33
Medium and Low Voltage Grounding Methods THE ASSET COMPANY

Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

Embed Size (px)

Citation preview

Page 1: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

Medium and Low Voltage Grounding Methods

THE ASSET COMPANY

Page 2: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Establish a voltage relationship between the system neutral and ground.

•Overvoltage protection for system component insulation•Controlled single-phase-to-ground fault current magnitude

Establish a voltage relationship between energized phase conductors and ground.

System Grounding

Page 3: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Establish a consistent reference plane for all system components.

•Personnel safety•Optimum single-line-to-ground fault current distribution•Safe conduction of lightning discharge currents•a.k.a. bonding

Equipment Grounding

Page 4: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

What’s the big deal?

Cable Sheath

Neutral Wire

Water Pipes

Building Steel

lg

Earth Potential Gradients – a Personnel Grounding Safety IssueHuman Physiological Response:

1 ma – threshold of sensation6-9 ma “let go” currents9-25 ma – muscular contraction60-100 ma – ventricular fibrillation

Body resistance: 5000 ohms or higher

Perceptable gradient voltage: 50 volts & above

Harmful gradients: 375 volts and above

Controlling factors

o Magnitude of Potential Gradients- magnitude of ground fault current phase-neutral voltage complexity of return patho Duration of Potential Gradients- protective device settings fuse, relay, & breaker operation

Z

Page 5: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

What’s the big deal?

Cable Sheath

Neutral Wire

Water Pipes

Building Steel

Ig

Earth Potential Gradients – Equipment and Insulation SurvivabilityDistribution of Ig:

Kaufmann’s work showed that 90-95% of the fault current will return through the cable sheath and/or neutral wire

Ig = IC + IN + IP + IS

Example: Ig = 20000 AIS = 0.05 x 20000 = 1000 AFor Vs > 100 V, Z > 0.1 Ohms

Power cable- ground shield at both ends to help equalize electric potential along cable length, but be mindful of magnitude and duration

Communication cable- do not ground communication cable at both ends to avoid circulating current that would act as noise

IC

IN

IP

IS

Z

Page 6: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

What’s the big deal?

Cable Sheath

Neutral Wire

Water Pipes

Building Steel

Ig

Really Only a Large Issue at System Voltages Higher than 1000 VACConclusions:

Ineffective grounding at any voltage sets the stage for personnel injury or death.

The likelihood of these “distracting gradients” is insignificant at low voltages

Low voltage systems can be solidly grounded without undue concern for “distracting” potential gradients.

Ineffective grounding at higher voltages can set the stage for potential gradient shocks which are severe enough to distract personnel in the workspaceIC

IN

IP

IS

Z

Page 7: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Cable Sheath

Neutral Wire

Water Pipes

Building Steel

IgIneffective grounding at any voltage sets the stage for personnel injury or death.

The likelihood of these “distracting gradients” is insignificant at low voltages

Low voltage systems can be solidly grounded without undue concern for “distracting” potential gradients.

Effective grounding at higher voltages can set the stage for potential gradient shocks which are severe enough to distract personnel in the workspaceIC

IN

IP

IS

Z

Working Definitions (Inexact):

System Neutral Ground- an intentional electrical connection between the neutral of the power system and groundGrounded System- a system in which one conductor, usually the neutral, is intentionally connected to ground.Ungrounded System- a system in which none of the electrical conductors is intentionally connected to ground

Solidly Grounded Neutral- a direct electrical connection between the neutral and ground with no added impedanceResistance Grounded Neutral- an electrical connection in which a resistor is inserted between neutral and groundReactance Grounded Neutral- an electrical connection in which an inductive reactance is inserted between neutral and groundCapacitance Grounded Neutral- an electrical connection in which a capacitor is inserted between neutral and ground

Note: There is an inherent distributed capacitance between each conductor and ground. Hence, an “ungrounded system” is really capacitively grounded

ss s

Page 8: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Exact Definitions (applies to surge arrester applications)

Effective Grounding- grounding such that the steady-state operating voltage on the healthy phases of the power system during a single-line-to-ground fault will not exceed 140% of the open-circuit line-to-neutral RMS voltage.

and

Both must be met

Page 9: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

- Industrial Power Systems Handbook General Electric Company ©

Donald Beeman, editor

“Since power sources are fewer in number than loads and are less likely to be disconnected, they are preferred as grounding points.”

