Networking:MediaAccessControl(2)

MestradoemEngenhariaInformáGcaedeComputadoresMasterDegree(MSc)inInformaGonSystemsandComputerEngineering

Administração e Gestão de Infra-estruturas de IT IT Infrastructure Management and Administration

Page 2: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

TODAY

PhysicalLayer

StructuredCabling

StructuredCablingStandards

TheTIA/EIA568CStandard

2

Page 3: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

3

StructuredCabling

Page 4: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

4

Whichoneoftheseinstallationswouldyouprefermanaging?

What is a disadvantage to the installation on the right?

http

://w

ww

.itrw

.net

Page 5: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

StructuredCabling

Cableplant:Hardwaremakingupenterprise-widecablingsystem

Standard:TIA/EIAjoint568CommercialBuildingWiringStandard

Components:

EntrancefaciliGes

MDF(maindistribuGonframe)andIDF(intermediatedistribuGonframe)

BackbonewiringandHorizontalwiring

TelecommunicaGonscloset

Workarea

5

Structured Cabling

Page 6: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

StructuredCabling 6

Structured Cabling

Page 7: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

StructuredCabling 7

Structured Cabling

PatchPanelincross-connect

DataJackWalloutlets

Page 8: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

StructuredCabling

BestPracGces:

Choosingcorrectcabling

Followmanufacturers’installaGonguidelines

Followstandards

8

Structured Cabling

Page 9: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

WorldStructuredCablingStandardsANSI/TIA/EIA-568-B.1andB.2raGfiedin2001,CAT5/CAT5E

ANSI/TIA/EIA-568-B.2-1raGfiedin2002,CAT6

ANSI/TIA/EIA-568-B.2-10finalizedMay2008,CAT6a

ISO/IEC118012ndediGongenericcablingstandardraGfiedin2002

CENELECEN50173-1genericcablingstandardraGfiedin2002

9

Page 10: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

StandardsHistoryANSI/TIA/EIA-568ANSI/EIA/TIA568publishedin1991

The1stCommercialBuildingTelecommunicaGonsWiringStandard

SpecifiedthebasictransmissionrequirementsofCategory3,4&5

ANSI/EIA/TIA568Apublishedin1995

RecognizedCablesforHorizontalCabling:

4pair100ΩUTPcables(includingS/UTP)

2pair150ΩSTPcables(IBMTYPE-1A)

62.5/125µand50/125µfiber-opGccable

10

Page 11: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

ANSI/TIA/EIA-568-BseriesANSI/TIA/EIA-568-B.1GeneralInfrastructurerequirements,CopperandFiber

ANSI/TIA/EIA-568-B.2CopperrequirementsCat3,Cat5,Cat5E

ANSI/TIA/EIA-568-B.3Fiberrequirements

B-3.1LaserOpGmized(OM-3)MM–10Gigabit

11

Page 12: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

CELENECEN50173-1SeriesEN50173-1GeneralRequirements

EN50173-2Office(Commercial)Premises

EN50173-3IndustrialPremises

EN50173-4ResidenGalPremises

EN50173-5DataCenters

12

Page 13: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

AreaofApplicaGonEurope

EN50173-1(2002)

GenericCablingforcustomerpremises

NorthAmerica

TIA/EIA568-C(2009)

CommercialBuildingTelecommunicaGons

WorldGlobal

ISO/IEC11801(2002)

GenericCablingforcustomerpremises

13

Page 14: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

CurrentCondiGonsofStandardisaGonWorld

ISO/IEC118012ndEd.

RaGfiedJanuary2011,PublishedinOct.2002

3rdEdiGoninprogress

Connectorstandard:ISO/IEC60603-7-4&5inProgress

14

NorthAmerica

ANSI/TIA/EIA568-C

RaGfied,PublishedinJuly2009

C.0GenericCablingforCustomerPremises

C.1CommercialBuildingCablingStandard

C.2BalancedTwistedPairCablingandComponentsStandard

C.3OpGcalFiberCablingComponentsStandardWorldGlobal

Europe

EN50173-12ndEdiLon

RaGfied,PublishedinNov.2002

EN50173-1GeneralRequirements

EN50173-2OfficePremises

EN50173-3IndustrialPremises

EN50173-4Homes

EN50173-4DataCenters

Page 15: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

ISO/IEC118013rdEdiGon

15

Europe International ApplicationArea

current 3rdEdition

EN50173-1 ISO/IEC11801 ISO/IEC11801-1 GeneralEN50173-2 ISO/IEC11801 ISO/IEC11801-2 Office

