Melink Intelli-Hood Product Specifications

Embed Size (px)

Citation preview

Page 1: Melink Intelli-Hood Product Specifications

®

Revision 130717

Product Specification

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

Melink Corporation

Energy solutions for a brighter tomorrow™

●Specifications are subject to change as updates are completed●

Page 2: Melink Intelli-Hood Product Specifications

A demand control ventilation (DCV) system that only includes a temperature sensor for detecting cooking activity shall not be permitted. Additionally a DCV that includes infrared sensors in the pathway of the smoke without benefit of separate of air purge units and auto-recalibration shall not be permitted. Modulating dampers in the exhaust ducts shall not be permitted.

Melink Corporation

Demand Control

Ventilation For Commercial Kitchens

Features

Saves up to 97% fan energy and 70% conditioned air by EF and MUA fan modulation.

Includes infrared optics and temperature sensors to detect heat and visually monitor cooking activity. Optic sensors mounted at ends of hoods respond in 0.2 seconds and auto-calibration for reliable savings. Automatically starts/stops fans based on heat from cooking appliances or programmable schedules. Provides remote monitoring and control via Ethernet and BACnet communications. ANSI/ASHRAE/IES Standard 90.1 2010 Compliant

Specifications Intelli-Hood controls to include: System Controller, Hood Controller for each hood, Temperature and Optic Sensors for each hood, Touchpad(s), and VFDs for each fan motor.

Temperature Sensors mounted in hoods shall detect the cooking appliances being turned on and operate the fans at a min speed of 30%-50%. Temperature Sensors mounted in exhaust ducts shall modulate the fan speeds above the min based on actual heat load.

Optic Sensors with Air Purge Units mounted on opposite ends of hoods shall immediately increase fan speed to 100% upon the detection of smoke or vapors. As soon as the effluent is removed the fan speeds shall slow back down and modulate according to the actual heat load. Touchpad shall be mounted on hood or convenient location to monitor and control system. Hood Controller to be mounted on top of hoods. System Controller and VFDs to be mounted in hood end-cabinet for new construction and on wall or above ceiling for retrofits. Remote monitoring and control shall be provided by connecting the System Controller to a building automation system via BACnet and/or Internet gateway. Electrical contractor shall be responsible for wiring the high-voltage components including System Controller, VFDs and fan motors. Melink or its Authorized Service Agency shall be responsible for wiring the low-voltage components including Hood Controller, Temperature and Optic Sensors, and Touchpad. Field start-up shall be coordinated by Melink.

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

Energy solutions for a brighter tomorrow™

Page 3: Melink Intelli-Hood Product Specifications

AIR PURGE UNITS

Miniature blowers send air into Optic Sensor housings to prevent smoke and grease from collecting on lenses.

SYSTEM CONTROLLER

Receives input from the Touchpad(s) and Hood Controller(s) to control the outputs for the VFDs.

TEMPERATURE SENSOR

Monitors the exhaust air temperature in the duct and sends a signal to the Hood Controller to vary fan speed in proportion to heat load.

Touchpad

Provides switches for operation of hood lights and fans, bypass, monitoring LEDs and programming.

OPTIC SENSORS

Monitor the presence of smoke and vapors inside the hood. Send a signal to the Hood Controller to increase fan speed during cooking.

HOOD CONTROLLER

Oversees Temperature and Optic Sensors on each hood and sends sensor data to the System Controller via RS-485 communication.

Intelli-Hood System Overview

1

1

3 2

4

4

2

3

5 6

VFDs

Variable Frequency Drives receive signals from the Hood Controller to control the speed of the fans based on heat and smoke load.

7

6

7

5

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

Page 4: Melink Intelli-Hood Product Specifications

System Controller Functional Description The System Controller controls the lights and fans for up to 39 Hood Controllers. It is typically mounted above the ceiling and communicates between the hood sensors and VFDs via low-voltage Hood Network Cables. It is also connected to a Touchpad mounted on the front face of one of the hoods for easy user interface. Control Specifications Painted enclosure for durable construction and smooth finish Communicates to Hood Controller(s), Touchpad(s), Temp Sensor(s), and Optic Sensor(s)

via proprietary RS-485 Protocol ● May communicate with up to (39) Hood Controllers, (10) Touchpads, (10)

Aux Touchpads, (10) Aux Power Supplies, and (10) Aux Light Controllers. Some limitations apply.