Page 10: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

Forms of Neutral

Grounding

-G Fault Magnitude

Transient Over-

voltages

Arrester Applications

(% of VL-L)

System Protection Selectivity

Comments

Ungrounded ~ 0 Very high 100% None Not Recommended

Solidly I3 < 140% 80% Generally Good

Common at high voltages and low voltages

Low Resistance

100 – 1200 A Not Excessive 100% Generally Good

Common at medium voltages

High Resistance

2 – 10 A Not Excessive 100% Requires Special

Equipment

Alarm application for continuity must trip >5kV

Reactive < I3> 0.125 I3

Not Excessive 100% Generally Good

Special case – rarely need

Resonant ~ 0 Not Excessive 100% Special Treatment

Special case – very rarely need

Capacitive I3 High 100% Generally Good

Special case – very rarely need

Medium Voltage System Grounding

The ASSET Company

August 20, 2010

Page 11: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

or or

Ungrounded Solidly Grounded

The ASSET Company

August 20, 2010

System Grounding Options

Page 12: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Solidly Grounded Generator

Page 13: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

Low Resistance

High

Reactance

HighResistance Ground

Low

XL R

The ASSET Company

August 20, 2010

Grounding Options

Page 14: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

A

B

C

A

B

C

Resonant Neutral Grounding

Capacitive Neutral Grounding

The ASSET Company

August 20, 2010

Two grounding methods you will probably never see.Let’s Dispense with

Page 15: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Low Resistance Grounding Details

R

AB

C400 A10 sec

VR=0Effectively Grounded

R

AB

C400 A10 sec

VR = 7970 VoltsIf V = IR, and you wish to limitI to 400 Amps, 7970 = 400 RR = 19.9 Resistor must be insulated at One terminal for 8000 V and to pass 400 Amps for 10 seconds without damage

7970

B

C

7970

7970

7970

A

B

C

7970

7970

7970

A

B

C VR

7970

7970

7970

A

B

C

Page 16: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Standard

Ratings

For Low Resistance

Resistors

ANG80-4 13800 8000 400 20 46 60 76 900

Page 17: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

IBM Substation

Neutral Grounding Resistor

Page 18: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Impedance Transformer

Effectively grounded under

normal conditions

High Resistance Grounding

7970:240 V Grounding

Transformer

Let’s limit ground fault current to 10 amps

Page 19: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

If IG is 10 amps, then the power through the transformer is:

Power in the secondary is the same:

Transformer spec : 75 kVA or 100 kVA 7970 : 120 V

Resistor spec: 0.723 Rated for 240 VAC operation for 10 seconds

IG IG

IR

Page 20: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

System Sources that are Ungrounded?What about…

- Low voltage or 5 kV process plant distribution- Delta winding transformers- Generators

Page 21: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Neutral Deriving TransformersScott-T Connection

- Small, lightweight- Economical

- Off-the-shelf in common ratings- Not practical for unusual applications

(i.e. voltage, frequency, current levels)- Limited to Low-R applications

Y - Transformer

- Standard transformer- Applications are readily

field-designed- Can be used for any grounding mode

- Grounding resistor can be inside deltaif single phase units are used in Hi-R scheme

- Offers option for redundant backup protection

Zig-Zag

Potential Transformers

-Custom designed-Can fit any application-Can be designed to provide full reactive limitation with no external impedance-Can be used for effectively grounded system

-Usually required for metering-Economical -Thermal ratings suitable for -highly restricted schemes only-Application may not provide desired limitation of transient overvoltages because the grounded wye winding is high impedance

H1,1

H2, 2

H3,3

X2

X1

X3

X2

X1

X3

H1,1

H2, 2

H3,3

1

3

2

X2

X3H1

X1

H2

12

H3

X2

3

Page 22: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

This wye-delta transformer connection doesn’t limit fault current, except the winding impedance of the grounding transformer.

