54 Technical modifications reserved
MCCBs and trip-free switches h400-h630
Designation In
Moulded case circuit breakers
h400, h630
Electronic trip unit LSI:
- long delay ( thermal equivalent)
adjustable:
Ir = 0.4 to 1 x In
- short delay (magnetic equiva-
lent) adjustable:
2.5 to 10 x Ir (400A)
2.5 to 8 x Ir (630A)
- time delay: 0,1 - 0,2 s
3P & 4P (adjustable neutral 0 -
50% - 100%).
Mechanical test button,
lockable settings
Cat. ref.
3P 4P
MCCBs h630 50kA
LSI
250A
400A
630A
HND250H
HND400H
HND630H
HND251H
HND401H
HND631H
Characteristics
breaking capacity
Icu : 50 kA (400/415 V AC)
Ics: 50 kA
MCCBs h630 70kA
LSI
250A
400A
630A
HED250H
HED400H
HED630H
HED251H
HED401H
HED631H
breaking capacity
Icu : 70 kA (400/415 V AC)
Ics: 50 kA
Trip-free switches 400A
630A
HCD400H
HCD630H
HCD401H
HCD631H
suitable for AC 22A / AC 23A
Ue: 415 V AC
Icw (0,3s) = 5kA
Connection:
Directly on copper cable terminal,
with end lug max. width: 30 mm
Comply with IEC 60 947-2.
Trip-free switches
Allows tripping at distance using
a voltmetrical trip unit (optional)
Comply with IEC 60 947-3.
AC 23A / DC 22A
Add-on blocks
For h630 (LSI) devices
These devices are intended to be
fixed at the bottom of the
devices.
Fixed version: 300mA
sensitivity and instantaneous
tripping
Adjustable version: sensitivity
from 30mA to 6A, tripping from
instantaneous to 1s delay.
Test button for differential
functioning check.
Mechanical test button.
LED or remote signal for tripping
or advance warning (25-50% l n).
Type A (for fault component DC
pulsating current) and HI
(reinforced immunity against
unexpected tripping).
Comply with IEC 60 947-2.
Add-on blocks
(only for h630)
400A
500A
-
-
HBD401H
HBD631H
adjustable sensitivity l n:
0,03 - 0,1 - 0,3 - 1 - 3 - 6A
adjustable tripping
instantaneous
time delay:
0,06s - 0,15s - 0,3s - 0,5s - 1s
HBD401H
HND630H
HXC021H HXC024H
55Technical modifications reserved
Designation Characteristics
Indication contacts
- 1 changeover switch (ON/OFF):
indicates the position of the
MCCB is “open” or “close”.
- 1 changeover alarm contact:
indicates MCCB tripping.
Coil connection
Connection capacity:
0,75mm2 flexible or rigid cables
Optional connection cables.
The cable capacity of the
terminals is 0,5 to 1,25 mm2.
Auxiliary contacts
AX
AL
1 changeover contact
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC
1 changeover alarm contact
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC
low level contact (ON/OFF)
125 V AC
1 NO + 1 NC
low level alarm contact
125 V AC
1 NO + 1 NC
HXC021H
HXC024H
HXC025H
HXC026H
Shunt trips
SH
24 V DC
48 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC
HXC001H
HXC002H
HXC003H
HXC004H
HXC005H
Undervoltage releases
UV
24 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC
HXC011H
HXC013H
HXC014H
HXC015H
Cat. ref.
Shunt trip
Remotes tripping of MCCBs or
trip-free switches.
Operating voltage: 0,7 to 1,1 x
Un
Under voltage release
Allows the tripping of MCCBs or
trip-free switches when voltage
level drop between 35 and 70%
of Un. Pick up voltage 0,85 x Un
Direct rotary handle
- padlockable
- equipped with front cover and
handle
- fixing without any additional
screw.
Extended rotary handle
- IP 55
- supplied complete with shaft
and handle.
Delayed undervoltage releases
DUVR
24 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC
HXD051H
HXD053H
HXD054H
HXD055H
Characteristics Cat. ref.
3P 4P
HXC051H
HXC053H
HXC054H
HXC055H
Accessories for MCCBs and trip-free switches h400-h630
HXC004H
HXC014H
Accessories for MCCBs and trip-free switches h400-h630
56 Technical modifications reserved
Direct rotary handle padlockable handle
max Ø 6 mm
HXD030H
Extended rotary handle padlockable handle
max Ø 8 mm
HXD031H
Padlock to mount on MCCBs for
handle locking
for 3 padlock
Ø 5 - 8 mm2 max
HXD039H
Designation Characteristics Cat. ref.
HXD030H
HXD039H
Interlocking wire type HXD065HHXD065H
Motor operators 24-48 V DC
100-240 V AC
HXD040H
HXD042H
HXD040H
HXD042H
HXD042H
Accessories for MCCBs and trip-free switches h400-h630
57Technical modifications reserved
Designation Characteristics Cat. ref.
3P 4P
Collar terminals set of 3 or 4 terminals for
copper conductors 240
mm2
set of 3 or 4 terminals for
aluminium conductors
1 x 35 - 240 mm2
set of 3 or 4 terminals for
multiple aluminium
conductors
2 x 35 - 240 mm2
HYD004H
HYD006H
HYD008H
HYD003H
HYD005H
HYD007H
Extended connections set of 4 pieces for
straight connections
spreader connections
HYD010H
HYD013H
HYD012H
HYD015H
HYD010H
HYD013H
HYD011H
HYD014H
Terminal covers for extended straight connections
for extended spreader connections
for rear connections
for collar terminals
HYD022H
HYD024H
HYD026H
HYD028H
HYD021H
HYD023H
HYD025H
HYD027H
In
250 - 400A
250 - 400 -
630A
250 - 400 -
630A
250 - 400A
630A
250 - 400A
630A
HYD003H
HYD006H
HYD008H
HYD015H
HYD022H
HYD010H
58 Technical modifications reserved
Accessories for MCCBs and trip-free switches h400-h630
Ring lugs compact lugs 120 mm2 Ø10
compact lugs 150 mm2 Ø10,5
compact lugs 185 mm2 Ø10,5
compact lugs 185 mm2 Ø12,8
suitable with spreader
compact lugs 240 mm2 Ø12,8
suitable with spreader
HYD093H
HYD095H
HYD096H
HYD097H
HYD098H
Designation Characteristics Cat. ref.
Rear connections HYD032H
HYD034H
HYD031H
HYD033H
250 - 400A
630A
Connecting kit HYA035HHYA035H0,75 mm2
set of 3 x 2 wires
length: 1,30m
HYD033H
Designation Characteristics Cat. ref.
3P 4P
In
59Technical modifications reserved
MCCBs, trip-free switchesh400 - h630
MCCBs
Settings
Magnetic and thermal settings
TM
400 A126
8 10
10,63
0,8
Ir (x In) Ii (x In)
B
A
220/240 V
AC
(kA)
380/415 V
AC
(kA)
660/690 V
AC
(kA)
H400/H630
HND
Icu 85 50 20
Ics 85 50 15
H630
HED
Icu 100 70 20
Ics 85 50 15
H630
HCD
Icm _ 9 _
Icw _ 5 kA-0,3 s _
Thermal adjustment from 0,63 to 1 x In
Magnetic adjustment from 6 to 12 x In
MCCBs, trip-free switchesh400 - h630
60 Technical modifications reserved
4
2.5 5 10 14
0.1S0.2S
5,6,7
7
6
5
31,2
4
3
1
2
T
x Ir I
Ir ajustable
Electronic trip unit setting (LSI)
LSI
250/400/630 A1 B2
3
1
0,4
0,5
0,8
0,63 0,95
0,90,85
1
2
4
3
6
7
5
CharacteristicsIr (A)
TEST INPICK UP
ON 1xIR
OFF 0,5xIR
NP
Neutral settings:
� Long delay current Ir setting
� Other curve characteristics setting (tr, Isd, tsd)
� Neutral protection against overloads setting
L - Long delay - protection against overloads: Ir and tr
settings
S - Short delay - protection against short circuits: Isd
and tsd settings
I - Instantaneous - max. instantaneous threshold (< 10
ms) in case of short circuit: 2,5 to 10 x Ir (250 - 400A)
and 2,5 to 8 x Ir (630A).
(*) Characteristic 1 : use for generators protection.
Characteristic 2 to 4 - standard protection : options allow coordination optimisation with other products.
Characteristic 5 to 7 - motor protection: use positions according to motor starting characteristics.
