
Power Factor � 0.98 (Full Load)
OUTPUT Nominal Voltage 200/208/220/230/240VAC (Selectable)
Current 5/4.8/4.5/4.3/4.2A 10/9.6/9/8.6/8.4A 15/14.4/13.5/12.9/12.6A
Voltage Regulation ±1%
Transient Response �5% (0% - 100% - 0%)
Transient Recovery �10ms (0% - 100% - 0%)
Voltage distortion �1% THD, Linear Load
�5.5% THD, Non – Linear Load �5% THD, Non – Linear Load �5% THD, Non – Linear Load
Power Factor 0.9 (lag)
Frequency Tolerance ±0.5% of normal
Crest Ratio 3:1 Max
���������� �����1�������}���,������������������ ~�����
'������1�'�~������ ~��������+������ ���}���,���+������ ~�����,�
Overload Capability (Inverter) 105 - 130% load: transfers to Bypass mode after 1minutes
150% load: transfers to Bypass mode after 30 seconds
Overload Capability (Battery) 105 – 130%: Shutdown after 10 seconds
150%: shutdown after 5 secondsEfficiency (Line Mode) 86% 89% 89% Efficiency (Battery Mode) 83% 87% 87% BATTERY
Rating 12VDC/7AH Depend on the capacity of
external battery
12VDC/7AH Depend on the capacity of
external battery
12VDC/7AH Depend on the capacity of
external battery Quantity 3 6 8
Voltage 36VDC 72VDC 96VDC
Current 35A Max 35A Max 37A Max
Charging Current 1A 8A 1A 8A 1A 8A
Type Value Regulated, Sealed Lead Acid, Maintenance Free
SYSTEM Operating Temperature 0°C - 40°C
Operating Humidity <95%
Operating Altitude <1000 m
Storage temperature -20°C - 70°C
Noise (1m away) <43dB @ <70% Load, <50dB @ >70% Load
<45dB @ <70% Load, <50dB @ >70% Load
<45dB @ <70% Load, <50dB @ >70% Load
Dimension (W × D × H) mm 144 x 353 x 222 190 x 374 x 336 190 x 426 x 336
Net Weight (kG) 12 6 21 10.5 25.6 11.5
Package Weight (kG) 13 7 22 12 27 13
Interface SNMP, RS232, USB
LED/LCD INFORMATION and Audible Alarm Status �������Load Level, Battery Level, Utility Power, Inverter, Bypass, Overload, System Fault�� ��+����� Audible Alarm Battery Mode, Battery Low, Overload, Fault STANDARD Safety IEC/EN 62040-1-1
EMI IEC/EN 62040-2 Class A
EMS IEC/EN 61000-4-2 Level 4, IEC/EN 61000-4-3 Level 3, IEC/EN 61000-4-4 Level 4, IEC/EN 61000-4-5 Level 4,
IEC/EN 61000-2-2 ISO ISO9001:2008, ISO14001:2004
� ������������������������9�����������,������������������������
METARTEC’S DECI H - KVA STANDALONE
Online double conversion, offering loadwith best power quality, support all kind of load and high overload capability
metartec
MODEL HR1101S HR1101L HR1102S HR1102L HR1103S HR1103L
INPUT Cold Start YES, default frequency=50Hz or settableAcceptable Input Voltage 110VAC~288VAC, 100% load@>176VAC, 80% load@>154VAC, 70% load@>132VAC, 50% load@>110VAC Phase Single phase in, single phase out
Transfer Voltage Range 200VAC/208VAC/220VAC/230VAC/240VAC
Line low transfer 110VAC, Line low recovery 121VAC, Line high transfer 288VAC, Line high recovery 281VACInput Current -Rating(nominal input) 4.8A 9.6A 14.4AInput Power Factor ≥0.98 Input Connection IEC C14 IEC C20 IEC C20Input Frequency Range 40~70Hz OUTPUT Frequency adaptable 50/60 Hz SettablePower -Power(kVA) max 1 2 3 -Power(kW) max 0.9(0.8 for 200VAC/208VAC) 1.8(1.6 for 200VAC/208VAC) 2.7(2.4 for 200VAC/208VAC)Output Voltage -Waveform (Bat. Mode) Pure Sine Wave -Nominal voltage 200/208/220/230/240VAC -Voltage regulation ± 1 % -Transient response ≤5% (0% - 100% -0%) -Transient recovery ≤30ms (0% - 100% -0%)
-Voltage distortion ≤2% THD, linear load
≤ 5.5% THD, non-linear load ≤ 5% THD, non-linear load ≤ 5% THD, non-linear loadOutput Frequency -Synchronization range ±5Hz default -Slew rate 0.5~5Hz/s,2 Hz/s default -Battery mode (50±0.1) Hz defaultTransfer Time Line mode to battery mode: 0, Inverter to bypass 2ms Efficiency -Line mode (Full charged) 86%@100% load, 87%@50% load 91%@100% load, 88%@50% load 88%@100% load, 90%@50% load -ECO mode 94.0% 97.0% 97.0% -Battery mode 83%@100% load, 84%@50% load 87%@100% load, 88%@50% load 87%@100% load, 89%@50% loadNoise(1m away) <45dB@<60%load,<50dB@>60%load <50dB@<60%load,<55dB@>60%load <50dB@<60%load,<55dB@>60%load Overload Capability
Inverter 105%~130%: Transfer to bypass after 1 mins., 150%: Transfer to bypass after 30s Battery 105%~130%:shutdown after 10s, 150%:shutdown after 5s Bypass <130%: Long time, >130%&<150%:Shutdown after 10min, >150%&<180%:Shutdown after 5 seconds
Output Connection (6) IEC C13 (6) IEC C13 (6)IEC C13+(1)IEC C19Crest Ratio 3:1BATTERY Rating/Type 12VDC/7Ah Depend on the
capacity of external batteries
12VDC/7Ah Depend on the capacity of
external batteries
12VDC/7Ah Depend on the capacity of
external batteries Quantity 3 6 8
DC Voltage 36VDC 72VDC 96VDC
