24
Masterpact Schneider Electric 90

Masterpact Schneider Electric breaker_files... · 2005-01-18 · 92 Masterpact Schneider Electric Installation recommendations E 5 1 2 6 1 B Test E 5 1 2 6 2 B Test E 5 1 2 6 0 B

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Masterpact Schneider Electric90

Masterpact Schneider Electric91

Installation recommendations

Presentation 1Functions and characteristics 9Dimensions and connection 53Electrical diagrams 81

Operating conditions 92Installation in switchboard 94Door interlock catch 96Cable-type door interlock 97Connection of MN, MX and XF voltage releases 97Power connection 98Recommended busbars drilling 100Busbar sizing 102Temperature derating 104Power dissipation and input/output resistance 104Derating in switchboards 105Substitution kit 112

Additional characteristics 115References 121

Masterpact

Masterpact Schneider Electric92

Installationrecommendations

E51

261B

Test

E51

262B

Test

E51

260B

Test

Ambient temperatureMasterpact devices can operate under the following temperature conditions:c the electrical and mechanical characteristics are stipulated for an ambienttemperature of -5° C to +70° C;c circuit-breaker closing is guaranteed down to -35° C;Storage conditions are as follows:c -40 to +85°C for a Masterpact device without its control unitc -25°C to +85°C for the control unit.

Extreme atmospheric conditionsMasterpact devices have successfully passed the tests defined by the followingstandards for extreme atmospheric conditions:c IEC 68-2-1: dry cold at -55° C;c IEC 68-2-2: dry heat at +85° C;c IEC 68-2-30: damp heat (temperature +55° C, relative humidity 95%);c IEC 68-2-52 level 2: salt mist.Masterpact devices can operate in the industrial environments defined by standardIEC 947 (pollution degree up to 4).It is nonetheless advised to check that the devices are installed in suitably cooledswitchboards without excessive dust.

VibrationsMasterpact devices are guaranteed against electromagnetic or mechanicalvibrations.Tests are carried out in compliance with standard IEC 68-2-6 for the levels requiredby merchant-marine inspection organisations (Veritas, Lloyd’s, etc.):c 2 to 13.2 Hz: amplitude ±1 mm;c 13.2 to 100 Hz: constant acceleration 0.7 g.Excessive vibration may cause tripping, breaks in connections or damage tomechanical parts.

Operating conditions

Masterpact Schneider Electric93

E51

263B

2000

m

Test

AltitudeAt altitudes higher than 2000 metres, the modifications in the ambient air (electricalresistance, cooling capacity) lower the following characteristics as follows:Altitude (m) 2000 3000 4000 5000Dielectric resistance 3500 3150 2500 2100voltage (V)Average insulation 1000 900 700 600 level (V)Maximum utilisation 690 590 520 460voltage (V)Average thermal 1 x In 0.99 x In 0.96 x In 0.94 x Incurrent (A) at 40 °C

E51

264B

Test

Electromagnetic disturbancesMasterpact devices are protected against:c overvoltages caused by devices that generate electromagnetic disturbances;c overvoltages caused by atmospheric disturbances or by a distribution-systemoutage (e.g. failure of a lighting system);c devices emitting radio waves (radios, walkie-talkies, radar, etc.);c electrostatic discharges produced by users.Masterpact devices have successfully passed the electromagnetic-compatibilitytests (EMC) defined by the following international standards:c IEC 60947-2, appendix F;c IEC 60947-2, appendix B (trip units with earth-leakage function).The above tests guarantee that:c no nuisance tripping occurs;c tripping times are respected.

Masterpact Schneider Electric94

Installationrecommendations

Possible positions

Power supplyMasterpact devices can be supplied either from the top or from the bottom withoutreduction in performance, in order to facilitate connection when installed in aswitchboard.

Installation in switchboard

Mounting the circuit-breakerIt is important to distribute the weight of the device uniformily over a rigid mountingsurface such as rails or a base plate.This mounting plane should be perfectly flat (tolerance on support flatness: 2 mm).This eliminates any risk of deformation which could interfere with correct operationof the circuit breaker.Masterpact devices can also be mounted on a vertical plane using the specialbrackets.

E47

656A

E47

657A

E47

658A

E47

650A

E47

651A

E47

652A

E47

653A

Mounting with vertical brackets.

Mounting on rails.

Masterpact Schneider Electric95

PartitionsSufficient openings must be provided in partitions toensure good air circulation around the circuit breaker;For high currents, of 2500 A and upwards, the metalsupports or barriers in the immediate vicinity of aconductor must be made of non-magnetic material A;Metal barriers through which a conductor passes mustnot form a magnetic loop.

A : non magnetic material

BusbarsThe mechanical connection must be exclude thepossibility of formation of a magnetic loop around aconductor.