LSI
In A
250 A / 400 A 630 A
Long Time Delay Short TimeDelay
Inst Long Time Delay Short Time Delay
Inst
Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr) Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr)
�
�Ir (x In)
0,4 OK OK
0,5 OK OK
0,63 OK OK
0,8 OK OK
0,85 _ OK
0,9 OK OK
0,95 OK OK
1 OK OK
�
�Characteristics
1 11s at 2 xlr 2,5 0,1 14
(max
13 x
In)
11s at 2 xlr 2,5 0,1 14
(max
10 x
In)
2 21s at 2 xlr 21s at 2 xlr
3 5 5
4 5 s at 6 xlr 10 5 s at 6 xlr 8
5 10 s at 6 xlr 0,2 10 s at 6 xlr 0,2
6 19 s at 6 xlr 16 s at 6 xlr
7 29 s at 6 xlr _ _ _
��Neutral
protection
0%
50%
100%
MCCBs, trip-free switchesh400 - h630
61Technical modifications reserved
0.01
0.1
1
10
100
1000
10000
Tem
ps d
e d
écle
nch
em
en
t (s
)
100001000100%Ir
3
1, 2, 3, 4
5, 6
1 24
5 67
Electronic trip unit setting (LSI)
MCCB h630 LSI (250A and 400A)
IR (A)
LTD Pick-up current IR xIn 0,4 0,5 0,63 0,8 0,9 0,95 1
Characteristics No. 1 2 3 4 5 6 7
Standard LTD tR (s) 11 21 21 5 10 19 29
200% x I R 600% x I R
STD Isd xIR 2,5 5 10
tsd (s) 0,1 0,2
INST Ii xIR 14 (max : 13 x In)
Optional N IN xIn 0 - 0,5 - 1
tN (s) tN=tR
Trip
pin
g t
ime (s)
Tripping curve
MCCB h630 LSI (250A and 400A)
62 Technical modifications reserved
MCCBs, trip-free switchesh400 - h630
Electronic trip unit setting (LSI)
MCCB h630 LSI (630A electronic)
IR (A)
LTD Pick-up current IR xIn 0,4 0,5 0,63 0,8 0,85 0,9 0,95 1
Characteristics No. 1 2 3 4 5 6
Standard LTD tR (s) 11 21 21 5 10 16
200% x I R 600% x I R
STD Isd xIR 2,5 5 8
tsd (s) 0,1 0,2
INST Ii xIR 14 (max : 13 x In)
Optional N IN xIn 0 - 0,5 - 1
tN (s) tN=tR
0.01
0.1
1
10
100
1000
10000
Tem
ps d
e d
écle
nch
em
en
t (s
)
100001000100
3
1, 2, 3, 4
5, 6
1 24 5
6
%Ir
Trip
pin
g t
ime (s)
Tripping curve
MCCB h630 LSI (630A electronic)
MCCBs, trip-free switchesh400 - h630
63Technical modifications reserved
Thermal constraint curve (Let-through energy)
MCCB h400 TM (400A)
I2t
(x A
s)
2
107
106
105
104
103
108
104103102101 105
HHD... upto 25kAHND... upto 50kA
MCCB h630LSI (250A and 400A)
I2t
(x 1
0
A
s)
62
0,1
1
101
102
101 10210,1
I2t
(x 1
0
A
s)
62
0,1
1
101
102
101 10210,1
MCCB h630 LSI (630A)
HND... upto 50kAHED... upto 70kA
HND... upto 50kAHED... upto 70kA
(kA)
(kA) (kA)
64 Technical modifications reserved
MCCBs, trip-free switchesh400 - h630
Current limiting curve (Let-through peak current)
MCCB h630 LSI (250A and 400A)
MCCB h400 TM
0.1
1
10
100
Ip (kA
)
1001010,1Icc (kA)
0,8
0,5
0,3
0,25
0,7
0,9
0.1
1
10
100
Ip (kA
)
1001010,1Icc (kA)
0,8
0,5
0,3
0,25
0,7
0,9
MCCB h630 LSI (630A)
HND... upto 50kAHED... upto 70kA
HHD... upto 25kAHND... upto 50kAHED... upto 70kA
MCCBs, trip-free switchesh400 - h630
65Technical modifications reserved
Dimensions
MCCBs
145
97
90
260
45 45
A
228
A
(mm)
B
(mm)
C
(mm)
3P 140 45 214
4P 185 45 214
Terminal covers for extended straight connections
B4
80
A DC
A
(mm)
B
(mm)
C
(mm)
D
(mm)
3P 140 85 97 94,5
4P 185 85 97 94,5
Terminal covers for extended spreader connectionsB
CA
A
(mm)
B
(mm)
C
(mm)
3P 180 110 97
4P 240 114 98
Terminal covers for rear connections and collar terminal
CA
B'
B
D
A
(mm)
B
(mm)
B’
(mm)
C
(mm)
D
(mm)
3P 140 3 4,5 97 93
4P 185 3 4,5 97 93
MCCBs, trip-free switchesh400 - h630
66 Technical modifications reserved
Connection
Cable connection (h400 TM 250 - 400A, h630 LSI 250 - 400A)
13
7,0-9,5 Nm
25 maxi.
Extended straight and spreader connections
3P
60
34
9
Ø14
148
4P
30
30
60 60
60 60
208
4P
163
30
30 45 Ø 14
30
4545 45
22
81
51
5
3P
4P55
(250-400A)45
(630A)15
115 (250-400 A)95 (630 A)
5 22,5 Nm8
7,0 - 9,5 Nm
max. 240 mm2
5 25 Nm8
Rear connections
67Technical modifications reserved
MCCBs, trip-free switchesh400 - h630
Connection with end lugs
M 10 30
max.
12max.
1 2
5 22,5 Nm8
Accessories
Direct rotary handle
140 200
103
24
1,5
140
12
7
180,5
x+46,5
27
19,5x
44
12
5
Extended rotary handle
24
4
139,5
16
0
Motor operator
Rated operating voltage
24-48V DC ok
100-240V AC ok
Operating current (A)
24-48V DC 4,3
100-240V AC 0,9
Starting current (A)
24-48V DC 9,8
100-240V AC 3,8
Operating method spring charging
Operating time (s)
ON 0,1
OFF 1,5
RESET 1,5
Operating switch rating
100V, 0.1A, opening voltage 48V, current 1mA
Power supply required
300 VA minimum
Dielectric properties
24-48V DC 1000 V AC
100-240V AC 1500 V AC
220
123
MCCBs, trip-free switchesh400 - h630
68 Technical modifications reserved
Auxiliaries
Auxiliaries for MCCBs and free tripping switches
6
TRIP
AL SH / UVAX
t
e
X
L
SH
UV
DUVR
6
AX
Auxiliary contact
AL
Alarm contact
SH
Shunt trip
UV
Undervoltage
release
DUVR
Delayed
undervoltage
release
Mounting combination for auxiliaries and releases
69Technical modifications reserved
Add-on block h630
63
10,30,1
0,03
I n (A)
1
0,50,30,15
0,06
Inst.
t (s)
103
10,3
0,1
0,03
1
0,50,30,15
0,06
Inst.
I n (A)
t (s)
5
2
N L1 L2 L3
N L1 L2 L3
incoming
outgoing
test button
CA
50%
electronic
ON
125A
250A
V
1
V
2
Add-on block operatingEarth leakage current (IΔn) and delay (Δt) setting
S (Δ
t)
A (IΔn)
0,03 0,1 0,3 1 3 6
Inst. OK OK OK OK OK OK
0,06 no OK OK OK OK OK
0,15 no OK OK OK OK OK
0,3 no OK OK OK OK OK
0,5 no OK OK OK OK OK
1 no OK OK OK OK OK
Characteristics
Reset button :
Signals add-on block tripping and must be acknowledged before switching on the installation.
Test button for differential functioning : Allows to check the electrical operating of the MCCB / Add-on block association.
Mechanical test button : Allows to check the mechanical operating of the MCCB / Add-on blockassociation.
LED signaling default current level in the installation:25% (orange) and 50% (red) IΔn; green light to signal correct operating.
Remote tripping and advanced warning (50% IΔn) signaling thanks tothese contacts:
When associated with MCCB, the add-on block provides an earth faultprotection and protects against electrical shocks by direct or indirectcontacts.
The add-on blocks are protected against nuisance tripping caused bytransient voltages. It’s able to detect sinusoidal alternating currents andresidual pulsating direct currents ( A type ). It also avoids miss tripping (HI type - High Immunity).
Add-on block h630
70 Technical modifications reserved
5 m
m
ON ON
Add-on block mounting
Dimensions
97
45
45 45 45120,5
16
185
11
9,5
8 22,5 Nm
�
� �
Association / Compatibility
250 - 400A 630A x 0,8
HBD401H
400A
HBD631H
500A
(Ie: 630A x 0,8)
MCCBs and trip-free switches h1000
71Technical modifications reserved
Designation In
Moulded case circuit breakers
h1000
Electronic trip unit LSI:
- long delay (thermal equivalent)
adjustable:
Ir= 0,4 to 1 x In
- short delay (magnetic
equivalent) adjustable:
2,5 to 10 x Ir (630-800A)
and 2,5 to 8 x Ir (1000A)
- time delay: 0,1-0,2 s
Cat. ref.
3P 4P
MCCBs h1000 50kA
LSI
800A
1000A
HNE800H
HNE970H
HNE801H
HNE971H
MCCBs h1000 70kA
LSI
800A
1000A
HEE800H
HEE970H
HEE801H
HEE971H
Designation
breaking capacity
Icu : 50 kA (400/415 V AC)
Ics: 50 kA
breaking capacity
Icu : 70 kA (400/415 V AC)
Ics: 50 kA
Trip-free switches 800A
1000A
HCE800H
HCE970H
HCE801H
HCE971H
suitable for
AC 22A / AC 23A
Ue : 415 V AC
Icw (0,3 s) = 10 kA
3P & 4P (adjustable neutral
0 - 50% - 100%).
Mechanical test button,
lockable settings.
Connection:
Directly on copper cable
terminal,
with end lug max. width: 50 mm
Comply with IEC 60 947-2.
Trip-free switches
Allows tripping at distance using
a voltmetrical trip unit (optional)
Comply with IEC 60 947-3.
AC 23A / DC 22A
HNE970H
Accessories for MCCBs and trip-free switches h1000
72 Technical modifications reserved
Designation Characteristics
Indication contacts
- 1 changeover switch (ON/OFF):
indicates the position of the
MCCB is “open” or “close”.
- 1 changeover alarm contact:
indicates MCCB tripping.
Coil connection
Connection capacity:
0,75mm2 flexible or rigid cables
Optional connection cables.
Cat. ref.
The cable capacity of the
terminals is 0,5 to 1,25 mm2.
Shunt trip
Remotes tripping of MCCBs or
trip-free switches.
Operating voltage:
0,7 to 1,1 x Un
Under voltage release
Allows the tripping of MCCBs or
trip-free switches when voltage
level drop between 35 and 70%
of Un. Pick up voltage 0,85 x Un
Shunt trips
SH
24 V DC
48 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC
HXC001H
HXC002H
HXC003H
HXC004H
HXC005H
Undervoltage releases
UV
24 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC
HXC011H
HXC013H
HXC014H
HXC015H
HXC021H HXC024H
Auxiliary contacts
AX
AL
1 changeover contact (ON/OFF)
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC
1 changeover alarm contact
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC
Low level contact (ON/OFF)
125 V AC
1 NO + 1 NC
Low level alarm contact
125 V AC
1 NO + 1 NC
HXC021H
HXC024H
HXA025H
HXA026H
HXC004H
HXC014H
Accessories for MCCBs and trip-free switches h1000
73Technical modifications reserved
Designation Characteristics
Direct rotary handle
- padlockable
- equipped with front cover and
handle
- fixing without any additional
screw.
Cat. ref.
3P 4P
Terminal covers for extended connections
for rear connections
HYE022H
HYE026H
HYE021H
HYE025H
In
Extended rotary handle
- IP 55
- supplied complete with shaft
and handle.
Delayed undervoltage releases
DUVR
24 V DC
110 - 120 V AC
220 - 240 V AC
380 - 415 V AC
HXE051H
HXE053H
HXE054H
HXE055H
HXE051H
HXE053H
HXE054H
HXE055H
Collar terminals set of 3 or 4 terminals for
conductors 4 x 35 - 240 mm2
HYE008HHYE007H630-800A
Connecting kits HYA035HHYA035H0,75 mm2
set of 3 x 2 wires
length: 1,30m
Rear connections HYE032H
HYE034H
HYE031H
HYE033H
630-800A
1000A
HYE031H
Accessories for MCCBs and trip-free switches h1000
74 Technical modifications reserved
Interlocking wire type HXE065H
Direct rotary handles padlockable handle HXE030H
Extended rotary handles padlockable handle HXE031H
Padlocks to mount on MCCB for
handle locking
for 3 padlock
max Ø 8 mm
HXD039H
Motor operators 24 - 48V DC
100 - 240V AC
HXE040H
HXE042H
Designation Characteristics Cat. ref.