The ASSET Company

August 20, 2010

13800 V

13800 V

Page 23: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

Low resistance ground fault limiting – same type calculations as before.

The ASSET Company

August 20, 2010

13800 V

13800 V

Page 24: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

LegendAM- AmmeterCPB- Control Power BreakerCR- Main ContactorCT- Current TransformerHR- Horn RelayHRX- Auxiliary RelayMR- Meter RelayPR- Pulsing RelayPT- Potential TransformerR3- Fault Time DelayR4- Pulsing AdjustmentTR- Timing RelayUV- Undervoltage

The ASSET Company

August 20, 2010

Schematic DiagramHigh Resistance Grounding

Page 25: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

Placing a Resistor in the transformer secondary will limit the primary ground fault current.

The ASSET Company

August 20, 2010

With a Secondary Resistor…Neutral Deriving Transformer

Page 26: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

H0

H3

H2

A C

B

H1

R= 0.106X1

X6

X4

X5

X3

X2

Transformer ratio is 23900 GRY – 120 V delta. This is 13800 V to ground on the primary, and is the voltage on each winding.

The secondary voltage of 120 V is the voltage acrosseach winding.

Page 27: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Under non-faulted balanced system conditions, the voltage at the corner delta = 0

13800 13800

1380

0

V = 0

120

120

120

Page 28: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

B

When one phase suffers a bolted fault, a phase for instance, the voltage vectors change:

1380

0

13800

C

v

v

208 V

The resulting voltage at the delta corner rises to 208 V. For a 0.106 Resistor with 208 V across it, the current through it is

1963 Amps.(The resistor is rated 208 V, 1960 Amps, 10 sec.)

Page 29: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

120 VB

7970

7970

C

v

v

The resulting voltage across the resistor is 120 V, and the 0.106 resistor has 1,132 Amps through it.

v

v

13800 V

69.3 V

69.3

V

Ours is actually a 13800 V L-L system:

Page 30: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

120 VB

7970

7970

C

v

v

v

v

13800 V

69.3 V

69.3

V

The resulting voltage across the resistor is 120 V, and the 0.106 resistor has 1,332 Amps through it.

This system is a high impedance grounding system that limits current to 10 Amps.

Page 31: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The relay settings for the job were: 300 Amp pickup on the secondary side, which equates to 2.6 Amp

primary. 50 V setting on the 59 G relay is equal to

A voltage element, looking at voltage across the resistor, and a current element, looking at current through the resistor, are used

in conjunction for redundant ground fault detection.

Voltage element is much more sensitive than current element

The ASSET Company

August 20, 2010

Page 32: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Typical Power Plant Grounding

Captive Transformer

High Voltage Bus

Generator Breaker•Normal central station practice – no

generator breaker•GSU neutral not required on generator side

• Saves cost of startup transformer• Availability of suitable breakers• GSU neutral grounding required

on generator side

Page 33: Medium and Low Voltage Grounding Methods. The ASSET Company August 20, 2010 Establish a voltage relationship between the system neutral and ground. Overvoltage

The ASSET Company

August 20, 2010

Low Voltage(< 1000 volts)

Medium Voltage(through 15kV)

High Voltage(> 15kV)

1. Solid Grounding2. High Resistance

1. Low resistance grounding2. High resistance grounding3. Effective grounding

3. Effective grounding(at the source)

System Grounding Summary

Voltage Level Grounding Preferences