Communicates to Variable Frequency Drives via Modbus Protocol

● Refer to VFD submittal sheet for more information ● Supports up to 64 VFDs

Programmable I/0: (3) Digital Inputs, (4) Digital Outputs, (1) Analog Output, (1) Analog Input

Adjustable Temperature vs. Fan Speed Curve

Automatic On/Off based on Hood Temperature or Clock Schedule

Versatile programming parameters for setting up exhaust and supply airflow control

Removable Memory stores setup files and operational history data

BACnet over TCP/IP Interface

Internet-based Service Application for programming and monitoring

Automatic notification of faults/alarms via BACnet and email

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

Page 5: Melink Intelli-Hood Product Specifications

System Controller Electrical Specifications

Input Voltage : 120 VAC to 220 VAC

Frequency : 50 Hz to 60 Hz +/- 3%

Power Consumption : 170 W

Ambient Temperature : 5 to 40°C, 32 to 120°F

Line Voltage Output Power Capacity: 15A General Purpose Load, Fused 6A Tungsten Load

Low Voltage plenum-rated, shielded cables to VFD(s), Optic Sensors, APU(s) and Temperature Sensors

12.5”

10”

12” 6”

Front View Top View

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

Page 6: Melink Intelli-Hood Product Specifications

Hood Controller Functional Description The Hood Controller oversees Temperature and Optic Sensors on each kitchen hood

and sends the sensor data to the System Controller via RS-485 communication. Mechanical Specifications Galvanized Steel Enclosure, 7”x7”, 2.1” tall Temperature Rating: 0 to 49°C, 32 to 120°F Steel Beam Clamps for installation on hoods or other mechanical structures above hood. (4) 3/4” conduit holes for connections of Intelli-Hood Hood Network cables (4) 3/4” conduit knockouts for connections of Intelli-Hood Hood Network cables Electrical Specifications

Low Voltage: 24VDC from the Hood Network, via Hood Network Cables Power Consumption: A fully loaded Hood Controller with four temperature sensors, two air purge units, and one set of optic sensors consumes approximately 15W.

7.0”

7.0”

2.1”

3.3”

Front View

Side View

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

Page 7: Melink Intelli-Hood Product Specifications

Touchpad Functional Description The Touchpad is the human interface point of the Intelli-Hood system. FANS and

LIGHTS switches provide interface points of kitchen staff to control the hoods. A full-color screen displays the status of the fans and sensors. Setup switches provide a means of programming the system.

A System Controller may have up to ten (10) Touchpads connected to it. Programmable

parameters allow the Setup Technician to dictate Touchpad and Hood relationships. Every System Controller is required to have at least one (1) Touchpad device connected to it to allow for human interface to diagnostics and programming parameters.

General Specifications

Full Color Screen: 2.5” diagonal, QVGA resolution, displays operating status and programming menus Switches: FANS: Changes system from Energy Saving Mode (fans running) to

Standby Mode (fans off) LIGHTS: Changes state of line voltage relays which may be used to

control Hood Lights circuits. Soft Keys: Allow user to boost fan speeds to full speed, access

programming menus, access diagnostic and help screens Stainless steel cover plate (304L) for durable construction and smooth finish

Synthetic membrane keypad for water protection

Temperature Rating: 5 to 40°C, 41 to 104°F Low voltage: 24VDC from the Hood Network, via Hood Network Cable

5.3”

5.25”

3.7”

2.7”

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

1.1”

Page 8: Melink Intelli-Hood Product Specifications

Temperature Sensors

Functional Description

A three-wire platinum resistive temperature device (RTD) sensor encased in a stainless steel tube. Threaded housing is designed to be assembled into UL-listed “Quick-Seal” exhaust duct fittings. Temperature Sensors are wired to the Hood Controllers via Hood Network Cables.

Standard sensors are installed in exhaust ducts, while Canopy sensors are installed in the hood canopy to provide enhanced automatic on/off functionality.