E47

659A

non magneticmaterial

E47

660A

E47

661A

E47

662B

A

E47

663A

F

351 (NT)453 (NW)

E47

664

Interphase barrierIncreases the length of the tracking path betweenphases;Reduces the risk of short circuits being caused byobjects falling from above onto circuit breakerconnections.

Dimensions and weights Main dimensions in mm (H x W x D)Masterpact NT06/12 NW08/40 NW40b/63

drawout 3P 322 x 288 x 280 439 x 441 x 395 479 x 786 x 3954P 322 x 358 x 280 439 x 556 x 395 479 x 1016 x 395

fixed 3P 301 x 276 x 211 352 x 422 x 297 352 x 767 x 2974P 301 x 346 x 211 352 x 537 x 297 352 x 997 x 297

Weight (kg)Masterpact NT06/12 NW08/40 NW40b/63

drawout 3P 30 90 2254P 39 120 300

fixed 3P 14 60 1204P 18 80 160

Masterpact Schneider Electric96

Installationrecommendations

Note: The door interlock can either be mounted on theright side or the left side of the breaker.F Datum.

Breaker in “connected” or “test” positionDoor cannot be opened

Breaker in “disconnected” positionDoor can be opened

Dimensions (mm)Type (1) (2)

NT08-16 (3P) 135 168NT08-16 (4P) 205 168NW08-40 (3P) 215 215NW08-40 (4P) 330 215NW40b-63 (3P) 660 215NW40b-63 (4P) 775 215

17

8

5

15

X

Y

(2) (1)

(1)

F

(2)

door

E47

669B

E47

670A

E47

671A

Dimensions (mm)Type (1) (2)

NT 5 23NW 83 103

Catch not supplied

Door interlock catch

Mounted on the right or left-hand side of the craddle,this device inhibits opening of the cubicle door whenthe circuit breaker is in «connected» or «test»position. It the breaker is put in the «connected»position with the door open, the door may be closedwithout having to disconnect the circuit breaker.

Masterpact Schneider Electric97

Cable-type door interlockConnection of MN, MX and XFvoltage releases

NT/NWCable-type door interlockThis option prevents door opening when the circuit breaker is closed and preventscircuit breaker closing when the door is open.For this, a special plate associated with a lock and a cable is mounted on the rightside of the circuit breaker.With this interlock installed, the source changeover function cannot beimplemented.

Wiring of voltage releasesDuring pick-up, the power consumed is approximately 150 to 200 VA. For lowcontrol voltages (12, 24, 48 V), maximum cable lengths are imposed by the voltageand the cross-sectional area of cables.Recommanded maximum cable lengths (meter)

12 V 24 V 48 V2,5 mm2 1,5 mm2 2,5 mm2 1,5 mm2 2,5 mm2 1,5 mm2

MN U source 100 % – – 58 35 280 165U source 85 % – – 16 10 75 45

MX-XF U source 100 % 21 12 115 70 550 330U source 85 % 10 6 75 44 350 210

Note: the indicated length is that of each of the two wires

121

84

10

165

46

79 52

E59

113A

E59

114B

E59

115A

Masterpact Schneider Electric98

Installationrecommendations

Power connection

Busbars connectionsThe busbars should be suitably adjusted to ensurethat the connection points are positioned on theterminals before the bolts are inserted BThe connections are held by the support which issolidly fixed to the framework of the switchboard, suchthat the circuit breaker terminals do not have tosupport its weight C. (This support should be placedclose to the terminals).

Cables connectionsIf cables are used for the power connections, makesure that they do not apply excessive mechanicalforces to the circuit breaker terminals.For this, make the connections as follows:c extend the circuit breaker terminals using short barsdesigned and installed according to therecommendations for bar-type power connections:v for a single cable, use solution B oppositev for multiple cables, use solution C opposite.c in all cases, follow the general rules for connectionsto busbars:v position the cable lugs before inserting the boltsv the cables should firmly secured to the framework ofthe switchboard.

E47

672A

A

B C

B

B

E

C

E

E47

673A

E47

674A

E47

675A

E47

676A

E47

677A

Electrodynamic stressesThe first busbar support or spacer shall be situated within a maximum distancefrom the connection point of the breaker (see table below). This distance must berespected so that the connection can withstand the electrodynamic stressesbetween phases in the event of a short circuit.Maximum distance A between busbar to circuit breaker connection and the first busbarsupport or spacer with respect to the value of the prospective short-circuit current.

Isc (kA) 30 50 65 80 100 150distance A (mm) 350 300 250 150 150 150

Masterpact Schneider Electric99

ClampingCorrect clamping of busbars depends amongst other things, on the tighteningtorques used for the nuts and bolts. Over-tightening may have the sameconsequences as under-tightening.For connecting busbars (Cu ETP-NFA51-100) to the circuit breaker, the tighteningtorques to be used are shown in the table below.These values are for use with copper busbars and steel nuts and bolts, class 8.8.The same torques can be used with AGS-T52 quality aluminium bars (Frenchstandard NFA 02-104 or American National Standard H-35-1).

