MD Guardline Distribution System

Embed Size (px)

Citation preview

  • 7/26/2019 MD Guardline Distribution System

    1/32

    Distribution SystemMCBs, RCCBs, Distribution Boards

    Keeping you protected

  • 7/26/2019 MD Guardline Distribution System

    2/32

    Warranty Policy :

    Product offered by us are warranted against defects arising out of manufacturing processes or use of defective raw materials, for a period of

    18 months from the date of supply or 12 months from the date of installation whichever is earlier. The company reserves the right to either replace

    or repair the defective items after ascertaining the facts through a detailed service report on usage of our products in normal conditions. However,

    MCB warranty is 3 years as standard and extends to 5 years in case used in GE make standard distribution boards.

    The prices mentioned in the buylog for the same are for guidance purposes only. The products may be sold at lower prices also. Goods are always

    sold subject to laws, rules and regulations relating to excise, customs and maximum retail price as applicable at the time of purchase and as printedon the goods. Excise duty is not applicable on Guardline MCB, however applicable on RCCBs and DBs.

  • 7/26/2019 MD Guardline Distribution System

    3/32

    GE Energy - Industrial Solutions, India offers innovative

    solutions to meet customer needs in Power & Protection.

    The company has a pan India presence, with 4 regionaloffices, 9 branch offices and one manufacturing plant.

    GE Energy, offers solutions to customers in several segments

    that include power sector, core infrastructure like marine

    establishments, airports, highways, heavy & light industries,

    IT & ITES infrastructure, healthcare, commercial and

    residential segments.

