Master Examination Practice Drill #3 2011

Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Embed Size (px)

Citation preview

Page 1: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Master Examination

Practice Drill #3 2011

Page 2: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded hubs, which contains a 125-volt, 20-ampere receptacle outlet. The conduits are to be threaded wrench tight into the hubs and, in general, shall be secured with at LEAST _____ of the enclosure.A. 8 inchesB. 12 inchesC. 18 inchesD. 24 inches

Page 3: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

1. C 314.23(F) 181

Page 4: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 2. In general, if the cablebus system is rated 95 amperes, the MAXIMUM allowable rating of the overcurrent device used to protect the cablebus is _______.A. 80 amperesB. 90 amperesC. 95 amperesD. 100 amperes

Page 5: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

2. D 370.5 227240.4(B)(2)&(3)

90

240.6(A) 91

Page 6: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 3. A twenty-five (25) ft. long tap conductor tapped from a 100 ampere rated feeder conductor, shall have an ampacity of NOT less than ________.A. 50 amperesB. 75 amperesC. 25 amperesD. 33.3 amperes

Page 7: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

3. D 240.21(B)&(B)(2)(1)

92&93

100 amperes/3 = 33.3 amperes

Page 8: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 4. Disregarding exceptions, bonding between Class I locations and the point of grounding for service equipment may be done by _________.A. Double locknutsB. Bonding jumpersC. Insulated bushingsD. Metal raceways

Page 9: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

4. B 501.30(A) 381

Page 10: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 5. Determine the demand load, in VA, on the ungrounded service-entrance conductors, for the general-lighting and receptacles for a 25,000 sq. ft. office building that has one hundred-fifty (150) general-purpose duplex receptacles. Consider the service overcurrent protection device is NOT listed for continuous use.A. 112,075 VAB. 106,000 VAC. 90,200 VAD. 127,875 VA

Page 11: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

5. D Tbl. 220.12 63

220.14(I) 63

220.44 64

Tbl. 220.44 64

Art. 100 27

230.42(A)(1) 8225,000 sq. ft. x 3.5 VA x 125% (lighting) = 109,375 VA150 receptacles x 180 VA each = 27,000VA 1st 10,000 VA @ 100% = 10,000 VA27,000 VA – 10,000 VA = 17,000 VA @ 50% = 8,500VA

Total = 127,875 VA

Page 12: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 6. When an electrical service is required to have a grounded conductor present, what is the smallest grounded conductor permitted for an electric service using size 1000 kcmil copper undergrounded (phase) conductors?A. 3/0 AWG copperB. 2/0 AWG copperC. 1/0 AWG copperD. 4/0 AWG copper

Page 13: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

6. B 250.24(C)(1) 105Tbl. 250.66 115

Page 14: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 7. Determine the MINIMUM number of 20-ampere, 277-volt, general-lighting branch circuits required for a 150,000 sq. ft. department store, when the actual connected lighting load is 400 kVA,A. 72 branch circuitsB. 82 branch circuitsC. 91 branch circuitsD. 102 branch circuits

Page 15: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

7. C 210.19(A)91) 52210.11(B) 51

400 kVA = 400,000 VA x 125% (continuous load) = 500,000 VA (bldg.)

277 volts x 20 amperes = 5540 VA (one circuit)

500,000 VA. (bldg. lighting) 5,540 VA (one circuit) = 90.2 = 91 circuits

*NOTE – Circuits need only to be installed to service the connected load.

Page 16: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 8. Where a two-gang box contains two (2) single-pole switches, unless the box is equipped with permanently installed barriers, the voltage between the switches shall NOT be in excess of _______.A. 120 voltsB. 277 voltsC. 240 voltsD. 300 volts

Page 17: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

8. D 404.8(B) 268

Page 18: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 9. An aluminum grounding electrode shall be _________.A. Installed at least 18 inches above the

earthB. Installed at least 24 inches above the

earthC. In direct earth burialD. Prohibited

Page 19: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

9. D 250.52(B)(2) 112

Page 20: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 10. A panelboard is limited to 42 overcurrent protective devices where ________.A. The panelboard is a power

panelboardB. The panelboard is a “split-bus”

type panelboardC. The panelboard supplies lighting

branch-circuits onlyD. One is installed

Page 21: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

10. B 408.36, Ex. 2 276

Page 22: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 11. When rigid polyvinyl chloride conduit (PVC) is used to enclose conductors feeding a wet-niche luminaire in a permanently installed swimming pool, a ______ insulated copper grounding conductor shall be installed in this conduit, unless a listed low-voltage lighting system not requiring grounding is used.A. 12 AWGB. 10 AWGC. 8 AWGD. 6 AWG

Page 23: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

11. C 680.23(B)(2)(b)

581

Page 24: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 12. In general, what is the largest size transformer, in kVA, that may be installed in an area or room that is NOT constucted in a fire-resistant manner?A. 75 KVAB. 112 ½ KVAC. 150 KVAD. 50 KVA

