Upload
tushar-karanwal-eit
View
183
Download
14
Embed Size (px)
Citation preview
FACULTY OF ENGINEERING AND APPLIED SCIENCE
MECE4450U
Energy and Economic Analysis of Ceiling Fans
for an Office Building in Turkey
GROUP PROJECT REPORT
Course Instructor: Dr. Marc Rosen
Teaching Assistant: Satyam Panchal
Project Report Submitted On: April 4, 2016
# Last Name First Name ID Signature
1 Bower Lowell 100500898
2 Karanwal Tushar 100481186
3 Owais Syed 100506689
Remarks:
If one in group cheats, the entire group will be responsible for it. Plagiarism and dishonesty will not be tolerated. The group member(s), who donβt sign the report, will be considered βnot contributedβ and given βzeroβ for
the report. This cover sheet should be fully completed.
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
1
Table of Contents List of Figures ................................................................................................................................. 2
1.0 Introduction ............................................................................................................................... 3
1.1 Problem Statement ................................................................................................................ 3
1.2 Project Objectives ................................................................................................................. 3
2.0 Case Study ................................................................................................................................ 4
3.0 Proposed System ....................................................................................................................... 5
4.0 System Analysis ........................................................................................................................ 6
4.1 Sensible Cooling ................................................................................................................... 6
4.2 Latent Cooling ...................................................................................................................... 7
4.3 Building Energy Calculations ............................................................................................... 7
4.4 Economic Analysis ............................................................................................................... 8
5.0 Conclusion ................................................................................................................................ 9
6.0 Nomenclature .......................................................................................................................... 10
7.0 Appendix ................................................................................................................................. 11
7.1 Project Assumptions ........................................................................................................... 11
7.2 Sample Calculations............................................................................................................ 12
7.3 EES Code ............................................................................................................................ 16
References ..................................................................................................................................... 17
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
2
List of Figures
Figure 1: Initial total hourly cooling load for building ................................................................... 4
Figure 2: Proposed fan positions..................................................................................................... 5
Figure 3: Emerson CF705 fan [10] ................................................................................................. 5
Figure 4: Cylinder in cross flow [4] ................................................................................................ 6
Figure 5: Evaporation of water from a body of water [8] ............................................................... 7
Figure 6: Reduction in total cooling load for three rooms .............................................................. 8
Figure 7: C and m constants for cylinder in cross flow [10] ........................................................ 13
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
3
1.0 Introduction
This report will investigate whether the cooling load for a building can be mitigated through the
addition of ceiling fans. By reducing the cooling load for a building there will be corresponding
economic benefits and potentially a reduction in environmental harm depending on the source of
energy for the cooling system. In order to determine if there is an economic benefit, the initial cost,
operating costs, and payback period must be considered.
Fans can be used to reduce cooling load because the increased air movement reduces the effective
temperature the occupants would experience which allows for a lower set point for the room
thermostat [1]. This is due to the convection coefficient (βΜ ) increasing as the wind velocity inside
the room increases which results in a larger sensible heat transfer rate (οΏ½ΜοΏ½π ). There is also an increase
in latent heat transfer rate (οΏ½ΜοΏ½π) as the increased air movement results in greater evaporative cooling.
This report proposes to reduce the overall cooling load for a three story office building located in
Adana, Turkey by installing three ceiling fans. This report will begin by describing the problem
statement and project objectives defined by the team. Section 2.0 will describe the relevant
parameters of the sample building for the report. In Section 3.0 the proposed system will be
detailed including fan type and placement. Section 4.0 will analyze the proposed system by
estimated the reduction in sensible and latent cooling and the effect on building energy use. An
economic analysis will also be carried out to quantify the benefit of the proposed system. The final
section will conclude on the proposed design, looking at the advantages and disadvantages as well
as suggesting possible improvements.
1.1 Problem Statement
Design and analyze a system that incorporates three ceiling fans into an actual building. Reduction
in cooling loads and costs are to be considered.