    About GE Energy - Industrial Solutions

  • 7/26/2019 MD Guardline Distribution System

    4/32

  • 7/26/2019 MD Guardline Distribution System

    5/32

    Contents

    Guardline

    Miniature Circuit Breakers

    Safetrip

    Residual Current Circuit Breakers

    Safeline

    Distribution Boards

    Dimensions & Diagrams

    A6

    B10

    C14

  • 7/26/2019 MD Guardline Distribution System

    6/32

    GuardlineMiniature Circuit Breakers

    Keeping you guarded

  • 7/26/2019 MD Guardline Distribution System

    7/32A7

    Conforms to IS8828:96/IEC60898-1

    0.5A to 63A, 10kA

    Trip free mechanism

    Disconnection with positive contact

    Low watt loss Energy saving

    Touch proof terminals IP20

    High grade engineering plastic housing

    ON-OFF flag indication

    Captive terminal screws

    Compatibility with all DBs

    Rated Current(In) : 0.5A, 1A, 2A, 3A, 4A, 6A, 10A, 16A,

    20A, 25A, 32A, 40A, 50A, 63A

    Number of Poles : 1 Pole, 2 Pole, 3 Pole and 4 Pole

    Breaking Capacity : 10kA

    Rated Voltage : 240/415V AC

    Insulation Voltage : 500V AC

    Frequency : 50/60Hz

    Tripping Characteristics* : C, D

    Operating Temp Range : -250C to +550C

    Mounting Arrangement : Snap on fixing, 35mm DIN Channel

    Isolators : 40/63A in 2 Pole, 3 Pole and 4 Pole

    Higher ratings on request*B series on request

    Tripping Characterstics CurveType - B, C & D

    Lower Limit as per Standard

    Upper Limit as per Standard

    Reference Calibration Temp. 40 Co

    IS: 8828-1996/IEC-60898-1-2002

    Limit Specified in

    In : Rated Current

    D Type - 0.5A to 63A

    B Type - 0.5A to 63AC Type - 0.5A to 63A

    1

    Multiple of Rated Current

    1.13 1.45 2 2.55 3 5 10 14 20 28 50

    -B-Type- - C- Type- - D- Type-

    TimeinSeconds

    1000

    100005000

    3600

    100

    10

    1

    0.1

    0.01

    Salient Features Technical Details

  • 7/26/2019 MD Guardline Distribution System

    8/32

    Single Pole

    0.5

    1

    2

    3

    4

    6

    10

    16

    2025

    32

    40

    50

    63

    Double Pole

    0.5

    1

    2

    3

    4

    6

    10

    16

    20

    25

    32

    40

    50

    63

    Triple Pole

    0.5

    1

    2

    3

    GLCSP00

    GLCSP01

    GLCSP02

    GLCSP03

    GLCSP04

    GLCSP06

    GLCSP10

    GLCSP16

    GLCSP20GLCSP25

    GLCSP32

    GLCSP40

    GLCSP50

    GLCSP63

    GLCDP00

    GLCDP01

    GLCDP02

    GLCDP03

    GLCDP04

    GLCDP06

    GLCDP10

    GLCDP16

    GLCDP20

    GLCDP25

    GLCDP32

    GLCDP40

    GLCDP50

    GLCDP63

    GLCTP00

    GLCTP01

    GLCTP02

    GLCTP03

    GLDSP00

    GLDSP01

    GLDSP02

    GLDSP03

    GLDSP04

    GLDSP06

    GLDSP10

    GLDSP16

    GLDSP20GLDSP25

    GLDSP32

    GLDSP40

    GLDSP50

    GLDSP63

    GLDDP00

    GLDDP01

    GLDDP02

    GLDDP03

    GLDDP04

    GLDDP06

    GLDDP10

    GLDDP16

    GLDDP20

    GLDDP25

    GLDDP32

    GLDDP40

    GLDDP50

    GLDDP63

    GLDTP00

    GLDTP01

    GLDTP02

    GLDTP03

    1212

    12

    12

    12

    12

    12

    12

    1212

    12

    12

    12

    12

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    6

    4

    4

    4

    4

    Guardline Ordering Codes

    Current Rating(A)

    Ordering Cat.No.Type C

    Ordering Cat.No.Type D

    StandardPack Qty

    A8

  • 7/26/2019 MD Guardline Distribution System

    9/32

    Current Rating(A)

    Ordering Cat.No.Type C

    Ordering Cat.No.Type D

    StandardPack Qty

    Current Rating

    For marked MCBs please contact your nearest GE sales office

    Poles

    40 Double Pole GLISDP40

    63 Double Pole GLISDP63

    40 Triple Pole GLISTP40

    63 Triple Pole GLISTP63

    40 Four Pole GLISFP40

    63 Four Pole GLISFP63

    GLCTP04

    GLCTP06

    GLCTP10

    GLCTP16

    GLCTP20

    GLCTP25

    GLCTP32

    GLCTP40

    GLCTP50

    GLCTP63

    GLCFP00

    GLCFP01

    GLCFP02

    GLCFP03

    GLCFP04

    GLCFP06

    GLCFP10

    GLCFP16

    GLCFP20

    GLCFP25

    GLCFP32

    GLCFP40

    GLCFP50

    GLCFP63

    GLDTP04

    GLDTP06

    GLDTP10

    GLDTP16

    GLDTP20

    GLDTP25

    GLDTP32

    GLDTP40

    GLDTP50

    GLDTP63

    GLDFP00

    GLDFP01

    GLDFP02

    GLDFP03

    GLDFP04

    GLDFP06

    GLDFP10

    GLDFP16

    GLDFP20

    GLDFP25

    GLDFP32

    GLDFP40

    GLDFP50

    GLDFP63

    4

    4

    4

    4

    4

    4

    4

    4

    4

    4

    3

    3

    3

    3

    3

    3

    3

    3

    3

    3

    3

    3

    3

    3

    A9

    Isolator

    4

    6

    10

    16

    20

    25

    32

    40

    50

    63Four Pole

    0.5

    1

    2

    3

    4

    6

    10

    16

    20

    25

    32

    40

    50

    63

    Ordering Cat.No.

  • 7/26/2019 MD Guardline Distribution System

    10/32

    SafetripResidual Current Circuit Breakers

    Keeping you safe

  • 7/26/2019 MD Guardline Distribution System

    11/32

    B11

    Personal protection - Against electrocution

    The use of exposed, substandard and poorly wired, or damaged

    equipment reduces the safety of an installation and increases the

    risk of an electric shock to the person in contact. Electrocution is a

    passage of current flowing through human body which affects

    the vital functioning like breathing and heartbeat. This can be verydangerous to the person in contact depending upon current and

    time for which it flows.

    A correctly selected RCCB can detect even small currents flowing

    to earth and reduces the risk of electrocution. The effect of electric

    current through human body has been well researched and is as

    below.