EN50173-3 ISO/IEC2470 ISO/IEC11801-3 IndustrialPremises

EN50173-4 ISO/IEC15018 ISO/IEC11801-4 Home

EN50173-5 ISO/IEC24764 ISO/IEC11801-5 DataCenter

EN50173-6 ANSI/TIA-862 ISO/IEC11801-6 DistributedBuildingServices

EN50173ispathbreakingfor3rdEdiGon

ClassificaGonisbasefornewstructure

Page 16: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

CategoriesandClassesforCopperComponents

16

EN50173-1,ISO/IEC118012ndEdiGon;3rdEdiGon

MaxBandwidthinMHz Category Class Application Approved

0,1 1 A PBX,V11

1 2 B 1MbitEthernet

16 3 C 10MbitEthernet 1991

100 5 D 10/100MbitEthernet 1995

250 6 E >1GbitEthernet 2002

500 6A EA 10GbitEthernet 2007

600 7 F >10GbitEthernet 2002

1000 7A FA Multimedia 20092000 8.1 I >40GbitEthernet (2016)2000 8.2 II >40GbitEthernet (2016)

Page 17: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

17

The568CStandardforCommercialBuildingTelecommunicaGonsCabling

Page 18: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

Thestandarddescribesthe6subsystemsofastructuredcablinginstallaGon.

Thestructureisbasedonastartopologywherecablesfanoutfromapoint.

Thestartopologycanaccommodateallothertopologies (thismayrequirespecializeddevices).

18

TheSixSubsystems

Page 19: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

1:TheBuildingEntranceFacility1-BuildingEntranceFacility(EF)LocaGonwherecableentersorexitsthebuildingsuchas:LinksfromServiceproviders(InternetServiceProviders,TelephoneCompanies,etc)Inter-buildingcabling(betweenbuildings)

ThephysicalcharacterisGcsofthisroomorfacilityaredefinedintheANSI/TIA569Bstandard.

19

Page 20: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

1:TheBuildingEntrance(conGnued)Outdoorcablesmustbeterminatedwithinashortdistanceoftheentrance:MostoutdoorcableswillnotmeetfirecoderequirementsOutdoorcablesaredifficulttomanageduetotheirphysical(rugged)construcGonConducGveoutdoorcablesrequirelightningprotecGonatthebuildingentrance.Issuessuchaswaterseepagemustbeconsidered(dripbends)OwnershiptransiGon(demarcaGon)

Detailsaddressedinthe569Bstandard.

20

Page 21: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

2:TheEquipmentRoom2-EquipmentRoom(ER)Housesequipmentofhighercomplexity(servers,switches,etc.).

OnenaworkspaceforITstaff.

ThisroommayalsoserveasaTelecommunicaGonsRoom.

ThephysicaldesignoftheequipmentroomisaddressedintheTIA/EIA569Bstandard.

ThecablingstandardsdonotaddresstheacGveequipmentintheequipmentroom.

21

EquipmentRackImage:int.fhsu.edu

Page 22: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

ExampleofanEquipmentRoomwiththeterminaGonfieldinthebackground.

22

EquipmentRoom

Image:hpp://www.rdkengineers.com/

Page 23: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

2:TheEquipmentRoom2-EquipmentRoom(ER)TheflooroftheEquipmentRoomisfrequentlyraised.RacksandcabinetsareplacedoverventsoropeninginthefloorColdairissuppliedtotheunderfloorspaceandflowsupthroughtheequipmenttokeepitcoolRaisedfloorsprovidepathwaysforelectrical&communicaGoncabling

23

http://www.aeti.com

http://mantaraltd.files.wordpress.com

Page 24: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

3:TheBackbone3-BackboneCablingConnecGonbetweenallroomsandfaciliGes.Itconsistsof:BackbonecableMainCross-Connect(MC)IntermediateCross-connect(IC)

BackbonecablingrequiresequipmentforterminaGonandcross-connecGng.

24

Page 25: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

3:Backbone(Structure)

25

from

TIA

/EIA

568

C

Page 26: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

TheBackboneLengths3-BackboneCabling(ConGnued)ConfiguredinastartopologyCannotexceed2hierarchicallevelsofcross-connecGonMaximumlengths:UTP: MCtoHC:800m,MCtoIC:500m,ICtoHC:300mMulGmodeFiber: MCtoHC:2000m,MCtoIC:1700m,ICtoHC:300mSinglemodeFiber: MCtoHC:3000m,MCtoIC:2700m,ICtoHC:300m

PatchCords:20m

26

Notethebackbonecablingtypeanddistancesareoftenapplicationdependent.Forinstance,GBEthernetcannotspan800metersonUTP.

Page 27: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

TheTelecommunicaGonsRoom4-TelecommunicaGonsRoom(TR)TransiGonareabetweenthebackboneandhorizontalcabling.CentralareathatcontainstheterminaGonsforcable.

27

TR

Backbone

Horizontal

I/O

I/O

I/O

I/O

I/O

I/O

ATelecommunicationsSpace(TS)isalsopermitted,providedthereisaTRonthesamefloor

Page 28: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

ExampleofaTelecommunicaGonsRoominabuilding.