General Specifications

Stainless Steel Probe: 0.25” outside diameter, 2 lengths available (Standard and Canopy)

Three-Wire Configuration

Brass Body, ½” external pipe thread

8 pin, RJ-45 connector

Temperature Rating: 0 to 535°C, 32 to 1000°F

RTD Rating: 100 Ohms with 0.385 platinum coefficient

Electrical Connection: Hood Network Cable

1.9” 4.4”

Recommended duct cut-out: 1.125” diameter.

Standard Canopy

1.9” 1.1”

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

Page 9: Melink Intelli-Hood Product Specifications

Optic Sensors Functional Description

The Optic Sensors consist of an Emitter and a Receiver which are installed on opposite ends of the kitchen hood. An infrared beam spans the length of the hood to detect any smoke or other vapors generated by the cooking appliances. Upon detection, a signal is sent to the System Controller which automatically ramps the associated fan(s) to 100% speed until the effluent is evacuated. Optic Sensors are wired to the Hood Controllers via Hood Network Cables.

General Specifications Stainless Steel Housing for durable construction and smooth finish Optic Span: 3 to 40 feet (automatic gain adjustment for distance) Auto-calibration: Every day at start-up or 24 hours Conformal-coated circuit boards and water-tight cable connectors at sensor PCB connections Temperature Rating: 0 to 85°C, 32 to 185°F Response Time: 0.2 seconds Low Voltage: 12VDC from the Hood Controller, via Hood Network Cable Ambient temperature: Max 105F purge air

0

0

5”

3” 4”

FRONT COVER BASE Opening for beam

Clean air

Lens

Clean air admission

Plug & play receptacle

Mounting Posts

SIDE

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

Page 10: Melink Intelli-Hood Product Specifications

Air Purge Unit Functional Description

The Air Purge Unit (APU) consists of a miniature blower in a steel box, mounted on each end of the hood above the optic sensors. The purpose of the APU is to pressurize the optic sensors housings with clean air to prevent grease vapors from fouling the lens. The blowing air also cools the optic circuit boards. The stainless steel conduit pipe that connects the APU and Optic Sensor provides a path for the air flow and optic sensor control cable.

General Specifications

Enclosure constructed of 18 gauge galvanized steel

Adjustable support leg

Blower fan bearings permanently lubricated

Temperature Rating: 0 to 51°C, 0 to 125°F

Low Voltage: 12 VDC from the Hood Controller, via Hood Network Cable

Power Consumption: Approximately 7W

2.5”

4.5” 9.8”

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

Page 11: Melink Intelli-Hood Product Specifications

Variable Frequency Drive

Functional Description

The electronic motor starter is a variable frequency drive (VFD) which is used to control the exhaust and supply fan motors. The VFD modulates the speed of the fan motors by varying the output voltage and frequency based on a serial RS-485 signal received from the System Controller. The VFD also sends a feedback signal to the System Controller in order for the Touchpad to display the actual speed of the motor.

Mechanical Specifications

NEMA 1 Enclosure.

Soft-start capability.

Digital keypad displays output frequency, current, voltage, and allows programming for field modifications.

Protective Functions: motor overload, overheating, overcurrent, overvoltage, output shorts, etc.

High and low frequency limiters.

Adjustable torque boost.

Daisy-chained via Hood Network Cables

Electrical Specifications

Input Voltage : 200-240 V/1 AC, 200-230 V/3 AC, 380-480 V/3

AC, or 460-600 V/3 AC

Input Frequency : 50 Hz to 60 Hz +/- 3%

Output Voltage : 80-240 V/ 3 AC or 160-480 V/ 3 AC

Ambient Temperature : -10 to 50°C, 14 to 122°F

Humidity : 20%-95% relative humidity (non-condensing)

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

Page 12: Melink Intelli-Hood Product Specifications

Hood Network Cables

Functional Description

Custom 8-conductor cables connect the various components of Intelli-Hood. The cable is shielded, plenum rated, UL Type CMP OR CL3P FT-6. Per NFPA 70, the cable is allowed to be run in horizontal plenums and vertical chases without conduit when carrying current-limited low-voltage power and signals as it does with the Intelli-Hood.

