s Metaloterm ® MF Twin wall insulated chimney system Total Solutions in Flue Systems Specialist distributor of flues, chimneys & renewable appliances www.docherty .co.uk

Metaloterm MF - SpecifiedBy · Metaloterm MF is a universal flue/chimney system suitable for both ... mm 100 130 150 180 200 250 300 350 400 450 500 600 700-1000 Outer diameter mm

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • s

    M e t a l o t e r m ® M FTwin wall insulated chimney system

    Total Solutions in Flue Systems

    Specialist distributor of flues, chimneys & renewable appliances

    www.docherty.co.uk

  • MFSystem description

    Metaloterm® MFThe Metaloterm®system, made of stainless steel, with a high temperature sealing ring. Metaloterm MF is a universal flue/chimney system suitable for both®high and low temperatures, non-condensing and condensing applications with

    Therefore the system is suitable for a wide range of applications such as boilers,stoves and ovens. The product range also contains a wide variety of silencers. For Passive house the Metaloterm® assortment provides the Iso-block which can be combined with MF. The system can also be used for CHP applications, in this case a special VITON® sealing ring might be necessary (for more information about CHP see chapter Aplications & Solutions > CHP).Due to the proven quality Metaloterm® MF has a 10 year guarantee.

    Applications· · Condensing boilers· · Industrial ovens, large scale establishments

    Advantages · · Inner- and outer wall from high quality stainless steel· No terminal bridges, uninterrupted insulation from base plate to top stub· Stress free thermal expansion· Fast-build system without the need of sealants· Compatible with Metaloterm ME, UE and EN systems · High density and high quality insulation· High temperature silicone sealing ring· Lightweight elements· Immediately ready for use·

    Technical characteristicsApplication Chimney/Flue systemOperating mode Dry/wetPressure Negative/positive pressureMax. working pressure 200 PaOperating temperature 450°C negative pressure 200°C positive pressureMax. temperature allowed 1000°C negative pressure (max. 30 min.) 200°C positive pressureInner wall material AISI 316L/EN 1.4404 thickness minimal 0.4 mmOuter wall material AISI 304/EN 1.4301 thickness minimal 0.5 mmInsulation type Rockwool thickness Ø100 - 400: 25 mm Ø450 - 600: 37.5 mm Ø700 - 1000: 50 mm*Sealant ElastomerFuel type Wood/coal/oil/natural gas/calor gas/propane gas

    Inner diametermm 100 130 150 180 200 250 300 350 400 450 500 600 700-1000

    Outer diametermm 150 180 200 230 250 300 350 400 450 525 575 675 *

    Cross sectioncm² 79 133 177 254 314 488 706 962 1256 1590 1963 2826 *

    Weight±kg/m 4,5 5,5 6,0 7,0 7,5 9,5 12 15 19 25 27 32 *

    *On request onlyET200 H1 W V2 L50040 O10, T600 N1 D V3 L50040 G70N 1856-1: T200-P1-W-V2-L50040-O10, T450-N1-D-V3-L50040-G50, T450-N1-W-V2-L50040-O40

    ET200 H1 W V2 L50040 O10N 1856-2: T200-P1-W-V2-L50040-O10, T450-N1-D-V3-L50040-G70, T450-N1-W-V2-L50040-O40

    NL 2:3 1:1,5

    GB 1:2

    BE 13:15 1:1,15

    FR 2:3 1:1,5

    DE 3:5 1:1,7

    CH 1:1

    IT 2:3 1:1,5

    FI 11:18 1:1,64

    NO 8:11 1:1,375

    LV 1:2

    PL 5:8 1:1,6

    CZ 2:3 1:1,5

    GR 2:3 1:1,5

    CY 3:5 1:1,7

    SE 10:16 1:1,6

    DK 28:37 1:1,32

    AT 2:3 1:1,5

    HU 1:2

    RO 2:3 1:1,5

    RS 2:3 1:1,5

    BG 3:5 1:1,7

    IE 1:2

    LU 1:2 (of 3:5)

    Vlaggen

    Land Verhouding vlag vlag+outline kleurcodes

    2012

    NL 2:3 1:1,5

    GB 1:2

    BE 13:15 1:1,15

    C - M - Y - K :0-84-77-32

    C - M - Y - K :0-0-0-0

    Pantone 032-C

    C - M - Y - K :0-0-0-0

    C - M - Y - K :76-50-0-46

    C - M - Y - K :100-72-0-18.5

    C - M - Y - K :0-0-0-0

    C - M - Y - K :0-91-76-6

    C - M - Y - K :0-0-0-100

    C - M - Y - K :0-15-95-0

    C - M - Y - K :0-90-80-5

    C - M - Y - K :100-70-0-5

    C - M - Y - K :0-0-0-0

    C - M - Y - K :0-90-86-0

    C - M - Y - K :0-0-0-100

    C - M - Y - K :0-100-100-0

    C - M - Y - K :0-12-100-5

    Pantone 144-C

    Pantone 336-C

    C - M - Y - K :0-0-0-0

    C - M - Y - K :0-100-100-0

    C - M - Y - K :0-0-0-0

    C - M - Y - K :100-0-100-45

    C - M - Y - K :0-0-0-0

    C - M - Y - K :0-100-100-0

    C - M - Y - K :100-70-0-10

    C - M - Y - K :0-10-95-0

    C - M - Y - K :0-90-80-5

    C - M - Y - K :100-70-0-10

    C - M - Y - K :0-10-95-0

    C - M - Y - K :0-90-80-5

    Pantone 347-C

    Pantone 151

    R G B :255-255-255

    R G B :0-150-110

    R G B :214-38-18

    C - M - Y - K :100-56-0-18.5

    C - M - Y - K :0-0-0-0

    Pantone Red 032 U

    C - M - Y - K :0-0-0-0

    Pantone Red 281 U

    C - M - Y - K :25-96-84-19

    C - M - Y - K :0-0-0-0

    Pantone 186-C

    C - M - Y - K :0-0-0-0

    C - M - Y - K :0-0-0-0

    Pantone 348-C

    #: D4 21 3Dca.10-96-71-1

    #: E9 E8 E7

    NCS 0580-Y10R

    NCS 4055-R95B

    Pantone 281 U

    Pantone Red 032 U

    C - M - Y - K :0-0-0-0

    C - M - Y - K :ca.98-99-22-14

    C - M - Y - K :0-0-0-0

    Pantone 186-C

    C - M - Y - K :0-0-0-0

    ®

  • MF

    x xx

    y

    KM

    K

    yy

    x

    y

    h2

    M

    h1

    Hx xx

    y

    K

    M

    K

    yy

    x

    yh2

    M

    h1

    H

    xxx

    y

    K

    M

    K

    yy

    x

    y

    h2

    M

    h1

    H

    x xx

    y

    yy

    h1

    H

    x

    y

    h2

    K

    M

    K

    M

    x xx

    y

    yy

    h1

    H

    x

    y

    h2

    K

    M

    K

    M

    x xx

    y

    yy

    h1

    H

    x

    y

    h2

    K

    M

    K

    M

    2 MFB 45º

    Ø 100 130 150 180 200 250 300 350 400 450 500 600 K 90 95 100 105 110 120 145 145 155 175 185 205 M 50 55 60 65 70 80 105 105 115 175 185 205 x 150 165 175 185 200 225 285 285 310 420 445 495 y 185 200 210 225 235 260 320 320 345 420 445 495 xx 100 105 115 120 125 140 175 175 190 250 260 290 yy 240 255 275 290 305 340 425 425 460 595 630 705

    Ø 130 150 180 200 250 300 350 400 450 500 600 H 400 400 450 500 600 700 750 850 1010 1010 1150 h1 300 300 335 375 450 525 560 625 830 820 950 h2 330 365 395 430 505 585 640 715 870 935 1010 x 330 355 390 415 475 560 605 660 790 845 970 y 235 255 280 305 355 415 455 505 615 660 715

    MFT 45º + MFB 45º

    Offsets

    MF

  • MF F

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 100 130 150 180 200 250 300 350 400 450 500 600

    MFAAdaptorÜbergangsstück

    Aansluitstuk

    50

    Ø

    50

    A

    100

    Ø

    170

    A

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 100 130 150 180 200 250 300 350 400 450 500 600

    MFAAdaptorÜbergangsstück

    Aansluitstuk

    50

    Ø50

    A

    100

    Ø

    170

    A

    50 180 200 250 300 350 400 450 500 60050 180 200 250 300 350 400 450 500 600

    50

    Ø

    50

    A

    100

    Ø

    170

    A

    150 180 200 250 300 350 400 450 500 600152 182 202 252 302 352 402 452 502 602

    k contra

    a

    A

    180

    Ø

    A

    130

    Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    MFAC00

    A

    Ø

    A

    Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 102 132 152 182 202 252 302 352 402 452 502 602

    MFAC

    Übergangsstück contra

    Aansluitstuk contra

    A

    180

    Ø

    A

    130

    Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    MFAC00

    A

    Ø

    A

    Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 102 132 152 182 202 252 302 352 402 452 502 602

    MFAC

    Übergangsstück contra

    Aansluitstuk contra

    A

    180

    Ø

    A

    130

    Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    MFAC00

    A

    Ø

    A

    Ø

    150 180 200 250149 179 199 249

    k contra, glatt

    a, glad

    A

    Ø

    130

    Ø 100 130 150 180 200 250A 99 129 149 179 199 249

    MFACG

    Übergangsstück contra, glatt

    Aansluitstuk contra, glad

    A

    Ø

    130

    Ø 130 150 180

    MFADDAdaptor, double-doubleÜbergangsstückRaccord, double-doubleAansluitstuk, dubbele huls

    6022

    5

    d1A

    Ø

    Ø 130 150 180A 129 149 179d1 151 171 201

    MFADDAdaptor, double-doubleÜbergangsstückRaccord, double-doubleAansluitstuk, dubbele huls

    6022

    5

    d1A

    Ø

    Total Solutions in Flue Systems

    ØØ

    A A

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A to be specified on order/bei Bestellung angeben/ à indiquér sur commande/bij bestelling aangeven

    MFA 00Adaptor, reducing, increasingÜbergangsstück, reduzierend, erweiterungRaccord simple paroi réduit ou augmentéAansluitstuk verlopend

    Total Solutions in Flue Systems

    ØØ

    A A

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A to be specified on order/bei Bestellung angeben/ à indiquér sur commande/bij bestelling aangeven