    500mA Immediate cardiac arrest resulting in death

    70-100mA Cardiac fibrillation; the heart begins to

    vibrate and no longer beats at a steady rate

    This situation is dangerous since it is

    irreversible

    20-30mA Muscle contraction can cause respiratory

    paralysis

    10mA Muscle contraction: the person remains stuck to

    the conductor

    1-10mA Prickling sensations

    Salient Features Technical Details

    Conforms to IEC61008-1

    2 Pole & 4 Pole

    Trip free mechanism

    Disconnection with positive contact

    Antiwelding contacts

    Bi-connect facility

    Touch proof terminals IP20

    Resistance against unwanted tripping

    Test facility - A test button T provided on device

    No ageing effect

    Compatibility with all DBs

    Protection

    Rated Current(In) : 25A, 40A, 63A

    Sensitivity* : 30mA, 100mA, 300mA

    Number of Poles : 2 Pole and 4 Pole

    Rated Voltage : 240/415V AC

    Insulation Voltage : 500V AC

    Frequency : 50/60Hz

    Operating Temp. Range : -250C to +600C

    Terminal Capacity : 25mm2

    Mounting Arrangement : 35mm DIN Channel

    Service Life : 20000 operations

    Optional Accessories : Aux. contact, shunt & undervoltage

    release, motor operator & panelboard switch

    *500mA sensitivity available on request for industrial applications

  • 7/26/2019 MD Guardline Distribution System

    12/32

    B12

    1 Usually has no reactions or effects.

    2 Usually has no harmful effects.

    3 Usually, no organic damage is expected.

    Here the likelihood present is of muscular contractions and difficulty in breathing. Reversible disturbances in

    the formation and conductance of impulses in the

    heart , including arterial fibrillation and transient

    cardiac arrest without ventricular fibrillation are

    possible. These effects increase with current

    magnitude and time.

    4 In addition to the effects of Zone 3, the probability of

    ventricular fibrillation increases from 5% (curve c2),

    to about 50% (curve c3) and beyond 50% above

    (curve c3). Increasing with magnitude and time are

    pathophysiological effects as cardiac and breathing

    arrest, whilst heavy burns are possible.

    However, electrocution should not be viewed in terms of current alone but in

    terms of contact voltage. A person gets electrocuted by coming in contact

    with an object that has a different potential from his/her own. The difference in

    potential causes the current to flow through the body.

    The human body has known limits:

    In a dry environment, voltage limit = 50V

    In a humid environment, voltage limit = 25V

    Over current protection devices like MCB are unable to act

    promptly on small earth leakage currents. To comply with wiring

    regulations the earth fault loop impedance in Ohms, multiplied

    by the rated tripping current of the RCD in amperes must not

    exceed 50.

    Against Indirect Contact Zone Physiological effects

    The majority of fires in an electrical installation are result of

    leakage current flowing to earth and even a current of the order

    of 1A can lead to big fire. These type of faults are not detected by

    the normal short circuit protection device like MCB or Fuse. A

    correctly selected RCCB will detect this leakage and save the risk

    of fire saving the installation.

    Against Fire

  • 7/26/2019 MD Guardline Distribution System

    13/32

    B13

    Selection

    30mA -This RCCB will provide a high degree of protection against

    electrocution. The current flowing through human body depends

    upon the resistance of human body and voltage across it and can

    vary between 80mA to 240mA. To be within zone of the IEC curve

    as shown in chart. It is necessary for the RCCB to operate within

    50ms at 240mA and 150ms at 80mA. Both these conditions are

    satisfied by 30mA RCCB. For households, individual loads, damp

    areas and construction installations, RCCB with sensitivity not

    exceeding 30mA is recommended.

    100mA -This RCCB will normally give high degree of protection

    against electrocution but there is a possibility that the shock

    current could fall below the tripping level of RCCB. This could occur

    if additional resistances to that of human body are included in the

    earth path. The 100mA RCCB protects against leakage currents

    and indirect contact with earth loop impedance upto 500 Ohms.

    300mA -This RCCB may be used where only fire protection is

    required. eg., on lighting circuits and larger installations. These will

    not give any protection against electrocution.