NotetheconduitonthefloorthatleadstoanotherTRonthefloorbelow.

28

image:www.k-engineers.co

Page 29: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

TheHorizontalCabling5-HorizontalCablingCablesthatextendfromaroomtoanoutlet.

Includes:InformaGonOutlet(IO)Patchcords(atTR)CrossConnecGons(atTR)Cable

29

Horizontal

I/OI/O

I/OI/O

TR

Page 30: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

HorizontalCablingMediaTypes5-HorizontalCabling(conGnued)MediaTypes:UTPScTPMulGmodefiber62.5/125(nolongerrecommendedfornewinstallaGons)MulGmodefiber50/125

Maximumlengths:All90meters,with10meterstotalforpatchcords.Iftheinstalledcableisshorter,longerpatchcordsareallowed,neverexceeding100mtotalhorizontallength.Totalpatchcordlength,however,cannoteverexceed22mforUTP,norestricGononFiber.

30

Page 31: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

HorizontalCabling–UnderfloorSystemUnderfloorsystemforhorizontalcabledistribuGon.

31

Image:hpp://www.gdsengr.com

Page 32: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

HorizontalCablingZoneWiring5-HorizontalCabling(conGnued)

ZoneCablingPermitstheextensionoftheTCtoanareaclosertousers.Especiallyhelpfulinlargeopen-officeareaswherea“homerun”structurewouldbedifficulttomanage.SeveraldefinedapplicaGonsinthestandards/TSBs,including:MuTOAConsolidaGonPointTelecommunicaGonEnclosuresZoneDistribuGonArea

32

Page 33: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

HorizontalCablingMuTOA5-HorizontalCabling: MulG-UserTelecommunicaGonsOutletAssembly(MuTOA)

TelecommunicaGonsoutletcontainingseveraljacks,uptoamax.of12.

Onensurfacemounted,doesnotallowceilingorflooraccessmounGng.TypicallymulGple4prUTPconnecGontotheTRI/OconnecGonstotheMuTOAarepatchcords.ApplicaGonsincludewarehouseareas,officeworkareas,andareaswheretheretendstobemanychangesandequipmentmoves.

33

Page 34: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

ExampleofaMuTOA

34

Images:www.siemon.com

Page 35: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

HorizontalCablingConsolidaGonPoints5-HorizontalCabling:ConsolidaGonPoints(CP)

AconsolidaGonpointisanintermediateconnecGonpointforhorizontalcabling.MaybeinstalledinceilingsorflooraccessmounGng.Mustbeatleast15metersfromtheTR,andislimitedto12connecGons.Typicallyusedwithcableorharnessassembliesforfurniturestructuresthatcontainintegratedraceways.

35

27

Page 36: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

ConsolidaGonPoint

36

TR

Backbone

Horizontal

I/O

I/O

I/O

I/O

I/O

I/O

CP

Backbone

Horizontal

I/O

I/O

I/O

I/O

I/O

I/O

TR Horizontal

AConsolidationPointmaymakesenseinsomeinstallations.Goodexamplesincludewiringopenofficesorclassrooms.

Page 37: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

ExampleofaConsolidaGonPoint

37

Image:http://www.siemon.com

Page 38: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

ConsolidaGonPointExampleofaConsolidaGonBox,using110connecGonsystem.

38

Imagesource:hpp://www.datacenterinfrastructure.org

Page 39: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

HorizontalCabling(Other)5-HorizontalCabling:Otherallowances

TelecommunicaGonsEnclosures(definedinAddendum5)SomeGmesreferredtoasa“collapsedbackbone”,it’sessenGallyaGnyTelecommunicaGonsRoomthatallowsarchitectstodesignbuildingswithfewertelecommunicaGonsrooms.Typicallyusedinenvironmentswhereitiseasiertostaroutclosertotheworkarea(suchasaclassroom).

ZoneDistribuGonArea(ZDA)(definedinTIA/EIA942)Specificallyaddressesunderflooraccesspointswithinacomputerroomordatacenter.

39

31

Page 40: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

TheWorkArea6-WorkArea(WA)TheareabetweentheInformaGonOutlet(IO)andtheuserequipment.Includes:patchcordsspecialiseddevicessuchasbalunsandadaptersUserequipment

Eachworkareamusthaveaminimumof2connecGons:VoiceData

40

Page 41: Mestrado em Engenharia InformáGca e de Computadores · PDF fileANSI/TIA/EIA-568-B.2-10 finalized May 2008, CAT6a ... The physical characterisGcs of this room or facility are defined

PhysicalLayer

StructuredCabling

StructuredCablingStandards

TheTIA/EIA568CStandard

41

SUMMARY