Back-up Time 6mins @80% load Depend on the
capacity of external batteries
6mins @80% load Depend on the
capacity of external batteries
5.5mins @80% load
Depend on the capacity of
external batteries Battery-Low Voltage 33VAC~35VDC depending on load 66VDC~70VDC depending on load 88VDC~94VDC depending on loadBattery Maintenance Front Maintenance Online Charger -Charging voltage float:41VDC/boost:42VDC float:82VDC/boost:84VDC float:109VDC/boost:112VDC -Charging current (max) 1A 8A or 4A 1A 8A or 4A 1A 8A or 4A
-Charging time 8h recharge to
90%
Depend on the capacity of
external batteries
8h recharge to 90%
Depend on the capacity of
external batteries
8h recharge to 90%
Depend on the capacity of
external batteries Leakage current <1mA <1mA <1mAINDICATOR & ALARM -Display LED+LCD
-Alarm Battery discharge/Input voltage abnormal: Sounding every 2 minutes
Low battery, Warn: Sounding every 6 seconds Overload, Fault: Continuous beeping
INTERFACE -Smart RS232 Standard Cable support INVT Power Monitor Software -SNMP(option) Power Management from SNMP Manager and Web Browser Options DB9 port, dry contact, USB port, SNMP KitsMECHANICAL -W D H (mm) 440*430*86(2U) 440*430*86(2U) 440*480*173(4U) 440*480*86(2U) 440*480*173(4U) 440*480*86(2U) -W D H (mm)(shipment) 580*565*250 580*565*250 580*660*335 580*615*250 580*660*335 580*615*250 -Net Weight (KG) 13.5 8 28 9.5 33 10.5 -Package Weight(KG) 16 11 31 12.5 36 13.5 -Rack / Tower Rack and TowerColor Black default
Standard Safety: IEC/EN 62040-1-1, EMI: IEC/EN 62040-2 Class A, EMS: IEC/EN 61000-4-2 L4, IEC/EN 61000-4-3 L3, IEC/EN 61000-4-4 L4,
IEC/EN 61000-4-5 L4, IEC/EN 61000-2-2 ISO: ISO9001, ISO14001*Products specifications are subject to change without further notice.
powering your future
METARTEC’S DECI HT 6 - 20KVA STANDALONE
Metartec’s DECI HT 1:1 and 3:1 Phase system Compatible of 380/400/415 V, 50/60 Hz.
Parallel up to 4 units.
Online double conversion, offering loadwith best power quality, support all kind of load and high overload capability
Fully digital control with three DSPs(Digital SignalProcessor) including IGBT rectifier, Inverter, Charger
Digital circulating current control technology, increasing the parallel reliability
Wide input voltage window, compatible with diferrent utilities.
Green Power Technology, high input power factor,
Intelligent battery management, extending battery life time.
Intelligent self-diagnostic function, all kinds of faultprotection, large capability of history record.
Full front maintenance, saving space.
Redundant design of power model fan, increasingsystem reliability.
Modularlized design of sub-system, convenient
High MTBF(Mean time between failures) > 200,000hr,Low MTTR(Mean time to repair) < 0.5 hr.
LED/LCD display with friendly human machine interface.
All kinds if option, included main back feed protection,
metartec
bypass back feed protection, battery leakage protection.
metartecpowering your future
Metartec Ltd. Solutions House Unit A19, 20 Heron Road Sydenham Business Park Belfast BT3 9LE
Tel: 0845 50 40 444www.metartec.com
Metartec Ltd.Elm Park House Elm Park Court PinnerMiddlesex HA5 3NN
Tel: 0845 643 9772www.metarteconline4ups.com
MODEL
Capacity
DECI HT11xx and HT31xx UPS SELECTION GUIDE HT1106K HT1106KL HT1110K HT1110KL HT3110KL HT3115KL HT3120KL
6KVA/4800W 10KVA/8000W 10KVA/8KW 15KVA/12KW 20KVA/16KW
INPUT Input Voltage 160 – 276 VAC (L+N) 274 – 478 VAC (LINE TO LINE)
Current 1 PHASE 2 WIRE + G 3 PHASE 4 WIRE + G
Frequency Range 50/60 Hz ± 5%
Power Factor > 0.99 (FULL LOAD)
OUTPUT
Output Voltage 220VAC ± 1% 220VAC ± 2%
Frequency Synchroni wi input(NORMAL MOze th DE); 50 Hz ± 2 Hz (BATTERY MODE)
Power Factor 0.8 (lag)
Waveform Sine Wave
Waveform Distortion Linear Load < 3%, Non Linear Load < 6% Linear Load < 3%, Non Linear Load < 10%
Overload Protection > 120% 2 min, > 150% 30 s > 120% 30 s, > 135% 100 ms
Transfer Time 0 ms
SYSTEM
Battery Sealed lead acid Maintenance Free Battery
External Battery Voltage 12V 7A x16 192 VDC 12V 7A x16 192 VDC 192 VDC
Environment Operation Temperature 0 – 43 °C/Humidity 0 – 95%(Non Condensing) Temperature 0 – 40 °C/
Humidity 20 – 95%(Non Condensing)
Communication Port RS-232/SNMP (Optional)
Size (WxDxH) mm 250x500x620 250x500x460 250x500x620 250x500x460 260x560x717
Weight (Kg) 56 10 66 20 25
STANDARD
EMI IEC 62040-2
EMS IEC 61000-4-2(ESD), IEC 61000-4-3(RS), IEC 61000-4-4(EFT), IEC 61000-4-5(SURGE)
ISO ISO9001:2008, ISO14001:2004
*Specifications are subject to change without prior notice.
