41
McGill Power Sales & Engineering, INC. 1

McGill Power Sales & Engineering, INC

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: McGill Power Sales & Engineering, INC

McGill Power Sales & Engineering, INC.

1

Page 2: McGill Power Sales & Engineering, INC

© 2007 Eaton Corporation. All rights reserved.

Power Factor Correction

Terry McGill President McGill Power Sales & Engineering Inc.

Page 3: McGill Power Sales & Engineering, INC

3

Agenda

• What is power factor? • What are the costs of low power factor? • What are the solutions to low power factor? • Power factor correction selection considerations • Design considerations and pitfalls

Page 4: McGill Power Sales & Engineering, INC

4

Power factor definition

• “Real” power = working power = kW • “Apparent” power = Volts x Amps = kVA • “Reactive” power = magnetizing power = kVAR

φ

kVA kVAr

kW

• Power factor is the ratio between the “real” power and the “apparent” power of an electrical system

Page 5: McGill Power Sales & Engineering, INC

5

Is the Glass Half Empty or Half Full?

Full Capacity

(KVA)

Foam/Fizz Capacity (KVAR)

Liquid (KW)

Page 6: McGill Power Sales & Engineering, INC

6

Utility must generate, transmit, and distribute active AND reactive power

Page 7: McGill Power Sales & Engineering, INC

7

If reactive power could come from another source – utility can reduce

Page 8: McGill Power Sales & Engineering, INC

© 2007 Eaton Corporation. All rights reserved.

Demonstration

Power Factor Demonstration Unit

Page 9: McGill Power Sales & Engineering, INC

9

Why Consider PFC? PF correction provides many benefits: • Primary Benefit:

• Reduced electric utility bill if there is a penalty (a typical payback period is less than two years)

• Other Benefits: • Increased system capacity • Improved voltage regulation • Reduced losses in transformers and cables • May reduce harmonics on the power system (with

harmonic filters)

Page 10: McGill Power Sales & Engineering, INC

10

Where has all the money gone?

+

Energy (kWh)

Demand (kW)

PF Charges

Taxes

Page 11: McGill Power Sales & Engineering, INC

11

Typical Uncorrected Power Factor

Low PF typically results from unloaded or lightly loaded motors Unloaded motor – PF = .20 Loaded motor – “rated PF” = .85

Industry Percent Uncorrected PF

Brewery 76-80

Cement 80-85

Chemical 65-75

Coal Mine 65-80

Clothing 35-60

Electroplating 65-70

Foundry 75-80

Forge 70-80

Hospital 75-80

Machine manufacturing 60-65

Metal working 65-70

Office building 80-90

Oil-field pumping 40-60

Paint manufacturing 55-65

Plastic 75-80

Stamping 60-70

Steelworks 65-80

Textile 65-75

Presenter
Presentation Notes
Speaker A
Page 12: McGill Power Sales & Engineering, INC

12

Typical Sources of Low Power Factor

• Reactive power is required by many loads to provide magnetizing current for: • Motors • Power transformers • Welding machines • Electric arc furnaces • Inductors • Lighting ballasts

Page 13: McGill Power Sales & Engineering, INC

13

Cost to end user or consumer- Utility fees and surcharges

• There is no free lunch!! • Many utilities pass on

the extra costs they incur through penalties, surcharges or other methods

• Methods of recovering these costs vary with each utility and can be confusing to customers

Page 14: McGill Power Sales & Engineering, INC

14

Where do PF charges appear on a bill?

• Explicit • Power Factor Penalty • Power Factor Adjustment • Power Factor Multiplier • Reactive Demand Charge • Calculated Demand • Billed Demand

Page 15: McGill Power Sales & Engineering, INC

15

Where do PF charges appear on a bill?

• Shift to Temp 624 Model

Page 16: McGill Power Sales & Engineering, INC

16

Escalation in Electrical Energy Cost

• Electrical Energy cost has increased nearly 50% over the last 10 years.

• The rate of increase has accelerated in the past few years.

• Currently the PF adjustment is being increased.

Industrial Electrical Energy Cost by Year

4

4.5

5

5.5

6

6.5

1997 1998 1999 2000 2001 2002 2003 2004 2005 2006

Year

Pric

e/KW

H (c

ents

)

Source Energy Information Administration

Page 17: McGill Power Sales & Engineering, INC

17

Cost savings due to increased capacity

• Correcting poor power factor can significantly reduce the load on transformers and conductors and allow for facility expansion • Transformers are rated

by kVA and must be sized accordingly

Page 18: McGill Power Sales & Engineering, INC

18

Example – increase capacity with new transformer • Existing plant has a

power factor of 0.80 or 80% PF

• Existing transformer is 500kVA

• Plant needs to add new production line of 75kW

kVA = 500

kVAr

=30

0

kW = 400

Page 19: McGill Power Sales & Engineering, INC

19

Example – increase capacity with new transformer

• Cost to increase capacity to accommodate new production • New transformer

• next standard size 750kVA • Long lead-time

• Plant shut down to add new transformer – days? • Labor and materials to install new transformer