1.2 Project Objectives
The following project objectives highlight the important parameters that must be met by the
proposed system and the final report:
Energy characterization of existing building
Proposed fan type and layout
Reduction in cooling load
Reduction in economic costs (consider initial and operating costs)
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
4
2.0 Case Study
The sample building that will be considered in this report is a three story office building located in
Adana, Turkey (36Β° 59β latitude, 35Β° 18β longitude, 20 m altitude) which is in the Mediterranean
portion of the country. This building was analyzed by Aktacir, BΓΌyΓΌkalaca, and Yilmaz for a case
study on the effects of thermal insulation on cooling loads [2]. The building has 27 offices, with
two workers per office, and is occupied between the hours of 9:00 to 20:00.
This report will use the insulation and cooling load parameters for the Building A-type insulation
with 3 m high walls, and an overall thermal resistance (ππ) for the wall, roof, and floor of 0.403
W/m2Β·K, 0.349 W/m2Β·K, and 0.07 W/m2Β·K respectively. The outdoor air conditions were for a dry
bulb temperature (ππππ) of 38 C and wet bulb temperature (πππ€π) of 26 C. The indoor air conditions
were set to an indoor dry bulb temperature (ππππ) of 26 C with a relative humidity (π) of 50%.
The total hourly cooling load for the building (οΏ½ΜοΏ½ππππ,π‘ππ‘) has been characterized in Figure 1 which
is assumed to apply to the entire cooling season of 184 days between May and October. The
sensible heat factor (ππ»πΉ) for the building was 0.97 with an outdoor air requirement (οΏ½ΜοΏ½π) of 1596
m3/h. The peak cooling load of 94 kW occurs at 13:00 with the minimum cooling load of 10 kW
occurring at 5:00.
0
20000
40000
60000
80000
100000
120000
0 4 8 12 16 20 24
Tota
l Co
olin
g Lo
ad (
W)
Time of Day (hours)
Figure 1: Initial total hourly cooling load for building
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
5
3.0 Proposed System
Three of the offices on the first floor of the office building will each have a fan installed centrally;
one each for zone 1 (ZO1), zone 2 (ZO2), and zone 3 (ZO3) as can be seen in Figure 2. The fans
will be operated at full capacity during the hours that the office is occupied (9:00 to 20:00). It is
imagined that these fans are installed as a pilot project before installing fans for the entire building.
The fan chosen in this report is the Emerson CF705 (see Figure 3). This fan has a total diameter
of 52β with an input power of 52.2 W and an air flow rate of 3110 cfm [1]. This fan was chosen
due to its low input energy since some of this energy will be transferred to the room as heat
counteracting the desired cooling effect.
Figure 2: Proposed fan positions
Figure 3: Emerson CF705 fan [10]
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
6
4.0 System Analysis
This section will begin by analyzing the sensible/latent cooling from the fan and the effect on the
building energy use and conclude with an economic analysis. Sample calculations, project
assumptions, and the EES code use for calculations are included in Section 7.0 Appendix.
4.1 Sensible Cooling
To approximate the sensible cooling that an occupant would feel in a room with a fan, an external
flow heat transfer model was used. Wind flowing over a human being was modeled as cross
flowing air over an upright cylinder. An example of this is shown in the figure below.
The person was assumed to have a surface area of 1.8 m2 [3] with 30% of the skin exposed to the
wind to approximate clothes covering the skin. All of the ambient conditions of the conditioned
space are used in this model and the internal temperature of the human was assumed constant at a
temperature of 37.5 C.
Using the model described above, a Nusselt number was found which enabled a convection
coefficient to also be calculated. In this way the sensible heat loss (οΏ½ΜοΏ½π ) the human would experience
in this wind was found to be approximately 312 W. This heat loss was assumed to be strictly
sensible, as the percentage of this heat which would promote latent cooling is difficult to
approximate.
An additional assumption was that this 312 W of additional cooling would reduce the cooling load
for the room by the same amount. Due to two occupants being present in each room, the total
cooling load reduction would then be 624 W per room.
