Element D Services Electrical
D5022 Master Lighting Fixture Schedule
PART 1 - GENERAL
1.01 OVERVIEW
A. The following Table lists lighting fixture types, manufacturers, and models that are based on various applications at MD Anderson facilities.
B. The A/E shall use the following baseline lighting fixture schedule in developing a project specific lighting fixture schedule. The A/E shall incorporate at least (3) “equivalent to, or better than” manufacturers and associated catalog numbers per each type of fixture. The criterion for evaluation of equivalency shall include, but not limited to, photometric characteristic, material, construction, features, finishes, lenses, and cost, etc.
C. Other manufacturers for lighting fixture(s) or lamp(s) equal (or better than) in design, performance and function will be considered upon A/E’s evaluation and approval. The approved lighting fixture(s) or lamp(s) shall be incorporated into project specific lighting fixture schedule.
D. Substitution to approved project lighting fixture schedule shall follow the substitution procedure outlined in 01 31 00 - Project Administration.
PART 2 - MASTER LIGHTING FIXTURE SCHEDULE
Type Manufacturer and Model Lamps Description Voltage Application FA
Lithonia 2SPGB332RWK20MVOLT1/3TUBIHPMP3875 Lightolier PRA2GRFK20332UNVH3 Cooper Lighting – Metalux 2GCRA-332-K20UNIV-HPT8
3 - 25w T8 3 lamp 2 x 4 lay-in with K20 , similar pattern K12, 3/16” Extruded virgin acrylic lens and aluminum regressed lens frame with reveal, single 3 lamp ballast
277 Exam rooms, offices, support spaces
The University of Texas MASTER LIGHTING FIXTURE SCHEDULE MD Anderson Cancer Center D5022 ODG021915 1 OF 8
Element D Services Electrical
D5022 Master Lighting Fixture Schedule Type Manufacturer and Model Lamps Description Voltage Application FB Lithonia
2SPGB232RWK20MVOLTTUBIHPMP3875
2 - 25w T8
2 lamp 2 x 4 lay-in with K20 acrylic lens and aluminum regressed lens frame with reveal
277 Offices, break rooms, support spaces
FC Lithonia SPGB232RWK20MVOLTTUBIHPMP3875
2 - 25 w T8
2 lamp 1 x 4 lay-in with K20 acrylic lens and aluminum regressed lens frame with reveal
277 Support spaces, break rooms, odd shaped spaces
FD Lithonia 2SPGB317RWK20MVOLT1/3TUBIHPMP3875
3 - 17w T8
3 lamp 2 x 2 lay-in with K20 acrylic lens and aluminum regressed lens frame with reveal
277 Inside corridors, support spaces, odd shaped rooms
FE Lithonia 2SPGB217RWK20MVOLTTUBIHPMP3875
2 - 17w T8
2 lamp 2 x 2 lay-in with K20 acrylic lens and aluminum regressed lens frame with reveal
277 Window corridors, elevator lobbies, dressing cubicles
FF Lithonia 2AVG317MDRMVOLT1/3TUBIHP Metalux 2RDI-317RP-UNV-TU-B332IUNVHPB-U
3 - 17w T8 3 lamp 2 x 2 lay-in direct/indirect
277 Waiting rooms, open office work station areas, imaging corridors and suites. With ADEZ suffix for conference rooms and dimming.
FF1 Lithonia 2AVG217MDRMVOLTTUBIHP Metalux 2RDI-217RP-UNV-TU-B232IUNVHPB-U
2 - 17w T8
2 lamp 2 x 2 lay-in direct/indirect
277 Open office work station areas, imaging corridors and suites. With ADEZ suffix for conference rooms and dimming.
The University of Texas MASTER LIGHTING FIXTURE SCHEDULE MD Anderson Cancer Center D5022 ODG021915 2 OF 8
Element D Services Electrical
D5022 Master Lighting Fixture Schedule Type Manufacturer and Model Lamps Description Voltage Application FG Lithonia 2AVG332MDRMVOLT1/3TUBIHP
Metalux 2RDI-332RP-UNV-TU-B332IUNVHPB-U
3 - 25 w T8
3 lamp 2 x 4 lay-in direct/indirect
277 Open office work station areas, private office. With ADEZ suffix for conference rooms and dimming.
FG1 Lithonia 2AVG232MDRMVOLTTUBIHP Metalux 2RDI-232RP-UNV-TU-B232IUMVHPB-U
2 - 32w T8
2 lamp 2 x 4 lay-in direct/indirect
277 Open office work station areas. With ADEZ suffix for conference rooms and dimming.
FM Series
Alkco SF332ECBRSW, SF325ECBRSW, SF317ECBRSW
1 - 32w T8, 1 - 25w T8, 1 - 17w T8
1 lamp solid front tasklight with right switch. All tasklights require area occupancy sensor control or an integral sensor.