METARTEC’S DECI HR 6 - 10KVA STANDALONE
Metartec’s DECI HR 1:1 Phase system Compatible of 220/230/240V, 50/60 Hz.
Parallel up to 3 units.
Online double conversion, offering load with best power quality, support all kind of load and high overload capability
Fully digital control with three DSPs(Digital Signal Processor) including IGBT rectifier, Inverter, Charger
It is designed to provide conditioned power to microcomputers and other sensitive electronic equipment.
Wide input voltage window, compatible with different utilities. Cold start support.
The HR11 protects equipment from these disturbances, including voltage sags, spikes and complete power failure, included overload, short circuit and bypass protection.
Intelligent self-diagnostic function, all kinds of fault protection, large capability of history record.
The HR11 is a compact, on-line UPS and supplies connected equipment with clean sine wave power.
LCD display and LED to indicate all information for UPS, and provide kinds of function buttons.
LED/LCD display with friendly human machine interface.
These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surge or interference present in the utility line and keep the sensitive equipment protected.
Metartec Ltd. Solutions House
13 Harbour View Heron Road
Belfast BT3 9LE Tel: 0845 50 40 444
www.metartec.com
Metartec Ltd. Elm Park House Elm Park Court
Pinner Middlesex HA5 3NN Tel: 0845 64 39 772
www.metartec.com
*Products specifications are subject to change without further notice.
TECHNICAL SPECIFICATION FOR DECI HR SERIESModel HR1106L HR1110L HR1106S HR1110SCapacity 6 KVA/5.4KW 10KVA/9KW 6KVA/5.4KW 10KVA/9KWINPUT Nominal voltage 220/230/240VAC Single Phase Voltage range 50% – 125% Freauency 50/60 Hz (Default 50Hz) Input frequency range 40 – 70 Hz Power factor 0.99 Input current THD(THDi) Generator Support Any Generator OUTPUT Frequency Adaptable Setable Output Voltage - Waveform Pure sine wave - Nominal voltage 220/230/240VAC - Voltage regulation ± 1 % - Transient response 5% (50% - 100% - 50%) - Transient recovery 15ms (0% - 100% - 0%) - Voltage distortion (THD) 1% (Linear load), 5% (Non-linear load) Power factor 0.9 Output Frequency - Synchronization range Settable, ± 3Hz default - Slew rate 0.5 – 5Hz/s, 2Hz/s default - Battery mode 50Hz (±0.5 Hz) Transfer Time - Line mode to battery mode 0 - Inverter to bypass 4ms 0 0.1ms 0 Efficiency - Line mode with battery full 92.0% - ECO Mode 97.0% - Battery mode 91.0% Overload Capability
- Line mode 110% transfer after 10 min, 130% transfer after 1 min,
150% transfer after 30s (shutdown after 1 min
- Battery mode <110% Shutdown after 10 min
>125% Shutdown after 10s Crest Ratio 3:1 BATTERY
Rating/Type Depend on the capacity of external batteries/ Valve Regulated, Non-spillable, lead acid
7AH VRLA, non-spillable, lead acid
9AH VRLA, non-spillable, lead acid
Quantity 16 x 12 V Backup Time Depend on the capacity of external batteries 4 min @80% load 4 min @80% load Battery-Low Voltage 176VDC ±3V Charging Voltage 220VDC ±1% Charging Current (max) 5A 1A Charging time Depend on the capacity of external batteries 8 Hours to 90% SYSTEM Maintenance Bypass Yes, maintenance without interruption Display LED + LCD Interface EPO, Smart RS232, USB, Dry Contactor, SNMP Options USB, SNMP, ECO Kit, Dry Contactor, Parallel Kit, Battery Cabinet Operating Temperature 0 – 40 °C, no derating Storage Temperature 0 – 70 °C Relative Humidity 0 – 95% Non-condensing Operating Elevation Up to 1000m (3281 ft) without derating Noise <48dB@<60%load, <60dB@>60%load; 1m away
Standard
IEC/EN 62040-2:2006 C3, IEC/EN 61000-4-2:2009 B (ESD), IEC/EN 61000-4-3:2006 +A1:2008 +A2:2010 A (RS), IEC/EN 61000-4-4:2004+A1:2010 B(EFT), IEC/EN 61000-4-
5:2006 B(Surge), IEC/EN 61000-4-6:2009 A(RF), IEC/EN 61000-4-8:2010 A(Magnetic Field), IEC/EN 61000-4-11:2004 A(VD), IEC/EN 61000-2-2:2002 A(LF)
ISO9001:2008, ISO14001:2004
METARTEC’S DECI HT 10-120KVA STANDALONE
Metartec’s DECI HT 3Phase in and out system Compatible of 380/400/415 V, 50/60 Hz.
Parallel up to 6 units.
Online double conversion, offering load with best power quality, support all kind of load and high overload capability
Fully digital control with three DSPs(Digital SinalProcessor) including IGBT rectifier, Inverter, Charger
Digital circulating current control technology, increasing the parallel reliability
Wide input voltage window, compatible with diferrent utilities.
Green Power Technology, high input power factor,THDi and efficiency.
Intelligent battery management, extending battery life time.
Intelligent self-diagnostic function, all kinds of faultprotection, large capability of history record.
Full front maintenance, saving space.
Redundant design of power model fan, increasingsystem reliability.
Modularlized design of sub-system, convenient field maintenance.
High MTBF(Mean time between failures) > 200,000hr,Low MTTR(Mean time to repair) < 0.5 hr.
Large LCD display(Touch Screen for 40kVA up), friendly human machine interface.
Configured with top and bottom cable connection.