    Amps Poles Sensitivity (mA) Sensitivity (mA)

    Rating at 240V/415V AC Rating at 240V AC

    Safetrip RCCB offering

    Poles

    25

    40

    63

    25

    40

    63

    25

    40

    63

    4

    4

    4

    4

    4

    4

    4

    4

    4

    30

    30

    30

    100

    100

    100

    300

    300

    300

    2

    2

    2

    2

    2

    2

    2

    2

    2

    30

    30

    30

    100

    100

    100

    300

    300

    300

  • 7/26/2019 MD Guardline Distribution System

    14/32

    SafelineDistribution Boards

    Keeping you secure

  • 7/26/2019 MD Guardline Distribution System

    15/32

    C15

    Aesthetically designed in compliance with latest standards

    Wide range-sheet steel DBs upto 18 ways

    SPN, TPN in single & double door

    Degree of protection IP30, IP42 & IP43

    Surface & flush mounting

    Powder coated Corrosion & scratch resistance

    Detachable gland plate

    Adequate knock-outs on all sides

    Generous wiring space

    Clear circuit identification

    Supplied complete with bus bars, earth & neutral bars

    Multitier, phase segregated, 7 segments, vertical DBs Plug & sockets boards

    Prewired DBs available on request Please contact your nearest GE Sales Office

    Voltage : 240V AC for SPN, 415V for

    TP/TPN DBs

    Standard Busbar Rating : 63A/100A/125A

    No. of Ways : 4, 6, 8, 10, 12, 14, 18 ways

    Mounting : Surface/FlushDielectric Strength : 2.5kV RMS AC for 1min

    Mounting Arrangement : 35mm DIN Rail for MCBs, RCCBs

    Salient Features Technical Details

  • 7/26/2019 MD Guardline Distribution System

    16/32

    C16

    Plane enclosures 1, 2, 3, 4, 5, 6, 8 ways

    IP30 pole incomer

    Salient Features

    Technical Details

    DescriptionCode Ref.

    Single Door

    1Way SLEMS0001Y

    2Way SLEMS0002Y

    3Way SLEMS0003Y

    4Way SLEMS0004Y

    6Way SLEMS0006Y

    8Way SLEMS0008Y

    Blanking Plate

    1Way SLMBP0001X

    Dimensions & Diagram - 1.1 | Page D28

    One Way Enclosures

    One Way Enclosures

  • 7/26/2019 MD Guardline Distribution System

    17/32

    C17

    Safe line - Sheet steel - SPN SPN version in 4, 6, 8, 10, 12, 14, 16 and 18 ways outgoing

    Single door, double door and acrylic door

    IP30, IP42 and IP43 protection

    Liberal wiring space, adequate cable glands

    Superior powder coated finish for better protection against heat

    & dust (Powder coating thickness of more than 60 microns)

    Detachable gland plates

    Complete with phase busbars, earthbars, neutral bars & cable kit

    Salient Features

    Technical Details

    DescriptionCode Ref. Code Ref. Code Ref.

    Single Door Double Door Acrylic Door

    Dimensions4Way SLSMS0204Y SLSMD0204Y 6Way SLSMS0206Y SLSMD0206Y SLSMA0206Y

    8Way SLSMS0208Y SLSMD0208Y SLSMA0208Y

    10Way SLSMS0210Y SLSMD0210Y SLSMA0210Y

    12Way SLSMS0212Y SLSMD0212Y SLSMA0212Y

    14Way SLSMS0214Y SLSMD0214Y SLSMA0214Y

    16Way SLSMS0216Y SLSMD0216Y SLSMA0216Y

    18Way SLSMS0218Y SLSMD0218Y SLSMA0218Y0

    Dimensions & Diagram - 1.2 | Page D28

    SPN Distribution Boards

    SPN Distribution Boards

  • 7/26/2019 MD Guardline Distribution System

    18/32

    C18

    4, 6, 8 and 12 ways Single door, double door and acrylic door (IP30, IP42 and IP43)

    With provision 8 module incomer and SP MCB as outgoing

    With copper busbar, neutral link, earth link

    Supplied with wire set

    Salient Features

    Technical Details

    DescriptionCode Ref. Code Ref. Code Ref.

    Single Door Double Door

    4Way SLTMS0804Y SLTMD0804Y SLTMA0804Y

    6Way SLTMS0806Y SLTMD0806Y SLTMA0806Y

    8Way SLTMS0808Y SLTMD0808Y SLTMA0808Y

    12Way SLTMS0812Y SLTMD0812Y SLTMA0812Y

    Acrylic Door

    Dimensions & Diagram - 1.3 | Page D28

    TPN Distribution Boards

    TPN Distribution Boards

  • 7/26/2019 MD Guardline Distribution System

    19/32

    C19

    Suitable for flush mounting and surface mounting IP30, IP42 and IP43 protection

    Detachable gland plates

    With copper bus bar

    Suitable for 8 module incomer and DP RCCB/RCBO as

    sub incomer and SP MCBs as outgoing

    3 separate mutual link for each phase

    With neutral link and earth bar

    6, 8, 12, 16 ways

    Salient Features

    Technical Details :With four neutral links, one earth link, excluding bus bars and interconnections

    DescriptionCode Ref. Code Ref.