Tightening torquesØ Ø tightening torque (Nm) with contactnominal (mm) drilling (mm) with grower or or corrugatec

flat washers washers10 11 37.5 50

Busbar drillingExamples

Isolation distance

Busbar bendingWhen bending busbars maintain the radius indicated below(a smaller radius wouldcause cracks).

4 532

6

1

e

r

X

Dimensions (mm)e radius of curvature r

min recommended5 5 7.510 15 18 to 20

E47

678A

E47

679A

E47

680A

E47

667B

E47

668

Examples

E47

665

1 terminal screw factory-tightened to 16 Nm (NW), 13 Nm (NT)2 breaker terminal3 busbar4 bolt5 washer6 nut

E47

329A

E47

330A

E47

331A

Dimensions (mm)Ui X min

600 V 8 mm1000 V 14 mm

Masterpact Schneider Electric100

Installationrecommendations

Recommended busbars drillingMasterpact NT06 to NT16

Rear connection Rear connection with spreaders

Vertical rear connection

E59

324A

2 Ø11

25 9,5

44

12,560

12,5

52

5 Ø11

13,5=25 =

38,5

77

15

305282

25

13,5=25 =

38,5

77

5282 15

30

25

52

5 Ø11 5 Ø11

13,5=25 =

38,5

77

15

305282

25

52

25

9,5

44

12,5

60

12,5

2 Ø11

25 9,5

44

13

2 Ø11

3 Ø11

12,5=25 =

89

15

21

20

10121

15

5 Ø11

13,5=25 =

38,5

77

15

305282

25

52

E59

325A

E59

326A

E59

327A

E59

328A

E59

329A

Front connection Front connection via vertical connection adapters

E59

330A

E59

332A

Middle left or middle Middle spreader Left or right spreader Left or right spreaderright spreader for 4P for 3P for 4P for 3P

12,5Ø12 maxi

25 12,5

50

12,5 12,5Ø12 maxi

25 12,5

50

12,5 25,5Ø12 maxi

25 12,5

63

12,515

Ø12 maxi

25 12,5

80

25

15E59

308A

E59

308A

E59

309A

E59

310A

Ø12 maxi

12,5

32

25

12,5

Ø12 maxi

12,5

40

25

12,5

Ø12 maxi

12,5

50

25

12,5

Ø12 maxi

12,5

63

25

12,5

Ø12 maxi

12,5

80

25

12,5

E59

311A

E59

312A

E59

313A

E59

314A

E59

315

A

12,5Ø12 maxi

25 12,5

50

12,5 25,5Ø12 maxi

25 12,5

63

12,512,5Ø12 maxi

25 12,5

50

12,515

Ø12 maxi

25 12,5

80

25

15E59

308A

E59

308A

E59

309A

E59

310A

9,525

44

13

2 Ø11

E59

331A

Top connection Bottom connection

Masterpact Schneider Electric101

Horizontal rear connection NW08 to NW38 NW40b to NW50

==

76

13

25

3 Ø11,5

12,5

38

47

14,5Y

115115115115115

3939 39 39 39

76

253 Ø11,5

38

12,513

47

14,5

=

=

12,5

25 25 13

3 Ø11,5

76

Masterpact NW08 to NW63

Vertical rear connection NW08 to NW32, NW40b to NW50

Front connection NW08 to NW32

E59

333A

E59

323A

E59

334A

E59

335A

Top connection Bottom connection

12,5Ø12 maxi

25 12,5

50

12,5 25,5Ø12 maxi

25 12,5

63

12,515

Ø12 maxi

25 12,5

80

25

15 22

Ø12 maxi

25 12,5

100

25

28 28

Ø12 maxi

25 12,5

100

25

22

Ø12 maxi

12,5

40

25

12,5

25Ø12 maxi

12,5

50

25

12,5

25Ø12 maxi

12,5

63

25

12,5

25Ø12 maxi

12,5

80

25

12,5

25Ø12 maxi

12,5

100

25

12,5

25

E59

308A

E59

309A

E59

310A

E59

316A

E59

317A

E59

318A

E59

319A

E59

320A

E59

321A

E59

322A

12,5Ø12 maxi

25 12,5

50

12,5 25,5Ø12 maxi

25 12,5

63

12,515

Ø12 maxi

25 12,5

80

25

15E59

308A

E59

309A

E59

310A

12,5

1325 25

3 Ø11,5

E59

336A

Masterpact Schneider Electric102

Installationrecommendations

Busbar sizing

Basis of tables:c maximum permissible busbars temperature: 100 °Cc Ti: temperature around the circuit breaker and itsconnectionc busbar material is unpainted copper.