• Upsize conductors for 750kVA transformer

• Disposal of old transformer

Page 20: McGill Power Sales & Engineering, INC

20

Example – increase capacity by adding PFCC • Correct power factor

from 80% PF to 97% PF by adding 200kVAR power factor correction capacitor

• Keep existing 500kVA • Add 75kW of new load • Existing 500kVA

transformer actually runs cooler than before!!!!

kVA = 412

kVAr

= 1

00

kW =400

kVA = 485

kVAr

= 1

00

kW =475

Power Factor Correction

Power Factor Correction and addition of 75kW

Page 21: McGill Power Sales & Engineering, INC

21

Example – increase capacity by adding PFCC

• Cost to increase capacity to accommodate new production • New power factor correction capacitor • Minimal interruption to energize and start up new

capacitor system

Page 22: McGill Power Sales & Engineering, INC

© 2007 Eaton Corporation. All rights reserved.

How to correct poor power factor

Page 23: McGill Power Sales & Engineering, INC

23

Capacitor Selection Capacitor selection issues (besides size) • Utility penalties • Installed cost, payback of equipment, and NPV • Load variability • Voltage regulation • Load requirements (Speed of changing PF) • Harmonic resonance

Presenter
Presentation Notes
This section of the paper is devoted to discussing factors in selecting a capacitor, other than the initial kvar sizing calculation, which was already discussed early in the paper. Some of the items in this list will be discussed further later in this paper (some in this section, some, i.e. harmonics, will be discussed in later sections), some won’t. The utility penalties were touched on briefly earlier in the paper.
Page 24: McGill Power Sales & Engineering, INC

24

Effect of Location

R2 R1

Motor Load

Resistive Load

Place here for utility PF penalty

Place here for utility PF penalty (utility owned transformer)

or

Place here to reduce losses in transformer or free capacity

Place here for line loss reduction and voltage

improvement

Page 25: McGill Power Sales & Engineering, INC

25

LV Fixed Capacitor Banks • Designed for industrial and

commercial power systems • Lowest installed cost • var Range: 1 kvar to 400 kvar • 208 Volts through 600 Volts AC • Must be harmonic free

environment

Page 26: McGill Power Sales & Engineering, INC

26

LV Switched (Automatic) PFC Capacitors Banks • Automatically sense changes in load

• Automatic Controller • Steps of 50 kvar standard

Smaller wall mounted units are available, and can be a real cost savings!

Page 27: McGill Power Sales & Engineering, INC

27

• Provides similar PF correction (as caps)

• Avoid harmonic capacitor interaction problems

• “Filter” harmonics to reduce voltage and current distortion

LV Harmonic Filtering Equipment

Page 28: McGill Power Sales & Engineering, INC

28

MV Capacitors

• Pole Mounted • These banks have exposed live parts and

are typically supported on a wood power pole.

• Rack Mounted • These banks have exposed live parts and

are supported on a steel structure. These banks are usually located in fenced-in substations.

• Metal Enclosed or Pad Mounted • These banks are typically enclosed in a

steel enclosure and are usually located within a fenced-in substation or switchgear room.

Page 29: McGill Power Sales & Engineering, INC

29

Cost of Power Factor Correction

TABLE 4 INSTALLED COST COMPARISON

OF POWER FACTOR CORRECTION EQUIPMENT

TYPE OF CORRECTION INSTALLED COST, $/KVAR

Fixed (LV – motor applied) $15

Fixed (LV) $25

Fixed (MV) $30

Switched (LV) $50

Switched (MV) $50

Static Switched (LV) $75

Switched Harmonic Filter (LV) $75

Switched Harmonic Filter (MV) $60

Active Harmonic Filter (LV) $150

Presenter
Presentation Notes
Speaker B A zero sequence trap is a special third harmonic filter designed for application on 120/208V circuit neutrals. The rating is based upon the third harmonic duty in the neutral conductor, the size of the neutral conductor, and its distance from the transformer. The trap is typically installed at the transformer or at the panel.
Page 30: McGill Power Sales & Engineering, INC

30

Additional Application considerations

• Switching transients • Potential resonance

Page 31: McGill Power Sales & Engineering, INC

31

Capacitor switching transients

• Capacitor energization (common event) • Voltage difference between system and capacitor • Capacitor voltage cannot change instantaneously • System voltage pulled nearly to initial capacitor

voltage • Inrush current as capacitor charges • Voltage overshoots and oscillation occurs

Page 32: McGill Power Sales & Engineering, INC

32

Definition • Steady state components of voltage and current at

higher frequencies than 60 Hz (or fundamental frequency)