Construction Specifications

UL TYPE OR STYLE: CMP OR CL3P FT-6 PRIMARY INSULATION TYPE: SGPVC JACKET THICKNESS: .015" JACKET COLOR: SPECIAL BLUE JACKET MATERIAL: CMP NOMINAL O.D.: 0.190" TEMP. RATING: 60C CONDUCTOR/PAIR COUNT: 4 PAIRS INSULATION THICKNESS: 0.007" GAUGE & STRANDING: 24 AWG, 7/32 BC VOLTAGE RATING: 300V SHIELD: FFE ALUMINUM POLYESTER DRAIN WIRE: 24 AWG, 7/32 TC

Stock Pre-Terminated Lengths

2CB3-001: 1’ (0.3m) 2CB3-005: 5’ (1.5m) 2CB3-015: 15 (4.5m) 2CB3-030: 30’ (9.1m)

2CB3-050: 50’ (15.2m) 2CB3-075: 75’ (22.8m) 2CB3-100: 100’ (30.5m) 2CB3-200: 200’ (61m)

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

Page 13: Melink Intelli-Hood Product Specifications

Aux Touchpad Functional Description

The Aux Touchpad is an additional human interface point of the Intelli-Hood system. FANS, LIGHTS, and 100% switches provide interface points of kitchen staff to control the hoods. Indicator LEDs provide status for the FANS, LIGHTS, 100%, and Faults.

A System Controller may have up to ten (10) Aux Touchpads connected to it. Programmable parameters allow the Setup Technician to dictate Aux Touchpad and Hood relationships.

General Specifications

FANS Switch: Changes associated Hoods between Active Mode (fans running) to Standby Mode (fans off)

LIGHTS Switch: Changes state of associated line voltage relays which may be used to control Hood Lights circuits.

100% Switch: Allows user to temporarily boost fan speeds to full speed on associated Hoods.

Stainless steel cover plate (304L) for durable construction and smooth finish

Synthetic overlay for water protection

Low Voltage: 24VDC from the Hood Network, via Hood Network Cable

4.55”

4.55”

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

5.3” 3.7”

2.7”

1.1”

Page 14: Melink Intelli-Hood Product Specifications

Aux Power Supply

Functional Description

The Aux Power Supply (APS) may be used for large installations additional power is needed to operate Hood Controllers, Optic Sensors, and Touchpads. Since each Hood Network Port is power-limited, depending on the quantity of devices in a series line and the length of cable between devices, Aux Power Supply Device(s) may be needed to provide power to the Hood Network. A System Controller may have up to 10 Aux Power Supplies connected to it.

Electrical Specifications

Input Voltage : 120 VAC to 220 VAC

Frequency : 50 Hz to 60 Hz +/- 3%

Output Voltage: 24VDC

Frequency : 50 Hz to 60 Hz +/- 3%

Power Consumption : 60W (max)

Ambient Temperature : 5 to 40°C, 41 to 104°F Hood Network Connection: 24VDC from the Hood Network, via Hood

Network Cable

7.0”

7.0”

Front View

Side View

2.1”

3.3”

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●

Page 15: Melink Intelli-Hood Product Specifications

Aux Lighting Controller

Functional Description

The Aux Light Controller (ALC) may be used for large installations where there is a need to control multiple light circuits. A System Controller may have up to 10 Aux Light Controllers connected to it. Relationships among the ALC and Touchpads are programmable via field editable parameters. A System Controller may have up to 10 Aux Lighting Controllers connected to it.

Electrical Specifications

Input Voltage : 120 VAC to 220 VAC

Frequency : 50 Hz to 60 Hz +/- 3%

Power Consumption : 5W (not including lights)

Ambient Temperature : 5 to 40°C, 41 to 104°F

Hood Lights (voltage matches input): 120 VAC to 220 VAC (15A max)

Line Voltage Output Power Capacity: 15A General Purpose Load, Fused 6A Tungsten Load

7.0”

7.0”

Front View

Side View

melinkcorp.com 5140 River Valley Road Milford, OH 45150 USA 513.965.7300

●Specifications are subject to change as updates are completed●