Figure 4: Cylinder in cross flow [4]
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
7
4.2 Latent Cooling
Obtaining a model that would provide an accurate estimation of the latent cooling effects due to
the evaporation of sweat off of the human skin was a challenging task. From research, the simplest
procedure found was to calculate the rate of evaporation by using an empirical method determining
rate of evaporation from a body of water due to air flow across its surface. It was assumed that the
human has a coating of sweat across the exposed skin, and when the sweat evaporates it is
replenished immediately.
The assumptions of exposed skin and surface area of the human model from the sensible cooling
section are maintained for this portion. Modifications to the aforementioned empirical method
were made accordingly. After setting these parameters and constraints, it was determined that the
latent cooling experienced by 2 people in a room due to the installation of a fan is 382.2 W.
4.3 Building Energy Calculations
The additional sensible and latent cooling effects of the fan have been calculated in the previous
sections and they can now be removed from the total cooling load for the three proposed rooms.
The total cooling load for the three rooms (οΏ½ΜοΏ½ππππ) was estimated by dividing the building cooling
load by the total number of offices (27 offices in the building). This is not entirely accurate since
it does not account for any variation in cooling load for offices on different floors or that are facing
different directions. For instance offices that are on a south-facing wall will receive more solar
radiation over the course of the day and require a larger cooling load [3].
The total reduction in cooling load due to the fan was calculated by subtracting the additional
sensible and latent cooling of 1006.2 W and adding the additional electrical consumption of 50.2
W from the fan. The net result was therefore 956 W per room for a total of 2868 W for all three
rooms. This reduction was only applied during the occupied hours of 9:00 to 20:00 since no benefit
would be seen if the office workers were not present.
Figure 5: Evaporation of water from a body of water [8]
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
8
As can be seen in Figure 6, the cooling load is displaced during the times of fan operation and
most importantly during the times of peak energy rates. By adding the three fans, the daily
reduction in cooling load is estimated to be 31.55 kW per day.
4.4 Economic Analysis
The fundamental reasoning behind implementing fans in this building was to decrease the cooling
load on the existing HVAC system and reduce costs. This section will consider the daily and annual
cost benefit of installing the fans as well as the payback period. All calculations were performed
in US dollars.
From the previous sections the reduction in cooling load for the three rooms was estimated at 2.868
kW over the 11 hour work day. Using an estimated cost of electricity in Turkey of 0.142 USD/kWh
[4], the total savings per day is $4.48. For 258 working days in Turkey in 2016 [5], the cost
saved per annum from the implementation of the three fans is $1157. The initial cost to install
the fans was estimated at $1797, given a fan cost of $199 [6] and an installation cost of $400 per
fan [7]. Using the estimated annual savings and cost to install the fan, the payback period for the
project is approximately 1.55 years.
0
2000
4000
6000
8000
10000
12000
0 4 8 12 16 20 24
Tota
l Co
olin
g Lo
ad (
W)
Time of Day (hours)
Without Fan
With Fan
Figure 6: Reduction in total cooling load for three rooms
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
9
5.0 Conclusion
This report has examined the energy and economic benefits of ceiling fans from a heat transfer
perspective. Additional sensible and latent cooling has resulted from the resulting increased air
movement which should reduce the cooling load on the HVAC system for the building. Ceiling
fans achieve this result by increasing the air flow around occupants resulting in greater sensible
heat transfer rates through convection and greater latent heat transfer rates through evaporative
cooling [8]. In this way the set point temperature for the cooling system can be increased without
sacrificing the comfort of the occupants. In the proposed system the fans are only run when the
office is occupied from 9:00 to 20:00 since the benefit results from occupants feeling comfortable
at higher indoor air temperatures.
It was initially assumed that the latent cooling effect would dominate, however latent cooling (οΏ½ΜοΏ½π)
was estimated at 382 W per room while sensible cooling (οΏ½ΜοΏ½π ) was estimated at 624 W. It is unclear
why οΏ½ΜοΏ½π is approximately double οΏ½ΜοΏ½π since existing literature estimate that latent cooling should be
larger. In a study on livestock, Gebremedhin and Wu estimate latent and sensible heat loss at 182
W and 159 W respectively for an air velocity of 0.5 m/s under conditions of 30 C dry bulb
temperature and 20% relative humidity [9]. However when velocity is increased to 2.0 m/s the
latent heat loss increases to 368 W whereas the convective heat loss remains approximately
constant 149 W. The discrepancy in the proposed heat transfer models is likely due to simplifying
assumptions.