Masterpact maximum Ti : 40 °C Ti : 50 °C Ti : 60 °Cservice no. of 5 mm no. of 10 mm no. of 5 mm no. of 10 mm no. of 5 mm no. of 10 mmcurrent thick bars thick bars thick bars thick bars thick bars thick bars

NT06 400 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10NT06 630 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10NT08 or NW08 800 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.63 x 10NT10 or NW10 1000 3b.50 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10NT12 or NW12 1250 3b.50 x 5 2b.40 x 10 3b.50 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10

2b.80 x 5 2b.40 x 10 2b.80 x 5NT16 or NW16 1400 3b.50 x 5 2b.40 x 10 2b.80 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10NT16 or NW16 1600 3b.63 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10 3b.80 x 5 3b.50 x 10

NW20 1800 3b.80 x 5 2b.63 x 10 3b.80 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10NW20 2000 3b.100 x 5 2b.80 x 10 3b.100 x 5 2b.80 x 10 3b.100 x 5 3b.63 x 10NW25 2200 3b.100 x 5 2b.80 x 10 3b.100 x 5 2b.80 x 10 4b.80 x 5 2b.100 x 10NW25 2500 4b.100 x 5 2b.100 x 10 4b.100 x 5 2b.100 x 10 4b.100 x 5 3b.80 x 10NW32 2800 4b.100 x 5 3b.80 x 10 4b.100 x 5 3b.80 x 10 5b.100 x 5 3b.100 x 10NW32 3000 5b.100 x 5 3b.80 x 10 6b.100 x 5 3b.100 x 10 8b.100 x 5 4b.80 x 10NW32 3200 6b.100 x 5 3b.100 x 10 8b.100 x 5 3b.100 x 10 4b.100 x 10NW40 3800 4b.100 x 10 5b.100 x 10 5b.100 x 10NW40 4000 5b.100 x 10 5b.100 x 10 6b.100 x 10NW50 4500 6b.100 x 10 6b.100 x 10 7b.100 x 10NW50 5000 7b.100 x 10 7b.100 x 10

E47

681A

ExampleConditions:c drawout versionc horizontal busbarsc Ti: 50 °Cc service current: 1800 A.Solution:For Ti = 50 °C, use an NW20 which can be connectedwith three 80x5 mm bars or two mm 63x10 bars.

Front or rear horizontal connection

NoteThe values indicated in these tables have been extrapolated from test data andtheoretical calculations. These tables are only intended as a guide and cannot replaceindustrial experience or a temperature rise test.

With Masterpact NT, it is recommanded to use 50 mm wideness bars (see "Recommended busbars drilling")

Masterpact Schneider Electric103

Masterpact Maximum Ti: 40 °C Ti: 50 °C Ti: 60 °Cservice no. of 5 mm no. of 10 mm no. of 5 mm no. of 10 mm no. of 5 mm no. of 10 mmcurrent thick bars thick bars thick bars thick bars thick bars thick bars

NT06 400 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10NT06 630 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10NT08 or NW08 800 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10NT10 or NW10 1000 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.63 x 5 1b.63 x 10NT12 or NW12 1250 2b.63 x 5 1b.63 x 10 2b.63 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10NT16 or NW16 1400 2b.63 x 5 1b.63 x 10 2b.63 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10NT16 or NW16 1600 2b.80 x 5 1b.80 x 10 2b.80 x 5 1b.80 x 10 3b.63 x 5 2b.50 x 10

NW20 1800 2b.80 x 5 1b.80 x 10 2b.80 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10NW20 2000 2b.100 x 5 2b.63 x 10 2b.100 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10NW25 2200 2b.100 x 5 2b.63 x 10 2b.100 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10NW25 2500 4b.80 x 5 2b.80 x 10 4b.80 x 5 2b.80 x 10 4b.100 x 5 3b.80 x 10NW32 2800 4b.100 x 5 2b.100 x 10 4b.100 x 5 2b.100 x 10 4b.100 x 5 3b.80 x 10NW32 3000 5b.100 x 5 3b.80 x 10 6b.100 x 5 3b.100 x 10 5b.100 x 5 4b.80 x 10NW32 3200 6b.100 x 5 3b.100 x 10 6b.100 x 5 3b.100 x 10 4b.100 x 10NW40 3800 4b.100 x 10 4b.100 x 10 4b.100 x 10NW40 4000 4b.100 x 10 4b.100 x 10 4b.100 x 10NW50 4500 5b.100 x 10 5b.100 x 10 6b.100 x 10NW50 5000 5b.100 x 10 6b.100 x 10 7b.100 x 10NW63 5700 7b.100 x 10 7b.100 x 10 8b.100 x 10NW63 6300 8b.100 x 10 8b.100 x 10

ExampleConditions:c drawout versionc vertical connectionsc Ti: 40 °Cc service current: 1100 A.Solution :For Ti = 40 °C use an NT12 or NW12 which can beconnected with two 63 x 5 mm bars or withone 63 x 10 mm bar.