Page 25: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

12. B 450.21(B) 352

Page 26: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 13. When calculating the total load of an office building, and the number of general-purpose receptacles to be installed is not yet determined, an additional load of _____ volt-amp(s) per square foot is required for the receptacle outlets.A. OneB. TwoC. One-HalfD. Three

Page 27: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

13. A 220.14(K)(2) 63

Page 28: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 14. When sizing time-delay Class CC fuses for motor branch-circuit, short-circuit and ground-fault protection, they are to be sized at the same value as ________.A. inverse-time circuit breakersB. Nontime-delay fusesC. Instantaneous trip circuit

breakersD. Adjustable trip circuit breakers

Page 29: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

14. B Tbl. 430.52, Note 1

323

Page 30: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 15. Conductors other than service-entrance conductors shall be permitted to be installed in a cable tray with service-entrance conductors provided __________.A. A solid fixed barrier of material

compatible with the cable tray is installed to separate the systems

B. The conductors are not in excess of 480 volts to ground

C. The voltage between the conductors is not in excess of 600 volts

D. The conductors have equal insulation and temperature ratings

Page 31: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

15. A 203.44, Ex 82

Page 32: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 16 The MAXIMUM allowable ampacity of a size 750 kcmil XHHW aluminum conductor where there are six (6) current-carrying conductors in the raceway, installed in a dry location, where the ambient temperature will reach 22°C is ________A. 323.40 amperesB. 365.40 amperesC. 361.92 amperesD. 348.00 amperes

Page 33: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

16. C Tbl. 310.15(B)(16)

154

Tbl. 310.15(B)(2)(a)

150

Tbl. 310.15(B)(3)(a)

152Size 750 kcmil AL ampacity (before derating) = 435 amperes435 amps x 1.04 (temp correction) x .8 (adj. factor) = 361.92 amperes

Page 34: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 17. In which of the following locations is a cable tray prohibited to be installed?A. BasementB. Storage RoomsC. Sealed Ceiling SpacesD. When Passing Through a Wall

Page 35: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

17. C 392.18 (D)&(E)

240

Page 36: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 18. What is the MINIMUM size copper common grounding electrode conductor required to run through a building to four (4) separately derived systems (transformers) each having size 3/0 AWG copper secondary conductors.A. 4 AWGB. 2 AWGC. 3/0 AWGD. 8 AWG

Page 37: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

18. C 250.30(A)(6)(a)(1)

108

Page 38: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 19. Where a commercial building has a 600 ampere, 3-phase, 208Y/120 volt service supplied with two (2) paralled sets of size 350 kcmil copper conductors installed in separate raceways, determine the MINIMUM size aluminum grounding electrode conductor permitted to the metal water piping system used as the grounding electrod.A. 250 kcmilB. 4/0 AWGC. 3/0 AWGD. 2/0 AWG

Page 39: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

19. B 250.66 115Tbl. 250.66 115

350 kcmil x 2 conductors = 750 kcmil

*NOTE – A size 4/0 AWG aluminum grounding electrode conductor should be selected

Page 40: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 20. The NEC permits trade size 3/8 in. flexible metal conduit (FMC) to be used to enclose tap conductors for luminaires, provided the length of the FMC does NOT exceed __________.A. 4 feetB. 6 feetC. 8 feetD. 10 feet

Page 41: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

20. B 348.20(A)(2)c.

206

Page 42: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 21. What is the MAXIMUM distance allowed to support intermediate metal conduit (IMC) from a junction box, where structural members do not readily permit fastening?A. 3 feetB. 5 feetC. 6 feetD. 8 feet

Page 43: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

21. B 342.30(A)(2) 203

Page 44: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 22. All of the following listed copper conductors are to be installed in an electrical metallic tubing (EMT) that is in excess of 24 inches long.24-size 10 AWG with TW insulation10-size 10 AWG with THW insulation14-size 12 AWG with THHN insulation

Determine the MINIMUM trade size of EMT required.A. 2 in.B. 2 ½ in.C. 3 in.D. 3 ½ in.

Page 45: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

22. A Chpt. 9, Tbl. 5 717&718

Chpt. 9, Tbl. 4 712Size 10 AWG TW = .0243 sq. in. x 24 = .5832 sq. in.Size 10 AWG THW = .0243 sq. in. x 10 = .2430 sq. in.Size 12 AWG THNN = .0133 sq. in. x 14 = .1862 sq. in.