    Single Door Double Door

    6Way 8+4+2 SLHMS0806Y SLHMD0806Y

    8Way 8+6+2 SLHMS0808Y SLHMD0808Y

    12Way 8+10+2 SLHMS0812Y SLHMD0812Y

    16Way 8+14+2 SLHMS0816Y SLHMD0816Y

    Dimensions & Diagram - 1.4 | Page D28

    Per Phase Isolation Horizontal Distribution Boards

    Per Phase IsolationHorizontal Distribution Boards

  • 7/26/2019 MD Guardline Distribution System

    20/32

    IP30, IP42 and IP43 protection With 8 cutting incomer and 3 rows with different

    configuration

    Separate neutral for each phase

    SP and TP outgoing are possible

    Sub incomer of 2 Pole

    Salient Features

    Single Door

    Technical Details :With four neutral links, one earth link, excluding bus bars and interconnections.

    DescriptionCode Ref. Code Ref.

    Double Door Acrylic Door

    8 Way (3 Rowx8+1 Rowx8) SLIMD0808Y SLIMA0808Y

    10 Way (3 Rowx10+1 Rowx8) SLIMD0810Y SLIMA0810Y

    12 Way (3 Rowx12+1 Rowx8) SLIMD0812Y SLIMA0812Y

    14 Way (3 Rowx14+1 Rowx8) SLIMD0814Y SLIMA0814Y

    16 Way (3 Rowx16+1 Rowx8) SLIMD0816Y SLIMA0816Y

    Dimensions & Diagram - 1.5 | Page D29

    Per Phase Isolation Vertical Distribution Boards

    C20

    Per Phase IsolationVertical Distribution Boards

  • 7/26/2019 MD Guardline Distribution System

    21/32

    IP30, IP42 and IP43 protection With MCB and 49 RCCB incomer (4 Pole)

    TP and SP outgoing

    IP30 and IP43

    With copper bus bar

    Spectra range MCCB upto 125A and Record range for

    higher rating

    Salient Features

    Technical Details - Provision for 4Pole MCB/RCCB

    DescriptionCode Ref. Code Ref. Code Ref.

    Single Door Double Door Acrylic Door

    4Way SLVMS0804Y SLVMD0804Y SLVMA0804Y

    6Way SLVMS0806Y SLVMD0806Y SLVMA0806Y

    8Way SLVMS0808Y SLVMD0808Y SLVMA0808Y

    12Way SLVMS0812Y SLVMD0812Y SLVMA0812Y

    Dimensions & Diagram - 1.6 | Page D29

    TPN Vertical Distribution Boards

    C21

    TPN Vertical Distribution Boards

  • 7/26/2019 MD Guardline Distribution System

    22/32

    C22

    Suitable for flush mounting and surface mounting IP30, IP42 and IP43 protection

    Detachable gland plates

    With copper bus bar

    With neutral bar and earth bar

    Pan assembly for ease of installation

    With provisions for Spectra / Record Range MCCB

    as incomer and SP/TP MCBs as outgoing

    4, 6, 8 and 12 ways

    Salient Features

    Technical Details - Provision for 4Pole MCB/RCCB

    DescriptionCode Ref. Code Ref.

    Double Door - 100A Double Door - 225A

    4Way SLVMDM04Y SLVMDM204Y

    6Way SLVMDM06Y SLVMDM206Y

    8Way SLVMDM08Y SLVMDM208Y

    12Way SLVMDM12Y SLVMDM212Y

    Dimensions & Diagram - 1.7 | Page D29

    TPN Vertical Distribution Boards with MCCB Incomer

    TPN Vertical Distribution Boardswith MCCB Incomer

  • 7/26/2019 MD Guardline Distribution System

    23/32

    C23

    With provision for 3nos. phase selector switches and in-built

    piano switches

    Suitable for flush mounting and surface mounting

    IP30, IP42 and IP43 protection

    Detachable gland plates

    With copper bus bar

    With neutral bar, earth bar, and wire set

    With provision for 8 module incomer and SP MCB, as outgoing

    4, 6, 8 and 12 ways

    Salient Features

    Technical Details - TPN phase selector DB with 3nos. piano switch

    DescriptionCode Ref. Code Ref.