E47

682A

Rear vertical connection

NoteThe values indicated in these tables have been extrapolated from test data andtheoretical calculations. These tables are only intended as a guide and cannot replaceindustrial experience or a temperature rise test.

Basis of tables:c maximum permissible busbars temperature: 100 °Cc Ti: temperature around the circuit breaker and itsconnectionc busbar material is unpainted copper.

Masterpact Schneider Electric104

Installationrecommendations

version drawout fixedpower dissipation (Watts) input/output resistance (µohm) power dissipation (Watts) input/ouput resistance (µohm)

NT06 H1/L1 55/115 (H1/L1) 38/72 30/45 26/39NT08 H1/L1 90/140 (H1/L1) 38/72 50/80 26/39NT10 H1/L1 150/230 (H1/L1) 38/72 80/110 26/39NT12 H1 250 36 130 26NT16 H1 460 36 220 26NW08 N1 137 42 62 19NW08 H/L 100 30 42 13NW10 N1 220 42 100 19NW10 H/L 150 30 70 13NW12 N1 330 42 150 19NW12 H/L 230 27 100 13NW16 N1 480 37 220 19NW16 H/L 390 27 170 13NW20 H/L 470 27 250 13NW25 H1/H2/H3 600 19 260 8NW32 H1/H2/H3 670 13 420 8NW40 H1/H2/H3 900 11 650 8NW40b H1/H2 550 7 390 5NW50 H1/H2 590 7 420 5NW63 H1/H2 950 7 660 5

Temperature derating

Temperature deratingThe table below indicates the maximum current rating,for each connection type, as a function of the ambienttemperature around the circuit breaker and thebusbars.Circuit breakers with mixed connections have thesame derating as horizontally connected breakers.For ambient temperatures greater than 60 °C,consult us.Ti: temperature around the circuit breaker and itsconnection

Power dissipation and input / outputresistanceTotal power dissipation is the value measured at IN,50/60 Hz, for a 3 pole or 4 pole breaker (values abovethe power P = 3RI2).The resistance between input / output is the valuemeasured per pole (cold state).

version drawout fixedconnection front or rear horizontal rear vertical front or rear horizontal rear verticaltemp. Ti 40 45 50 55 60 40 45 50 55 60 40 45 50 55 60 40 45 50 55 60

NT06 H1/L1 630 630 630 630NT08 H1/L1 800 800 800 800NT10 H1/L1 1000 1000 1000 1000NT12 H1 1250 1250 1250 1250NT16 H1 1600 1520 1480 1430 1600 1560 1510 1600 1550 1600NW08 N/H/L 800 800 800 800NW10 N/H/L 1000 1000 1000 1000NW12 N/H/L 1250 1250 1250 1250NW16 N/H/L 1600 1600 1600 1600NW20 H1/H2/H3 2000 1980 1890 2000 2000 1920 2000NW20 L1 2000 1900 1850 1800 2000 – – – – – – – – – –NW25 H1/H2/H3 2500 2500 2500 2500NW32 H1/H2/H3 3200 3100 3000 2900 3200 3200 3200NW40 H1/H2/H3 4000 3900 3750 3650 4000 3850 4000 3900 3800 4000NW40b H1/H2 4000 4000 4000 4000NW50 H1/H2 5000 5000 5000 5000NW63 H1/H2 – – – – – 6300 6200 – – – – – 6300

Masterpact Schneider Electric105

Factors affecting switchboard designThe temperature around the circuit breaker and itsconnections:This is used to define the type of circuit breaker to beused and its connection arrangement.Vents at the top and bottom of the cubicles:Vents considerably reduce the temperature inside theswitchboard, but must be designed so as to respectthe degree of protection provided by the enclosure.For weatherproof heavy-duty cubicles, a forcedventilation system may be required.The heat dissipated by the devices installed in theswitchboard:This is the heat dissipated by the circuit breakersunder normal conditions (service current).The size of the enclosure:This determines the volume for cooling calculations.Switchboard installation mode:Free-standing, against a wall, etc.Horizontal partitions:Partitions can obstruct air circulation within theenclosure.

Derating in switchboard

NoteThe values indicated in these tables have been extrapolated from test data andtheoretical calculations. These tables are only intended as a guide and cannot replaceindustrial experience or a temperature rise test.

