Standards and Guides for Transformer Maintenance and Diagnostics
Matz Ohlen, Megger Sweden
2
Testing and Standards
� CIGRE
• CIGRE Brochure 342 (SFRA-FRAX)
• CIGRE Brochure 414 (DFR-IDAX)
• CIGRE Brochure 445 (Guide for Transformer Maintenance)
� IEC, TC 14
• IEC 60076-1, Power Transformers
• IEC 60076-2, Temperature rise
• IEC 60076-3, Insulation levels, dielectric tests and external clearances in air
• IEC 60076-18, Measurement of frequency response (SFRA)
� ANSI, IEEE Transformer Committee
• IEEE C57.152 (former IEEE 62-1995)
• IEEE C57.12.00-2006 (under revision)
• IEEE C57.12.90-2006 (under revision)
• IEEE PC57.149 (SFRA)
3
Guides and standards for transformer testing (1)
� Most standards (IEC and ANSI/IEEE) are focusing on new
transformers and factory testing
� Workgroups in e.g. Cigré have over the years produced a lot of
Technical Brochures (TB) e.g. on sweep frequency response
measurements (TB342), partial discharge (TB366), dielectric
response measurements (TB414) etc
� IEEE 62-1995 “Diagnostic Field Testing of Fluid-Filled Power
Transformers, Regulators, and Reactors” is probably the most
well-known guide for diagnostic field testing of oil filled power
transformers. The guide today belong to the IEEE C57-series and
last published revision is C57.152-2013
4
Cigré Technical Brochure 445, 2011
Guide for Transformer Maintenance
5
CIGRE TB 445
� Cigré TB 445, ”Guide for Transformer Maintenance”, was
published 2011
� TB 445 is a comprehensive combination of education handbook,
transformer encyclopedia and a guide for transformer
maintenance including guidelines for how to perform
measurements in the field
6
TB 445- Content
7
IEEE C57.152-2013
Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors
8
IEEE C57-152
� IEEE C57.152 “Guide for Diagnostic Field Testing of Fluid-Filled
Power Transformers, Regulators, and Reactors”, is a revision of
IEEE 62-1995 and was published 2013
� IEEE C57.152 is a guide that “describes diagnostic field tests and
measurements that are performed on fluid-filled power
transformers and regulators” and does NOT contain general
information on transformer components and transformer
maintenance
9
IEEE C57-152- Content
10
”Diagnostic” and ”Maintenance” test charts” IEEE C57.152
11
”Diagnostic” matrix CIGRE TB445
12
Differences GIGRE - IEEE
� CIGRE test categories – by methodso Basic Electrical
o Advanced Electrical
o Dissolved Gas Analysis (DGA)
� IEEE test categorieso By component
o ”Event based”
13
Diagnostic Technique (CIGRE)
� Basic Electrical
� Advanced Electrical
� Dissolved Gas Analysis (DGA)
14
Basic Electrical
� Winding Ratio
� Winding Resistance
� Magnetization (excitation) current
� Capacitance and DF/PF
� Insulation Resistance
� Core Ground Test
15
Winding Ratio
16
Winding Resistance
17
Magnetization (excitation) current
18
Capacitance and DF/PF
19
Capacitance and DF/PF - Bushings
20
Leakage Reactance
21
Insulation Resistance
22
Core Grounding
23
Advanced Electrical
� Frequency Response of Stray Losses (FRSL)
� Frequency Response Analysis
� Polarization/Depolarization
� Frequency Domain Spectroscopy
� Recovery Voltage Method
� Electrical Detection of PD
� Acoustical Detection of PD
� UHF Detection of PD
24
Frequency Response Analysis
25
Frequency Domain Spectroscopy(FDS/DFR)
26
Bushingmeasurements
27
Summary CIGRE TB 445
� TB 445 is a combination of a transformer handbook,
transformer encyclopedia and application guide for
transformer maintenance including guidelines for
transformer field testing
� Lots of very good information. Details and guidelines
can and will be discussed e.g. assessment data and
advantages/disadvantages with different
measurement methods (e.g. combined PDC-FDS
combination versus true AC DFR/FDS measurements)