All kinds if option, included main back feed protection,bypass back feed protection, battery leakage protection.
metartec����������� �����
metartecpowering your future
DECI HT33xx UPS SELECTION GUIDE
DECI HT33xx
10kVA/8kW
INPUT egatloV tupnI
OUTPUT
Frequency wodniW
SYSTEMS
Metartec Ltd. Solutions House Unit A19, 20 Heron Road Sydenham Business Park Belfast BT3 9LE
Tel: 0845 50 40 444www.metartec.com
Metartec Ltd.Elm Park House Elm Park Court PinnerMiddlesex HA5 3NN
Tel: 0845 643 9772www.metarteconline4ups.com
15kVA/12kW 20kVA/16kW 30kVA/24kW 40kVA/32kW 60kVA48kW 80kVA/64kW 100kVA/80kW 120kVA/96kW
HT3310 HT3315 HT3320 HT3330 HT3340 HT3360 HT3380 HT33100 HT33120
380V/400V/415V (Line to Line) 3Ph + N + PE
wodniW egatloV tupnI +25% ~ 20%, Full Load
+25% ~ 40%, Power Derating Between 100% to 70%
40Hz - 70Hz
> 0.99 Full Load
≤ 3%
BYPASS INPUT
Bypass Voltage&Window 380V/400V/415V, +15% ~ -20%, Full Load
± 5Hz
BATTERY (Design Life 5-10 Years)± 240VDCBattery Voltage
Battery Protection Battery Low Pre-Warning, Battery Discharge (EOD) Protection, Battery Circuit Breaker(BCB) Alarm
OUTPUT
Voltage Precision 380/400/415VAC ± 1%(Balanced Load) ± 1.5% (Unbalanced Load)
Output Voltage Transient 5%(0-100% load step)
Voltage THDv THD<1%(Linear Load), THD<5%(Non-Linear Load)
Power Factor 0.8 lag
Frequency Tracking Synchronization 50Hz/60Hz ± 2Hz Frequency Precision(Free Running) ± 0.02% Phase Tolerance 120% ± 0.5° (Balanced and Unbalanced Load) Voltage Unbalance degree(100%) ± 1%
Frequency Tracking Speed 0.5Hz/sec to 5Hz/sec, Adjustable
Crest Factor 3:1
Overload Capability102% for long time operation, 110% transfered to bypass after 1Hr, 125% transfered to bypass after 10mins,
>150% transfered to bypass after 1mins, >150% transfered to bypass after 200ms
Bypass Overload Capability125% for long time operation, 125% < Load < 130% last for more than 1Hr
130% < Load < 150% last for more than 6mins, >1000% last for more than 100ms
Normal Mode: 95%
ECO Mode: 99%Battery Mode: 95%
12V, 40PCS(36-44PCS Acceptable)Display LCD+LED+Keyboard Touch Screen LCD+LED+Keyboard
EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111), EN50091-1-1/IEC62040-1-1/AS 62040-1:2009
EMS/EMI/EMC
ISO /Product Standard and Others ISO9001:2008, ISO14001:2004, CE, C-Tick
STANDARDS
Isulation Resistance > 2M(500VDC)Dielectric Strength (Input, Output to PE)2820VDC, Leakage current < 3.5mA, no Flashover in 1 minute
Surger Protection Comply with IEC60664-1 Class IV, Endure surge of 1.2/50ns + 8/20ns higher than 6kV/3kAIP Class IP20Interface(Communication Ports) RS-232, RS-485, Dry Contacts, SNMP Card, EPO, Generator InterfaceEnvironment Operation Operationtemperature: 0-40°C, Relative Himidity: 0-95%(non-condensing), Noise Level: < 55dB
Physical
Weight 68/46 80/60 182 204 226 270 292
Dimension(W*D*H) mm.540*690*1100(Internal Battery)
600*900*1400 600*900*1700280*720*668(No Battery) 320*781*788
EN50091-2/IEC62040-2/AS 62040-2, ESD(IEC61000-4-2), RS(IEC61000-4-3), EFT(ESD(IEC61000-4-4), SurgeESD(IEC61000-4-5)
Performance and Safety
Frequency Range
Power Factor
Current Distortion(THDi)
Power Rating
METARTEC’S DECI MODULAR RM Series 10- 400kVA
Metartec’s DECI Modular system has independentpower and control sections, this means that eachmodule runs as an independent UPS.
incomparable with traditional UPS’ as the DECIModular system adopts the centralized multipleparallel N+X format. The unit is designed forsystem expansion and supports the load withN+1 to N+X levels of protection(Up to 2 systems).The DECI Modular’s maximum capacity can beexpanded from 10kVA to 400kVA. The system’scapacity of 400kVA has a power module thatincreases in increments of 20kVA allowing theuser to choose the power requirement accordingto their need.The DECI Modular is a modular parallelredundant Modular system. The system consistsof three modules: Static Switch module, Display& Communication Module, and Power Modulewhich can be placed in parallel from 1 to 20pcs.
≤ 95% and is designed to produce lower heatemissions, unlike traditional UPS’ that can wasteup to 10% energy making the DECI UPS’ more
With an input THD <3%, and a Power Factorof 0.99, Metartec’s DECI Modular is truly anenvironmentally sound UPS.The DECI Modular Management Softwareprovides real time monitoring and access todata including current operational status, control
The biggest appeal for the DECI Modular is itscapability for easy expansion. Previously when acustomers’ load increased, the original UPS hadto be replaced with a new and higher capacitysystem. With the DECI Modular UPS there is noneed to replace the whole UPS, only the requirednumber of modules for expansion need to beadded. This reduces the customer’s costs for theinitial equipment purchase and future expansion.Similarly the ‘Hot Swappable Modules’ can beadded or removed online. There is no need forsenior technical personnel to perform this job,which is an all round safer and more convenientprocess for maintenance and repair as there is noneed to switch to a bypass system. Subsequentlyonline expansion or redundancy enhancement
Power Module 10kVA, 15kVA and 20kVA with independent IGBT technology inside rectifier
added or removed online. There is no need for
and Inverter
Metartec Ltd. Solutions House
13 Harbour View Heron Road
Belfast BT3 9LE Tel: 0845 50 40 444
www.metartec.com
Metartec Ltd. Elm Park House Elm Park Court
Pinner Middlesex HA5 3NN Tel: 0845 64 39 772
www.metartec.com
����
*Products specifications are subject to change without further notice.