HXD039H
MCCBs, trip-free switchesh1000
75Technical modifications reserved
MCCBs
Electronic trip unit settings (LSI)
1
0,4
0,5
0,8
0,63 0,95
0,90,85
1
2
4
3
6
7
5
CharacteristicsIr (A)
TEST INPICK UP
ON 1xIR
OFF 0,5xIR
NP
1 2
3
220/240 V
AC
(kA)
380/415 V
AC
(kA)
660/690 V
AC
(kA)
HNEIcu 85 (630-800A), 75 (1000A) 50 20
Ics 85 (630-800A), 75 (1000A) 50 20
HEEIcu 100 70 20
Ics 100 (630-800A), 75 (1000A) 50 20
HCEIcm _ 17 _
Icw _ 10 kA-0,3 s _
L - Long delay - protection against overloads: Ir and tr settings
S - Short delay - protection against short circuits: Isd and tsd set-
tings
I - Instantaneous - max. instantaneous threshold (< 10 ms) in case of
short circuit: 2,5 to 10 x Ir (630-800A) and 2,5 to 8 x Ir (1000A).
1
2
4
5,6,7
7
6
5
31,2
4
3
1
2
T
x Ir I
Ir ajustable
0,2S
0,1S
2,5 5 10 14
LSI
In A
630-800 A 1000 A
Long Time Delay Short TimeDelay
Inst Long Time Delay Short TimeDelay
Inst
Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr) Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr)
�
�
Ir (x In)
0,4 OK OK
0,5 OK OK
0,63 OK OK
0,8 OK OK
0,9 OK OK
0,95 OK OK
1 OK OK
�
�
Characteristics*
1 11s at 2 xlr 2,5 0,1 14
(max
12 x
In)
11s at 2 xlr 2,5 0,1 14
(max
10 x
In)
2 21s at 2 xlr 21s at 2 xlr
3 5 5
4 5 s at 6 xlr 10 5 s at 6 xlr 8
5 10 s at 6 xlr 0,2 10 s at 6 xlr 0,2
6 19 s at 6 xlr 16 s at 6 xlr
7 29 s at 6 xlr _ _ _
��
Neutral
protection
0%
50%
100%
(*) Characteristic 1 : use for generators protection.
Characteristic 2 to 4 - standard protection : options allow coordination optimisation with other products.
Characteristic 5 to 7 - motor protection: use positions according to motor starting characteristics.
MCCBs, trip-free switchesh1000
76 Technical modifications reserved
Tripping curve
MCCB h1000 LSI (630-800A)
Electronic trip unit setting (LSI)
MCCBs 630-800A electronic
IR (A)
LTD Pick-up current IR xIn 0,4 0,5 0,63 0,8 0,9 0,95 1
Characteristics No. 1 2 3 4 5 6 7
Standard LTD tR (s) 11 21 21 5 10 19 29
200% x I R 600% x I R
STD Isd xIR 2,5 5 10
tsd (s) 0,1 0,2
INST Ii xIR 14 (max : 12 x In)
Optional NP IN xIR 0,5 or 1 or NON (IN x 105% NT, IN x 120% T)
tN (s) IN=tR
MCCBs, trip-free switchesh1000
77Technical modifications reserved
Tripping curve
MCCB h1000 LSI (1000A)
Electronic trip unit setting (LSI)
MCCBs 1000A electronic
IR (A)
LTD Pick-up current IR xIn 0,4 0,5 0,63 0,8 0,9 0,95 1
Characteristics No. 1 2 3 4 5 6
Standard LTD tR (s) 11 21 21 5 10 16
200% x I R 600% x I R
STD Isd xIR 2,5 5 8
tsd (s) 0,1 0,2
INST Ii xIR 14 (max : 10 x In)
Optional NP IN xIn 0,8
tN (s) IN=tR
MCCBs, trip-free switchesh1000
78 Technical modifications reserved
Thermal constraint curve (Let-through energy)
MCCB h1000
Current limiting curve (Let-through peak current)
MCCB h1000
MCCBs, trip-free switchesh1000
79Technical modifications reserved
Dimensions
MCCBs
145
99,5
35 10
90
433
40 70
273
403
331
B
A
243
Terminal covers for extended straight connections
A
(mm)
B
(mm)
C
(mm)
3P 215 130 99,5
4P 285 130 99,5
A
(mm)
B
(mm)
D
(mm)
3P 210 180 243
4P 280 250 243
A C
53
4
B
80 Technical modifications reserved
MCCBs, trip-free switchesh1000
Connection
Extended straight connections
40
36 Ø13
1
Direct cable connection on terminal
Copper with conductor max. width: 50 mm
2
CA
B A
(mm)
B
(mm)
C
(mm)
3P 210 14 101
4P 280 18 99
Terminal covers for rear connections
5 65,7 Nm19
MCCBs, trip-free switchesh1000
81Technical modifications reserved
Connection with end lugs
1 2
Rear connections
90°
58
12
2
121258
12
24
3
28
8 (1
00
0 A
)2
85
(8
00
A)
20 36
Ø 13
601010
6010
1000 A
800 A
1000A:
vertical only.
630-800A:
vertical or horizontal
position.
MCCBs, trip-free switchesh1000
82 Technical modifications reserved
Accessories
Direct rotary handle
120
12
7
120
12
7
Extended rotary handle
140
16
0
Motor operator
Rated operating voltage
24-48V DC ok
100-240VAC
ok
Operating method spring charging
Power supply required300 VA minimum
Dielectric properties
24-48V DC 1000 V AC
100-240VAC
1500 V AC
213
113,5
200
103
12
5
180,5
92
27
322
19,5
45
83Technical modifications reserved
MCCBs, trip-free switchesh1000
Auxiliaries
Auxiliaries for MCCBs and free tripping switches
TRIP
6
1
2
Mounting combination for auxiliaries and releases
AL SH / UVAX
HXC 024 H
HXC 026 H
L
X
HXC 021 H
HXC 025 H
SH
UV
DUVR
3 P
4 P
AX
Auxiliary contact
AL
Alarm contact
SH
Shunt trip
UV
Undervoltage
release
DUVR
Delayed
undervoltage
release
MCCBs and trip-free switches h1600
84 Technical modifications reserved
Designation In
Moulded case circuit
breakers h1600,
selection and protection
Electronic trip unit LSI
- Long delay (thermal equivalent)
adjustable:
Ir = 0,4 to 1 x In
- short delay (magnetic equiva-
lent) adjustable:
2,5 to 10 x Ir
- time delay: 0,1-0,2 s
3 pole, 3 trip units,
Cat. ref.
3P 4P
MCCBs h1600 50kA
LSI
1250A
1600A
HNF980H
HNF990H
HNF981H
HNF991H
MCCBs h1600 70kA
LSI
1250A
1600A
HEF980H
HEF990H
HEF981H
HEF991H
Designation
breaking capacity
Icu : 50 kA (400/415 V AC)
Ics: 50 kA
breaking capacity
Icu : 70 kA (400/415 V AC)
Ics: 50 kA
Trip-free switches 1250A
1600A
HCF980H
HCF990H
HCF981H
HCF991H
suitable for
AC 22A / AC 23A
Ue : 415 V AC
Icw (0,3 s) = 20 kA
4 pole, 4 trip units,
adjustable neutral 0 - 50% -
100%
Mechanical test button,
lockable settings.
Connection:
Directly on copper cable termi-
nal,
with end lug max. width: 60 mm
Comply with IEC 60 947-2.
Trip-free switches
Allows tripping at distance using
a voltmetrical trip unit (optional)
Comply with IEC 60 947-3.
AC 23A / DC 22A
HNF990H
85Technical modifications reserved
Accessories for MCCBs and trip-free switches h1600
Designation Characteristics
Indication contacts
- 1 changeover switch (ON/OFF):
indicates the position of the
MCCB is “open” or “close”.
- 1 changeover alarm contact:
indicates MCCB tripping.
Coil connection
Connection capacity:
0,75mm2 flexible or rigid cables
Optional connection cables.
The cable capacity of the
terminals is 0,5 to 1,25 mm2.
Cat. ref.
Shunt trip
Remotes tripping of MCCBs or
trip-free switches.
Operating voltage:
0,7 to 1,1 x Un
Under voltage release
Allows the tripping of MCCBs or
trip-free switches when voltage
level drop between 35 and 70%
of Un. Pick up voltage 0,85 x Un
Direct rotary handle
- padlockable
- equipped with front cover and
handle
- fixing without any additional
screw.
Extended rotary handle
- IP 55
- supplied complete with shaft
and handle.
Rear connection: included
Shunt trips
SH
24 V DC
48 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC
HXC001H
HXC002H
HXC003H
HXC004H
HXC005H
Undervoltage releases
UV
24 V DC
100 - 120 V AC
200 - 240 V AC
380 - 450 V AC
HXC011H
HXC013H
HXC014H
HXC015H
HXC021H HXC024H
Auxiliary contacts
AX
AL
1 changeover contact (ON/OFF)
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC
1 changeover alarm contact
250 V AC / 3A
125 V DC / 0,4A
1 NO + 1 NC
Low level contact (ON/OFF)
125 V AC
1 NO + 1 NC
Low level alarm contact
125 V AC
1 NO + 1 NC
HXC021H
HXC024H
HXA025H
HXA026H
HXC004H
HXC014H
Headline 1Headline 2
86 Technical modifications reserved
Undervoltage releases
UV
24 V DC
110 - 120 V AC
220 - 240 V AC
380 - 415 V AC
HXE011H
HXE013H
HXE014H
HXE015H
Direct rotary handle padlockable handle, max Ø 8 mm HXF030H
Extended rotary handle padlockable handle, max Ø 8 mm HXF031H
Padlock to mount on MCCB for
handle locking
for 3 padlock
max Ø 8 mm
HXF039H
Motor operators 24 V DC
200 - 230 V AC
HXF040H
HXF042H
Headline 1Headline 2
87Technical modifications reserved
Interphase barriers 3/4 P HYF019H
Delayed undervoltage
releases
DUVR
24 V DC
110 - 120 V AC
220 - 240 V AC
380 - 415 V AC
HXF051H
HXF053H
HXF054H
HXF055H
Connection kit HYA035H0,75 mm2
set of 3 x 2 wires
length: 1,30m
MCCBs, trip-free switchesh1600
88 Technical modifications reserved
MCCBs
Electronic trip unit settings (LSI)
220/240 V
AC
(kA)
380/415 V
AC
(kA)
660/690 V
AC
(kA)
HNFIcu 100 50 25
Ics 75 50 25
HEFIcu 100 70 45
Ics 75 50 34
HCFIcm 45 kA
Icw 20 kA-0,3 s
L - Long delay - protection against overloads: Ir and tr settings
S - Short delay - protection against short circuits: Isd and tsd settings
I - Instantaneous - max. instantaneous threshold (< 10 ms) in case of short
circuit: 2,5 to 10 x Ir.