The decrease in cooling load for three rooms was estimated at 2.868 kW for a daily reduction of
31.55 kW which considered the additional electricity consumption of the fans. The savings from
installing the system was estimated at $4.48 per day and $1157 per year for a payback period of
1.55 years.
It was assumed that the fans would be operated at full operating speed during operating hours,
however a greater reduction in energy could result from more intelligent control. For instance a
motion sensor could be used to turn off the fans when the rooms were unoccupied for a certain
period. Depending on the usage of the room the additional cost of installing this system may be
justified. A major assumption that may not be justified was that the additional cooling afforded by
the fans would directly translate to a reduction in cooling load on the HVAC system in the office.
A more accurate model would consider the effective temperature seen by the occupants and relate
it to the change in set point of the cooling system. Additionally since only three of the rooms in
the building will have fans installed, there would only be a reduction in cooling load if each of the
rooms had their own thermostat. Although the proposed heat transfer models certainly have
inaccuracies, it has been demonstrated that there is likely some beneficial reduction in cooling load
through installation of ceiling fans.
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
10
6.0 Nomenclature
General
π΄ - Exposed surface area [m2]
πΆ - Factor of human body exposed
π - Diameter [m]
π - Evaporation rate [kgmoisture/s]
β - Height [m]
βΜ - Average convection coefficient [W/m2Β·K]
π - Thermal conductivity [W/mΒ·K]
πΏ - Depth of skin
ππ’π· - Nusselt number [dimensionless]
ππ - Prandtl number [dimensionless]
π" - Heat transfer rate per unit area [W/m2]
οΏ½ΜοΏ½ - Heat transfer rate [W]
οΏ½ΜοΏ½ - Volumetric flow rate [m3/s]
π - Thermal resistance [m2Β·K/W]
π ππ· - Reynolds number [dimensionless]
ππ»πΉ - Sensible heat factor
π - Temperature [C or K]
ππ - Overall heat transfer coefficient [W/m2Β·K]
π - Velocity [m/s]
π - Absolute humidity ratio [kgmoisture/kgair]
Subscripts
ππ - Dry bulb
πππ - Indoor dry bulb
π - Latent
π - Outdoor
π - Sensible
π€π - Wet bulb
Greek Letters
π - Evaporation coefficient [kgmoisture/m2Β·h]
π - Kinematic viscosity [m2/s]
π - Relative humidity [kgmoisture/kgmoisture at saturation]
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
11
7.0 Appendix
7.1 Project Assumptions
Air
Ideal gas at 1 atm (101 kPa)
Outdoor Conditions
Dry Bulb Temperature
o ππππ = 38 πΆ
Wet Bulb Temperature
o ππ€ππ = 26 πΆ
Building Conditions
Indoor Design Dry Bulb Temperature
o ππππ = 26 πΆ
Indoor Relative Humidity
o π = 50%
Occupants (Men) per Room
o ππππ πππ = 2
Total Number of Rooms
o π ππππ = 27
Total Outdoor Air Flow
o οΏ½ΜοΏ½ = 1596π3
β= 0.443
π3
π
Base Room Air Flow Rate
o π = 0.15π
π
Person
Surface Area
o π΄π‘ππ‘ = 1.82 π2
Skin Temperature (Wind Project)
o ππ πππ = 37.5 Β°πΆ
Heat Transfer
30 % of total human skin is exposed and affected by the sensible and latent cooling
Human is modeled as a cylinder in cross flow
Constant internal temperature
Evaporation modeled as a person completely covered in perspiration
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
12
7.2 Sample Calculations
Convection Calculations
This section covers the calculations performed to produce the sensible cooling load reduction due
to the convectional heat loss.