Masterpact NT06-16 H1/L1 (switchboard 2000 x 400 x 400 mm)Type NT06 H1/L1 NT08 H1/L1 NT10 H1/L1 NT12 H1 NT16 H1

4 H1/L1 H1/L13 630 630 800 800 1000/1000 1000/1000 1250 1250 1400 15202143 630 630 800 800 1000/950 1000/1000 1250 1250 1330 14402143 630 630 800 800 1000/890 1000/960 1200 1250 1250 134021

43 630 630 800 800 1000/960 1000/1000 1250 1250 1330 14002143 630 630 800 800 1000/910 1000/980 1220 1250 1260 13302143 630 630 800 800 1000/860 1000/930 1150 1230 1200 126021

Switchboard composition

Connection type

Busbar dimensions (mm)

Ventilated switchboard(� IP31)

Ta = 35°C

Ta = 45°C

Ta = 55°C

Non ventilatedswitchboard (� IP54)

Ta = 35°C

Ta = 45°C

Ta = 55°C

4321

2b. 40x5 2b. 50x5 3b. 63x52b. 63x5

3b. 63x53b. 50x5

3b. 80x53b. 63x5

Basis of tablesc switchboard dimensionsc number of circuit-breakers installedc type of breaker connectionsc drawout versionsc ambient temperature outside of the switchboard: Ta

(IEC 60439-1).

2000

400400

2000

400400

E47

710A

E47

709A

Masterpact Schneider Electric106

Installationrecommendations

Derating in switchboards

Masterpact NT06-08 H1/L1 (switchboard 2300 x 1100 x 500 mm)Type NT06 H1/L1 NT08 H1/L1

5 630 630 8004 630 630 630 800 8003 630 630 630 630 800 800 8002 630 630 630 630 630 630 800 800 800 800 8001 6305 630 630 8004 630 630 630 800 8003 630 630 630 630 800 800 8002 630 630 630 630 630 630 800 800 800 800 8001 6305 630 630 8004 630 630 630 800 8003 630 630 630 630 800 800 8002 630 630 630 630 630 630 800 800 800 800 8001 6305 630 630 8004 630 630 630 800 8003 630 630 630 630 800 800 8002 630 630 630 630 630 630 800 800 800 800 8001 6305 630 630 8004 630 630 630 800 8003 630 630 630 630 800 800 8002 630 630 630 630 630 630 800 800 800 800 8001 6305 630 630 8004 630 630 630 800 8003 630 630 630 630 800 800 8002 630 630 630 630 630 630 800 800 800 800 8001 630

500

600

2300

200

300

500

600

2300

200

300

E47

712B

E47

711B

54321

NoteThe values indicated in these tables have been extrapolated from test data andtheoretical calculations. These tables are only intended as a guide and cannot replaceindustrial experience or a temperature rise test.

Switchboard composition

Connection type

Busbar dimensions (mm)

Ventilated switchboard (� IP31)

Ta = 35°C

Ta = 45°C

Ta = 55°C

Non ventilated switchboard (� IP54)

Ta = 35°C

Ta = 45°C

Ta = 55°C

2b. 40x5 2b. 50x5

Masterpact Schneider Electric107

NoteThe values indicated in these tables have been extrapolated from test data andtheoretical calculations. These tables are only intended as a guide and cannot replaceindustrial experience or a temperature rise test.

Masterpact NT10-16 H1/L1 (switchboard 2300 x 1100 x 500 mm)Type NT10 H1/L1 NT12 H1 NT16 H1

5 H1/L1 H1/L1 H1/L1 H1/L14 1000/1000 12503 1000/1000 1000/1000 1250 1250 15002 1000/1000 1000/1000 1000/1000 1000/1000 1250 1250 1250 1250 1460 1600 1550154 1000/1000 12503 1000/1000 1000/1000 1250 1250 14202 1000/960 1000/1000 1000/1000 1000/1000 1250 1250 1250 1250 1400 1500 1480154 1000/920 12503 1000/950 1000/930 1250 1250 13302 1000/900 1000/1000 1000/970 1000/950 1250 1250 1250 1250 1300 1400 1370154 1000/950 12503 1000/1000 1000/960 1250 1250 13702 1000/1000 1000/1000 1000/1000 1000/970 1250 1250 1250 1250 1400 1500 140054 1000/900 11803 1000/950 1000/910 1250 1190 13002 1000/950 1000/1000 1000/960 1000/930 1250 1250 1250 1220 1350 1430 132054 1000/850 11203 1000/900 1000/860 1200 1130 12102 1000/880 1000/970 1000/910 1000/870 1210 1250 1210 1150 1250 1350 1250

500

600

2300

200

300

500

600

2300

200

300

E47

712B

E47

711B

54321

Switchboard composition

Connection type

Busbar dimensions (mm)

Ventilated switchboard (� IP31)

Ta = 35°C

Ta = 45°C

Ta = 55°C

Non ventilated switchboard (� IP54)

Ta = 35°C

Ta = 45°C

Ta = 55°C

3b. 63x52b. 63x5

3b. 63x53b. 50x5

3b. 80x53b. 63x5

Masterpact Schneider Electric108

Installationrecommendations

Derating in switchboards

NoteThe values indicated in these tables have been extrapolated from test data arndtheoretical calculations. These tables are only intended as a guide and cannot replaceindustrial experience or a temperature rise test.