�
Ir(A)
�
Im
�
N
LSI 0,4 - 1
In
2,5 -
10 Ir
0%
50%
100 %
LSI
In A
1250 - 1600 A
Long Time Delay Short Time Delay Inst
Ir (x In) tr (s) isd (xlr) tsd (s) li (xlr)
�
�
Ir (x In)
0,4 OK
0,5 OK
0,63 OK
0,8 OK
0,9 OK
0,95 OK
1 OK
�
�
Characteristics*
1 11s at 2 xlr 2,5 0,1 14 (max 12 x
In)2 21s at 2 xlr
3 5
4 5 s at 6 xlr 10
5 10 s at 6 xlr 0,2
6 19 s at 6 xlr
7 29 s at 6 xlr
��
Neutral
protection
0%
50%
100%
(*) Characteristic 1 : use for generators protection.
Characteristic 2 to 4 - standard protection : options allow coordination optimisation with other products.
Characteristic 5 to 7 - motor protection: use positions according to motor starting characteristics.
7
0,4
0,5
0,8
0,63 1
0,950,9
1
2
4
3
65
CharacteristicsIr (A)
TEST INPICK UPOFF
ON
MCCBs, trip-free switchesh1600
89Technical modifications reserved
Tripping curve
MCCB h1600 LSI
2
1
3
4
5
6
7
5,6,7
1,2,3,4
tim
e
80
90
10
0
12
5
20
0
25
0
50
0
60
0
70
0
80
0
90
0
10
00
15
00
25
00
30
00
40
00
50
00
60
00
20
00
70
00
80
00
15
0
[%]
4
2
150
40
30
20
10
8
654
3
2
1
50
40
30
20
3
10
8
6
54
3
2
1
0.8
0.60.5
0.4
0.3
0.2
0.1
0.08
0.060.050.04
0.03
0.02
0.01
0.005
ho
ur
min
ute
seco
nd
IR
Electronic trip unit setting (LSI)
MCCBs 1250A and 1600A electronic
IR (A)
LTD Pick-up current IR xIn 0,4 0,5 0,63 0,8 0,9 0,95 1
Characteristics No. 1 2 3 4 5 6 7
Standard LTD tR (s) 11 21 21 5 10 19 29
200% x I R 600% x I R
STD Isd xIR 2,5 5 10
tsd (s) 0,1 0,2
INST Ii xIR 14 (max : 12 x In)
Optional NP IN xIR 0,5 or 1 or NON (IN x 105% NT, IN x 120% T)
tN (s) IN=tR
MCCBs, trip-free switchesh1600
90 Technical modifications reserved
Thermal constraint curve (Let-through energy)
MCCB h1600
I2t
(x 1
0
A
s)
62
109
1010
104 105
108
107
103102
Current limiting curve (Let-through peak current)
MCCB h1600
1000
100
10
1
0.1
Max.
Let-
thro
ugh
peak
curr
ent
(kA
)
001011 1000
Prospective short-circuit current in RMS sym. (kA)
HNE…up to 50kAHEE…up to 70kA
HNF... upto 50kAHEF... upto 70kA
MCCBs, trip-free switchesh1600
91Technical modifications reserved
Dimensions
MCCBs
191
140
95570
44,5 46 2070
370
541
476
11
BA
A
(mm)
B
(mm)
3P 210 185
4P 280 255
Connection
Connection with end lugs
65 Nm
1 2
5 65,7 Nm19
MCCBs, trip-free switchesh1600
92 Technical modifications reserved
140
16
5
268
136
257 45
12
5
140
322
19,5
27
16
5
210
17
3,5
Motor operator
Rated operating voltage
24V DC ok
200-230V AC ok
Operating current (A) 200-230V AC 1
Starting current (A) 200-230V AC 3,2
Operating method spring charging
Operating time (s)
ON 0,06
OFF 3
RESET 3
Power supply required 300 VA minimum
Dielectric properties24V DC 500 V AC
200-230V AC 1500 V AC
260,5
130
Accessories
Direct rotary handle Extended rotary handle
93Technical modifications reserved
MCCBs, trip-free switchesh1600
Auxiliaries
Auxiliaries for MCCBs and free tripping switches
TRIP
1
Mounting combination for auxiliaries and releases
AL
SH / UV
AX
HXC 024 H
HXC 026 H
AL
AX
HXC 021 H
HXC 025 H
SH
UV
DUVR
3 P
4 P
AX
Auxiliary contact
AL
Alarm contact
SH
Shunt trip
UV
Undervoltage
release
DUVR
Delayed
undervoltage
release
94 Technical modifications reserved
Cascading according to CEI 60947-2MCCBs x160, x250, h250, h630, h1000, h1600
Upstream
x160 TM x250 TM h250 TM
HDA HHA HNA HHB HNB HHG HNG
18 kA 25 kA 40 kA 25 kA 40 kA 25 kA 50 kA
Do
wnstr
eam
x160 TM
HDA 18 kA - 25 kA 40 kA 25 kA 40 kA 25 kA 50 kA
HHA 25 kA - 30 kA 40 kA 30 kA 40 kA 25 kA 50 kA
HNA 40 kA - - 40 kA - 40 kA - 50 kA
x250 TMHHB 25 kA - - - 25 kA 40 kA 25 kA 50 kA
HNB 40 kA - - - - 40 kA - 50 kA
h250 TM
HHG 25 kA - - - - 40 kA 25 kA 50 kA
HNG 50 kA - - - - - - 50 kA
HEG 65 kA - - - - - - -
h250 LSIHNC 50 kA - - - - - - -
HEC 70 kA - - - - - - -
h400 TMHHD 25 kA - - - - - - -
HND 50 kA - - - - - - -
h630 LSIHND 50 kA - - - - - - -
HED 70 kA - - - - - - -
h1000 LSIHNE 50 kA - - - - - - -
HEE 70 kA - - - - - - -
h1600 LSIHNF 50 kA - - - - - - -
HEF 70 kA - - - - - - -
Upstream
x160 TM x250 TM h250 TM
HDA HHA HNA HHB HNB HHG HNG
25 kA 35 kA 85 kA 35 kA 85 kA 35 kA 85 kA
Do
wnstr
eam
x160 TM
HDA 25 kA - 35 kA 85 kA 35 kA 85 kA 35 kA 85 kA
HHA 35 kA - 50 kA 85 kA 50 kA 85 kA 35 kA 85 kA
HNA 85 kA - - 85 kA - 85 kA - 85 kA
x250 TMHHB 35 kA - - - 35 kA 85 kA 35 kA 85 kA
HNB 85 kA - - - - 85 kA - 85 kA
h250 TM
HHG 35 kA - - - - 85 kA 35 kA 85 kA
HNG 85 kA - - - - - - 85 kA
HEG 85 kA - - - - - - -
h250 LSIHNC 85 kA - - - - - - -
HEC 100 kA - - - - - - -
h400 TMHHD 35 kA - - - - - - -
HND 85 kA - - - - - - -
h630 LSIHND 85 kA - - - - - - -
HED 100 kA - - - - - - -
h1000 LSIHNE 85 kA - - - - - - -
HEE 100 kA - - - - - - -
h1600 LSIHNF 85 kA - - - - - - -
HEF 100 kA - - - - - - -
Cascading values in kA according to CEI 947-2 Network : 3 phases + neutral 380V - 415V AC
Cascading values in kA according to CEI 947-2 Network : 3 phases + neutral 220V - 240V AC
95Technical modifications reserved
h250 LSI h400 TM h630 LSI h1000 LSI h1600 LSI
HEG HNC HEC HHD HND HND HED HNE HEE HNF HEF
65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA
65 kA 50 kA 40 kA 25 kA 30 kA 30 kA 40 kA 30 kA 40 kA 30 kA 40 kA
65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA
65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 50 kA
65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA
65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 50 kA
65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 50 kA 50 kA 50 kA 25 kA 25 kA
65 kA 50 kA 70 kA - 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA
65 kA - 70 kA - - - 70 kA - 70 kA - 70 kA
- 50 kA 70 kA - 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA
- - 70 kA - - - 70 kA - 70 kA - 70 kA
- - 70 kA 25 kA 50 kA 50 kA 50 kA 50 kA 70 kA 25 kA 25 kA
- - - - 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA
- - - - - 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA
- - - - - - 70 kA - 70 kA - 70 kA
- - - - - - - 50 kA 70 kA 50 kA 70 kA
- - - - - - - - 70 kA - 70 kA
- - - - - - - - - 50 kA 70 kA
- - - - - - - - - - 70 kA
h250 LSI h400 TM h630 LSI h1000 LSI h1600 LSI
HEG HNC HEC HHD HND HND HED HNE HEE HNF HEF
85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA
85 kA 50 kA 85 kA 35 kA 85 kA 50 kA 85 kA 50 kA 85 kA 50 kA 85 kA
85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA
85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA
85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA
85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA
85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA 85 kA
85 kA 85 kA 100 kA - 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA
85 kA 85 kA 100 kA - - - 100 kA - 100 kA - 100 kA
- 85 kA 100 kA - 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA
- - 100 kA - - - 100 kA - 100 kA - 100 kA
- - 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA
- - - - 85 kA 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA
- - - - - 85 kA 100 kA 85 kA 100 kA 85 kA 100 kA
- - - - - - 100 kA - 100 kA - 100 kA
- - - - - - - 85 kA 100 kA 85 kA 100 kA
- - - - - - - - 100 kA - 100 kA
- - - - - - - - - 85 kA 100 kA
- - - - - - - - - - 100 kA
96 Technical modifications reserved
Cascading MCCBs / MCBs
Rangex160 TM x250 TM h250 TM
HDA HHA HNA HHB HNB HHG
Breaking capacity IEC 60898 / 61009-1 - - - - - -
Breaking capacity IEC 60947-2 25 KA 35 kA 85 kA 35 kA 85 kA 35 kA
Curve - - - - - -
Ax8xx 4,5 kA 6 kA B, C 10 kA 10 kA 10 kA 10 kA 10 kA 7,5 kA
Ax9xx 6 kA 10 kA B, C 15 kA 15 kA 15 kA 15 kA 15 kA 12,5 kA
AC1xx, AD1xx, AE1xx, AF1xx, ACx1xx,
ADx1xx, AEx1xx
6 kA - B, C 25 kA 30 kA 50 kA 30 kA 40 kA 30 kA
10 kA - B, C - 35 kA 85 kA 35 kA 50 kA 35 kA
MV, MW 3 kA 10 kA B, C 20 kA 20 kA 30 kA 20 kA 20 kA 20 kA
MU, MT, MV 6 kA 20 kA B, C 25 kA 30 kA 50 kA 30 kA 40 kA 30 kA
NB, NC, ND 10 kA 30 kA B, C, D - 35 kA 85 kA 35 kA 50 kA 35 kA
MHN, MJN 4,5 kA 6 kA B, C 10 kA 10 kA 10 kA 10 kA 10 kA 7,5 kA
MLN 6 kA 7,5 kA B, C 15 kA 15 kA 15 kA 10 kA 10 kA 10 kA
MBN, MCN 6 kA - B, C 25 kA 30 kA 50 kA 30 kA 40 kA 30 kA
MB, MC, NGN 6 kA 20 kA B, C, D 25 kA 30 kA 50 kA 30 kA 40 kA 30 kA
NBN, NCN, NDN 10 kA 30 kA B, C, D - 35 kA 85 kA 35 kA 50 kA 35 kA
NQN, NRN, NSN
- 50 kA B, C, D - - 85 kA - 85 kA -
- 40 kA B, C, D - - 85 kA - 70 kA -
- 30 kA B, C, D - 35 kA 85 kA 35 kA 50 kA 35 kA
MMN 2xx, MMN 3xx - 50 kA magn. - - 85 kA - 85 kA -
MMN 2xx, MMN 3xx - 40 kA magn. - - 85 kA - 70 kA -
HLE, HLF, HLS - 20 kA B, C 25 kA 30 kA 50 kA 30 kA 40 kA 30 kA
HMB, HMC, HMD - 30 kA B, C, D - 35 kA 85 kA 35 kA 60 kA 35 kA
HMJ, HMK - 60 kA B, C - - 85 kA - 85 kA -
HMX - 100 kA C - - - - - -
Rangex160 TM x250 TM h250 TM
HDA HHA HNA HHB HNB HHG
Breaking capacity IEC 60898 - - - - - -
Breaking capacity IEC 60947-2 18 KA 25 kA 40 kA 25 kA 40 kA 25 kA
Curve - - - - - -
MV, MW 3 kA 4,5 kA B, C 10 kA 10 kA 15 kA 10 kA 10 kA 10 kA
MU, MT, MV 6 kA 10 kA B, C 18 kA 20 kA 30 kA 20 kA 20 kA 20 kA
NB, NC, ND 10 kA 15 kA B, C, D 18 kA 25 kA 40 kA 25 kA 30 kA 25 kA
MVN, MWN 3 kA - B, C 10 kA 10 kA 15 kA 10 kA 10 kA 10 kA
MBN, MCN 6 kA - B, C 18 kA 20 kA 30 kA 20 kA 20 kA 20 kA
MB, MC, NGN 6 kA 10 kA B, C, D 18 kA 25 kA 30 kA 20 kA 25 kA 25 kA
NBN, NCN, NDN 10 kA 15 kA B, C, D 18 kA 25 kA 40 kA 25 kA 30 kA 25 kA
NQN, NRN, NSN
- 25 kA B, C, D - 25 kA 40 kA 25 kA 40 kA 25 kA
- 20 kA B, C, D - 25 kA 40 kA 25 kA 35 kA 25 kA
- 15 kA B, C, D 18 kA 25 kA 40 kA 25 kA 30 kA 25 kA
MMN 2xx, MMN 3xx - 25 kA magn. - 25 kA 40 kA 25 kA 40 kA 25 kA
MMN 2xx, MMN 3xx - 30 kA magn. - 25 kA 40 kA 25 kA 35 kA 25 kA
HLE, HLF, HLS 10 kA 10 kA B, C 18 kA 20 kA 30 kA 20 kA 25 kA 20 kA
HMB, HMC, HMD 15 kA 15 kA B, C, D 18 kA 25 kA 40 kA 25 kA 30 kA 25 kA
HMJ, HMK - 30 kA B, C - - 40 kA - 40 kA -
HMX - 50 kA C - - - - - -
Cascading MCCBs / MCBs 1PP+N / 2PP 230V - 240 V IEC 947-2
Cascading MCCBs / MCBs 1PP 230V - 240 V 2PP / 3PP / 3PP+N / 4PP 400 - 415 V IEC 947-2
97Technical modifications reserved
h250 LSI h400 LSI h630 LSI h1000 LSI h1600 LSI
HNG HEG HNC HEC HHD HND HND HED HNE HEE HNF HEF
- - - - - - - - - - - -
85 kA 85 kA 85 kA 100 kA 35 kA 85 kA 85 kA 100 kA 85 kA 100 kA 100 kA 100 kA
- - - - - - - - - - - -
7,5 kA 7,5 kA 10 kA 7,5 kA 10 kA 10 kA 6 kA 6 kA 6 kA 6 kA 6 kA 6 kA
12,5 kA 12,5 kA 15 kA 12,5 kA 15 kA 15 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA
40 kA 40 kA 40 kA 40 kA 25 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA
50 kA 50 kA 50 kA 50 kA 35 kA 40 kA 40 kA 40 kA 30 kA 30 kA 30 kA 30 kA
20 kA 20 kA 20 kA 20 kA 15 kA 15 kA 15 kA 15 kA 10 kA 10 kA 10 kA 10 kA
40 kA 40 kA 40 kA 40 kA 25 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA
50 kA 50 kA 50 kA 50 kA 35 kA 40 kA 40 kA 40 kA 30 kA 30 kA 30 kA 30 kA
7,5 kA 7,5 kA 10 kA 7,5 kA 10 kA 10 kA 6 kA 6 kA 6 kA 6 kA 6 kA 6 kA
10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 7,5 kA 7,5 kA 7,5 kA 7,5 kA 7,5 kA 7,5 kA
40 kA 40 kA 40 kA 40 kA 25 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA
40 kA 40 kA 40 kA 40 kA 25 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA
50 kA 50 kA 50 kA 50 kA 35 kA 40 kA 40 kA 40 kA 30 kA 30 kA 30 kA 30 kA
85 kA 85 kA 85 kA 85 kA - 65 kA 65 kA 65 kA 50 kA 50 kA 50 kA 50 kA
70 kA 70 kA 70 kA 70 kA - 50 kA 50 kA 50 kA 40 kA 40 kA 40 kA 40 kA
50 kA 50 kA 50 kA 50 kA 35 kA 40 kA 40 kA 40 kA 30 kA 30 kA 30 kA 30 kA
85 kA 85 kA 85 kA 85 kA - 65 kA 65 kA 65 kA 50 kA 50 kA 50 kA 50 kA
70 kA 70 kA 70 kA 70 kA - 50 kA 50 kA 50 kA 40 kA 40 kA 40 kA 40 kA
40 kA 40 kA 40 kA 40 kA 25 kA 30 kA 30 kA 30 kA 30 kA 30 kA 20 kA 20 kA
60 kA 60 kA 60 kA 60 kA 35 kA 40 kA 40 kA 40 kA 40 kA 40 kA 30 kA 30 kA
85 kA 85 kA 85 kA 85 kA - 85 kA 85 kA 85 kA 85 kA 85 kA 60 kA 60 kA
- - - - - - - 100 kA - 100 kA 100 kA 100 kA
h250 LSI h400 LSI h630 LSI h1000 LSI h1600 LSI
HNG HEG HNC HEC HHD HND HND HED HNE HEE HNF HEF
- - - - - - - - - - - -
50 kA 65 kA 50 kA 70 kA 25 kA 50 kA 50 kA 70 kA 50 kA 70 kA 50 kA 70 kA
- - - - - - - - - - - -
10 kA 10 kA 10 kA 10 kA 6 kA 6 kA 6 kA 6 kA 4,5 kA 4,5 kA 4,5 kA 4,5 kA
20 kA 20 kA 20 kA 20 kA 15 kA 15 kA 15 kA 15 kA 10 kA 10 kA 10 kA 10 kA
30 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA 15 kA 15 kA
10 kA 10 kA 10 kA 10 kA 6 kA 6 kA 6 kA 6 kA 4,5 kA 4,5 kA 4,5 kA 4,5 kA
20 kA 20 kA 20 kA 20 kA 15 kA 15 kA 15 kA 15 kA 10 kA 10 kA 10 kA 10 kA
20 kA 20 kA 25 kA 20 kA 20 kA 20 kA 20 kA 20 kA 10 kA 10 kA 10 kA 10 kA
30 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA 15 kA 15 kA
40 kA 40 kA 40 kA 40 kA 25 kA 40 kA 40 kA 40 kA 30 kA 30 kA 25 kA 25 kA
35 kA 35 kA 35 kA 35 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 20 kA 20 kA
30 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA 15 kA 15 kA
40 kA 40 kA 40 kA 40 kA 25 kA 40 kA 40 kA 40 kA 30 kA 30 kA 25 kA 25 kA
35 kA 35 kA 35 kA 35 kA 25 kA 25 kA 25 kA 25 kA 25 kA 25 kA 20 kA 20 kA
25 kA 25 kA 25 kA 25 kA 15 kA 15 kA 15 kA 15 kA 15 kA 15 kA 10 kA 10 kA