First, the properties of air at the ambient design conditions of 26 C and 101.325 kPa were obtained
from Engineering Equation Solver (EES),
Kinematic Viscosity: π£πππ = 1.571 β 10β5 π2
π
Prandlt Number: Prπππ = 0.7278
Number of People in Room: πππππππ = 2
Then the fan velocity was to be calculated,
οΏ½ΜοΏ½πππ = 3110ππ‘3
πππβ 1.56
π3
π
οΏ½ΜοΏ½πππ = π΄πππππππ
β΄ ππππ =οΏ½ΜοΏ½πππ
π΄πππ=
οΏ½ΜοΏ½ππππ
4βπ·πππ
2
ππππ =1.56
π3
π
π
4[(52 πππβ)(
1π
0.0254 πππβ)]
2 β 1.1385π
π
To find the Reynolds number, the diameter of the cylinder would have to approximate. This
diameter would be found by constraining the height and surface area of the cylinder. It was
assumed that the average height of the workers in the building would be,
βππ¦ππππππ = 6ππ‘ β 1.8288π
The average area of human skin was obtained [3].
π΄π πππ = 1.82 π2
The diameter of the cylinder is then,
πππ¦ππππππ =π΄ππ¦ππππππ
πβππ¦ππππππ
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
13
πππ¦ππππππ =1.82 π2
πβ1.8288 π= 0.31678π
The Reynolds number can then be found [10],
π ππ· =πππππππ¦ππππππ
π£πππ=
(1.138π
π )(0.31678 π)
(1.571Β·10β5 π2
π )
β 22958.3
To calculate the Nusselt number the following equation is used [10],
ππ’π· =βΜ πππ¦ππππππ
π= πΆπ ππ·
πPr1
3
Where the C and m coefficients are shown in the table below, sorted by Reynolds Number,
With πΆ = 0.193 and π = 0.618, the equation is then,
ππ’π· =βΜ πππ¦ππππππ
ππ πππ= (0.193)(22958.30.618)(0.7278
1
3) = 86.02
Where ππ πππ is the thermal conductivity of skin [11] and is taken as ππ πππ = 0.3075π
πΒ·π, the
average of the given range.
The above equation then gives the convection coefficient,
ππ’π· =βΜ πππ¦ππππππ
ππ πππ
β΄ βΜ =ππ’π·ππ πππ
πππ¦ππππππβ 83.505
π
π2Β·π
Using a thermal resistance circuit of the inside of the human skin, assuming that the thickness of
the skin is πΏπ πππ = 0.0025π [12].
π π‘ππ‘ππ = πΏπ πππ
ππ πππ+
1
β=
0.0025π
0.3075π
π2Β·π
+1
83.505π
π2Β·π
β 0.0201 π2π
π€
Figure 7: C and m constants for cylinder in cross flow [10]
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
14
The heat loss per square meter of human skin is then,
πβ²β² =ππ πππβππππ
π π‘ππ‘ππ=
37.5ββ26β
0.0201π2π
π€
β 571.99π€
π2
Then the total heat loss per person is then found with the following. Notice the reduction of human
skin area, as assumed that only 30% is exposed, due to clothing.
οΏ½ΜοΏ½π = πΆππππππππβ²β²π΄ = (0.2)(2 ππππππ) (571.99π€
π2) (1.82 π2) β 624.6 π
Latent Cooling Calculations
The following parameters are required for determining the latent cooling effects due to
evaporation:
Surface Area of Body: π΄ = 1.82 π2
Factor of Body Exposed to Air: πΆ = 0.3
Indoor Humidity Ratio: ππππ£ππππππππ‘ = 0.0105ππππππ π‘π’ππ
πππππ
Saturated Humidity Ratio: ππ ππ‘π’πππ‘πππ = 0.02164ππππππ π‘π’ππ
πππππ
Number of People in Room: πππππππ = 2
Diameter of Fan: π = 1.3208 π
Volumetric Flow Rate of Fan: οΏ½ΜοΏ½πππ = 1.56π3
π
Temperature of Skin: ππ πππ = 37.5 πΆ
Ambient Temperature: ππππππππ‘ = 26 πΆ
To approximate the temperature of sweat on the skin an average of skin temperature and ambient
room temperature was taken.