    MFA 00Adaptor, reducing, increasingÜbergangsstück, reduzierend, erweiterungRaccord simple paroi réduit ou augmentéAansluitstuk verlopend

    Total Solutions in Flue Systems

    Ø Ø

    A A

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A to be specified on order/bei Bestellung angeben/ à indiquér sur commande/bij bestelling aangeven

    MFA 00Adaptor, reducing, increasingÜbergangsstück, reduzierend, erweiterungRaccord simple paroi réduit ou augmentéAansluitstuk verlopend

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 100 130 150 180 200 250 300 350 400 450 500 600

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 102 132 152 182 202 252 302 352 402 452 502 602

    Ø 100 130 150 180 200 250A 99 129 149 179 199 249

    Ø 130 150 180A 129 149 179d1 151 171 201

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A

    MFA 00Adaptor, reducing, increasing

    MFAAdaptor ME

    MFACCounter adaptor ME

    MFAC 00Counter adaptor, reducing, increasing

    MFACGCounter adaptor, smooth

    MFADDAdaptor double-double

  • MF

    1 80 200 250 300 350 400

    100

    Ø 1 30 1 50 1 80 200 250 300 350 400

    MFAG

    Ø

    100

    Total Solutions in Flue Systems

    100

    A

    Ø

    Ø 130 150 180 200A 135 155 185 205

    MFAGAAdaptor, smooth increased (for negative pressure only)Übergangsstück, glatt erweitert (ausschließlich Unterdruck)Raccord simple paroi, lisse augmenté (uniquement pour dépression)Aansluitstuk, glad vergroot (uitsluitend voor onderdruk)

    Total Solutions in Flue Systems

    Ø 10

    A

    15 15

    310

    D

    65

    Ø

    Ø 130 150 180 200 250 300 350 400A 320 320 350 370 450 500 550 600D 127 147 177 197 247 297 347 397

    MFSAChimney connector (for negative pressure only)Fundamentverankerung für Schornsteinerhöhung (ausschließlich Unterdruck)Plaque de base ouverte (uniquement pour dépression)Schoorsteenaansluitstuk (uitsluitend voor onderdruk)

    Total Solutions in Flue Systems

    Ø 10

    A15 15

    310

    D

    65

    Ø

    Ø 130 150 180 200 250 300 350 400A 320 320 350 370 450 500 550 600D 127 147 177 197 247 297 347 397

    MFSAChimney connector (for negative pressure only)Fundamentverankerung für Schornsteinerhöhung (ausschließlich Unterdruck)Plaque de base ouverte (uniquement pour dépression)Schoorsteenaansluitstuk (uitsluitend voor onderdruk)

    Total Solutions in Flue Systems

    A

    Ø

    970

    Ø 130 150 180 200 250

    MFALAdaptorÜbergangsstückRaccordAansluitstuk

    Total Solutions in Flue Systems

    A

    Ø

    970

    Ø 130 150 180 200 250

    MFALAdaptorÜbergangsstückRaccordAansluitstuk

    Ø 1 00 1 30 1 30 1 80 200 250 300 350 400 450 500 600K 90 95 95 1 05 1 1 0 1 20 1 20 1 20 1 45 1 1 0 1 1 0 1 1 0M 50 55 55 65 70 80 80 80 1 05 1 1 0 1 1 0 1 1 0x 1 5 1 5 1 5 20 20 20 20 20 30 30 30 30y 1 40 1 40 1 40 1 65 1 7 5 1 95 1 95 1 95 2 45 2 1 5 2 1 5 2 1 5

    MFB 15Elb o w 1 5°Bogen 1 5°Coude 1 5°Bo c ht 1 5°

    Ø

    KK y

    y

    M

    M

    15°15°

    Ø

    xx

    Ø

    K y

    y

    M

    15°

    x

    Ø 1 00 1 30 1 50 1 80 200 250 300 350 400 450 500K 90 95 1 00 1 05 1 1 0 1 20 1 20 1 20 1 45 1 35 1M 50 55 60 65 70 80 80 80 1 05 1 35 1 45x 30 30 35 35 40 45 45 45 55 70 7 5 y 1 35 1 40 1 50 1 60 1 70 1 90 1 90 1 90 235 255 2

    MFB 30Elb o w 30°Bogen 30°Coude 30°Bo c ht 30°

    Ø

    MKK

    yy

    M

    30°30°

    Ø

    x x

    MFB 30Elb o w 30°Bogen 30°Coude 30°Bo c ht 30°

    Ø

    MKK

    yy

    M

    30°30°

    Ø

    x x

    Total Solutions in Flue Systems

    100

    A

    Ø

    Ø 130 150 180 200A 135 155 185 205

    MFAGAAdaptor, smooth increased (for negative pressure only)Übergangsstück, glatt erweitert (ausschließlich Unterdruck)Raccord simple paroi, lisse augmenté (uniquement pour dépression)Aansluitstuk, glad vergroot (uitsluitend voor onderdruk)

    Ø 10

    A

    15 15

    310

    D

    65

    Ø

    Ø 130 150 180 200 250 300 350 400A 320 320 350 370 450 500 550 600D 127 147 177 197 247 297 347 397

    MFSAChimney connector (for negative pressure only)Fundamentverankerung für Schornsteinerhöhung (ausschließlich Unterdruck)Plaque de base ouverte (uniquement pour dépression)Schoorsteenaansluitstuk (uitsluitend voor onderdruk)

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 130 150 180 200 250 300 350 400A 129 149 179 199 249 299 349 399

    Ø 130 150 180 200A 136 156 186 206

    Ø 130 150 180 200 250 300 350 400A 320 320 350 370 450 500 550 600D 127 147 177 197 247 297 347 397

    Ø 130 150 180 200 250A 128 148 178 298 248

    Ø 100 130 150 180 200 250 300 350 400 450 500 600K 90 95 100 105 110 120 120 120 145 110 110 110M 50 55 60 65 70 80 80 80 105 110 110 110x 15 15 15 20 20 20 20 20 30 30 30 30y 140 140 160 165 175 195 195 195 245 215 215 215

    Ø 100 130 150 180 200 250 300 350 400 450 500 600K 90 95 100 105 110 120 120 120 145 135 145 155M 50 55 60 65 70 80 80 80 105 135 145 155x 30 30 35 35 40 45 45 45 55 70 75 80y 135 140 150 160 170 190 190 190 235 255 270 290

    MFAGAdaptor EN

    MFAGAAdaptor, smooth increased (for negative pressure only)

    MFALAdaptor long EN

    MFSAChimney connector (for negative pressure only)

    MFB 1515° Elbow

    MFB 3030° Elbow

  • MF F

    Ø 1 00 1 30 1 50 1 80 200 250 300 350 400 450 500 600

    x 40 40 45 50 50 60 7 5 7 5 90 1 25 1 30 1 45y 1 25 1 35 1 40 1 50 1 60 1 7 5 220 220 235 300 3 1 5 350

    MFB 45

    Ø

    yy

    45°

    45°

    Ø

    xx

    30 1 50 1 80 200 250 300 350 400 450 500 600

    45 50 50 60 7 5 7 5 90 1 25 1 30 1 45 1 40 1 50 1 60 1 7 5 220 220 235 300 3 1 5 350

    Ø

    yy

    45°

    45°

    x

    Ø 1 00 1 30 1 50 1 80 200 250 300 350 400 450 500

    x 1 25 1 40 1 50 1 60 1 7 5 200 2 40 250 2 7 5 385 4 1y 1 60 1 70 1 85 1 95 2 1 0 230 2 70 290 3 1 0 385 4 1

    MFB 87

    Ø

    xx

    yy

    87°87°

    Ø

    Ø 1 00 1 30 1 50 1 80 200 250 300 350 400

    x 1 25 1 40 1 50 1 60 1 7 5 200 2 40 250 2 7 5 y 1 60 1 70 1 85 1 95 2 1 0 230 2 70 290 3 1 0

    MFB 87

    Ø

    xx

    yy87°87°

    Ø

    Ø

    xx K

    GL

    K

    yy

    90°90°

    Ø

    M

    GL

    M

    Ø 100 130 150 180 200 250 300 350 400 450 500 600G 100 130 140 140 140 180 180 180 240 240 240 240K 90 95 100 105 110 120 145 145 155 175 185 205L 135 160 155 140 145 165 185 205 225 300 320 365M 50 55 60 65 70 80 105 105 115 145 185 205x 145 170 170 165 175 200 235 250 275 360 415 465y 185 210 210 205 215 240 275 290 315 390 415 465

    MFBI90Elbow 90° with inspection coverBogen 90° mit InspektionsöffnungCoude 90° avec trappe de visiteBocht 90° met inspectie-opening

    Ø

    xx K

    yy

    90°90°

    M

    GL

    M

    pection coverektionsöffnung

    appe de visiteectie-opening

    Total Solutions in Flue Systems

    Ø

    xx KK

    yy

    M ML L

    87°87°

    Ø

    G G

    Ø 100 130 150 180 200 250 300 350 400 450 500 600G 100 130 140 140 140 180 180 180 240 240 240 240K 90 95 100 105 110 115 140 140 150 175 185 205L 135 160 155 140 145 165 185 205 225 300 320 365M 50 55 60 65 70 80 105 105 115 175 185 205x 145 170 170 165 175 200 240 250 275 390 415 465y 185 210 210 205 215 230 270 285 310 390 415 465

    MFBI87Elbow 87° with inspection coverBogen 87° mit InspektionsöffnungCoude 87° avec trappe de visiteBocht 87° met inspectie-opening

    Total Solutions in Flue Systems

    Ø

    y

    xM

    K

    L

    90°

    Ø 100 130 150 180 200 250 300 350 400K 90 95 100 105 110 120 145 145 155L 105 115 125 140 145 165 185 205 225M 50 55 60 65 70 80 105 105 115x 125 135 150 165 175 200 235 250 275y 165 175 190 205 215 235 275 290 315

    x = M + ( )

    y = K + ( )

    L2

    L2

    MFB 90Elbow 90°Bogen 90°Coude 90°Bocht 90°

    Ø 1 30 1 50 1 80 200 250 300 350 400 450 500 600H 400 400 450 500 600 700 7 50 850 1 0 1 0 1 0 1 0 1 1 50h1 300 300 335 37 5 450 525 560 625 830 820 950x 1 95 2 1 5 2 40 255 300 3 40 385 425 490 530 620y 1 05 85 1 00 1 20 1 50 1 85 1 80 200 3 40 290 380