Masterpact NW08-10 N/H/L (switchboard 2300 x 800x 900 mm)Type NW08 N/H/L NW10 N/H/L

4 8003 800 800 10002 800 800 800 1000 10001 800 800 800 800 800 1000 1000 1000 10004 8003 800 800 10002 800 800 800 1000 10001 800 800 800 800 800 1000 1000 1000 10004 8003 800 800 10002 800 800 800 1000 10001 800 800 800 800 800 1000 1000 1000 10004 8003 800 800 10002 800 800 800 1000 10001 800 800 800 800 800 1000 1000 1000 10004 8003 800 800 10002 800 800 800 1000 10001 800 800 800 800 800 1000 1000 1000 10004 8003 800 800 10002 800 800 800 1000 10001 800 800 800 800 800 1000 1000 1000 1000

2300

800900

2300

800900

E47

714A

E47

713A

4321

Switchboard composition

Connection type

Busbar dimensions (mm)

Ventilated switchboard (� IP31)

Ta = 35°C

Ta = 45°C

Ta = 55°C

Non ventilated switchboard (� IP54)

Ta = 35°C

Ta = 45°C

Ta = 55°C

2b. 50x5 3b. 63x52b. 63x5

Masterpact Schneider Electric109

NoteThe values indicated in these tables have been extrapolated from test data andtheoretical calculations. These tables are only intended as a guide and cannot replaceindustrial experience or a temperature rise test.

Masterpact NW12-16 N/H/L (switchboard 2300 x 800 x 900 mm)Type NW12 N1 NW12 H/L NW16 N1 NW16 H/L

43 1250 12502 1250 1250 1250 1250 1600 16001 1250 1250 1250 1250 1250 1250 1250 1250 1550 1600 1600 1600 1600 160043 1250 12502 1250 1250 1250 1250 1500 16001 1250 1250 1250 1250 1250 1250 1250 1250 1470 1600 1600 1600 1600 160043 1250 12502 1250 1250 1250 1250 1380 14701 1200 1250 1250 1250 1250 1250 1250 1250 1380 1500 1500 1520 1600 160043 1240 12502 1250 1250 1250 1250 1425 16001 1250 1250 1250 1250 1250 1250 1250 1250 1440 1550 1550 1600 1600 160043 1170 12502 1210 1210 1250 1250 1360 15001 1200 1250 1250 1250 1250 1250 1250 1250 1360 1470 1470 1500 1600 160043 1100 12502 1140 1170 1250 1250 1280 14001 1130 1200 1200 1200 1250 1250 1250 1250 1280 1380 1380 1400 1520 1520

2300

800900

2300

800900

E47

714A

E47

713A

4321

Switchboard composition

Connection type

Busbar dimensions (mm)

Ventilated switchboard (� IP31)

Ta = 35°C

Ta = 45°C

Ta = 55°C

Non ventilated switchboard (� IP54)

Ta = 35°C

Ta = 45°C

Ta = 55°C

3b. 63x53b. 50x5

3b. 63x53b. 50x5

3b. 80x53b. 63x5

3b. 80x53b. 63x5

Masterpact Schneider Electric110

Installationrecommendations

Derating in switchboards

NoteThe values indicated in these tables have been extrapolated from test data andtheoretical calculations. These tables are only intended as a guide and cannot replaceindustrial experience or a temperature rise test.

Masterpact NW20-40 N/H/L (switchboard 2300 x 800 x 900 mm)Type NW20 H1/H2/H3 NW20 L1 NW25 H1/2/3 NW32 H1/2/3 NW40 H1/2/3

43 2000 18302 2000 2000 2000 2000 2000 2000 2375 2500 3040 3200 3320 3700143 2000 17502 2000 2000 2000 1810 1960 1920 2250 2380 2880 3100 3160 3500143 1880 16402 2000 2000 2000 1700 1850 1800 2100 2250 2690 2900 2960 3280143 2000 17502 2000 2000 2000 1800 1900 1890 2125 2275 2650 2850 3040 3320143 1900 16602 1900 1960 1960 1680 1810 1800 2000 2150 2550 2700 2880 3120143 1780 15502 1800 1920 1920 1590 1700 1700 1900 2020 2370 2530 2720 29601

2300

800900

2300

800900

E47

714A

E47

713A

4321

Switchboard composition

Connection type

Busbar dimensions (mm)

Ventilated switchboard (� IP31)

Ta = 35°C

Ta = 45°C

Ta = 55°C

Non ventilated switchboard (� IP54)

Ta = 35°C

Ta = 45°C

Ta = 55°C

3b. 100x5 3b. 100x5 4b. 100x5 3b. 100x10 4b. 100x10

Masterpact Schneider Electric111

NoteThe values indicated in these tables have been extrapolated from test data andtheoretical calculations. These tables are only intended as a guide and cannot replaceindustrial experience or a temperature rise test.