30 kA 30 kA 30 kA 30 kA 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA 15 kA 15 kA
50 kA 50 kA 50 kA 50 kA - 50 kA 50 kA 50 kA 50 kA 50 kA 35 kA 35 kA
50 kA 50 kA 50 kA 50 kA - 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA
98 Technical modifications reserved
Selectivity chart
Limits (kA)
x160 TM
18/25/40kA
x250 TM
25/40kA
h250 TM
25/50/65 kA
In 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 160A 100A 125A 160A 200A 250A 32A
MH
N
B c
urv
e
6A 1,6 1,7 1,8 2,1 2,6 3,4 4,6 T T T T T T T T T 2,9
10A 1,4 1,5 1,6 1,9 2,3 2,7 3,2 3,8 4,5 5,5 T 5,3 T T T T 2,5
16A - - 1,5 1,7 2 2,3 2,7 3,1 3,6 4,1 5,2 4,3 5,3 T T T 2,2
20A - - - 1,7 2 2,3 2,7 3,1 3,6 4,1 5,2 4,3 5,3 T T T 2,2
25A - - - - 1,9 2,1 2,3 2,6 2,8 3,2 4 3,3 4,1 5,4 T T 2
32A - - - - - 2,1 2,3 2,6 2,8 3,2 4 3,3 4,1 5,4 T T -
40A - - - - - - 1,6 1,9 2,1 2,4 3,1 2,5 3,1 4,2 T T -
MJN
, M
LN
C c
urv
e
1A 1,5 1,6 1,8 2,3 2,9 4 T T T T T T T T T T 3
2A 1,5 1,6 1,8 2,3 2,9 4 T T T T T T T T T T 3
6A 1,3 1,4 1,6 1,9 2,3 2,9 3,9 5,5 T T T T T T T T 2,5
10A 1,1 1,2 1,4 1,7 2 2,4 2,8 3,4 4 4,9 T 4,6 T T T T 2,3
16A - - 1,2 1,5 1,8 2 2,3 2,7 3 3,6 4,6 3,6 4,6 T T T 1,9
20A - - - 1,5 1,8 2 2,3 2,7 3 3,6 4,6 3,6 4,6 T T T 1,9
25A - - - - 1,6 1,8 2 2,2 2,4 2,9 3,6 2,9 3,6 4,8 T T 1,8
32A - - - - - 1,8 2 2,2 2,4 2,9 3,6 2,9 3,6 4,8 T T -
40A - - - - - - 1,4 1,7 1,9 2,2 2,8 2,2 2,8 3,7 5,5 T -
MB
, M
U, M
V
B c
urv
e
6A 1,4 1,5 1,6 1,9 2,3 3 4 5,5 6,7 8,6 T 7,8 T T T T 2,5
10A 1,2 1,3 1,4 1,7 2 2,4 2,8 3,4 4 4,9 6,4 4,7 6,2 8,6 T T 2,2
13A - 1,2 1,3 1,5 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 T 2
16A - - 1,3 0 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 T 2
20A - - - 0 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 T 2
25A - - - - 1,7 1,9 2,1 2,3 2,5 2,9 3,6 3 3,7 4,9 7,4 T 1,8
32A - - - - - 1,9 2,1 2,3 2,5 2,9 3,6 3 3,7 4,9 7,4 T -
40A - - - - - - 1,6 1,7 1,9 2,2 2,8 2,3 2,8 3,8 5,9 9,9 -
50A - - - - - - - 1,4 1,5 1,8 2,3 1,8 2,3 3,2 4,9 8,6 -
63A - - - - - - - - 1,5 1,5 1,8 1,4 1,8 2,4 4,2 7,7 -
MC
, M
N, M
W, M
T
C c
urv
e
0,5A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 T T T T T T T T 2,6
1A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 T T T T T T T T 2,6
2A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 T T T T T T T T 2,6
3A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 T T T 2,2
4A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 T T T 2,2
6A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 T T T 2,2
10A - 1,1 1,25 1,5 1,8 2,1 2,5 3 3,5 4,3 5,6 4,1 5,4 7,6 T T 2
13A - 1 1,1 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 T 1,7
16A - - 1,1 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 T 1,7
20A - - - 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 T 1,7
25A - - - - 1,4 1,6 1,8 2 2,2 2,6 3,2 2,6 3,2 4,3 6,3 9,9 1,6
32A - - - - - 1,6 1,8 2 2,2 2,6 3,2 2,6 3,2 4,3 6,3 9,9 -
40A - - - - - - 1,3 1,5 1,7 2 2,5 2 2,5 3,4 5 8,5 -
50A - - - - - - - 1,1 1,5 1,5 2 1,5 1,9 2,7 4,2 7,3 -
63A - - - - - - - - 1,5 1,5 1,6 1,3 1,6 2,2 3,8 6,7 -
MB
N
B c
urv
e
6A 1,1 1,2 1,3 1,5 1,8 2,4 3,2 4,4 5,4 T T T T T T T 2
10A 0,95 1,05 1,2 1,4 1,6 1,9 2,2 2,7 3,2 3,9 5,1 3,8 5 T T T 1,6
13A - 0,95 1,05 1,2 1,4 1,7 1,9 2,2 2,6 3 3,7 3 3,8 5 T T 1,6
16A - - 1,05 1,2 1,4 1,7 1,9 2,2 2,6 3 3,7 3 3,8 5 T T 1,6
20A - - - 1,2 1,4 1,7 1,9 2,2 2,6 3 3,7 3 3,8 5 T T 1,6
25A - - - - 1,3 1,5 1,7 1,8 2 2,3 2,9 2,4 3 3,9 5,9 T 1,4
32A - - - - - 1,5 1,7 1,8 2 2,3 2,9 2,4 3 3,9 5,9 T -
40A - - - - - - 1,3 1,4 1,5 1,8 2,2 1,8 2,2 3 4,7 T -
50A - - - - - - - 1,1 1,5 1,5 1,8 1,4 1,8 2,6 3,9 T -
63A - - - - - - - - 1,5 1,5 1,6 1,3 1,625 2,1 3,4 T -
MC
N
C c
urv
e
0,5A 1,05 1,1 1,3 1,6 2 2,8 4,5 T T T T T T T T T 2,1
1A 1,05 1,1 1,3 1,6 2 2,8 4,5 T T T T T T T T T 2,1
2A 1,05 1,1 1,3 1,6 2 2,8 4,5 T T T T T T T T T 2,1
3A 0,9 1 1,1 1,4 1,6 2 2,7 3,8 4,6 5,4 T 5,4 T T T T 1,8
4A 0,9 1 1,1 1,4 1,6 2 2,7 3,8 4,6 5,4 T 5,4 T T T T 1,8
6A 0,9 1 1,1 1,4 1,6 2 2,7 3,8 4,6 5,4 T 5,4 T T T T 1,8
10A 0,8 0,9 1 1,2 1,4 1,7 2 2,4 2,8 3,4 4,5 3,3 4,3 T T T 1,6
13A - 0,8 0,9 1,05 1,3 1,5 1,7 1,9 2,1 2,6 3,3 2,6 3,3 4,5 T T 1,4
16A - - 0,9 1,05 1,3 1,5 1,7 1,9 2,1 2,6 3,3 2,6 3,3 4,5 T T 1,4
20A - - - 1,05 1,3 1,5 1,7 1,9 2,1 2,6 3,3 2,6 3,3 4,5 T T 1,4
25A - - - - 1,1 1,3 1,4 1,6 1,8 2,1 2,6 2,1 2,6 3,4 5 T 1,3
32A - - - - - 1,3 1,4 1,6 1,8 2,1 2,6 2,1 2,6 3,4 5 T -
40A - - - - - - 1,05 1,2 1,5 1,6 2 1,6 2 2,7 4 T -
50A - - - - - - - 1 1,5 1,5 1,7 1,3 1,625 2,2 3,4 5,8 -
63A - - - - - - - - 1,5 1,5 1,6 1,3 1,625 2,1 3 5,4 -
T = total selectivity. Each underlined value must be read as T when it is over the breaking capacity range of MCBs or RCBOs.
All values are given with MCCB at the maximum setting.
99Technical modifications reserved
h250 LSI
50/70 kA
h400 TM
25/50 kA
h630 LSI
50/70 kA
h1000 LSI
50/70 kA
h1600 LSI
50/70 kA
63A 100A 125A 160A 200A 250A 40A 125A 250A 250A 400A 250A 400A 630A 630A 800A 1000A 1250A 1600A
5,9 T T T T T 3,1 T T T T T T T T T T T T
4,1 5,9 T T T T 2,6 T T T T T T T T T T T T
3,5 4,7 5,8 T T T 2,4 5,3 T T T T T T T T T T T
3,5 4,7 5,8 T T T 2,4 5,3 T T T T T T T T T T T
3 3,7 4,6 6 T T 2,2 4,1 T T T T T T T T T T T
3 3,7 4,6 6 T T - 4,1 T T T T T T T T T T T
2,3 2,8 3,4 4,6 T T - 3,1 T T T T T T T T T T T
T T T T T T 3,3 T T T T T T T T T T T T
T T T T T T 3,3 T T T T T T T T T T T T
5 T T T T T 2,6 T T T T T T T T T T T T
3,6 5,2 T T T T 2,4 T T T T T T T T T T T T
2,9 3,9 5 T T T 2,1 4,6 T T T T T T T T T T T
2,9 3,9 5 T T T 2,1 4,6 T T T T T T T T T T T
2,4 3,2 4 5,3 T T 1,9 3,6 T T T T T T T T T T T
2,4 3,2 4 5,3 T T - 3,6 T T T T T T T T T T T
2,3 2,4 3,1 4,2 T T - 2,8 T T T T T T T T T T T
5,2 8,7 T T T T 2,7 T T T T T T T T T T T T
3,6 5,2 6,9 9,6 T T 2,3 6,2 T T T T T T T T T T T
3,1 4,2 5,2 6,9 T T 2,1 4,7 T T T T T T T T T T T
3,1 4,2 5,2 6,9 T T 2,1 4,7 T T T T T T T T T T T
3,1 4,2 5,2 6,9 T T 2,1 4,7 T T T T T T T T T T T
2,7 3,3 4,1 5,4 8,2 T 2 3,7 T T T T T T T T T T T
2,7 3,3 4,1 5,4 8,2 T - 3,7 T T T T T T T T T T T
2,1 2,5 3,1 4,2 6,5 T - 2,8 9,9 T T T T T T T T T T
1,7 2 2,5 3,5 5,4 9,6 - 2,3 8,6 T T T T T T T T T T
- 1,6 2 2,7 4,7 8,5 - 1,8 7,7 9,4 T T T T T T T T T
7,3 T T T T T 2,9 T T T T T T T T T T T T
7,3 T T T T T 2,9 T T T T T T T T T T T T
7,3 T T T T T 2,9 T T T T T T T T T T T T