Causes • ‘Nonlinear’ loads, normally electronic loads • In industrial facility, predominately motor drives (AC

or DC), also large UPSs, computer loads, rectifiers • These electronic loads draw non-sinusoidal current • All load current (particularly transformers and motors)

has some amount of harmonic content

Harmonics

Page 33: McGill Power Sales & Engineering, INC

33

H = NP+/-1

i.e. 6 Pulse Drive - 5, 7, 11, 13, 17, 19,…

Source Typical Harmonics* 6 Pulse Drive/Rectifier 5, 7, 11, 13, 17, 19… 12 Pulse Drive /Rectifier 11, 13, 23, 25… 18 Pulse Drive 17, 19, 35, 37… Switch-Mode Power Supply 3, 5, 7, 9, 11, 13… Fluorescent Lights 3, 5, 7, 9, 11, 13… Arcing Devices 2, 3, 4, 5, 7... Transformer Energization 2, 3, 4 * Generally, magnitude decreases as harmonic order increases

Expected Harmonics

Presenter
Presentation Notes
Speaker B Transformer heating - Increased RMS current causes increased lossed: conductor losses, eddy current losses, core losses. For every 10 degrees Celcius rise in temperature, there is a corresponding reduction in the life of that transformer. Discuss K-factor here. Motor and generator - voltage distortion at the motor terminals cause harmonic flux within motors. Negative sequence harmonics rotate opposite the rotor synchronous frequency causing heating. NEMA - MG1 tells you how to derate the motor for harmonics or will estimate a decrease in life from harmonics. Neutral heating - Triplen harmonics act like zero sequence components and add arithmetically on the neutral Nuisance fuse - increased current, especially at higher frequencies Insulation deterioration - Continuous magnitude voltage peaks due to distortion deteriorating the dielectric strength of the insulation Electronic Control Malfunctioning - Higher magnitude voltage peaks and premature zero crossings. Inconsistent meter readings - Phase unbalance and high harmonic voltages and currents. Revenue energy meters may read incorrect due to harmonics I[ to +/- 20% off. Two court cases due to this in Ontario and CA Voltage regulator misoperation - voltage distortion affecting the rms magnitude of the voltage may cause regulators to misinterpret the 60 Hz voltage.
Page 34: McGill Power Sales & Engineering, INC

34

If a capacitor exists on the power system

AND

Harmonic producing loads are in use

You MUST check for harmonic resonance.

(Series and Parallel)

Harmonic Resonance

The “Self Correcting” Problem •Blown Fuses •Failed Capacitor

Page 35: McGill Power Sales & Engineering, INC

35

Harmonic Resonance - Solutions 1. Change the method of kvar compensation (harmonic

filter, active filter, etc.) 2. Change the size of the capacitor bank to over-

compensate or under-compensate for the required kvar and live with the ramifications (i.e. overvoltage or PF penalty).

Natural System frequency of oscillation typically at 5th to 13th harmonic

Page 36: McGill Power Sales & Engineering, INC

36

Several factors must converge simultaneously for resonance to be a potential problem

1) P.F. correction kVAr >25% of xfmr kVA 2) Nonlinear load > 25% of xfmr kVA 3) Larger, fixed capacitance Often, resonance effects exist to some degree, but is not

severe enough to cause problems

When is resonance a concern ?

Page 37: McGill Power Sales & Engineering, INC

37

Resonance not generally a concern when: • Total kVAR <15% system kVA • Total nonlinear load <25% of system kVA • Adding capacitors to individual motors

When is resonance not a concern ?

Page 38: McGill Power Sales & Engineering, INC

38

Resonance will happen when: Ht = (Sqrt ((xfmer kva / z)/kvar)) Ht = (Sqrt((1000/.058)/300) Ht = (Sqrt(17,241/300)) Ht = (Sqrt (57.47)) Ht = 7.58 • Record harmonic data. • Determine resonance points. • Compare to required kVAr.

How to know for sure?

Page 39: McGill Power Sales & Engineering, INC

39

?

Questions

Page 40: McGill Power Sales & Engineering, INC

40

Power Quality Experience Center and Lab • Overview of Lab and Capabilities

• Purpose • To demonstrate and Test PQ

Problems and Solutions • Power Quality solutions, especially

harmonic solutions, are difficult to understand

• Demystify solutions – mis-information and confusion regarding PQ and energy savings

• Equipment (Harmonic Related) • 18 Pulse Drives

• HMT’s • Active Filters • Broadband Filters

• Link:http://www.eaton.com/EatonCom/Markets/Electrical/ServicesSupport/Experience/index.htm – Simply search on Google for Eaton Experience Center

• Passive (Fixed) Filters • Passive (Switched) Filters • Active Rectifier (UPS) • Reactors

Page 41: McGill Power Sales & Engineering, INC

41

Thank You.