TECHNICAL SPECIFICATION FOR DECI MODULAR RM SERIESCapacity 10 – 400 kVAINPUT
Input voltage 380V/400V/415V(line to line)
220V/230V/240V(line to neutral) Input frequency 50/60Hz Power factor >0.99 Input current THD(THDi) <3% Input voltage window -40%~+25%,-10%~-40% rated power derating from 100%~50% Frequency window 40—70Hz BYPASS Bypass System Automatic and Manual Bypass
Bypass voltage 380V/400V/415V(line to line)
220V/230V/240V(line to neutral) Bypass voltage window —20% — +15%, full load
Bypass overload capability
125%, long time operation 125% < load < 130%, last for more than 1 hour
130% < load < 150%, last for more than 6 minutes >1000%, last for more than 100ms
OUTPUT
Output voltage 380V/400V/415V(line to line)
220V/230V/240V(line to neutral) Voltage precision 1%(balance load), 1.5%(unbalance load) Voltage THD(Total Harmonic Distortion) THD <1.5%(linear load), THD <5%(nonlinear load) Power factor 0.8 Phase tolerance 120°±0.5°(balance and unbalance load) Crest factor 3:1
Overload capability
105%,long time operation 110%, transfer to bypass after 1hour
125%, transfer to bypass after 10 minutes 150%, transfer to bypass after 1 minute >150%, transfer to bypass after 200ms
BATTERY Battery Type VRLA (Sealed Lead Acid, Maintenance Free, optional design life 5 – 12 years) Battery voltage ±240VDC Charger power 20%*Active Power Charger voltage precision 1% SYSTEM
System efficiency Normal mode (online): 94.5% @60 – 70% load
ECO mode: 98% Battery mode (Standby): 94.5% @60 – 70% load
Display LED + LCD, Touch screen and keyboard IP class IP20 Interface(Communication Ports) RS232(modbus), RS485(modbus), Dry contacts, SNMP card, EPO, Generator interface Network Management WEB Browser and SNMP via network (LAN or Internet) Platform Support Windows Family, MacOS, Linux, and Unix Installation/Connection Top or bottom cable connection Operation temperature 0 — 40 °C Storage temperature —25 °C — 70 °C Relative humidity 0 — 95% non-condensation) Noise(dB) 55dB
Weight(KG)
6-module cabinet RM060/10, RM090/15, RM120/20: 150KG 10-module cabinet RM100/10, RM150/15, RM200/20: 180KG
PM10 10KVA: 20KG PM15 15KVA: 21KG PM20 20KVA: 22KG
Dimension(W*D*H)(mm) 6-module cabinet 600*900*1600
10-module cabinet 600*900*2000 Power Module 400*600*133 (10KVA/15KVA/20KVA)
Standard
Safety: EN50091-1-1/IEC62040-1-1/AS 62040-1-1 EMC: EN50091-2/IEC62040-2/AS 62040-2(C3)
EMS: EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111) ISO: ISO9001:2008, ISO14001
�METARTEC’S DECI MODULAR HT33X SERIES
�•� Metartec’s DECI Modular HT33X series is
modular and online double conversion UPS for sensitive equipment. The power rating covers from 30KVA to 120KVA which delivers the best of combination of reliability, functionality, hot-swappable and flexibility. It is designed specifically for data centers, computer systems or critical equipment. As the result of state of the art design, this innovative and reliable power system absolutely.
•� Modular Design Both power module and Battery unit are designed to be hot swappable. Each power module is designed be hot swappable which makes the power expansion and system maintenance easily.
•� Intelligent Battery Management The charger is controlled by DSP with intelligent digital arithmetic thus to prolong the life time of the battery.
•� Intelligent Protection System All the power modules and the system are protected simultaneously by the hardware and the software. All kinds of protection functions are realized, including current and voltage abnormal, thermal abnormal, short circuit, etc.
•� High reliability design Integrated IGBT modules are used in the power module. Comparing to discrete chips, system reliability and manufacturing consistency are much improved. Low-loss integrated three-level IGBT modules help to increase system efficiency.
•� Strong load adaptability for linear and nonlinear load.
•� Intelligent module and system protection design. •� Incredible low noise system design. •� Digital control for the whole parts including
rectifier, inverter, charger and discharger. •� Independent IGBT for each modules on rectifier
and inverter. •� Digital controlled independent charger, intelligent
battery management system. •� Inbuilt switch for cabinet input, output and
maintenance connection. •� Large touch screen LCD with plenty of information. •� Digital paralleling technology, very low circle
current between modules. •� Totally front access, bottom cable connection. •� Each individual module is configured with
independent controller, avoid single point failure risk.
•� Friendly generator interface. •� Individual LCD display on each power module.