120 Only Exam rooms, kitchens, lab areas
FN Lithonia 2SPG332K20MVOLT1/3TUBIHP
3 - 32w T8
3 lamp 2 x 4 lay-in with flat white lens frame
277 Lab areas, research area offices, inpatient areas.
FO Lithonia 2SPG232K20MVOLTTUBIHP
2 - 32w T8
2 lamp 2 x 4 lay-in with flat white lens frame
277 Lab support areas, research area support spaces, inpatient areas.
FP Lithonia SPG232K20MVOLTTUBIHP
2 - 32w T8
2 lamp 1 x 4 lay-in with flat white lens frame
277 Lab areas along benchtops, inpatient areas.
FR Lithonia AF2/13DTT8AR277TRWEMB
2 - 13TT
2 lamp downlight with integral white trim ring
277 Downlight in elevator lobbies (pre-energy code)
FR1 Lithona AF1/13DTT8AR277TRWEMB
1 - 13TT
1 lamp downlight with integral white trim ring
277 Downlight in elevator lobbies (pre-energy code)
The University of Texas MASTER LIGHTING FIXTURE SCHEDULE MD Anderson Cancer Center D5022 ODG021915 3 OF 8
Element D Services Electrical
D5022 Master Lighting Fixture Schedule Type Manufacturer and Model Lamps Description Voltage Application FR2 Lithonia AF2/13DTT8AR120TRWEMB
2 - 13TT
2 lamp downlight with integral white trim ring
120 Reading light, accent light in patient rooms (pre-energy code)
FS Lithonia AF126TRT8ARMVOLTTRWGEB10
1 - 26TRT 1 lamp downlight with integral white trim ring
277 Special downlight applications
FS2 Lithonia AF1/26TRT8AR277TRWADEZ
1 - 26TRT 1 lamp downlight with integral white trim ring
277 Dimming downlight applications
FT Lithonia AFV 18/26/32 TRT8AR TRW 1 – 18W/ 26W/32W TRT
1 lamp vertical lamp downlight
MVOLT General downlighting
M1 Devine LMS500-LED-277-BLK
LED
embedded exterior
277 Step, ramp, exteriors, etc.
M2 Moldcast PERSRL250MH277DBZ
250w MH
exterior poletop
277 Sidewalk areas
M2P Ameron Centrecon SEO-03TG412 (pole for Type M2 fixture)
Pole
octagonal, 13 foot embedded, 10 foot flange, polished green color
277
Lithonia KBR8100MR5277LPI 50w or 100w 42 inch bollard 277 Walkways M3 Hydrel 4630P3035M277SPCAIHLBZ
35w MH par 30
landscape
277 Planting areas
XA Lithonia LQMS1R120/277
LED
one side EXIT sign, black finish
120/277
Exit marking
XB Lithonia LQMS3R120/277
LED two side EXIT sign, black finish
120/277 Exit marking
The University of Texas MASTER LIGHTING FIXTURE SCHEDULE MD Anderson Cancer Center D5022 ODG021915 4 OF 8
Element D Services Electrical
D5022 Master Lighting Fixture Schedule Type Manufacturer and Model Lamps Description Voltage Application XC Lithonia LQMP1R120/277MROOMINUSE,
Lithonia LQMP1R120/277MXRAYINUSE,
LED custom room sign, black finish
120/277 Outside x-ray rooms, darkrooms, treatment rooms, etc.
Miscellaneous Fixtures (Fixture Type Not Indicated) Lithonia BV2 250M R2 277 RPB04 HS with
pole Lithonia RTS206-5B FINISH
250w MH
exterior poletop, 20 foot pole
277
Lithonia KAD 400M Rx 480SPD09 with pole Lithonia SSS30-6G-DMI-9-DDB (x - distribution to be determined)
400w MH exterior pole top, 30 foot pole
480 South Campus
Lithonia TWA50M277DMB
50w MH
Cut off exterior wall
277 Exterior area
Lithonia TWA26TRTMVOLT DMB 26w TRT Cut off Exterior wall pack
277 Egress door
Allscape SP-0218CF-PLC-277-color
18w
exterior
277 Steps, ramps
ALKCO WG2H2SWH
LED
Wall mounted single side or thru-wall
120/277 Night light or step light
Lithonia DMW232MVOLTTUBIHP 2 - 32w T8 elevator pit
120 Only Worklight
Versailles #1105 Brushed Aluminum 2 - 9w TT Two lamp sconce 277 Lactation rooms Lithonia Avante AVSP 2 13DTT MDR 277 2 - 13 DTT Two lamp sconce 277 Corridor, special applications Lithonia AF10232277TUBIHPHC
2 - 32w T8
10% uplight reflector
277 Mechanical, electrical, janitor’s closet
Lithonia DMW232277TUBIHP
2 - 32w T8
2 lamp vapor tight
277 Wet locations
Lithonia DMW3321201/3TUBIHP
3 - 32w T8
3 lamp vapor tight
120 Only Cold rooms
Speclight FCW4232MVOLT2/1TUBIHPSNREZ
2 – 32w T8 2 lamp wall mount with occupancy sensor and two ballasts
277 Interior stairways
The University of Texas MASTER LIGHTING FIXTURE SCHEDULE MD Anderson Cancer Center D5022 ODG021915 5 OF 8
Element D Services Electrical
D5022 Master Lighting Fixture Schedule Type Manufacturer and Model Lamps Description Voltage Application betaLED
BLD-CAN-40-PD-170-LED-B-UL-WH-43K
LED
Area or pole mounted 277 Parking garage, drive thru, poletop fixtures
Lithonia KVE2400MSYMC277SPD09 with Lithonia SSS20-5G-DM19-DDB pole
400w MH
poletop on typical 20 foot pole
277 Parking garage rooftop
Philips/Color Kinetics io Lighting
LED
accent specialty
120 Coves, accent, decorative
Speclight FSW4332S2X20 AR MVOLT TUBIHP STSL
3-32WT8 3 lamp vapor tight w/ two ballasts
MVOLT Parking garage
Prudential WAL-8-SD-2T8-04-YGW-SC-277-WM-DM
32WT8 wall mount dimming 277 Reading rooms in Diagnostic Imaging Oncology. Lutron Hi-Lume 1% dimmer.