4,4 7,5 9,5 T T T 2,3 8,6 T T T T T T T T T T T
4,4 7,5 9,5 T T T 2,3 8,6 T T T T T T T T T T T
4,4 7,5 9,5 T T T 2,3 8,6 T T T T T T T T T T T
3,2 4,6 6 8,4 T T 2,1 5,4 T T T T T T T T T T T
2,6 3,5 4,5 6,2 9,2 T 1,9 4,1 T T T T T T T T T T T
2,6 3,5 4,5 6,2 9,2 T 1,9 4,1 T T T T T T T T T T T
2,6 3,5 4,5 6,2 9,2 T 1,9 4,1 T T T T T T T T T T T
2,2 2,9 3,6 4,8 7 T 1,7 3,2 9,9 T T T T T T T T T T
2,2 2,9 3,6 4,8 7 T - 3,2 9,9 T T T T T T T T T T
2,1 2,2 2,8 3,8 5,6 9,4 - 2,5 8,5 T T T T T T T T T T
1,3 1,7 2,1 3 4,7 8,1 - 1,9 7,3 8,9 T T T T T T T T T
- 1,3 1,6 2,4 4,2 7,4 - 1,75 6,7 8,2 T T T T T T T T T
4,2 T T T T T 2,2 T T T T T T T T T T T T
2,9 4,2 5,5 T T T 1,8 5 T T T T T T T T T T T
2,5 3,4 4,2 5,5 T T 1,7 3,8 T T T T T T T T T T T
2,5 3,4 4,2 5,5 T T 1,7 3,8 T T T T T T T T T T T
2,5 3,4 4,2 5,5 T T 1,7 3,8 T T T T T T T T T T T
2,2 2,6 3,3 4,3 T T 1,6 3 T T T T T T T T T T T
2,2 2,6 3,3 4,3 T T - 3 T T T T T T T T T T T
1,7 2, 2,5 3,4 5,2 T - 2,2 T T T T T T T T T T T
1,4 1,6 2 2,8 4,3 T - 1,8 T T T T T T T T T T T
- 1,3 1,625 2,2 3,8 T - 1,75 T T T T T T T T T T T
5,8 T T T T T 2,3 T T T T T T T T T T T T
5,8 T T T T T 2,3 T T T T T T T T T T T T
5,8 T T T T T 2,3 T T T T T T T T T T T T
3,5 T T T T T 1,8 T T T T T T T T T T T T
3,5 T T T T T 1,8 T T T T T T T T T T T T
3,5 T T T T T 1,8 T T T T T T T T T T T T
2,6 3,7 4,8 T T T 1,7 4,3 T T T T T T T T T T T
2,1 2,8 3,6 5 T T 1,5 3,3 T T T T T T T T T T T
2,1 2,8 3,6 5 T T 1,5 3,3 T T T T T T T T T T T
2,1 2,8 3,6 5 T T 1,5 3,3 T T T T T T T T T T T
1,8 2,3 2,9 3,8 5,6 T 1,4 2,6 T T T T T T T T T T T
1,8 2,3 2,9 3,8 5,6 T - 2,6 T T T T T T T T T T T
1,7 1,8 2,2 3 4,5 T - 2 T T T T T T T T T T T
1 1,4 1,7 2,4 3,8 T - 1,75 5,8 T T T T T T T T T T
- 1,3 1,625 2,1 3,4 5,9 - 1,75 5,4 T T T T T T T T T T
100 Technical modifications reserved
Selectivity chart
Limits (kA)
x160 TM
18/25/40kA
x250 TM
25/40kA
h250 TM
25/50/65 kA
In 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A 160A 100A 125A 160A 200A 250A 32A
NQ
N, N
BN
B c
urv
e
6A 1,4 1,5 1,6 1,9 2,3 3 4 5,5 6,7 8,6 12 7,8 11 16 T T 2,5
10A 1,2 1,3 1,4 1,7 2 2,4 2,8 3,4 4 4,9 6,4 4,7 6,2 8,6 14 23 2,2
13A - 1,2 1,3 1,5 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 17 2
16A - - 1,3 1,5 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 17 2
20A - - - 1,5 1,8 2,1 2,4 2,8 3,2 3,7 4,6 3,8 4,7 6,2 9,9 17 2
25A - -- - - 1,7 1,9 2,1 2,3 2,5 2,9 3,6 3 3,7 4,9 7,4 13 1,8
32A - -- - - - 1,9 2,1 2,3 2,5 2,9 3,6 3 3,7 4,9 7,4 13 -
40A - - -- - - - 1,6 1,7 1,9 2,2 2,8 2,3 2,8 3,8 5,9 9,9 -
50A - - - - - - - 1,4 1,5 1,8 2,3 1,8 2,3 3,2 5,9 8,6 -
63A - - - - - - - - 1,5 1,5 1,8 1,4 1,8 2,4 4,2 7,7 -
NR
N, N
CN
C c
urv
e
0,5A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 12 16 23 14 20 T T T 2,6
1A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 12 16 23 14 20 T T T 2,6
2A 1,3 1,4 1,6 2 2,5 3,5 5,6 8,8 12 16 23 14 20 T T T 2,6
3A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 12 17 T 2,2
4A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 12 17 T 2,2
6A 1,1 1,2 1,4 1,7 2 2,5 3,4 4,8 5,8 6,8 8,5 6,8 8,6 12 17 T 2,2
10A 1 1,1 1,25 1,5 1,8 2,1 2,5 3 3,5 4,3 5,6 4,1 5,4 7,6 12 20 2
13A - 1 1,1 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 14 1,7
16A - - 1,1 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 14 1,7
20A - - - 1,3 1,6 1,8 2,1 2,4 2,7 3,2 4,1 3,2 4,1 5,6 8,3 14 1,7
25A - - - - 1,4 1,6 1,8 2 2,2 2,6 3,2 2,6 3,2 4,3 6,3 11 1,6
32A - - - - - 1,6 1,8 2 2,2 2,6 3,2 2,6 3,2 4,3 6,3 11 -
40A - - - - - - 1,3 1,5 1,7 2 2,5 2 2,5 3,4 5 8,5 -
50A - - - - - - - 1,1 1,5 1,5 2 1,5 1,9 2,7 4,2 7,3 -
63A - - - - - - - - 1,5 1,5 1,6 1,3 1,625 2,2 3,8 6,7 -
NG
N, N
SN
, N
DN
D c
urv
e
0,5A 1 1,1 1,3 1,6 2 3 4,5 7,4 10 13 18 12 16 24 T T 2,1
1A 1 1,1 1,3 1,6 2 3 4,5 7,4 10 13 18 12 16 24 T T 2,1
2A 1 1,1 1,3 1,6 2 3 4,5 7,4 10 13 18 12 16 24 T T 2,1
3A 0,9 1 1,1 1,3 1,6 2,1 2,7 3,8 4,7 5,7 7,3 5,5 7,2 9,9 14 23 1,7
4A 0,9 1 1,1 1,3 1,6 2,1 2,7 3,8 4,7 5,7 7,3 5,5 7,2 9,9 14 23 1,7
6A 0,9 1 1,1 1,3 1,6 2,1 2,7 3,8 4,7 5,7 7,3 5,5 7,2 9,9 14 23 1,7
10A - 0,9 1 1,2 1,4 1,7 2 2,4 2,8 3,4 4,4 3,3 4,3 5,9 8,6 14 1,6
13A - - 0,95 1,1 1,3 1,5 1,7 1,9 2,2 2,6 3,3 2,6 3,2 4,5 6,8 11 1,4
16A - - - 1,1 1,3 1,5 1,7 1,9 2,2 2,6 3,3 2,6 3,2 4,5 6,8 11 -
20A - - - - 1,3 1,5 1,7 1,9 2,2 2,6 3,3 2,6 3,2 4,5 6,8 11 -
25A - - - - - 1,2 1,4 1,6 1,8 2 2,5 2,1 2,5 3,4 5,3 8,6 -
32A - - - - - - 1,4 1,6 1,7 2 2,5 2,1 2,5 3,4 5,3 8,6 -
40A - - - - - - - 1,2 1,5 1,5 1,8 1,5 1,9 2,4 4,1 6,8 -
50A - - - - - - - - 1,5 1,5 1,6 - 1,9 2,4 4,1 6,8 -
63A - - - - - - - - - 1,5 1,6 - - 2,08 3,1 5,3 -
MM
N
0,63A 1,1 1,15 1,2 1,35 1,5 1,8 2,7 4,9 8 13 22 9 16 T T T 1,8
1,25A 1,1 1,15 1,2 1,35 1,5 1,8 2,7 4,9 8 13 22 9 16 T T T 1,8
1,6A 1 1,05 1,1 1,2 1,4 1,7 2,1 2,7 3,3 4,5 7 3,9 5,7 9,9 17 T 1,6
2,5A 1 1,05 1,1 1,2 1,4 1,7 2,1 2,7 3,3 4,5 7 3,9 5,7 9,9 17 T 1,6
4A - - 1 1,1 1,3 1,5 1,9 2,4 3 4,1 5,6 3,5 5,1 7,6 12 20 1,4
6,3A - - - - 1,3 1,5 1,9 2,4 3 4,1 5,6 3,5 5,1 7,6 12 20 -
10A - - - - - - 1,7 2,1 2,7 3,7 4,5 3,2 4,7 6,1 8,8 14 -
12,5A - - - - - - - 2,1 2,7 3,7 4,5 3,2 4,7 6,1 8,8 14 -
16A - - - - - - - - 2,5 3,3 4 - 4,1 5,4 7,8 13 -
20A - - - - - - - - - 3,3 4 - - 5,4 7,8 13 -
25A - - - - - - - - - - 4 - - - 7,8 13 -
HLE
,H
MB
,H
MJ
B c
urv
e 80A - - - - - - - - - 7,8 8,6 - 6,9 7,7 8,8 11 -
100A - - - - - - - - - - 8,6 - - 7,7 8,8 11 -
125A - - - - - - - - - - - - - - 8,8 11 -
HL
F, H
MC
, H
MK
, H
MX
C c
urv
e
10A 1,6 1,9 2,3 3 3,7 4,6 5,6 6,7 7,7 8,6 9,5 9 11 13 16 23 3,9
16A - - 2 2,6 3,2 4 4,9 5,9 6,9 7,8 8,6 8,1 9,9 12 15 21 3,4
20A - - - 2,1 2,7 3,4 4,3 5,2 6,2 7 7,8 7,3 8,8 11 14 20 2,7
25A - - - - 2,4 3,1 3,9 4,9 5,8 6,7 7,5 6,8 8,5 11 14 20 2,4
32A - - - - - 2,9 3,6 4,5 5,4 6,3 7,1 6,3 7,9 9,9 13 18 -
40A - - - - - - 3,3 4,2 5,1 6 6,8 5,9 7,6 9 12 17 -
50A - - - - - - - 3,9 4,8 5,7 6,5 5,6 7,2 8,6 11 16 -
63A - - - - - - - - 4,5 5,4 6,2 5,3 6,8 8,4 11 16 -
80A - - - - - - - - - 7,4 8,2 - 6,6 7,3 8,6 11 -
100A - - - - - - - - - - 8,2 - - 7,3 8,6 11 -
125A - - - - - - - - - - - - - - 8,6 11 -
HM
D
D c
urv
e 80A - - - - - - - - - - - - - - 8,9 12 -
100A - - - - - - - - - - - - - - - 10 -
125A - - - - - - - - - - - - - - - - -
T = total selectivity. Each underlined value must be read as T when it is over the breaking capacity range of MCBs or RCBOs.
All values are given with MCCB at the maximum setting.