Metartec Ltd. Solutions House
13 Harbour View Heron Road
Belfast BT3 9LE Tel: 0845 50 40 444
www.metartec.com
Metartec Ltd. Elm Park House Elm Park Court
Pinner Middlesex HA5 3NN Tel: 0845 64 39 772
www.metartec.com
TECHNICAL SPECIFICATION FOR METARTEC’S DECI MODULAR HT33X SERIES
Model HT3330X HT3360X HT3390X HT33120XCapacity 30KVA/27KW 60KVA/54KW 90KVA/81KW 120KVA/108KWMain Input Grid System 3 Phases + Neutral + GroundRated Input Voltage 380/400/415VAC (Line-Line), 220/230/240VAC (Line-Neutron) Rated Frequency 50/60Hz
Input Voltage Range 304~478Vac (Line-Line),full load;228V~304Vac (Line-Line),load decreases linearly according to the min phase voltage
Input Frequency Range 40Hz 70HzInput Power Factor >0.99 Input Current THDi <3% (full Linear Load)Bypass Input Rated Bypass Voltage 380/400/415VAC (Line-Line), 220/230/240VAC (Line-Neutron) Rated Frequency 50/60Hz
Bypass Voltage Range Selectable, default -20% +15%;Upper limit: +10%, +15%, +20%, +25%; Lower limit: -10%, -15%, -20%, -30%, -40%
Bypass Frequency Range Selectable, ±1Hz, ±3Hz, ±5Hz
Bypass Overload 110% Long term operation; 110%~125% for 5min; 125%~150% for 1min; 150%~400% for 1s; >400% ,less than 200ms
Output Rated Inverter Voltage 380/400/415VAC (Line-Line), 220/230/240VAC (Line-Neutron) Rated Frequency 50/60HzOutput Power Factor 0.9 Voltage precision ±1.5%(0-100% linear load)Transient Response <5% for step load (20% - 80% -20%)Transient recovery < 30ms for step load (0% - 100% -0%)Output Voltage THDu <1% from 0% to 100% linear load; < % full non-linear load according to IEC/EN62040-3Inverter Overload 110%, 60min; 125%,10min; 150%,1min; >150%, 200msFrequency Regulation 50/60Hz ±0.1%Synchronized Range ±0.5Hz ±5Hz, Settable, default ±3HzSynchronized Slew Rate 0.5Hz/S 3Hz/s, Settable, default 0.5Hz/sBattery And Charger Battery Rate Voltage ±240VDCBattery Type VRLA (Design life 5 – 12 years)Charger Voltage precision 1%Charger Power max=20% Efficiency Normal Operation >95%Battery Operation >95%System Display LED + LCD + Touch screen
Interface Standard: RS232, RS485, USB, Dry Contact;Option: SNMP, AS/400 Parallel kit, Battery Cold start, Dust Filter
Environment Operation Temperature 0 40 °C Storage Temperature -40 70 °C Relative Humidity 0 95% Non-condensingNoise (1 meter) 65dB @ 100% load, 62dB @ 45% loadAltitude <1000m, Load derated 1% per 100m From 1000 2000mProtection Level (IEC60529) IP20 Physical data Dimension (W*D*H, mm 600*980*950 600*980*1400Weigh(Kg) (without power module) 176 231 266Power Module Model PM30 (30KVA)Power Module Quantity/Slot 1/2 2/2 3/4 4/4Standard General Safety Requirements EN50091-1-1/IEC62040-1-1/AS 62040-1-1Electromagnetic Compatibility (EMC) EN50091-2/IEC62040-2/AS 62040-2 (C3) Performance and Test Requirements EN50091-3/IEC62040-3/AS 62040-3 (VFI SS 111) Other ISO9001, ISO14001, CE
*Product specifications are su bject to change without fur ther notice BS.DOC.039 Issue 1
METARTEC’S DECI MODULAR RM180-300/30X
Metartec’s DECI Modular system has independentpower and control sections, this means that eachmodule runs as an independent UPS.
incomparable with traditional UPS’ as the DECIModular system adopts the centralized multipleparallel N+X format. The unit is designed forsystem expansion and supports the load withN+1 to N+X levels of protection.The DECI Modular’s maximum capacity can beexpanded from 20kVA to 00kVA. The system’scapacity of 00kVA has a power module thatincreases in increments of 0kVA allowing theuser to choose the power requirement accordingto their need.The DECI Modular is a modular parallelredundant Modular system. The system consistsof three modules: Static Switch module, Display& Communication Module, and Power Modulewhich can be placed in parallel from 1 to 20pcs.
> 95% and is designed to produce lower heatemissions, unlike traditional UPS’ that can wasteup to 10% energy making the DECI UPS’ more
With an input THD <3%, and a Power Factorof 0.99, Metartec’s DECI Modular is truly anenvironmentally sound UPS.The DECI Modular Management Softwareprovides real time monitoring and access todata including current operational status, control
The biggest appeal for the DECI Modular is itscapability for easy expansion. Previously when acustomers’ load increased, the original UPS hadto be replaced with a new and higher capacitysystem. With the DECI Modular UPS there is noneed to replace the whole UPS, only the requirednumber of modules for expansion need to beadded. This reduces the customer’s costs for theinitial equipment purchase and future expansion.Similarly the ‘Hot Swappable Modules’ can beadded or removed online. There is no need forsenior technical personnel to perform this job,which is an all round safer and more convenientprocess for maintenance and repair as there is noneed to switch to a bypass system. Subsequentlyonline expansion or redundancy enhancement
20kVA, 30kVA
Metartec Ltd. Solutions House
13 Harbour View Heron Road
Belfast BT3 9LE Tel: 0845 50 40 444
www.metartec.com
Metartec Ltd. Elm Park House Elm Park Court
Pinner Middlesex HA5 3NN Tel: 0845 64 39 772
www.metartec.com
����
*Products specifications are subject to change without further notice.