Peerless Envision series
32w T8
cable direct/indirect, custom cable, custom length
277 Specialty indirect applications
A. Notes to Table; Fixture Type ‘F’:
1. 1/3 must be specified to ensure one, three-lamp ballast per fixture.
2. Substitute ADEZ for TUBI for Advance Mark X dimming ballasts.
3. Regressed lens frames with reveal, are typically used to match existing spaces and for enhanced appearance.
4. New compact fluorescent down lights shall be equipped with dual voltage electronic ballasts. Lamp sizing per application.
5. All linear fluorescent lamps shall contain no more than 1.7 mg mercury. All four foot linear lamps shall be high efficiency equivalent to or better than Philips F32T8/ADV841/XEW/ALTO2 or Sylvania FO32/25W/8410XP/SS/ECO 25 watt lamps.
6. Provide program start ballast where occupancy sensor is being specified.
The University of Texas MASTER LIGHTING FIXTURE SCHEDULE MD Anderson Cancer Center D5022 ODG021915 6 OF 8
Element D Services Electrical
D5022 Master Lighting Fixture Schedule PART 3 - DOCUMENT REVISION HISTORY
Issue Date Revision Description Reviser 05-03-07 Initial Adoption of Element. Re-Numbered Element From Z5010 to D5022 DOS Rev. 1 05-17-07 Clarification on voltage “F” fixtures; revised FS and FS2 fixture, added walkway fixture,
added South Campus exterior pole fixture, added exterior wall pack fixture, changed fixture for elevator pit, added wall sconce fixtures, revised interior walkway fixture.
SAK
Rev. 2 12-09-08 Included sustainability requirements based upon TGCE's evaluation. (Part 2) JCD Rev. 3 03-02-10 Revisions made to type FA, FB, FC, FD, FE, FF, FF1, FG, FG1, FN, FO, FP, FT, M1,
fixtures. Deleted Phoenix DL70MHDWT60-277, and Widelight RSPM-100-RSPM-100-S-277-LMP-PND-RC-F1-SA, Added Speclight FSW4332S2X20 AR MVOLT TUBIHP STSL, and Prudential WAL-8-SD-2T8-04-YGW-SC-277-WM-DM.
DC
Rev. 4 09-16-10 A. Revised 1.01 Overview to read as:
B. The following Table lists lighting fixture types, manufacturers, and models that are based on various applications at MD Anderson facilities.
C. The A/E shall use the following baseline lighting fixture schedule in developing a project specific lighting fixture schedule. The A/E shall incorporate at least (1) additional equivalent manufacturer(s) and associated catalog numbers per each type of fixture. The criterion for evaluation of equivalency shall include, but not limited to, photometric characteristic, material, construction, features, finishes, lenses, and cost, etc.
D. Other manufacturers for lighting fixture(s) or lamp(s) equal (or better than) in design, performance and function will be considered upon A/E’s evaluation and approval. The approved lighting fixture(s) or lamp(s) shall be incorporated into project specific lighting fixture schedule.
E. Substitution to approved project lighting fixture schedule shall follow the substitution procedure outlined in 01 31 00 - Project Administration.
DC, PL, JD
The University of Texas MASTER LIGHTING FIXTURE SCHEDULE MD Anderson Cancer Center D5022 ODG021915 7 OF 8
Element D Services Electrical
D5022 Master Lighting Fixture Schedule Issue Date Revision Description Reviser
F. Added alternate manufacturers to type FA, FF, FF1, FG, FG1 lighting fixtures.
G. Added manufacturers for LED lighting fixtures.
H. Revised Note 5 to read as: “All linear fluorescent lamps shall contain no more than 1.7 mg mercury. All four foot linear lamps shall be high efficiency equivalent to or better than Philips F32T8/ADV841/XEW/ALTO2 or Sylvania FO32/25W/8410XP/SS/ECO 25 watt lamps.”
I. Added Note 6: “Provide program start ballast where occupancy sensor is being specified.”
Rev. 5 03-17-11 Clarified that A/E shall incorporate “at least (3) equivalent or better manufacturers” for
project lighting fixture schedule. JD
Rev. 6 02-19-15 Removed Wattstopper reference. JP
END OF ELEMENT D5022