Restaurant & Kitchen MEPThe Architect Guide to Pre-Empting
MEP Engineering Nightmares (Almost! )
Challenges / Restrictions: Issues / Problems:
- Construction Codes
- Roof & Exterior Wall
Space
- Space Requirements for
MEP Equipment
- Reuse of Existing MEP
Systems
- Capacity of Existing
Utilities
- Construction Budgets
- Temperature & Humidity
Out of Control
- Grease Duct
Construction & Routing
- Exhaust Termination
- Grease Interceptor
- Domestic Hot Water
- Cross Connection BFP
- Gas Pressure
- Electrical Capacity
Building Codes / Jurisdictions
- International Building Code
- International Mechanical Code
- International Plumbing Code
- International Fuel Gas Code
- International Energy Conservation Code
- International Fire Code
- National Electrical Code
- Washington Suburban Sanitary Commission (WSSC )
- DC Codes Supplement of 2013
- Local Health Department
- Metropolitan Washington Airport Authority (MWAA)
Temperature & Humidity is Out of Control!
1. Fresh Air: Avoid Oversizing
2. Apply Smart Fresh Air Solutions
3. Design Proper Space Air Balance
Fresh Air SolutionsDifferent Methods for Different Scenarios
i) Blue Jacket Brewery (BJB): 100% outside air system, see next slide
ii) Sugar Shack: High and Low Fresh Air `Intake Settings
Architect: ALine Architecture Alexandria, VA
iii) Dream Café: Energy Recovery System
combined with Exhaust Or Relief Air Fan
Architect: The Lieumann Firm Fairfax Station, VA
Space Air Balance Design Design Case: BJB
Architect:Form Design
Fairfax, VA
Grease Duct Construction & Routing
- Separation Of Grease Duct Systems a separate system for solid fuel cooking
- Construction, 16 gage steel or 18 gage SS.
- Enclosure: One Per Grease Duct
- Clearances: 18” to combustibles, 3” to non-combustibles where not enclosed, 6” to non-combustibles in an enclosure, Exception: use listed fire wrap.
- Slope: 2% for < 75 Ft, 8.3% for > 75 Ft 50’ 12” fall, 75’ 6.25’ fall.
- Cleaning Access
Grease Duct Construction & RoutingBen’s Chili Bowl, H Street
Architect:Form Design
Fairfax, VA
Grease Duct Termination
IMC (VA, MD)
DC (w/o Scrubber)
DC (w/ Scrubber)
Property Line 10’ 10’ 10’
Exterior Walls & Roofs 3’ 3’ 3’
Openings in the Building / Horizontal 10’ 20’ (1) 10’
Or Vertical 3’ 5’ 3’
Adjoining Grade 10’ 15’ 15’
(1) On narrow lots where 20’ distance is not doable the code official is authorized to approve a smaller distance.
CaptiveAire Pollution
Control Unit (PCU)
Grease Duct Termination Use of Scrubber (Grease and Odor Removal)
Architect:GrizForm Design
District of Columbia
Grease InterceptorSizing: WSSC or Not-WSSC
IPC WSSC All The Rest
Section 1003.3.4 and Table 1003.3.4.1
Hydromechanical Grease Interceptor shall be sized in accordance with: ASME 112.14.4 or PDI G101
Flow Based GI vs Volume Based GI
Flow Based GI: sizing based Tables 1003.a & 1003.b
Volume Based GI: sizing based on Table 1003.c
Sizing is based on PDI G101
Grease InterceptorSizing: WSSC Methods
Flow Based GI: • Sizing is based on flow rate• Indoor Installation • Serves particular group of fixtures
Volume Based GI: • Sizing is based on retention time• Outdoor Installation• Serves Building Wide
If DFUs are not known, the GI shall be sized on the maximum DFUs allowed for the pipe size connected (2”=21 DFU, 3”=36 DFU, 4”=180 DFU)
Grease InterceptorSizing: PDI G101 Method
Grease InterceptorPiping: Under The Sink Flow Based GI
Important Note: Where food waste grinder connects to a grease interceptor, a solid interceptor shall be installed between the grinder and the grease interceptor
Domestic Water Heater- Two Temperature System (140F and 110F)
- Recovery Requirements 80 degrees temp. rise for manual dishwashing and 100 degrees when using dishwashing machine
- Gas vs Electric 36 KW electrical water heater requires 100 amps
- Tank vs Tankless Tankless electrical is not feasible Two gas tankless would be required
- Installation, Equipment Weight, 8.33 lbs./gal, 100-gals HWH is 1500 lbs. or more
Cross Connection & Backflow Prevention Guide
Equipment AVB PVB DCV DCV withIntermed. AV
Pre-Rinse Hose with Spray Nozzle X
Hose Bib, Threaded Faucet X
Mechanical Dishwashing Machine X X
Soap or Detergent Dispenser X X
Coffee Urn, Ice Maker X
Carbonated Beverage Dispenser X (1)
Garbage Can Washer X X
(1) Stainless steel or composite, copper is not allowed
AVB: Atmospheric Vacuum BreakerPVB: Pressure Vacuum BreakerDCV: Double Check ValveDCV+AV: Double Check with Intermediate Atmospheric Vent
Electrical & Lighting
- Fifty (50) foot-candles (FC) in food prep, bar, beverage service islands, and areas where knifes, slicers, saws or grinders are used.
- Twenty (20) foot-candles in buffet / salad bar, dishwashing, inside reach-in and under-counter refrigerator equipment, utensil storage, handwashing, toilet rooms, and at handsinks.
- Ten (10) FC in walk-in, dry food storage, dining and all other areas.
- Covered light fixtures with a lens, or shatter-resistant lamps / bulbs are required in food storage, preparation, service, and display areas, and where utensils and equipment are cleaned and stored, including bars and waitstaff service areas.
- IECC, Allowable LPD is 1.4 w/ft2
- Electrical Service Sizing
Questions?