TECHNICAL SPECIFICATION FOR DECI MODULAR RM SERIESCapacity 300 – 900 kVAINPUT
Input voltage 380V/400V/415V(line to line)
220V/230V/240V(line to neutral) Input frequency 50/60Hz Power factor >0.99 Input current THD(THDi) <3% (Full Linear Load) Input voltage window -40%~+25% Frequency window 40—70Hz BYPASS Bypass System Automatic and Manual Bypass
Bypass voltage 380V/400V/415V(line to line)
220V/230V/240V(line to neutral) Bypass voltage window —20% — +15% default, adjustable for other value
Bypass overload capability 110%, continuity operation 110% - 125%, for 5 min 125% - 150% for 1 min
OUTPUT
Output voltage 380V/400V/415V(line to line)
220V/230V/240V(line to neutral) Voltage precision ±1.5% for 0 - 100% linear load Output frequency 50/60Hz ±0.1% Voltage THD(Total Harmonic Distortion) THD <1%(linear load), THD <5%(nonlinear load) Power factor 0.9 Crest factor 3:1
Overload capability
110%, transfer to bypass after 60 minutes 125%, transfer to bypass after 10 minutes 150%, transfer to bypass after 1 minute >150%, transfer to bypass after 200ms
BATTERY Battery Type VRLA (Sealed Lead Acid, Maintenance Free, optional design life 5 – 12 years) Battery voltage ±240VDC Charger power 20%*Active Power Charger voltage precision 1% SYSTEM
System efficiency Normal mode (online): >95%
ECO mode: 99% Battery mode (Standby): >95%
Display LED + LCD, Touch screen and keyboard IP class IP20 Interface(Communication Ports) RS232(modbus), RS485(modbus), Dry contacts, SNMP card, EPO, Generator interface Network Management WEB Browser and SNMP via network (LAN or Internet) Platform Support Windows Family, MacOS, Linux, and Unix Installation/Connection Top or bottom cable connection Operation temperature 0 — 40 °C Storage temperature —25 °C — 70 °C Relative humidity 0 — 95% non-condensation) Noise(dB) 60dB @ 1 meter (for load 30%),(<65dB for 100%)
Weight(KG) cabinet 220KG PM30 34KG
Dimension(W*D*H)(mm) 600*1100*2000
Standard
Safety: EN50091-1-1/IEC62040-1-1/AS 62040-1-1 EMC: EN50091-2/IEC62040-2/AS 62040-2(C3)
EMS: EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111) ISO: ISO9001:2008, ISO14001
/RM600
Metartec’s DEC Modular system has independentpower and control sections, this means that eachmodule runs as an independent UPS.
6
Metartec Ltd. Solutions House
13 Harbour View Heron Road
Belfast BT3 9LE Tel: 0845 50 40 444
www.metartec.com
Metartec Ltd. Elm Park House Elm Park Court
Pinner Middlesex HA5 3NN Tel: 0845 64 39 772
www.metartec.com
*Products specifications are subject to change without further notice.
TECHNICAL SPECIFICATION FOR DECI MODULAR RM SERIESModel
RM600/30X RM500/25X
RM300/30X RM250/25X
RM180/30X RM150/25X
Capacity 25 – 900 kVA (22.5 – 810 kW) Power Module Type PM30X (30kVA)/PM25X (25kVA)INPUT
Input voltage 380V/400V/415V (line to line)
220V/230V/240V (line to neutral) Input frequency 50/60Hz Power factor >0.99 Input current THD(THDi) <3% (Full Linear Load)
Input voltage window 304 – 478 VAC (Line – Line) Full Load
228 – 304 VAC (Line – Line) Load decreases linearly according to the min phase voltage Frequency window 40 – 70 Hz BYPASS Bypass System Automatic and Manual Bypass
Bypass voltage 380V/400V/415V (line to line)
220V/230V/240V (line to neutral) Bypass voltage window —20% — +15% default, adjustable for other value
Bypass overload capability
110%, continuity operation 110% - 125%, for 5 minutes 125% - 150% for 1 minutes 150% - 400% for 1 second
OUTPUT
Output voltage 380V/400V/415V (line to line)
220V/230V/240V (line to neutral) Voltage Regulation 1.5% Output frequency 50/60Hz ±0.1% Voltage THD(Total Harmonic Distortion) THD <1% (linear load), THD <5% (nonlinear load) Power factor 0.9 Crest factor 3:1
Overload capability
110%, transfer to bypass after 60 minutes 125%, transfer to bypass after 10 minutes 150%, transfer to bypass after 1 minute >150%, transfer to bypass after 200ms
BATTERY Battery Type VRLA (Sealed Lead Acid, Maintenance Free, optional design life 5 – 12 years) Battery voltage ±240VDC Charger power 20%*Active Power Charger voltage precision ±1% SYSTEM
System efficiency Normal mode (online): >95%
ECO mode: 99% Battery mode (Standby): >95%
Display LED + LCD 10.4” Color touch screen and keyboard IP class IP20 Interface(Communication Ports) RS232, RS485, Dry contacts, USB; Optional SNMP, Expansion Dry contact card Network Management WEB Browser and SNMP via network (LAN or Internet) Platform Support Windows Family, MacOS, Linux, and Unix Installation/Connection Top or bottom cable connection Operation temperature 0 — 40 °C Storage temperature —40 °C — 70 °C Relative humidity 0 — 95% non-condensing)
Noise(dB) (1 meter away) 7 dB @ 100% load, 68 @ 45% load 65dB @ 100% load, 62 @ 45% load
Weight(KG) Cabinet 20 Slot cabinet: 660Kg 10 slot cabinet: 220Kg 6 slot cabinet: 165Kg Power Module PM30X: 34Kg; PM25X: 32Kg
Dimension(W*D*H)(mm) Cabinet 2000*1 0*2000 600*1100*2000 600*1100* 00Power Module PM30X/PM25X: 460*790*134
Standard
Safety: EN50091-1-1/IEC62040-1-1/AS 62040-1-1 EMC: EN50091-2/IEC62040-2/AS 62040-2(C3)
EMS: EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111) ISO: ISO9001:2008, ISO14001
DEKA Series
Metartec’s DEKA is one of the most effi cient uninterruptible power supplies and is the most technologically advanced UPS in its class. It delivers an unbeatable combination of low input current distortion and unity power factor.