ππ π€πππ‘ =ππ πππ+ππππππππ‘
2=
37.5+26
2= 31.75 πΆ
Using ππππ = 1.1385π
π from the previous section and introducing an exposure factor C we
obtain the evaporation rate.
πβ = ππ΄ππππππππΆ(ππ ππ‘π’πππ‘πππ β ππππ£ππππππππ‘) [7]
Where the evaporation coefficient (π) includes the air velocity,
π = 25 + 19π£ = 25 + 19 (1.1385π
π ) β 46.63
ππ
π2Β·β
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
15
The amount of evaporated water per hour (πβ) and per second (ππ ) can then be found:
πβ = (46.63 ππ
π2Β·β) (1.82 π2)(2 ππππππ)(0.3)(0.02164 β 0.0105)
ππππππ π‘π’ππ
πππππ
β΄ πβ = 0.5673ππ
βπ
β΄ ππ = 1.575 Β· 10β4 ππ
π
By using EES, the value of the enthalpy of vaporization at ππ π€πππ‘ is obtained. Multiplying by
the evaporation rate we obtain the latent cooling experienced by two people:
οΏ½ΜοΏ½π = ππ βπ£ππ = (1.575 Β· 10β4 ππ
π ) (2426
ππ½
ππ) = 382.2 π
Economic Analysis
A short economic analysis was conducted to financially quantify the benefits of implanting fans
throughout this building. The following are general calculations on the currency savings generated
by the fans and their payback period. All numbers are in US dollars.
Sensible cooling rate: οΏ½ΜοΏ½π = 0.6246 ππ
Latent cooling rate: οΏ½ΜοΏ½π = 0.3822 ππ
Fan energy consumption: οΏ½ΜοΏ½πππ = 0.0502 ππ
Cost of One Fan: πΆππ π‘πππ = $199
Cost of Installing One Fan: πΆππ π‘πππ π‘πππ = $400
Sensible cooling is equivalent to the value determined in the convection sample calculations. The
energy consumption and cost of the fan were provided by manufacturing specifications, and
installation cost was from published values.
οΏ½ΜοΏ½ππππ,ππππ’ππ‘πππ = 3(οΏ½ΜοΏ½π + οΏ½ΜοΏ½π β οΏ½ΜοΏ½πππ) = 3(0.6246 + 0.3822 β 0.0502) ππ β 2.868 ππ
πΆππ π‘πππππ‘πππππ‘π¦ = (οΏ½ΜοΏ½ππππ,ππππ’ππ‘πππ)(πππ‘π)(π’π π)
β΄ πΆππ π‘πππππ‘πππππ‘π¦ = (2.868 ππ) ($ 0.142
ππβ) (11
βππ’ππ
πππ¦) β $4.48 πππ πππ¦
πΆππ π‘π ππ£π,ππππ’π = πΆππ π‘πππππ‘πππππ‘π¦ (258 πππ¦π
π¦πππ) = (
$4.48
πππ¦) (
258 πππ¦π
π¦πππ) β $1157 πππ π¦πππ
πΆππ π‘πππ,π‘ππ‘ππ = 3(πΆππ π‘πππ + πΆππ π‘πππ π‘πππ) = 3($199 + $400) β $1797
πππ¦ππππ ππππππ =πΆππ π‘πππ,π‘ππ‘ππ
πΆππ π‘π ππ£π,ππππ’π=
($1797)
($1157
π¦πππ)
β 1.55 π¦ππππ
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
16
7.3 EES Code "Enter Parameters" A= 1.82 "Surface area of body" C= 0.3 "Percentage of body exposed to air, aka no clothes" x_env= 0.0105 "Relative humidity of room" Num_people= 2 "Number of people in room" x_sat= 0.02164 "Saturated at indoor temp" d = 1.3208 "Diameter of fan" Q = 1.56 "flowrate of fan" T_skin = 37.5 "Skin temp" T_ambient = 26 "Ambient temp" T_sweat = (T_skin + T_ambient)/2 A_fan = pi*(d^2)/4 Q = A_fan * v g_h = theta*A*Num_people*C*(x_sat - x_env) theta = 25 + 19*v h_vap=Enthalpy_vaporization(Water,T=T_sweat) q_dot_l = (g_h/3600)*h_vap "ECONOMIC ANALYSIS" Fan_gain = .0502 "Fan operational cost" q_dot_s = .6246 Total_reduction_fan = (3*q_dot_s) + (3*q_dot_l) - (3*Fan_gain) Cost_elec_Turkey = (Total_reduction_fan *(.142)*(11)) "Electrical energy saved from total cooling" Cost_Fan = 199 Fan_installation_cost = 400 Total_fan_cost = (Cost_Fan*3) + (Fan_installation_cost*3) "Total fan installation and purchase cost" Cost_save_annum = Cost_elec_Turkey * 258 "Annual money saved from adding fans per fan" Payback_Period = Total_fan_cost/Cost_save_annum "Payback period"
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
17
References
[1] M. A. Rosen, "Development of an Enhanced Ceiling Fan: An Engineering Design Case
Study Highlighting Health, Safety and the Environment," Minerva Canada, Oshawa, 2009.