Masterpact NW40b-63 H1/H2 (switchboard 2300 x 1400 x 1500 mm)Type NW40b H1/H2 NW50 H1/H2 NW63 H1/H2

432 4000 4000 4700 5000 60501432 4000 4000 4450 4850 56701432 4000 4000 4200 4600 53501

432 4000 4000 4350 4650 52901432 4000 4000 4100 4400 50401432 3840 3840 3850 4150 47301

Switchboard composition

Connection type

Busbar dimensions

Ventilated switchboard (� IP31)

Ta = 35°C

Ta = 45°C

Ta = 55°C

Non ventilated switchboard (� IP54)

Ta = 35°C

Ta = 45°C

Ta = 55°C

2300

14001500

2300

14001500

E47

716B

E47

715B

4321

5b. 100x10 7b. 100x10 8b. 100x10

Masterpact Schneider Electric112

Installationrecommendations

Substitution kitFixed / drawout devices800 to 3200 A

Mounting diagramFixed version Drawout version

Ø11,5

Ø10,5

2 Ø11,5 x 22

175

F

162,5167,5 (3P)282,5 (4P)

Y

11010

4 Ø6,5

2 Ø11 X 6

267,5 (4P)

Ø14

Ø11

Door cut-outc without an escutcheon, the cut-out is identical (270 x 325 mm).c with the former escutcheon, the cut-out is identical (270 x 325 mm).c with the new escutcheon, the cut-out is different.

Fixed version Drawout version

Y

X135 (1)158 (2)

270 (1)316 (2)

295 mini (3P)410 mini (4P) 295 mini

162,5 (1)182 (2)

325 (1)364 (2)

X

300 mini (3P)415 mini (4P)

Y

300 mini

135 (1)222 (2)

270 (1)379 (2)

153,3 (1)

47 (1)162,5 (1)182 (2)325 (1)

364 (2)

E59

220A E

5922

1A

Note:(1) Without escutcheon(2) With escutcheonReferences X and Y represent the symmetry planes forthree-pole devices

Fixing points are identical for Masterpact (M08 to M32) and Masterpact (NW08 to NW32),except for the four-pole craddle.

It is possible to replace a Masterpact (M08 to M32) with a new Masterpact (NW08to NW32) with the same power rating.Substitution is possible for the following types of circuit breakers:c N1, H1, H2 for both fixed and drawout versionsc L1 for drawout versions up to 2000 A.

E59

218B

E59

219A

Power connectionsSelect a set of retrofit connectors to replace the standard connectors and avoid anymodifications to the busbars (see the retrofit section in "orders and quotations")

Y

200

124162

F

2Ø9,5 X 25

200 (3P)315 (4P)

150

2Ø11 X 6

Ø9,5

Ø11

Ø14

: Masterpact NW: Masterpact M

Masterpact Schneider Electric113

Indication contacts Craddle contacts

T4T3T2T1

Micrologic

Z4Z3Z2Z1

N L3L2L1

Q

Z5VN

V1

V2

V3

M3

M2

M1

F2+

F1

I

U

24 V DC

X2

X1

SG

2

SG

1

471

S1

474

484

S2Q

1

Q2

Q3

M2C M6C

181

182

184

SDE2

81

82 84

SDE1

K2

Res

K1

D2

D1

AT

MN MX2

C12

C11

MX1

C2

C3

C1

BPO

A2

A3

A1

BPF

XFPF

252

254

251

B1

MCH

B3

B2

CH

D1

C11 C1

A1

251

B1

81

82 84 D4 C12

C2

A4

252

254

262

B4

Z21

Z22

Z11

Z12

Z21

F2+

F1(1)

power

or

faul

t

faul

t

oror

read

y to

clos

e

char

ged

ALR, V, MR6, Roptions

equivalent functionsusing M2C or M6C

E59

217A

CT3

12 1411

22 2432 3431 21

OF4

42 4441

OF3 OF2 OF1

12 1422 2432 3442 44

1131 2141

OF . . OF

CE

. . 1

. . 2

. . 4

. . 6

. . 8

. . 5

EF . .

. . 2

. . 4

. . 1

912

911

934

932

931

CT2 CT1

924

922

921

914

374

372

371

331

332

334

CE3

321

322

324

CE2

311

312

314

CE1

334

332

324

322

314

312

331

321

311

822

824

821

812

814

811

832

834

831

CD3 CD2 CD1

362

364

352

354

361

351

closedopen closed connectedand closed

not connectedor connectedand open

or

Testconnecteddisconnected

E59

223A

M08 to M32 NW08 to NW32

Identical to Masterpact M

New or additional functions (1) The current transformer for the external neutral must be replaced

Different than Masterpact M

E59

222A

Electrical diagramsCorrespondences between Masterpact NW and Masterpact M terminal blocks

Power Control unit Remote operation