    Single Door Double Door

    4Way SLXMS0804Y SLXMD0804Y

    6Way SLXMS0806Y SLXMD0806Y

    8Way SLXMS0808Y SLXMD0808Y

    12Way SLXMS0812Y SLXMD0812Y

    Dimensions & Diagram - 1.8 | Page D29

    Phase Selector Distribution Boards

    Phase Selector Distribution Boards

  • 7/26/2019 MD Guardline Distribution System

    24/32

    DB with phase segregation and separator between incomer

    and outgoing

    Suitable for flush mounting and surface mounting

    IP30, IP42 and IP43 protection

    Detachable gland plates

    With copper bus bar

    With neutral bar, earth bar

    With provision for 8 module incomer and DP RCCB/RCBO as

    sub incomer and SP MCB, as outgoing

    4, 6, 8 and 12 ways

    Salient Features

    C24

    Technical Details - Compartmental space for 4P MCB

    DescriptionCode Ref. Code Ref.

    Single Door Double Door

    4Way SLCMS0804Y SLCMD0804Y

    6Way SLCMS0806Y SLCMD0806Y

    8Way SLCMS0808Y SLCMD0808Y

    12Way SLCMS0812Y SLCMD0812Y

    Dimensions & Diagram - 1.9 | Page D30

    Phase Segregated Distribution Boards

    Phase Segregated Distribution Boards

  • 7/26/2019 MD Guardline Distribution System

    25/32

    Suitable for flush mounting and surface mounting

    IP30, IP42 and IP43 protection

    Detachable gland plates

    Flexibility to organize the distribution as per site requirements

    With neutral bar and earth bar

    26, 28, 39, 42, 52, 56 ways in 2, 3 and 4 rows

    Other configurations on request

    C25

    Salient Features

    Technical Details

    DescriptionCode Ref. Code Ref.

    Double Door Acrylic Door

    13module x 2 tier SLFMD0213Y SLFMA0213Y

    13module x 3 tier SLFMD0313Y SLFMA0313Y

    13module x 4 tier SLFMD0413Y SLFMA0413Y

    14module x 2 tier SLFMD0214Y SLFMA0214Y

    14module x 3 tier SLFMD0314Y SLFMA0314Y

    14module x 4 tier SLFMD0414Y SLFMA0414Y

    Dimensions & Diagram - 1.10 | Page D30

    Universal Distribution Boards

    Universal Distribution Boards

  • 7/26/2019 MD Guardline Distribution System

    26/32

    C26

    SPN and TPN Distribution Boards

    With in-built plug and socket

    Ideal for protection of appliances like ACs, Geysers etc.

    Available from 20A SPN to 63A TPN

    Available for DP RCCB incomer

    Excellent aesthetics

    Salient Features

    Technical Details

    DescriptionCode Ref.

    Single Door

    20A SPN SLRMS0S20Y

    20A TPN SLRMS0T20Y

    32A TPN SLRMS0T32Y

    20A with provision for DP RCCB SLRMS0220Y

    32A TP with provision for 4P RCCB SLRMS0432Y

    63A TP with provision for 3P MCB SLRMS0363Y

    Dimensions & Diagram - 1.11 | Page D30

    Plug & Socket Boards

    Plug & Socket Boards

  • 7/26/2019 MD Guardline Distribution System

    27/32

    Dimensions & DiagramPlease contact your nearest GE sales office for drawings in printable format

  • 7/26/2019 MD Guardline Distribution System

    28/32

    D28

    Dimensions & Diagram - 1.1

    One Way Enclosures

    Dimensions & Diagram - 1.2

    SPN Distribution Boards

    Dimensions & Diagram - 1.4

    Per Phase Isolation Horizontal Distribution Boards

    Dimensions & Diagram - 1.3

    TPN Distribution Boards

    245

    105

    225

    47

    0

    340

    450

  • 7/26/2019 MD Guardline Distribution System

    29/32

    D29

    Dimensions & Diagram - 1.6

    TPN Vertical Distribution Boards

    Dimensions & Diagram - 1.7

    TPN Vertical Distribution Boards with MCCB Incomer

    Dimensions & Diagram - 1.5

    Per Phase Isolation Vertical Distribution Boards

    Dimensions & Diagram - 1.8

    Phase Selector Distribution Boards

  • 7/26/2019 MD Guardline Distribution System

    30/32

    D30

    Dimensions & Diagram - 1.9

    Phase Segregated Distribution Boards

    Dimensions & Diagram - 1.11

    Plug & Socket Boards

    Dimensions:

    168x137x60

    275x135x65

    275x135x65

    235x180x65

    275x180x65

    317x140x127

    Dimensions & Diagram - 1.10

    Universal Distribution Boards

    168

    137

    78

    60

    5

    5124

    110

    155

  • 7/26/2019 MD Guardline Distribution System

    31/32

    Note :

    Product upgradation is a continuous process. The data given is subject to change without any prior notice.