    MFT 45T ee-piece 45°T - S tü c k 45°T é 45°T - s tuk 45°

    Ø

    y

    h1H

    Ø

    x

    y

    h1H

    x

    Ø

    xx KK

    yy

    M ML L

    87°87°

    Ø

    G G

    Ø 100 130 150 180 200 250 300 350 400 450 500 600G 100 130 140 140 140 180 180 180 240 240 240 240K 90 95 100 105 110 115 140 140 150 175 185 205L 135 160 155 140 145 165 185 205 225 300 320 365M 50 55 60 65 70 80 105 105 115 175 185 205x 145 170 170 165 175 200 240 250 275 390 415 465y 185 210 210 205 215 230 270 285 310 390 415 465

    MFBI87Elbow 87° with inspection coverBogen 87° mit InspektionsöffnungCoude 87° avec trappe de visiteBocht 87° met inspectie-opening

    Ø 1 30 1 50 1 80 200 250 300 350 400 450 500 H 400 400 450 500 600 700 7 50 850 1 0 1 0 1 0 1 0h1 300 300 335 37 5 450 525 560 625 830 820

    MFT 45T ee-piece 45°T - S tü c k 45°T é 45°T - s tuk 45°

    Ø

    y

    h1H

    Ø

    x

    y

    h1H

    x

    Ø 100 130 150 180 200 250 300 350 400 450 500 600K 90 95 100 105 110 120 145 145 155 175 185 205M 50 55 60 65 70 80 105 105 115 175 185 205x 40 40 45 50 50 60 75 75 90 125 130 145y 125 135 140 150 160 175 220 220 235 300 315 350

    Ø 100 130 150 180 200 250 300 350 400 450 500 600K 85 90 95 100 105 115 140 145 155 175 185 205L 105 115 125 135 145 165 185 205 225 300 320 365M 55 60 60 65 75 80 110 115 115 175 185 205x 125 140 150 160 175 200 240 250 275 385 410 465y 160 170 185 195 210 230 270 290 310 385 410 465

    Ø 100 130 150 180 200 250 300 350 400K 90 95 100 105 110 120 145 145 155L 105 115 125 140 145 165 185 205 225M 50 55 60 65 70 80 105 105 115x 125 135 150 165 175 200 235 250 275y 165 175 190 205 215 235 275 290 315

    Ø 100 130 150 180 200 250 300 350 400 450 500 600G 100 130 190 190 140 180 180 180 240 240 240 240K 85 90 95 100 110 115 140 145 150 175 185 210L 130 160 155 140 145 165 185 200 220 300 320 370M 55 55 60 70 70 80 110 110 120 175 185 205x 145 170 170 170 170 195 240 250 275 385 410 465y 175 205 205 200 215 230 270 290 310 385 410 465

    Ø 100 130 150 180 200 250 300 350 400 450 500 600G 100 130 190 190 140 180 180 180 240 240 240 240K 85 90 95 100 110 115 140 145 150 175 185 210L 130 160 155 140 145 165 185 200 220 300 320 370M 55 55 60 70 70 80 110 110 120 175 185 205x 145 170 170 170 170 195 240 250 275 385 410 465y 175 205 205 200 215 230 275 285 305 385 410 465

    Ø 130 150 180 200 250 300 350 400 450 500 600H 400 400 450 500 600 700 750 850 1010 1010 1150h1 300 300 335 375 450 525 560 625 830 820 950x 195 215 240 255 300 340 385 425 490 530 620y 105 85 100 120 150 185 180 200 340 290 380

    MFB 4545° Elbow

    MFB 8787° Elbow

    MFB 9090° Elbow

    MFBI8787° elbow with inspection cover

    MFBI9090° Elbow with inspection cover

    MFT 4545° Tee

  • MF

    Ø 130 150 180 200 250 300 350 400H 500 500 500 500 500 500 600 650h1 250 250 250 250 250 250 300 350x 145 155 170 180 205 235 260 285

    MFT 90Tee-piece 90°T-Stück 90°Té 90°T-stuk 90°

    Ø

    h1H

    x

    Ø 130 150 180 200 250 300 350 400H 500 500 500 500 500 500 600 650h1 250 250 250 250 250 250 300 350x 145 155 170 180 205 235 260 285

    MFT 90Tee-piece 90°T-Stück 90°Té 90°T-stuk 90°

    Øh1

    H

    x

    Ø 1 00 1 30 1 50 1 80 200 250 300 350 400 450 500 600H 500 500 500 500 500 500 500 600 650 700 800 1 000h1 250 250 250 250 250 250 250 300 350 350 400 500x 1 25 1 40 1 50 1 65 1 80 205 230 260 285 330 360 4 1 0

    MFT 87

    Ø

    h1H

    Ø

    x

    h1H

    x

    1 00 1 30 1 50 1 80 200 250 300 350 400 450 500 600500 500 500 500 500 500 500 600 650 700 800 1 000250 250 250 250 250 250 250 300 350 350 400 500

    1 25 1 40 1 50 1 65 1 80 205 230 260 285 330 360 4 1 0

    MFT 87

    Ø

    h1H

    Ø

    x

    h1

    x

    Ø 1 30 1 50 1 80 200 250

    x 1 50 1 65 1 7 5 1 90 2 1 5

    MFTI 87

    250

    500

    x

    Ø

    1 30 1 50 1 80 200 250

    1 50 1 65 1 7 5 1 90 2 1 5

    250

    500

    x

    Ø

    Ø 1 00 1 30 1 50 1 80 200 250H 300 300 350 350 400 450h1 1 50 1 50 1 7 5 1 7 5 200 225x 1 20 1 35 1 45 1 60 1 65 1 90

    MFTV08

    h1H

    x

    Ø

    80 97

    Ø 1 00 1 30 1 50 1 80 200 250H 300 300 350 350 400 450h1 1 50 1 50 1 7 5 1 7 5 200 225x 1 20 1 35 1 45 1 60 1 65 1 90

    MFTV08

    h1H

    x

    Ø

    80 97

    Ø

    H1 - H

    2 - H

    3 - H

    4

    H1 - H

    2 - H

    3 - H

    4

    Ø

    100 130 150 180 200 250 300 350 400 450 500 600H1 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000H2 500 500 500 500 500 500 500 500 500 500 500 500H3 250 250 250 250 250 250 250 250 250 250 250 250

    MF 100/50/25/10ength

    Längenelementongueurectieura

    Ø

    H1 - H

    2 - H

    3 - H

    4

    H1 - H

    2 - H

    3 - H

    4

    Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600H1 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000H2 500 500 500 500 500 500 500 500 500 500 500 500H3 250 250 250 250 250 250 250 250 250 250 250 250H4 100 100 100 100 100 100 100 100 100 100 100 100

    MF 100/50/25/10LengthLängenelementLongueurSectieRura

    Ø 1 00 1 30 1 50 1 80 200 250 300 350 400 450 500 600A 9 7 1 2 7 1 4 7 1 7 7 1 9 7 2 4 7 2 9 7 3 4 7 3 9 7 4 45 495 595

    MFPPA dju s t able leng t hLängenaus g lei c hselementLongueur a ju s t ableP a s pijp

    545

    Hmin

    100

    Hmax

    400

    A

    365

    Hmin

    60Hm

    ax 25

    0

    Ø

    A

    Ø

    Ø 1 00 1 30 1 50 1 80 200 250 300 350 400 450A 9 7 1 2 7 1 4 7 1 7 7 1 9 7 2 4 7 2 9 7 3 4 7 3 9 7 4

    MFPPA dju s t able leng t hLängenaus g lei c hselementLongueur a ju s t ableP a s pijp

    545

    Hmin

    100

    Hmax

    400

    A

    365

    Hmin

    60Hm

    ax 25

    0

    Ø

    A

    Ø

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 100 130 150 180 200 250 300 350 400H 500 500 500 500 500 500 500 600 650h1 250 250 250 250 250 250 250 300 350x 125 145 155 170 180 205 235 260 285

    Ø 130 150 180 200 250G 100 140 140 140 180x 150 165 175 190 215

    Ø 100 130 150 180 200 250 300 350 400 450 500 600H 500 500 500 500 500 500 500 600 650 700 800 1000h1 250 250 250 250 250 250 250 300 350 350 400 500x 125 140 150 165 180 205 230 260 285 330 360 410y 245 245 245 245 235 245 235 345 345 340 390 490

    Ø 100 130 150 180 200 250H 300 300 350 350 400 450h1 150 150 175 175 200 225x 120 135 145 160 165 190

    Ø 100 130 150 180 200 250 300 350 400 450 500 600H1 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000H2 500 500 500 500 500 500 500 500 500 500 500 500H3 250 250 250 250 250 250 250 250 250 250 250 250H4 100 100 100 100 100 100 100 100 100 100 100 100

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 97 127 147 177 197 247 297 347 397 445 495 595Lmin 60 60 60 60 60 60 60 60 60 100 100 100Lmax 250 250 250 250 250 250 250 250 250 400 400 400

    MFT 8787° Tee

    MFT 9090° Tee

    MFTI 8787° tee with inspection cover

    MFTV0887° reducing tee

    MF100/50/25/10Length

    MFPPAdjustable length

  • MF F

    Total Solutions in Flue Systems

    180

    500

    Ø

    120

    Ø 130 150 180 200 250 300 350 400

    MFTRInspection length (for negative pressure only)Reinigungselement (ausschließlich Unterdruck)Élément porte de visite (uniquement pour dépression)Reinigingsstuk (uitsluitend voor onderdruk)

    Total Solutions in Flue Systems

    180

    500

    Ø

    120

    Ø 130 150 180 200 250 300 350 400

    MFTRInspection length (for negative pressure only)Reinigungselement (ausschließlich Unterdruck)Élément porte de visite (uniquement pour dépression)Reinigingsstuk (uitsluitend voor onderdruk)

    Ø 130 150 180 200 250 300 350 400

    MFTK

    113

    38

    50

    172

    Ø 130 150 180 200 250 300 350 40083

    311

    50

    172

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    MFI

    Ø

    500

    500

    Ø

    100 130 150 180 200 250 300 350 400 450 500 600

    MFI

    Ø

    500

    500

    Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    MFEM

    Drain (horizontal)/probe lengthEntwässerungs- (waagerecht)/MeßelementElément de purge (horizontal)/prise de mesureCondens- (horizontaal)/meetelement