[2] M. A. Aktacir, O. BΓΌyΓΌkalaca and T. Yilmaz, "A case study for influence of building
thermal insulation on cooling load and air-conditioning system in hot and humid regions,"
Applied Energy, vol. 87, pp. 599-607, 2010.
[3] F. C. McQuiston, J. D. Parker and J. D. Spitler, Heating, Ventilating, and Air Conditioning
(6th Edition), Hoboken: John Wiley & Sons Inc., 2005.
[4] Ankara, "Turkish Electricity and Gas Prices in 2014," 30 March 2015. [Online]. Available:
http://aa.com.tr/en/economy/turkish-electricity-and-gas-prices-in-2014/62404. [Accessed 3
April 2016].
[5] Business Days Calculator, "Turkey Working Days," 2016. [Online]. Available:
http://turkey.workingdays.org/#a20. [Accessed 3 April 2016].
[6] Capital Lighting, "Emerson CF705," [Online]. Available:
http://cdn1.1800lighting.com/jqzoom/emerson/cf705ck.jpg. [Accessed 1 April 2016].
[7] Homewyse, "Cost to Install a Ceiling Fan," January 2016. [Online]. Available:
http://www.homewyse.com/services/cost_to_install_ceiling_fan.html. [Accessed 2 April
2016].
[8] M. Rosen, MECE4450U - Module 8: Minerva Case Study, Oshawa: University of Ontario
Institute of Technology, 2016.
[9] K. G. Gebremedhin and B. Wu, "Simulation of sensible and latent heat losses from wet-
skin surface and fur layer," Journal of Thermal Biology, vol. 27, pp. 291-297, 2002.
[10] T. L. Bergman, F. P. Incropera, A. S. Lavine and D. P. Dewitt, Fundamentals of Heat and
Mass Transfer, Hoboken: John Wiley & Sons, 2011.
[11] M. Cohen, Measurement of the thermal properties of human skin, J. Invest. Dermatol,
1977.
[12] H. J. Bennett, "Ever wondered about your skin?," 25 May 2014. [Online]. Available:
https://www.washingtonpost.com/lifestyle/kidspost/ever-wondered-about-your-
skin/2014/05/23/02cc93ca-ba79-11e3-96ae-f2c36d2b1245_story.html. [Accessed 31
March 2016].
[13] M. P. C. J. K. S. ,. G. H. S. Danny S. Parker, "Development of a High Efficiency Ceiling
Fan "The Gossamer Wind"," 5 January 1999. [Online]. Available:
http://www.fsec.ucf.edu/en/publications/html/FSEC-CR-1059-99/. [Accessed 31 March
2016].
MECE4450U - Energy and Economic Analysis of Ceiling Fans for an Office Building in Turkey
18
[14] "Evaporation from water surfaces," engineeringtoolbox.com, 2016. [Online]. Available:
http://www.engineeringtoolbox.com/evaporation-water-surface-d_690.html. [Accessed 31
March 2016].