101Technical modifications reserved
h250 LSI
50/70 kA
h400 TM
25/50 kA
h630 LSI
50/70 kA
h1000 LSI
50/70 kA
h1600 LSI
50/70 kA
63A 100A 125A 160A 200A 250A 40A 125A 250A 250A 400A 250A 400A 630A 630A 800A 1000A 1250A 1600A
5,2 8,7 12 18 T T 2,7 11 T T T T T T T T T T T
3,6 5,2 6,9 9,6 15 T 2,3 6,2 23 T T T T T T T T T T
3,1 4,2 5,2 6,9 11 19 2,1 4,7 17 21 T T T T T T T T T
3,1 4,2 5,2 6,9 11 19 2,1 4,7 17 21 T T T T T T T T T
3,1 4,2 5,2 6,9 11 19 2,1 4,7 17 21 T T T T T T T T T
2,7 3,3 4,1 5,4 8,2 14 2 3,7 13 15 T T T T T T T T T
2,7 3,3 4,1 5,4 8,2 14 - 3,7 13 15 T T T T T T T T T
2,1 2,5 3,1 4,2 6,5 11 - 2,8 9,9 12 T T T T T T T T T
1,7 2 2,5 3,5 5,4 9,6 - 2,3 8,6 11 T T T T T T T T T
- 1,6 2 2,7 4,7 8,5 - 1,8 7,7 9,4 T T T T T T T T T
7,3 16 22 T T T 2,9 20 T T T T T T T T T T T
7,3 16 22 T T T 2,9 20 T T T T T T T T T T T
7,3 16 22 T T T 2,9 20 T T T T T T T T T T T
4,4 7,5 9,5 13 19 T 2,3 8,6 T T T T T T T T T T T
4,4 7,5 9,5 13 19 T 2,3 8,6 T T T T T T T T T T T
4,4 7,5 9,5 13 19 T 2,3 8,6 T T T T T T T T T T T
3,2 4,6 6 8,4 13 22 2,1 5,4 20 24 T T T T T T T T T
2,6 3,5 4,5 6,2 9,2 16 1,9 4,1 14 18 T T T T T T T T T
2,6 3,5 4,5 6,2 9,2 16 1,9 4,1 14 18 T T T T T T T T T
2,6 3,5 4,5 6,2 9,2 16 1,9 4,1 14 18 T T T T T T T T T
2,2 2,9 3,6 4,8 7 12 1,7 3,2 11 13 T T T T T T T T T
2,2 2,9 3,6 4,8 7 12 - 3,2 11 13 T T T T T T T T T
2,1 2,2 2,8 3,8 5,6 9,4 - 2,5 8,5 10 T T T T T T T T T
1,3 1,7 2,1 3 4,7 8,1 - 1,9 7,3 8,9 24 T T T T T T T T
- 1,3 1,625 2,4 4,2 7,4 - 1,75 6,7 8,2 22 T T T T T T T T
5,9 13 18 T T T 2,3 16 T T T T T T T T T T T
5,9 13 18 T T T 2,3 16 T T T T T T T T T T T
5,9 13 18 T T T 2,3 16 T T T T T T T T T T T
3,5 6,1 8 11 16 T 1,9 7,2 23 T T T T T T T T T T
3,5 6,1 8 11 16 T 1,9 7,2 23 T T T T T T T T T T
3,5 6,1 8 11 16 T 1,9 7,2 23 T T T T T T T T T T
2,6 3,7 4,8 6,6 9,6 16 1,6 4,3 14 18 T T T T T T T T T
2,2 2,9 3,6 5 7,5 12 1,5 3,2 11 13 T T T T T T T T T
2,2 2,9 3,6 5 7,5 12 1,5 3,2 11 13 T T T T T T T T T
2,2 2,9 3,6 5 7,5 12 1,5 3,2 11 13 T T T T T T T T T
1,8 2,3 2,8 3,8 5,9 9,5 - 2,5 8,6 10 T T T T T T T T T
- 2,3 2,8 3,8 5,9 9,5 - 2,5 8,6 10 T T T T T T T T T
- 1,7 2,1 2,7 4,5 7,6 - 1,9 6,8 8,4 23 T T T T T T T T
- - 1,7 2,2 3,9 6,5 - 1,9 6,8 7,2 20 T T T T T T T T
- - - 2,08 3,4 5,9 - 1,75 5,3 6,5 18 T T T T T T T T
3,5 10 18 T T T 1,8 16 T T T T T T T T T T T
3,5 10 18 T T T 1,8 16 T T T T T T T T T T T
2,7 4,3 6,3 11 19 T 1,6 5,7 T T T T T T T T T T T
2,7 4,3 6,3 11 19 T 1,6 5,7 T T T T T T T T T T T
2,5 3,9 5,7 8,4 13 22 1,5 5,1 20 24 T T T T T T T T T
2,5 3,9 5,7 8,4 13 22 - 5,1 20 24 T T T T T T T T T
2,2 3,5 5,2 6,8 9,8 16 - 4,7 14 18 T T T T T T T T T
- 3,5 5,2 6,8 9,8 16 - 4,7 14 18 T T T T T T T T T
- 3,3 4,6 6 8,7 14 - 4,1 13 15 T T T T T T T T T
- - 4,6 6 8,7 14 - - 13 15 T T T T T T T T T
- - - 6 8,7 14 - - 13 15 T T T T T T T T T
- 7,7 8,5 9,8 12 16 - 6,9 11 18 T T T T T T T T T
- - 8,5 9,8 12 16 - - 11 18 T T T T T T T T T
- - - 9,8 12 16 - - 11 18 T T T T T T T T T
7,3 10 12 14 18 26 4,3 11 23 19 T T T T T T T T T
6,4 9 11 13 16 23 3,7 9,9 21 25 T T T T T T T T T
5,6 8,1 9,8 12 15 22 3,2 8,8 20 24 T T T T T T T T T
5,1 7,5 9,4 12 15 22 2,8 8,5 20 24 T T T T T T T T T
4,7 7 8,8 11 14 20 - 7,9 18 22 T T T T T T T T T
4,3 6,6 8,4 10 13 19 - 7,6 17 21 T T T T T T T T T
4 6,2 8 9,6 12 18 - 7,2 16 20 T T T T T T T T T
- 5,9 7,6 9,3 12 18 - 6,8 16 20 T T T T T T T T T
- 7,3 8,1 9,6 12 16 - 6,6 11 18 T T T T T T T T T
- - 8,1 9,6 12 16 - - 11 18 T T T T T T T T T
- - - 9,6 12 16 - - 11 18 T T T T T T T T T
- - - - 9,8 13 - - 12 14 T T T T T T T T T
- - - - - 11 - - 10 12 T T T T T T T T T
- - - - - - - - 8,7 10 T T T T T T T T T
102 Technical modifications reserved
Selectivity chart
Breaking capacity according to IEC 947-2. Network : 3 phasis + neutral 220/380 ~ 240/415 V AC
notes : “T” = total discrimination (up to the breaking capacity of the downstream device)
“-” = no discrimination
Icc (kA) Upstream x160 TM x250 TM h250 TM
Downstream (A) 16 - 50 63 80 100 125 160 100 125 160 200 250 32 63 100
x160 TM
18/25/40 kA
16 - 2 2 2,9 2,9 3 2,15 2,9 4,1 5,6 5,4 - 1,2 2,15
20 - 2 2 2,9 2,9 3 2,15 2,9 4,1 5,6 5,4 - 1,2 2,15
25 - 2 2 2,9 2,9 3 2,15 2,9 4,1 5,6 5,4 - 1,2 2,15
32 - 1,8 1,8 2,6 2,6 2,7 2 2,6 3,6 5 4,8 - 1,15 2
40 - 1,6 1,6 2,35 2,35 2,4 1,8 2,35 3,3 4,3 4,2 - 1,1 1,8
50 - 1,6 1,6 2,35 2,35 2,4 1,8 2,35 3,15 4,25 4,15 - 1,1 1,8
63 - - - 2,15 2,15 2,2 1,7 2,15 3 4,05 3,9 - - 1,7
80 - - - 2,15 2,15 2,2 1,7 2,15 2,9 3,9 3,8 - - 1,7
100 - - - - - 2,1 - 1,95 2,75 3,7 3,6 - - -
125 - - - - - 2,1 - 1,95 2,65 3,5 3,4 - - -
160 - - - - - - - 1,95 2,6 3,45 3,35 - - -
x250 TM
25/40 kA
100 - - - - - - - 1,95 2,5 3,15 3,3 - - -
125 - - - - - - - - 2,5 3,15 3,3 - - -
160 - - - - - - - - - 3,15 3,3 - - -
200 - - - - - - - - - - 3,3 - - -
250 - - - - - - - - - - - - - -
h250 TM
25/50/65 kA
32 - - - - - - 1,55 1,95 2,5 3,15 3,3 - 1 1,55
63 - - - - - - 1,55 1,95 2,5 3,15 3,3 - - 1,55
100 - - - - - - - 1,95 2,5 3,15 3,3 - - -
125 - - - - - - - - 2,5 3,15 3,3 - - -
160 - - - - - - - - - 3,15 3,3 - - -
200 - - - - - - - - - - 3,3 - - -
250 - - - - - - - - - - 3,3 - - -
h250 LSI
50/70 kA
40 - - - - - - 1,55 1,95 2,5 3,15 3,3 - 1 1,55
125 - - - - - - - - 2,5 3,15 3,3 - - -
250 - - - - - - - - - - - - - -
h400 TM
25/50 kA
250 - - - - - - - - - - - - -
400 - - - - - - - - - - - - - -
h630 LSI
50/70 kA
250 - - - - - - - - - - - - - -
400 - - - - - - - - - - - - - -
630 - - - - - - - - - - - - - -
h1000 LSI
50/70 kA
630 - - - - - - - - - - - - - -
800 - - - - - - - - - - - - - -
1000 - - - - - - - - - - - - - -
h1600 LSI
50/70 kA
1250 - - - - - - - - - - - - - -
1600 - - - - - - - - - - - - - -
103Technical modifications reserved
h250 LSI h400 TM h630 LSI h1000 LSI h1600 LSI
125 160 200 250 40 125 250 250 400 250 400 630 630 800 1000 1250 1600
2,9 4,1 5,6 5,4 - T T 6,5 13 T T T T T T T T
2,9 4,1 5,6 5,4 - T T 6,5 13 T T T T T T T T
2,9 4,1 5,6 5,4 - T T 6,5 13 T T T T T T T T
2,6 3,6 5 4,8 - T T 5,6 10,5 T T T T T T T T
2,35 3,3 4,3 4,2 - T T 4,95 9,2 T T T T T T T T
2,35 3,15 4,25 4,15 - T T 4,8 8,8 T T T T T T T T
2,15 3 4,05 3,9 - T T 4,6 8,3 T T T T T T T T
2,15 2,9 3,9 3,8 - T T 4,35 7,9 T T T T T T T T
1,95 2,75 3,7 3,6 - T T 4,15 7,5 T T T T T T T T
1,95 2,65 3,5 3,4 - T T 4 7 T T T T T T T T
1,95 2,6 3,45 3,35 - T T 3,9 6,6 T T T T T T T T
1,95 2,5 3,15 3 - T T 3,6 5,75 T T T T T T T T
- 2,5 3,15 3 - - T 3,6 5,75 T T T T T T T T
- - 3,15 3 - - T 3,6 5,75 T T T T T T T T
- - - 3 - - T 3,6 5,75 T T T T T T T T
- - - - - - T 3,6 5,75 T T T T T T T T
1,95 2,5 3,15 3 T T T 3,6 5,75 T T T T T T T T
1,95 2,5 3,15 3 - T T 3,6 5,75 T T T T T T T T
1,95 2,5 3,15 3 - T T 3,6 5,75 T T T T T T T T
- 2,5 3,15 3 - - T 3,6 5,75 T T T T T T T T
- - 3,15 3 - - T 3,6 5,75 T T T T T T T T
- - - - - - T 3,6 5,75 T T T T T T T T
- - - - - - T 3,6 5,75 T T T T T T T T
1,95 2,5 3,15 3 - 1,65 3,25 3,6 5,75 T T T T T T T T
- 2,5 3,15 3 - - 3,25 3,6 5,75 T T T T T T T T
- - - - - - - - 5,75 T T T T T T T T
- - - - - - 3,25 - 5,75 T T T T T T T T
- - - - - - - - - - T T T T T T T
- - - - - - - - 5,75 - 5,2 6,3 T T T T T
- - - - - - - - - - - 6,3 T T T T T
- - - - - - - - - - - - T T T T T
- - - - - - - - - - - - - 9,6 10 T T
- - - - - - - - - - - - - - 10 T T
- - - - - - - - - - - - - - - T T
- - - - - - - - - - - - - - - - 19,2
- - - - - - - - - - - - - - - - -