    Ø

    170

    90100 15

    0

    Ø

    MFE ¾"1" MFE

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    MFEM

    Drain (horizontal)/probe lengthEntwässerungs- (waagerecht)/MeßelementElément de purge (horizontal)/prise de mesureCondens- (horizontaal)/meetelement

    Ø

    170

    90100 15

    0

    Ø

    MFE ¾"1" MFE

    180

    500

    Ø

    120

    Ø 130 150 180 200 250 300 350 400

    MFNLDraught stabilizer, negative pressure (for negative pressure only)Nebenluftvorrichtung, unterdruck (ausschließlich Unterdruck)Modérateur de tirage, dépression (uniquement pour dépression)Trekonderbreker, onderdruk (uitsluitend voor onderdruk)

    180

    500

    Ø

    120

    Ø 130 150 180 200 250 300 350 400

    MFNLDraught stabilizer, negative pressure (for negative pressure only)Nebenluftvorrichtung, unterdruck (ausschließlich Unterdruck)Modérateur de tirage, dépression (uniquement pour dépression)Trekonderbreker, onderdruk (uitsluitend voor onderdruk)

    Dd1

    8549

    0

    d2

    Ø 130 150 180 200d1 126 146 176 196d2 123 143 173 193D 184 204 234 254

    MFPRCeiling/wall connectorGeschoß/WanddurchführungRaccord au plafond/murPlafond-/wandaansluiting

    Dd1

    8549

    0

    d2

    Ø 130 150 180 200d1 126 146 176 196d2 123 143 173 193

    MFPRCeiling/wall connectorGeschoß/WanddurchführungRaccord au plafond/murPlafond-/wandaansluiting

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 130 150 180 200 250 300 350 400 Ø 130 150 180 200 250 300 350 400

    Ø 100 130 150 180 200 250 300 350 400 450 500 600G 100 130 140 140 140 180 180 180 240 240 240 240

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    Ø 130 150 180 200 250 300 350 400 Ø 130 150 180 200d 126 146 176 196d2 123 143 173 193D 184 204 234 254

    MFTRInspection length

    MFTKEnd cap for MFTR, anti-condensation

    MFIInspection element

    MFEMProbe length and drain

    MFNLDraught stabilizer

    MFPRCeiling / wall connector

  • MF

    Total Solutions in Flue Systems

    115

    "¾ "1

    40

    Ø Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    MFRBKCondensate collector with drainKondensatschale mit zentr. KondensatablaufBac suie avec purgeRoetbak met condensafvoer

    Total Solutions in Flue Systems

    115

    "¾ "1

    40

    Ø Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    MFRBKCondensate collector with drainKondensatschale mit zentr. KondensatablaufBac suie avec purgeRoetbak met condensafvoer

    ADSI A1/2

    ADSIR1ADSIR2ADSIC1

    MFSIR1MFSIR2MFSIC1

    2/1A ISFM

    A A AAAA

    Ø

    L L

    L L

    Ø ØØ

    ADSI A1/2

    ADSIR1ADSIR2ADSIC1

    MFSIR1MFSIR2MFSIC1

    MEMEME

    2/1A ISFM

    A A AAAA

    Ø

    L L

    L L

    Ø ØØ

    ADSI A1/2

    ADSIR1ADSIR2ADSIC1

    MFSIR1MFSIR2MFSIC1

    MEMEME

    2/1A ISFM

    A A AAAA

    Ø

    L L

    L L

    Ø ØØ

    MFSIR1MFSIR2MFSIC1

    MESIR1MESIR2MESIC1

    2/1A ISEM2/1A ISFM

    A AØ

    L LL

    Ø Ø

    2

    MFSIR1MFSIR2MFSIC1

    MESIR1MESIR2MESIC1

    2/1A ISEM2/1A ISFM

    A AAA

    Ø

    L LL

    L LL

    Ø Ø Ø

    Ø Ø

    ADSI A1/2

    ADSIR1ADSIR2ADSIC1

    MFSIR1MFSIR2MFSIC1

    MESMESMES

    M2/1A ISFM

    A A AAAA

    Ø

    L L

    L L

    Ø ØØ

    ADSI A1/2

    ADSIR1ADSIR2ADSIC1

    MFSIR1MFSIR2MFSIC1

    MEMEME

    M2/1A ISFM

    A A AAAA

    Ø

    L L

    L L

    Ø ØØ

    ADSI A1/2

    ADSIR1ADSIR2ADSIC1

    MFSIR1MFSIR2MFSIC1

    MESMESMES

    M2/1A ISFM

    A A AAAA

    Ø

    L L

    L L

    Ø ØØ

    MFSIR1MFSIR2MFSIC1

    MESIR1MESIR2MESIC1

    2/1A ISEM2/1A ISFM

    A AAA

    Ø

    LL

    L L

    Ø Ø Ø

    Ø ØMFSIR1MFSIR2MFSIC1

    MESIR1MESIR2MESIC1

    2/1A ISEM2/1A ISFM

    A AAA

    Ø

    L L

    L L

    Ø Ø Ø

    Ø Ø

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 100 130 150 180 200 250 300 350 400 450 500 600L 1870 1870 1870 2120 2370 2620 3120 3370 3870 4370 4620 4870A 400 500 525 575 625 675 875 975 1050 1100 1225 1325

    Ø 100 130 150 180 200 250 300 350 400 450 500 600L 600 750 750 1000 1250 1250 1750 1750 1750 2000 2000 2000A 225 255 275 305 325 375 425 475 525 575 625 725

    Ø 100 130 150 180 200 250 300 350 400 450 500 600L 1000 1000 1000 1250 1500 1500 2500 2500 2500 3000 3000 3000A 225 255 275 325 325 375 425 475 525 575 625 725

    Ø 100 130 150 180 200 250 300 350 400 450 500 600L 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200 2200A 400 450 500 600 650 700 850 950 1000 1100 1150 1350

    Ø 100 130 150 180 200 250 300 350 400 450 500 600L 2200 2200 2200 2200 2200 2400 2600 2800 3000 3200 3400 3600A 550 650 750 800 850 1000 1000 1100 1200 1300 1350 1550

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    MFRBKCondensate collector with drain

    MFSIA1Absorption silencer 25 dB

    MFSIA2Absorption silencer 35 dB

    MFSIR1Resonance silencer 20 dB

    MFSIR2Resonance silencer 30 dB

    MFSIC1Combination silencer 25 dB

  • MF

    Total Solutions in Flue Systems

    H

    A

    Ø 100 130 150 180 200 250 300 350 400 450 500 600tseuqer no 039 075 075 075 093 093 093 H

    A 200 230 250 280 300 350 tseuqer no 004

    MFSI AEExtension set for MFSI AVerlängerung für MFSI ARallonge pour MFSI AVerlengset voor MFSI A

    Total Solutions in Flue Systems

    H

    Ø

    A

    Ø 100 130 150 180 200 250 300H 620 620 620 800 800 800 1160A 200 230 250 280 300 350 400

    MFSI AAbsorption silencerAbsorptionsschalldämpferSilencieux à absorptionAbsorptiedemper

    Total Solutions in Flue Systems

    H

    A

    Ø 100 130 150 180 200 250 300 350 400 450 500 600tseuqer no 039 075 075 075 093 093 093 H

    A 200 230 250 280 300 350 tseuqer no 004

    MFSI AEExtension set for MFSI AVerlängerung für MFSI ARallonge pour MFSI AVerlengset voor MFSI A

    Total Solutions in Flue Systems

    H

    Ø

    A

    Ø 100 130 150 180 200 250 300H 620 620 620 800 800 800 1160A 200 230 250 280 300 350 400

    MFSI AAbsorption silencerAbsorptionsschalldämpferSilencieux à absorptionAbsorptiedemper

    Total Solutions in Flue Systems

    A

    60 105

    ØØ

    A

    Ø 11

    18 18

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 185 215 235 265 285 335 385 435 485 560 610 710

    Ø 1”Ø 3/4”

    MFAPUBase plate with condensate drainFundamentverankerung mit seitlichem KondensatablaufPlaque de départ avec purge latéraleVoetplaat universeel met condensafloop

    Total Solutions in Flue Systems

    A

    60 105

    ØØ

    A

    Ø 11

    18 18

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 185 215 235 265 285 335 385 435 485 560 610 710

    Ø 1”Ø 3/4”

    MFAPUBase plate with condensate drainFundamentverankerung mit seitlichem KondensatablaufPlaque de départ avec purge latéraleVoetplaat universeel met condensafloop

    Total Solutions in Flue Systems

    Ø Ø

    7015

    0 7015

    0

    Ø 11

    A A

    B

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 185 215 235 265 275 335 385 435 485 560 610 710B 235 265 285 315 335 385 435 485 535 610 660 760

    MFAPOWall support elementWandstützeÉlément pour support muralMuurondersteuningselement

    Total Solutions in Flue Systems

    Ø Ø

    7015

    0 7015

    0

    Ø 11

    A A

    B

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 185 215 235 265 275 335 385 435 485 560 610 710B 235 265 285 315 335 385 435 485 535 610 660 760

    MFAPOWall support elementWandstützeÉlément pour support muralMuurondersteuningselement

    Ø 1 30 1 50 1 80 200 250 350D 1 80 200 230 250 300 400h min 1 00 1 1 0 1 25 1 35 1 60 2 1 0h max 7 50 7 35 7 25 7 1 0 690 630

    MFBTSElb o w suppo r t (incl. MFMO)Bogen s tüt z e (inkl. MFMO)Suppo r t de coude (incl. MFMO)Bo c h t en s t eun (incl. MFMO)

    D + 50

    min

    100

    max

    735

    D

    1010

    140110

    100

    h min/

    h max

    MFMO

    150

    3580

    50 50 25250

    50Ø 6,5

    50

    D6,5

    50 20

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675

    MFDQRoof supportDachkonsoleSupport au toitDakondersteuning

    150

    3580

    50 50 25250

    50Ø 6,5

    50

    D6,5

    50 20

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675

    MFDQRoof supportDachkonsoleSupport au toitDakondersteuning

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 100 130 150 180 200 250 300 350 400 450 500 600L 390 390 390 570 570 570 930 on requestA 200 230 250 280 300 350 400 on request

    Ø 100 130 150 180 200 250 300 350 400 450 500 600H 620 620 620 800 800 800 1160 on requestA 200 230 250 280 300 350 400 on request

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 185 215 235 265 285 335 385 435 485 560 610 710

    Ø 130 150 180 200 250 350D 180 200 230 250 300 400Hmin 100 110 125 135 160 210Hmax 750 735 725 710 690 630