Metartec’s DEKA is designed with an IGBT rectifi er and an advanced PFC (Power Factor Control) keeping harmonic distortion at less than 3%.The On-Line Double Conversion Technology isolates output power from all the input anomalies, providing a clean output.
The parallel control system tightly manages both active and reactive type loads, allowing for intelligent load/current sharing between each individual phase.
Effi ciency - The use of DSP, IGBT and tricore technology ensures that the DEKA offers AC/AC effi ciency of 95%. This is typically around 10% to 15% better than the conventional UPS and provides savings of 2.8kW per hour on an 80kVA installation.
The IGBT (Isolated Gate Bipolar Transistors) rectifi er - allows the DEKA to provide less than 3% harmonic distortion. The main benefi t of this is that the generator can be downsized by as much as 50%. This may help the user fall outside the fi nancial penalty band that the EEC countries are currently considering.
metartecpowering your future
DEKA 400-800kVA
Ideal for both industrial requirements and also large commercial projects - It has been designed to cope in the harshest environments, which is perfect for companies who use production line machinery, as it offers the ideal backup allowing a controlled shutdown on the machinery.
Unitary, Parallel or N+1- The DEKA is a true double conversion UPS and can also be confi gured and programmed to run as a frequency converter or in green mode as a line interactive system which further reduces energy costs. Up to eight machines can be connected in this way making the DEKA a fl exible and versatile solution.
To offset unavoidable battery decay, the DEKA incorporates a battery management system that is calibrated in accordance with most battery manufacturers’ specifi cations. The DEKA is suitable for almost any type of load accepting a power factor of either 0.9 leading or 0.9 lagging (many other manufacturers standard is 0.8pf).
metartecpowering your future
DEKA UPS SELECTION GUIDE
MODEL 400kVA 500kVA 600kVA 800kVA
Capacity 400/320 500/400 600/480 800/640
Input/output connection Hardwired (dual input)
Battery External, 300 cells
INPUT
Voltage Range -20%, +10% from nominal
Frequency Range 50/60 Hz (45-65 Hz)
Power Factor 0.99 @ 100% Load
Current distortion (THDi) <3%
OUTPUT
Nominal Voltage 220/380, 230/400, 240/415 Vac three phase
Frequency 50/60Hz
Voltage Regulation ± 1% static; ± 5% dynamic 100% load charge, <20 ms recovery time
PF acceptable without de-rating Lagging to 0.9 leading
Overload Capacity 101-125% for 10 min (on-line); 126 -150% for 1 min (online); 1000% for cycle (bypass)
EFFICIENCY
AC Mode ~ 95%
Eco Mode ~ 98%
OPTIONS
Parallel capacity/redundancy; isolation transformer; external bypass; external battery cabinets, battery switch box; battery thermal probe; transformers/autotransformers for voltage adaption; top cable entry
INDICATORS
Front Panel Graphical LCD display, mimic with LED’s and keyboard
Standard communication ports RS232 serial port, USB port, Remote Emergency Power Off input, battery switch monitoring port
Optional Web/SNMP, ModBus, relay, modem cards; remote panel; monitoring, managing and shutdown software
PHYSICAL
Dimensions 1990x1920x952 2440x2020x952 3600x2020x952
Weight 1820 2220 2400 4000
ENVIRONMENT
Operating temperature 0°C - +40°C
Storage temperature -10°C - +70°C
Altitude <1000 m
Noise Level Less than 60dBA @ 1 Meter
MANAGEMENT
Smart RS-232 Supports Windows Windows family, Novell, Linux and FreeBSD
USB
Optional SNMP Power management from SNMP manager and web browser
Warranty 2 Year replacement (from delivery)
STANDARDS
Marking CE
Safety IEC EN 62040-1
EMC IEC EN 62040-2
Test and Performance IEC EN 62040-3
Quality ISO9001 : 2000
* Product specifi cations are subject to change without further notice
Metartec Ltd. Solutions House Unit A19, 20 Heron Road Sydenham Business Park Belfast BT3 9LE
Tel: 0845 50 40 444www.metartec.com
Metartec Ltd.Elm Park House Elm Park Court PinnerMiddlesex HA5 3NN
Tel: 0845 643 9772www.metarteconline4ups.com
Automatic Transfer Switch (ATS) 16A max. input current Powered by two separately independent power sources Dual power supply for redundancy Provides seamless power switch for IT equipment Preferred source selection on front panel Highly reliablity 19" rack design (1U) to fit into a diverse working environment Built-in USB and RS-232 communications
System Configuration:
USB communication port
Power On/Off switch for input
Output breaker for IEC-C13
RS-232 communication port
Source preference selector
Priority setting LEDs
Input source availability LEDs
Output source LEDs
Intelligent slot
Fault LEDMute button
Automatic Transfer Switch Selection Guide
Input Voltage 220/230/240 VACAcceptable Input Voltage 180 - 258 VACInput Frequency 50 Hz / 60 HzMaximum Input Current 16 A
Output Voltage 220/230/240 VAC
Maximum Output Current 10 A for IEC-C13 outlets16 A for IEC-C19 outlet
Input 2 x IEC-C20 inlets
Output 8 x IEC-C13 1 x IEC-C19
Communication USB/RS-232Transfer time 9-12ms (Typical)
Dimension, D X W X H (mm) 330 X 483 X 44Net Weight (kgs) 5
Operating Temperature 20-95 % RH @ -5-45°C (non-condensing)
otice
MODEL ATSINPUT
OUTPUT
CONNECTION
PHYSICAL
ENVIRONMENT
AC
CESSO
RY