    Please contact your nearest GE Sales office for the latest product information.

    REGIONAL OFFICES BRANCH OFFICES

  • 7/26/2019 MD Guardline Distribution System

    32/32

    NORTH

    New Delhi

    GE India Industrial Pvt. Ltd.71/1, Shivaji MargNew Delhi-110015Ph: (011) 45052277/8Fax: (011) 25928088

    Chandigarh

    GE India Industrial Pvt. Ltd.SCO No. 72 & 73, First FloorSector 8/C, Madhya MargChandigarh-160008Ph: (0172) 3982908-10Fax: (0172) 3982905

    Jaipur

    GE India Industrial Pvt. Ltd.448, 4th Floor, Ganapati PlazaM.I. Road, Jaipur-302001Ph: (0141) 5112802Fax: (0141) 2389012

    Lucknow

    GE India Industrial Pvt. Ltd.101, Ace Business Center19, Vidhan Sabha MargLucknow-226001Ph: (0522) 3203808, 3012444/666Fax: (0522) 4045909

    SOUTH

    Bangalore

    GE India Industrial Pvt. Ltd.The Millenia, Level-6, Tower B1 & 2, Murphy Road, UlsoorBangalore-560008Ph: (080) 41434000Fax: (080) 41434199

    Chennai

    GE India Industrial Pvt. Ltd.Temple Tower, 6th Floor476, (New No. 672) Anna SalaiNandanamChennai-600035Ph: (044) 45070470-84Fax: (044) 45070474

    Coimbatore

    GE India Industrial Pvt. Ltd.No.36/6 & 7, 1st FloorAshirwad BuildingD.B.Road, R.S. PuramCoimbatore-641002Ph: (0422) 4393520 / 4393529

    WEST

    Mumbai

    GE India Industrial Pvt. Ltd.361/362, Solitaire Corporate ParkM. Vasanji Road, ChakalaAndheri (E), Mumbai-400093Ph: (022) 40101610Fax: (022) 40101611

    EAST

    Kolkata

    GE India Industrial Pvt. Ltd.Horizon Building, 4th Floor57, Chowringhee RoadKolkata-700071

    Ph: (033) 40034056Fax: (033) 40034071

    Works:GE India Industrial Pvt. Ltd.Plot No. 42/1 & 45/14Electronic City - Phase IIBangalore-560100Ph: (080) 41113000Fax: (080) 28528469/552

    HO:GE India Industrial Pvt. Ltd.The Millenia, Level-6, Tower B1 & 2, Murphy Road, UlsoorBangalore-560008Ph: (080) 41434000Fax: (080) 41434199Email: [email protected]

    Toll Free No:18001024343

    Customer Care:[email protected]

    We are committed to continuous development and improvement of our products and the specifications aresubject to change without notice. For product availability and latest prices, please contact GE Sales Team.

    For any further information, visit us at http://www.geindustrial.com

    gand General Electric are registered trade marks of General Electric Co. USA

    Ahmedabad

    GE India Industrial Pvt. Ltd.405-406, Kirtiman ComplexKinariwala House, Behind CitibankOff C.G. Road, Ahmedabad-380006Ph: (079) 65427385/55427389Fax: (079) 26460637

    Pune

    GE Money Financial Services LimitedShop No. 405-410, 4th FloorCity Point, Dhole Patil RoadPune-411001Mob: +91 9850867507

    Cochin

    GE India Industrial Pvt. Ltd.Mayur Business Center & MotelChittur Road, Pullepadi JunctionCochin-682035Ph: (0484) 2364139Fax: (0484) 4031400

    Hyderabad

    GE India Industrial Pvt. Ltd.5-2-45, Hyderbasti, RP RoadNear Gujarati High SchoolSecunderabad-500003Ph: (040) 27543162, 66311264Fax: (040) 66339272

    1

    107/MODGLMCB