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675

    MFSI AAbsorption silencer

    MFSI AEExtension set for MFSI A

    MFAPOWall support element

    MFAPURotating base plate with condensate drain

    MFBTSElbow support (incl. MFMO)

    MFDQRoof support

  • MFF

    Total Solutions in Flue Systems

    75

    75x1

    MFMB

    V2 9

    0 - 2

    00MF

    MBV3

    190

    - 30

    0MF

    MBV4

    290

    - 40

    0

    x

    D

    MFMBV2/3/4Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675x 180 210 230 260 280 330 380 430 480 535 585 685x1 MFMBV2 - - - - - - - - - 70 70 MFMBV3 - - - - - - - - - 110 110 MFMBV4 - - - - - - - - - 105 105

    MFMBV2/3/4Wall band adjustableGebäudeabspannband verstellbarBride murale réglableMuurbeugel verstelbaar

    Total Solutions in Flue Systems

    75

    75x1

    MFMB

    V2 9

    0 - 2

    00MF

    MBV3

    190

    - 30

    0MF

    MBV4

    290

    - 40

    0

    x

    D

    MFMBV2/3/4Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675x 180 210 230 260 280 330 380 430 480 535 585 685x1 MFMBV2 - - - - - - - - - 70 70 MFMBV3 - - - - - - - - - 110 110 MFMBV4 - - - - - - - - - 105 105

    MFMBV2/3/4Wall band adjustableGebäudeabspannband verstellbarBride murale réglableMuurbeugel verstelbaar

    Total Solutions in Flue Systems

    75

    75x1

    MFMB

    V2 9

    0 - 2

    00MF

    MBV3

    190

    - 30

    0MF

    MBV4

    290

    - 40

    0

    x

    D

    MFMBV2/3/4Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675x 180 210 230 260 280 330 380 430 480 535 585 685x1 MFMBV2 - - - - - - - - - 70 70 MFMBV3 - - - - - - - - - 110 110 MFMBV4 - - - - - - - - - 105 105

    MFMBV2/3/4Wall band adjustableGebäudeabspannband verstellbarBride murale réglableMuurbeugel verstelbaar

    Total Solutions in Flue Systems

    75

    75x1

    MFMB

    V2 9

    0 - 2

    00MF

    MBV3

    190

    - 30

    0MF

    MBV4

    290

    - 40

    0

    x

    D

    MFMBV2/3/4Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675x 180 210 230 260 280 330 380 430 480 535 585 685x1 MFMBV2 - - - - - - - - - 70 70 MFMBV3 - - - - - - - - - 110 110 MFMBV4 - - - - - - - - - 105 105

    MFMBV2/3/4Wall band adjustableGebäudeabspannband verstellbarBride murale réglableMuurbeugel verstelbaar

    Total Solutions in Flue Systems

    BA

    H

    D

    2210

    255 255

    12 11

    11

    180

    12

    180

    Ø 350, 400, 450

    Ø 500, 600

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675A 160 160 160 160 160 160 160 360 360 360 510 510B 55 55 55 55 55 55 55 60 60 60 60 60H 50-90 09-05 09-05 09-05 09-05 09-05 09-05 09-05 09-05 09-05 09-05 09-05

    MFMBWall band adjustableGebäudeabspannband verstellbarBride murale réglableMuurbeugel verstelbaar

    Total Solutions in Flue Systems

    D

    70

    Ø 100 130 150 180 200 250 D 150 180 200 230 250 300

    MFMOBand for wall supportStützband zu WandstützeBride pour support muralBand voor muurondersteuning

    Total Solutions in Flue Systems

    D

    70

    Ø 100 130 150 180 200 250 D 150 180 200 230 250 300

    MFMOBand for wall supportStützband zu WandstützeBride pour support muralBand voor muurondersteuning

    53

    H

    0331

    32

    11

    40

    13

    CB

    A

    MFOL 1 (50 - 90 mm)Ø 100 130 150 180 200 250A 220 220 220 285 285 285B 190 190 190 255 255 255C 125 125 125 130 130 130H 170 170 170 230 230 230

    MFOL 2 (90 - 200 mm)Ø 100 130 150 180 200 250A 315 335 335 345 370 395B 285 305 305 315 340 365C 165 180 180 200 215 240H 255 275 275 285 305 325

    H

    H

    A

    A

    3131

    13

    40 13

    13

    13

    13

    13

    19

    19

    13

    02208

    0112h

    13

    40

    x

    MFOH 2 (50 - 200 mm)Ø 100 130 150 180 200 250 300 350 400 450 500 600A 475 475 475 475 600 600 600 740 740 740 915 915H 240 240 240 240 330 330 330 330 330 330 380 380 h2 - - - - 310 310 310 310 310 310 360 360x - - - - 270 270 270 330 330 330 355 355

    MFOH 4 (200 - 400 mm)Ø 100 130 150 180 200 250 300 350 400 450 500 600A 600 600 740 740 740 740 915 915 915 1090 1090 1090H 330 330 330 330 330 330 380 380 380 430 430 430h2 310 310 310 310 310 310 360 360 360 410 410 410x 270 270 330 330 330 330 355 355 355 350 350 350

    Ø 100 130 150 180 200 250 300 350 400A 350 380 400 430 450 500 550 600 650

    MFVQCeiling supportGeschoßkonsoleSupport au plafondVerdiepingsondersteuning

    55

    25

    Ø 6,5 (4x)> Ø 200 (8x)

    25

    AD

    Ø 100 130 150 180 200 250 300 350 400

    MFVQCeiling supportGeschoßkonsoleSupport au plafondVerdiepingsondersteuning

    55

    25

    Ø 6,5 (4x)> Ø 200 (8x)

    25

    AD

    Total Solutions in Flue Systems

    B A

    H

    D

    2210

    255 255

    12 11

    11

    180

    12

    180

    Ø 350, 400, 450

    Ø 500, 600

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675A 160 160 160 160 160 160 160 360 360 360 510 510B 55 55 55 55 55 55 55 60 60 60 60 60H 50-90 09-05 09-05 09-05 09-05 09-05 09-05 09-05 09-05 09-05 09-05 09-05

    MFMBWall band adjustableGebäudeabspannband verstellbarBride murale réglableMuurbeugel verstelbaar

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675x 160 160 160 160 160 160 160 360 360 360 510 510b 55 55 55 55 55 55 55 60 60 60 60 60h1 50-90 50-90 50-90 50-90 50-90 50-90 50-90 50-90 50-90 50-90 50-90 50-90

    Ø 100 130 150 180 200 250D 150 180 200 230 250 300

    Ø 100 130 150 180 200 250 300 350 400A 350 380 400 430 450 500 550 600 650

    MFMBAdjustable wall band

    MFMBV2, MFMBV3, MFMBV4Adjustable wall band

    MFMOBand for wall support

    MFOH 2 / MFOH 4Support heavy (pair) for MFAPO/MFAPU

    MFOL 1 / MFOL 2Support light (pair) for MFMO

    MFVQCeiling support

    x = Max. distance to cut

  • MF F

    Ø 100 130 150 180 200 250 300 350 400 450 500 600

    MFSK

    340

    50 180 200 250 300 350 400 450 500 600

    340

    Ø 100 130 150 180 200 250 300 350 400 450 500 600L 200 230 250 280 300 350 400 450 500 575 625 725

    MFTSTelescopic support for MFAPUTeleskopstütze für MFAPUSupport téléscopique pour MFAPUVerstelbare ondersteuning voor MFAPU

    L

    L

    50

    Hmin

    270

    Hmax

    500

    Ø 100 130 150 180 200 250 300 350 400 450 500 600L 200 230 250 280 300 350 400 450 500 575 625 725

    MFTSTelescopic support for MFAPUTeleskopstütze für MFAPUSupport téléscopique pour MFAPUVerstelbare ondersteuning voor MFAPU

    L

    L

    50

    Hmin

    270

    Hmax

    500

    � A

    � A

    Ø D

    � A

    745

    093

    � A

    300/

    500/

    700

    � A

    � A

    Ø D

    Ø D

    Ø D

    � A

    325100

    � A

    � A

    Ø D

    � A

    745

    093

    � A

    300/

    500/

    700

    � A

    � A

    Ø D

    Ø D

    Ø D

    1000

    A

    A325100

    � A

    Ø D

    � A

    300/

    500/

    700

    � A

    Ø D

    1000

    � A

    A

    � A

    Ø D

    745

    093

    � A

    300/

    500/

    700

    Ø D

    � AØ

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 150 180 200 230 250 300 350 400 450 525 575 675

    Ø 100 130 150 180 200 250 300 350 400 450 500 600L 200 230 250 280 300 350 400 450 500 575 625 725

    Ø 130 150 180 200A 325 325 325 375

    Ø 130 150 180 200A 325 365 365 430

    Ø 130 150 180 200A 385 425 425 490

    Ø 130 150 180 200A 325 365 365 430

    MFSKReinforced locking band

    MFTSTelescopic support for MFAPU

    MFIBBLStandard block low

    MFIBBHStandard block high

    MFIBExtension set for MFIBBH

    MFIBMT (black)Casing, resizable

  • MFF

    900

    � A

    Ø D

    � A

    � A

    1000

    � Ø D

    AA

    A325100

    1210 830

    Ø D

    900

    � A

    � A

    � A

    Ø D

    � A

    � A

    1000

    � Ø D

    � A

    A

    A325100

    1210

    B

    830

    Ø D

    � A

    745

    � A

    300/

    500/

    700

    � A

    � A

    Ø D

    Ø D

    � A

    � A

    � A

    1000

    � Ø D

    325100

    1210

    � A

    C

    A

    B

    � A

    Ø D

    � A

    � A

    � A

    Ø D

    Ø D

    � A

    1000

    � A

    A

    A325100

    B

    B

    B

    A

    A� B

    C

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 130 150 180 200A 265 265 330 330

    Ø 130 150 180 200A 265 265 330 330

    Ø 130 150 180 200A 325 365 365 430

    Ø 130 150 180 200A 325 365 365 430

    Ø 130 150 180 200A 185 205 235 255B 415 455 455 520C 385 425 425 490

    MFIBMHMounting aid (2 pcs)

    MFIBVQLCeiling support for ATIBBL

    MFIBMDMoisture-retarding seal

    MFIBMRRain retaining seal

    MFIBP10 MFIBP30

  • MFC

    900

    A

    B

    830

    � A

    Ø D

    Ø D

    � A

    � A

    � A

    1000

    � Ø D

    A325100

    1210

    � A� A

    B

    B

    A

    A� B

    C

    C

    900

    � A

    A

    B

    830

    � A

    � A

    Ø D

    745

    093

    � A

    300/

    500/

    700

    � A

    Ø D

    � A

    � A

    Ø D

    100

    1210

    � A

    �A

    B

    A

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 130 150 180 200A 325 365 365 430

    Ø 130 150 180 200A 325 365 365 430

    Ø 130 150 180 200A 355 395 395 460

    Ø 130 150 180 200A 375 415 415 480

    Ø 130 150 180 200A 325 365 365 430B

    MFIBD30 MFIBD50

    MFIBDV MFIBLS

    MFIBPN MFIBVHVentilation plate for MFIBBH

  • MF

    � A

    Ø D

    900

    � A

    � A

    � A

    Ø D

    Ø D

    � A

    � A

    1000

    � Ø D

    1000

    � A

    A

    A325100

    1210

    B

    830

    Ø D

    � A

    � A Ø D

    745

    � A

    300/

    500/

    700

    � A

    Ø D

    � A

    � A

    � A

    Ø D

    100

    1210

    � A

    � A

    Ø D

    � A

    � A

    Ø D

    � A

    745

    093

    � A

    300/

    500/

    700

    � A

    � A

    Ø D

    Ø D

    Ø D

    � A

    1000

    3 25100

    � A� A

    B

    B

    A

    A� B

    C

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 130 150 180 200A 375 375 375 425

    Ø 130 150 180 200A 455 455 455 520

    Ø 130 150 180 200D 380 400 430 450

    Ø 130 150 180 200D 380 400 430 450

    Ø 130 150 180 200A 185 205 235 255B 235 275 275 355

    MFIBVLVentilation plate for MFIBBL

    MFIBVR (black)Rain retaining ventilation plate

    MFIBWPVentilation plate wall penetration

    MFIBSStorm collar Iso-block

    MFIBRRosette

    MFIBR2Rosette 2 parts

  • MFØ D

    900

    � A

    � A

    � A

    Ø D

    � A

    � A

    1000

    � Ø D

    1000

    � A

    A

    A325100

    1210

    B

    830

    � A

    Ø D

    � A

    745

    3

    � A

    300/

    500/

    700

    � A

    � A

    Ø D

    Ø D

    � A

    � A

    � A

    1000

    � Ø D

    1000

    3 25100

    1210

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 160 190 210 240 260 310 360 410 460 535 585 685C 440 470 490 520 540 590 640 690 740 815 865 965

    MFDPFlat roof flashingDachdurchführung FlachdachSolin de toit platDakplaat plat dak

    D

    315

    C

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 160 190 210 240 260 310 360 410 460 535 585 685C 440 470 490 520 540 590 640 690 740 815 865 965

    MFDPFlat roof flashingDachdurchführung FlachdachSolin de toit platDakplaat plat dak

    D

    315

    C

    Total Solutions in Flue Systems

    C x C"5°-30°

    H

    D

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 155 185 205 235 255 305 355 405 455 530 580 680C 520 550 575 605 630 685 740 795 850 935 990 1100C" 500 530 550 580 600 655 705 760 810 890 940 1045H 155 160 160 165 170 175 185 195 200 215 220 235

    MFDHSlope roof flashing 5°- 30°Dachdurchführung 5°- 30°Solin de toit incliné pente 5°- 30°Dakplaat hellend dak 5°- 30°

    Total Solutions in Flue Systems

    C x C"5°-30°

    H

    D

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 155 185 205 235 255 305 355 405 455 530 580 680C 520 550 575 605 630 685 740 795 850 935 990 1100C" 500 530 550 580 600 655 705 760 810 890 940 1045H 155 160 160 165 170 175 185 195 200 215 220 235

    MFDHSlope roof flashing 5°- 30°Dachdurchführung 5°- 30°Solin de toit incliné pente 5°- 30°Dakplaat hellend dak 5°- 30°

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 160 190 210 240 260 310 360 410 460 535 585 685C 500 750 750 750 750 750 750 750 1000 1100 1200 1300C" 500 1000 1000 1000 1000 1000 1000 1000 1200 1200 1300 1400

    MFLSLead slope roof flashing 20°- 45°Dachdurchführung 20°- 45° mit bleier PlatteSolin de toit incliné pente 20°- 45° base plombLoden slabpan 20°- 45°

    C x C"

    20°-45°

    120

    D

    Ø 100 130 150 180 200 250 300 350 400 450 500 600D 160 190 210 240 260 310 360 410 460 535 585 685C 500 750 750 750 750 750 750 750 1000 1100 1200 1300C" 500 1000 1000 1000 1000 1000 1000 1000 1200 1200 1300 1400

    MFLSLead slope roof flashing 20°- 45°Dachdurchführung 20°- 45° mit bleier PlatteSolin de toit incliné pente 20°- 45° base plombLoden slabpan 20°- 45°

    C x C"

    20°-45°

    120

    D

    200

    A x B

    45°- 60°

    D

    Ø 130 150 180 200 250D 215 235 265 285 335A 750 750 750 1000 1000B 1000 1000 1100 1200 1300

    ATLELead slope roof flashing 45°- 60°Dachdurchführung 45°- 60° mit bleier PlatteSolin de toit incliné pente 45°- 60° base plombLoden slabpan 45°- 60°

    200

    A x B

    45°- 60°

    D

    Ø 130 150 180 200 250D 215 235 265 285 335A 750 750 750 1000 1000B 1000 1000 1100 1200 1300

    ATLELead slope roof flashing 45°- 60°Dachdurchführung 45°- 60° mit bleier PlatteSolin de toit incliné pente 45°- 60° base plombLoden slabpan 45°- 60°

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 130 150 180 200A 355 355 420 420

    Ø 130 150 180 200A 315 315 365 365

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 160 190 210 240 260 310 360 410 460 535 585 685C 440 470 490 520 540 590 640 690 740 815 865 965

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 155 185 205 235 255 305 355 405 455 530 580 680C 520 550 575 605 630 685 740 795 850 935 990 1100C” 500 530 550 580 600 655 705 760 810 890 940 1045H 155 160 160 165 170 175 185 195 200 215 220 235

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 160 190 210 240 260 310 360 410 460 535 585 685C 750 750 750 750 750 750 750 750 1000 1100 1200 1300C” 750 1000 1000 1000 1000 1000 1000 1000 1200 1200 1300 1400

    Ø 130 150 180 200 250D 215 235 265 285 335A 750 750 750 1000 1000B 1000 1000 1100 1200 1300

    MFIBAPH MFIBAPL

    MFDP MFDH

    MFLS MFLE

  • MFF

    Ø 1 00 1 30 1 50 1 80 200 250 300 350 400A 2 7 5 305 325 355 37 5 425 4 7 5 525 5 7D 1 50 1 80 200 230 250 300 350 400 450

    MFSS t o r m collarRegena b weiser/ W and r os e t t eColl e t de solinS t o r mk r aag

    D

    A

    70

    Ø 1 00 1 30 1 50 1 80 200 250 300 350 400 450 A 2 7 5 305 325 355 37 5 425 4 7 5 525 5 7 5 650 D 1 50 1 80 200 230 250 300 350 400 450 525

    MFSS t o r m collarRegena b weiser/ W and r os e t t eColl e t de solinS t o r mk r aag

    D

    A

    70

    D

    550

    450

    550450

    455

    520

    555

    620

    450

    130

    400

    900

    0-45°

    B

    mounting sethaufbau

    e montage incl. montageset

    D

    550

    450

    550450

    455

    520

    555

    620

    004054

    900

    0-45°

    B

    Ø 130 150 180 200 B 180 200 230 250D 185 205 235 255

    Modularer Schornstein Dachaufbau inkl. MontagesetSouche modulaire incl. kit de montageModulair schoorsteenblok incl. montageset

    Total Solutions in Flue Systems

    A

    D

    BH

    Ø

    70B

    A

    Ø 100 130 150 180 200 250 300 350 400A 220 285 330 395 440 550 660 770 880B 110 145 165 200 220 275 330 385 440

    MFKAll weather capRegenhaube mit WindabweiserChapeau antirefouleurTrekkende kap

    Total Solutions in Flue Systems

    A

    D

    BH

    Ø

    70B

    A

    Ø 100 130 150 180 200 250 300 350 400A 220 285 330 395 440 550 660 770 880B 110 145 165 200 220 275 330 385 440

    MFKAll weather capRegenhaube mit WindabweiserChapeau antirefouleurTrekkende kap

    AG

    AG

    BH

    Ø

    BH

    Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 220 285 330 395 440 550 660 770 880 890 990 1190B 110 145 165 200 220 275 330 385 440 435 490 590H 70 70 70 70 70 70 70 70 70 65 65 65G 100 130 150 180 200 250 250 250 250 250 250 250

    MFKRAll weather cap with inspectionRegenhaube mit Windabweiser und ReinigungsöffnungChapeau avec trappe de ramonageTrekkende kap met veegopening

    AG

    AG

    BH

    Ø

    BH

    Ø

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 220 285 330 395 440 550 660 770 880 890 990 1190B 110 145 165 200 220 275 330 385 440 435 490 590H 70 70 70 70 70 70 70 70 70 65 65 65G 100 130 150 180 200 250 250 250 250 250 250 250

    MFKRAll weather cap with inspectionRegenhaube mit Windabweiser und ReinigungsöffnungChapeau avec trappe de ramonageTrekkende kap met veegopening

    Asso

    rtm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 275 305 325 355 375 425 475 525 575 650 700 800D 150 180 200 230 250 300 350 400 450 525 575 675

    Ø 100 130 150 180 200 250 300 350 400A 220 285 330 395 440 550 660 770 880B 110 145 165 200 220 275 330 385 440

    Ø 100 130 150 180 200 250 300 350 400 450 500 600A 220 285 330 395 440 550 660 770 880 890 990 1190B 110 145 165 200 220 275 330 385 440 435 490 590H 70 70 70 70 70 70 70 70 70 65 65 65G 100 130 150 180 200 250 250 250 250 250 250 250

    Ø 130 150 180 200B 180 200 230 250D 185 205 235 255

    MFTOPModular chimney cover incl. mounting set

    MFSStorm collar

    MFKAll weather cap

    MFKRAll weather cap with inspection

    Also available in black

  • Approved Engineer. Written documentation to demonstrate the inspection and

    MFAs

    sort

    men

    t | Li

    efer

    prog

    ram

    m |

    Dét

    ails

    des

    pièc

    es |

    Ass

    ortim

    ent |

    Ass

    ortm

    ent |

    Lief

    erpr

    ogra

    mm

    | D

    étai

    ls de

    s pi

    èces

    | A

    ssor

    timen

    t | A

    ssor

    tmen

    t | Li

    efer

    prog

    ram

    m MFWarranty terms and conditionsMetaloterm MF chimney systems are manufactured to the highest quality standards. Under normal operating conditions, Metaloterm MF provides many years of reliable service and carries a 10 year conditional warranty depending on application, installation and maintenance.The components within the range can be vulnerable when exposed to the products of combustion from solid fuel appliances and this is especially true for terminals. Condensate collectors are also vulnerable, particularly if the flue system is not regularly maintained and cleaned. These components are considered ‘incidental‘ and their life expectancy will vary depending on location, application, fuel usage and maintenance. For this reason, these fittings are covered by a 2 year warranty and not the 10 year conditional warranty.The Metaloterm MF chimney system carries a 10 year conditional warranty for any defect due to faulty manufacture, this is provided the system has been installed in accordance with Metaloterm installation instructions, and has been used for the purpose it was designed for. Furthermore, the system must be regularly cleaned, maintained and inspected. This should be carried out at least once per year, and more regularly if the appliance is used continuously or frequently, by a member of one of the HETAS recognised chimney sweep associations (APICS, GMCS or NACS) or a HETAS

    cleaning of the chimney must be kept to validate the ten year warranty.When burning mineral fuel or smokeless fuel in your appliance, care should always be taken to use a high quality fuel. Only HETAS or SFA (Solid Fuel Association) approved fuels must be used with Metaloterm MF. For guidance on fuel choices please visit www.hetas.co.uk.Under no circumstances should an appliance be located where there is the potential of chemical contamination of the combustion air.Where the chimney system is exposed to severe coastal locations, you must ensure adequate protection to the outer components of Metaloterm MF.A chimney fire will invalidate the warranty; in the event of a chimney fire it is always advisable to replace the complete chimney system.

    Installation GuideMetaloterm MF must only be installed by a competent approved installer and in accordance with the full installation instructions that are available on request.Chimney and flue designThe chimney and flue design is the responsibility of the engineer or installer and should conform to the requirements of Approved Document J and, where appropriate, BS EN 15287 part 1.Any variation will require the designer to ensure the performance of the chimney meets the requirements of the appliance by calculation using the methods given in BS EN 13384 part 1 or any proprietary software programme based on this standard.Regulations and standardsThe regulations and standards covering the design and installation of a flue pipe in the UK are:Building RegulationsEngland and Wales - Approved Document J – Combustion Appliances and Fuel Storage SystemsScotland – Scottish Building Standards Technical Hand Book Section 3Northern Ireland – Building Regulations Part L – Combustion Appliances and Fuel Storage SystemsStandardsBS EN 15287 Part 1 – Chimneys. Design, installation and commissioning of chimneys Part 1: Chimneys for non-room sealed heating appliances.BS EN 13384 Part 1 – Chimneys. Thermal and fluid dynamic calculation methods.Flue sizingThe sizing of flues for appliances should be based on the type of fuel and the appliance to be used.• Gas AppliancesIn the case of gas appliances the Building Regulations Approved Document J table 5, the gas safety in use regulations and in all cases as required by the manufacturer’s installation instructions.

    NL 2:3 1:1,5

    GB 1:2

    BE 13:15 1:1,15

    FR 2:3 1:1,5

    DE 3:5 1:1,7

    CH 1:1

    IT 2:3 1:1,5

    FI 11:18 1:1,64

    NO 8:11 1:1,375

    LV 1:2

    PL 5:8 1:1,6

    CZ 2:3 1:1,5

    GR 2:3 1:1,5

    CY 3:5 1:1,7

    SE 10:16 1:1,6

    DK 28:37 1:1,32

    AT 2:3 1:1,5

    HU 1:2

    RO 2:3 1:1,5

    RS 2:3 1:1,5

    BG 3:5 1:1,7

    IE 1:2

    LU 1:2 (of 3:5)

    Vlaggen

    Land Verhouding vlag vlag+outline kleurcodes

    2012

    • Oil AppliancesFlues for oil appliances should be sized in accordance with the requirements of ApprovedDocument J Paragraphs 4.4 and 4.5.• Solid Fuel AppliancesThe size of flues for solid fuel appliances should be in accordance with the requirements ofApproved Document J Paragraphs 2.4 to 2.7 and as given in table 2 of ADJ.For solid fuel appliances with back or side flue outlet, the maximum permitted length of horizontal chimney or flue pipe is 150mm. Greater horizontal lengths up to 450mm are now possible subject to meeting the requirements of the National Annex for BS EN15287-1.Please refer to NA.7.2.2 for full details.Building Regulations do not allow any part of the chimney system to form an angle greater than45 degree from the vertical. Where the system is used for solid fuels and oil, no system can be constructed with more than two separate offsets in the chimney. If a 90 degree tee is used on the back of the appliance it would constitute as one offset, any change of direction in a flue will create resistance to the flue gas movement.

    The maximum length of the offset must not exceed 20% of the total length of the chimney.Where the chimney passes through a wall, the opening must be lined with a wall sleeve. The termination height of the chimney will depend on appropriate regulations and standards. The connection between the connecting flue pipe to Metaloterm MF must be made in the same room as the appliance. When coming off the rear of the stove we recommend a provision for cleaning access.

    Where the chimney passes through any occupied space other than the room in which the appliance is installed, it must be fully enclosed with non-combustible board a minimum of 9mm thickness with at least a 30 minute fire rating maintaining a minimum air gap of 41mm (we would recommend 50mm or more to provide increased protection) between the inside of the enclosure and the outer wall of the chimney. The enclosure is to prevent damage to the chimney, accidental human contact and to prevent combustible material being placed too close to the chimney.

    Provision for inspection throughout the enclosed length is required under Building Regulation ADJ paragraph 1.47 if this cannot be achieved via the fire stop a non-combustible access hatch 100mm x 100mm with a minumum 30 minute fire rating will be required. The access hatch should form an airtight seal.

    Using a Solid Fire Stop Option 1: This can only be used on the first ceiling penetration of the room where the appliance is fitted and used in conjunction with a ventilated plate on the second and final penetration.

    First floor penetration: When passing through a combustible floor a suitably sized box frame (four sides) should be created, remove any combustible ceiling material within the boxed area. The box frame should then be shielded with a non-combustible board 9mm (min) thickness with a fire rating of at least 30 minutes whilst maintaining a minimum air gap of 41mm (we would recommend 50mm or more to provide increased protection) between the inside of the enclosure and the outer wall of the chimney the non-combustible lining should finish flush with the finished floor level and ceiling and secured to the boxing using suitable fixings.

    A ventilated support plate (MFIBVQ) should be fitted to the top side of the penetration and secured to the floor using 6mm screws.

    Method 1 for second penetration: When passing through a combustible floor or ceiling a second box frame (four sides) of similar size should be created in-line with the first, remove any combustible ceiling material within the boxed area. Take a measurement from the top side of the second penetration to floor level/ventilated plate at first penetration. Cut board to the correct length and width as required, using suitable vertical galvanised or stainless steel angle trims 25mm x 25mm or plasterboard angle fixing bead to form a corner or use as a vertical fixings against a wall. Please note if it is deemed to be a combustible wall you will be required to also line this area with a non-combustible board to form part of the enclosure. Where the board passes through the top boxed section secure the board to the boxing using suitable fixings. Angle trim may also be used at the bottom of the shaft to give further strength and support by fixing it to the floor creating an upstand to secure the board too.A ventilated support plate (MFIBVQ) should be fitted to the top side of the penetration and secured to the top of the joists using 6mm screws.

    All joints will need to be sealed to form a continuous air tight enclosure using appropriate materials.

  • MF MFFFMFMF

    The ventilated fire stop option is suitable for multiple floor penetrations further details on request.

    Minimum 41mm air gap

    150mm

    Alternative method of fitting enlosure for solid fire stop (see details for method 2 for second penetration)

    Where the chimney system penetrates more than one floor please contact us for more information.

    Rain cap

    Storm collar

    Roof flashing

    Ventilated support plateused with MFIBVQ

    30 minute (min) non-combustible fire rated board around aperture

    Ventilated fire stop kit with support clampMFV29

    No joint should occur within thickness of floor or within 50mm of the ceiling

    or floor surface

    Minimum air gap of 41mm (we recommend 50mm to provide

    increased protection) clearance between the outer chimney surface

    and the inside of the enclosure

    Square solidfire stop plate(DOCMFFS)

    Where the enclosure is required to form a part of the fire separation of the dwelling it should be in an appropriately rated fire resistant board

    Solid fire stop arrangement

    Loft insulation

    Where flue passes through insulation provision must be made not to allow insulation to penetrate guard

    Suitable protective guard in loft space

    425mm minimum

    Adaptor to MF

    Maximum 2 metres (BS EN 15287-2007+A1:2010)

    1000

    mm

    Length

    Locking band

    Ventilated plate with support bracket MFL29

    Ventilated support plateMFIBVQ

    Method 2 for second penetration: When the box frame has been formed remove any combustible ceiling material within the boxed area. Cloak the box frame with a non-combustible board 9mm (min) thickness with a fire rating of at least 30 minutes whilst maintaining a minimum air gap of 41mm (we would recommend 50mm or more to provide increased protection) between the inside of the enclosure and the outer wall of the chimney. The non-combustible lining should finish flush with the top of the formed boxing and extend below the ceiling by a minimum 150mm. Take a measurement from finished ceiling to floor and cut the non-combustible board to required length and width as required.

    The enclosure can now be formed around the 150mm non-combustible lining extending below the ceiling; this section can also be used to affix each side of the enclosure using suitable fixings. Using suitable vertical galvanised or stainless steel angle trims 25mm x 25mm or plasterboard angle fixing bead to form a corner or use as a vertical fixings against a wall. Please note if it is deemed to be a combustible wall you will be required to also line this area with a non-combustible board to form part of the enclosure. NOTE the first floor penetration non-combustible board within the joist area must be in line with the finished board of the non-combustible enclosure.All joints will need to be sealed to form a continuous air tight enclosure using appropriate materials.A ventilated support should be fitted and secured in place with 6mm screws on the top of the final ceiling penetration as shown MFIBVQ, if intermediate lateral support is required a wall bracket may be fitted within the enclosure. The MFIBVQ will support up to 5mtr’s of flue when used with sizes of 100mm to 200mm.

    Where the chimney passes through a roof space, it is essential that it is adequately supported by bracing to roof timbers. If there is a chimney run of more than 1.5m from the ceiling support to the roof support, use a bracing bracket and rigid stays for such application. Also, provision must be made to ensure that no accidental placement of combustible product can occur within 50mm of the external casing of the chimney. For example, a mesh or screen around the chimney. This must cover the first 1mtr of the chimney and must go down to the upper face of the ceiling or the top of the ventilated plate depending on type of installation allowed ensuring that no airways are obstructed on the ventilated plate assembly.Where it passes through any insulation provision should be made to ensure that no insulation can penetrate the guard.

    Each chimney section and connected fittings shall be used as manufactured for assembly on site without any alteration. Please make sure that all elements are installed the right way up. The system must be adequately supported with elements supplied by Metaloterm. The support components must be used at intervals depending on the load bearing criteria quoted on page 19. Wall brackets are not load bearing and should be used to provide lateral support only. They can be used as load bearing on flue sizes 100mm to 200mm on the condition that at least three wall brackets (MFMB, MFMBV2, MFMBV3, MFMBV4) are being used with a maximum distance between the brackets of 2 metres. When an offset is present a lateral support bracket is required; one before the first bend and one after the second bend.

    Ventilated Fire Stop Option 2:If using a ventilated fire-stop (MFV) the first floor lead through is cut and a box frame is formed (four sides) to create a chamber which is then lined with none combustible board with at least 30 minute fire rating and sized to accept the fire stop assembly. The top plate and clamp supplied with the fire stop is secured to the finished floor/top of formed chamber and secured in place using 6mm screws.

    Second floor penetration as described in Method 1 and Method 2 please note that the top ventilated plate and clamp is different to that used in the solid fire stop arrangement. The top ventilated plate and clamp when using this option is a (MFL) - see diagram.

    An alternative method for constructing the enclosure would be to use vertical batons no larger than 34mm x 34mm cross section, they must not extend into any part of the combustible floor or ceiling as this will affect the free air flow a minimum of 50mm clearance is required from the face of the flue to wooden baton. This option can only be used when installing the ventilated fire stop assembly option, IT IS NOT SUITABLE FOR USE WITH THE SOLID FIRE STOP ARRANGEMENT.

    Diagram showing solid fire stop Option 1 first floor penetration and Method 1 for second floor penetration

    Square solidfire stop plate(DOCMFFS)

    Wherseparated fi

    Solid fire stop arrangement

    Loft insulation

    Where flue passes through insulation provision must be made not to allow insulation to penetrate guard

    Ventilated support plateMFIBVQ

  • Single Penetration in to Unoccupied Space (Example Bungalow) Method 1When penetrating the ceiling into the loft space a box frame (four sides) should be created. The box frame should then be shielded with a minimum of 9mm non-combustible board giving a minimum fire rating of 30minutes maintaining a minimum air gap of 41mm (we would recommend 50mm or more to provide increased protection) between the inside of the enclosure and the outer wall of the chimney, sizing is to suit the ventilated support plate MFIBVQ. Remove any ceiling material within 60mm of the outside face of the flue and fit a solid trim plate (DOCMFFS) to the ceiling using suitable screws. The plate is drilled and the screws should penetrate the undersideof the formed boxing. Fit a ventilated support plate to the loft side of the box frame (MFIBVQ) secured with suitable screws. Where protection is required to prevent accidental contact in a loft space a suitable fire rated guard with 50mm clearance is required for the first 1000mm. Where loft insulation is present provision should be made to ensure that no insulationcan penetrate the guard.

    Alternative method using a Ventilated Fire Stop Assembly Method 2If using a ventilated Fire Stop the ceiling lead through is cut and boxing frame are formed and shielded with non-combustible board to accept the assembly, fit the top ventilated plate and support bracket using 6mm screws. NOTE the Ventilated Fire Stop assembly comes complete with top plate and support bracket.

    Single storey building penetration into unoccupied loft space

    Where flue passes through insulation provision must be made not to allow insulation to penetrate the guard

    425mm minimum

    100

    0 m

    m

    425mm minimum

    1000

    mm

    30 minute (min) non-combustible fire rated board

    Ventilated support plate used with solid fire stopMFIBVQØ 130 150 180 200

    A

    A

    A

    Ø D

    Ø D

    A

    A

    1000

    D

    1000

    A

    A

    A32510 0

    1210

    Solid fire stop plateDOCMFFS

    Locking band

    Top Stub or Rain Cap

    30° Elbows

    Wall BandMaximum distance between wall brackets4.0 metres (see table)

    Length

    Locking Band

    135° Tee

    Wall sleeve

    Base SupportSupports up to 10 metres of chimney; heavy duty option available; see table

    End cap (drain option available)

    Adaptor to MF

    45° Vitreous Elbow with Door

    Vitreous Enamel Connecting Flue

    Where a drain can be incorporated in the tee at the base of the chimney then a top stub should be usedNote: Rain water ingress can be reduced by use of a terminal where a drain cannot be included

    It is not a requirement, but ideally 30° elbows should be used to form the offset as this reducesrisk of blockage and corrosion of the inner skin

    External Trim Plate

    Internal Trim Plat

    The use of a secured guy wire bracket can increase unsupported length by 1.0 metre

    Standard Unsupported LengthMaximum 2 metres (see table)

    Minimum height of 600mm before an offset

    Full installation instructions on request

    Ø 130 150 180 200

    Ventilated plate with support bracket used with ventilated fire stopMFL29Ø 130 150 180 200

    Ventilated fire stopMFV29Ø 130 150 180 200

    Where the chimney system penetrates more than one floor please contact us for more information.

    Rain cap

    Storm collar

    Roof flashing

    30 minute (min) non-combustible fire rated board around aperture

    Ventilated fire stop kit with support clampMFV29

    No joint should occur within thickness of floor or within 50mm of the ceiling

    or floor surface

    Ventilated fire stop arrangement

    m a part of the fire he dwelling it should be in an appropriately

    Solid fire stop arrangement

    Suitable protective guard in loft space

    425mm minimum

    Adaptor to MF

    Maximum 2 metres (BS EN 15287-2007+A1:2010)

    Length

    Locking band

    Minimum air gap of 41mm (we recommend 50mm to provide

    increased protection) clearance between the outer chimney surface

    and the inside of the enclosure

    Diagram shows ventilated fire stop to first floor penetration and method 1 for the second level penetration.

    Please see notes for second floor penetration method 1 & 2, also alternative enclosure fitment diagram

    Ventilated support plateused with MFIBVQ

  • FFMFMF

    2

    4

    5

    6 7 8

    10

    1

    3

    9

    11

    KW

    IV

    AB

    PH

    PA

    DD

    FK

    G

    KY

    KAML

    EH

    TD

    NEDG

    IM

    CA

    LA

    DL

    YO

    LL

    SY

    SA

    TR

    PL

    EX

    DN

    LN

    PE

    NN

    NR

    IP

    NG

    S

    LD HR

    NPCF

    GL

    SN

    TA

    DT

    BA

    RG

    LEB

    CB

    OX

    DE

    SP

    DH

    TS

    SR

    HU

    HGBD

    LSBBPR

    WN

    FY

    L

    CW

    OLHX

    WFHD

    SK

    ST

    TF WS

    WV

    DYCV

    MKSG

    CMCO

    SSRM

    SO

    BH

    BS

    TQ

    PO

    GU RH

    BN

    DAME

    CT

    TN

    SL

    ALLU

    HP

    WR

    BL

    M

    CHWA

    Units 15/16 Colthrop Business ParkColthrop Lane, Thatcham Berkshire, RG19 4NB T: 01635 292400 F: 01635 201737 E: [email protected]

    The Docherty Group in the UK

    www.docherty.co.uk

    Specialist distributor of & heating appliances

    Area Sales Managers

    Birmingham branchBranch Manager: Alan Turberville55 Woodburn RoadBirmingham, West Midlands, B66 2PUT: 0121 555 6789

    5

    3

    Nottingham branchBranch Manager: Lee HarrisUnit 15, Robin Hood Street Ind. Est.off Alfred Street SouthNottingham, NG3 1GE

    4

    2

    Gateshead branchBranch Manager: Yasmin BlakeburnEleventh Avenue, Unit 15 Kingsway Interchange, Team Valley Trading EstateGateshead, NE11 0JYT: 0191 488 1111

    1

    Bristol branch Branch Manager: Neil JewellFlue House, Portway Trading EstatePortview Road, Bristol, BS11 9LQT: 0117 982 8252

    6

    Norbiton branchBranch Manager: James MoorcroftUnit C Station Yard, Coombe RoadNorbiton, Kingston, KT2 7AZT: 020 8391 0093

    8

    Thatcham branchBranch Manager: Liam IlottUnits 15/16 Colthrop Business ParkColthrop Lane, Thatcham Berkshire, RG19 4NB T: 01635 292400

    7

    Dunkeswell branchBranch Manager: Darren HooperUnit 20, Flightway Business ParkDunkeswell, Devon, EX14 4RDT: 01404 890098

    9

    Sure Fire Training ServicesUnit E, Fairview BuildingsHeage Road Industrial EstateRipley, Derbyshire, DE5 3GHT: 01773 570408 • 0345 260 0166

    10

    Leeds branch Branch Manager: Ryan MoorhouseUnit 7, Overland ParkGelderd Road, Leeds, LS27 7JNT: 01132 381200

    Warrington branchBranch Manager: Mark GarrettUnit 2, Rivington CourtWarrington, WA1 4RTT: 01925 807950

    Adina Heating ProductsUnit C, Fairview BuildingsHeage Road Industrial EstateRipley, Derbyshire, DE5 3GHT: 01773 571 330 E: [email protected]

    11

    Issu

    e: M

    arch

    201

    6

    Benjamin Chapman07771 654897 [email protected]

    Darren Willetts07850 994 [email protected]

    Jason Edwards07918 561 431 [email protected]

    Alan Smith07545 503 [email protected]

    Sacha Aarons07974 975 [email protected]

    Andy Bishop07595 205 [email protected]

    Marc Foster07918 561 430 [email protected]

    Mark Kerry07966 471 [email protected]

    Phil Chaplain07590 228 [email protected]

    Alex Daynes07818 030 721 [email protected]