TOTAL = 1.1024 sq. in. *NOTE – Trade size 2 inch EMT with a permitted fill of 1.342 sq. in. @ 40% should be selected

Page 46: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 23. When combination surface nonmetallic raceways are used both for signaling and for power and lighting circuits, the different systems shall be ________.A. ProhibitedB. Run in the same compartmentC. Separated by at least ½ in.D. Run in separate compartments

Page 47: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

23. D 388.70 238

Page 48: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 24. When sizing fuses for a branch circuit serving a hermetic refrigerant motor-compressor, the device shall NOT exceed ____ of the rated load current marked on the nameplate of the equipment.A. 115 percentB. 125 percentC. 175 percentD. 225 percent

Page 49: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

24. D 440.22(A) 343

Page 50: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 25. Where rigid metal conduit (RMC) is used to protect a grounding conductor, the conduit must ________.A. Be isolated from the grounding

conductorB. Be electrically continuous from

cabinet to ground clampsC. Be identified with green paintD. Not be connected to or touching

the ground clamp

Page 51: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

25. B 250.64(E) 114

Page 52: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Click here to advance to non-timed drill

Page 53: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded hubs, which contains a 125-volt, 20-ampere receptacle outlet. The conduits are to be threaded wrench tight into the hubs and, in general, shall be secured with at LEAST _____ of the enclosure.A. 8 inchesB. 12 inchesC. 18 inchesD. 24 inches

Page 54: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

1. C 314.23(F) 181

Page 55: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 2. In general, if the cablebus system is rated 95 amperes, the MAXIMUM allowable rating of the overcurrent device used to protect the cablebus is _______.A. 80 amperesB. 90 amperesC. 95 amperesD. 100 amperes

Page 56: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

2. D 370.5 227240.4(B)(2)&(3)

90

240.6(A) 91

Page 57: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 3. A twenty-five (25) ft. long tap conductor tapped from a 100 ampere rated feeder conductor, shall have an ampacity of NOT less than ________.A. 50 amperesB. 75 amperesC. 25 amperesD. 33.3 amperes

Page 58: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

3. D 240.21(B)&(B)(2)(1)

92&93

100 amperes/3 = 33.3 amperes

Page 59: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 4. Disregarding exceptions, bonding between Class I locations and the point of grounding for service equipment may be done by _________.A. Double locknutsB. Bonding jumpersC. Insulated bushingsD. Metal raceways

Page 60: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

4. B 501.30(A) 381

Page 61: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 5. Determine the demand load, in VA, on the ungrounded service-entrance conductors, for the general-lighting and receptacles for a 25,000 sq. ft. office building that has one hundred-fifty (150) general-purpose duplex receptacles. Consider the service overcurrent protection device is NOT listed for continuous use.A. 112,075 VAB. 106,000 VAC. 90,200 VAD. 127,875 VA

Page 62: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

5. D Tbl. 220.12 63

220.14(I) 63

220.44 64

Tbl. 220.44 64

Art. 100 27

230.42(A)(1) 8225,000 sq. ft. x 3.5 VA x 125% (lighting) = 109,375 VA150 receptacles x 180 VA each = 27,000VA 1st 10,000 VA @ 100% = 10,000 VA27,000 VA – 10,000 VA = 17,000 VA @ 50% = 8,500VA

Total = 127,875 VA

Page 63: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 6. When an electrical service is required to have a grounded conductor present, what is the smallest grounded conductor permitted for an electric service using size 1000 kcmil copper undergrounded (phase) conductors?A. 3/0 AWG copperB. 2/0 AWG copperC. 1/0 AWG copperD. 4/0 AWG copper

Page 64: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

6. B 250.24(C)(1) 105Tbl. 250.66 115

Page 65: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 7. Determine the MINIMUM number of 20-ampere, 277-volt, general-lighting branch circuits required for a 150,000 sq. ft. department store, when the actual connected lighting load is 400 kVA,A. 72 branch circuitsB. 82 branch circuitsC. 91 branch circuitsD. 102 branch circuits

Page 66: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

7. C 210.19(A)91) 52210.11(B) 51

400 kVA = 400,000 VA x 125% (continuous load) = 500,000 VA (bldg.)

277 volts x 20 amperes = 5540 VA (one circuit)

500,000 VA. (bldg. lighting) 5,540 VA (one circuit) = 90.2 = 91 circuits

*NOTE – Circuits need only to be installed to service the connected load.

Page 67: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 8. Where a two-gang box contains two (2) single-pole switches, unless the box is equipped with permanently installed barriers, the voltage between the switches shall NOT be in excess of _______.A. 120 voltsB. 277 voltsC. 240 voltsD. 300 volts

Page 68: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

8. D 404.8(B) 268

Page 69: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 9. An aluminum grounding electrode shall be _________.A. Installed at least 18 inches above the

earthB. Installed at least 24 inches above the

earthC. In direct earth burialD. Prohibited

Page 70: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

9. D 250.52(B)(2) 112

Page 71: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 10. A panelboard is limited to 42 overcurrent protective devices where ________.A. The panelboard is a power

panelboardB. The panelboard is a “split-bus”

type panelboardC. The panelboard supplies lighting

branch-circuits onlyD. One is installed

Page 72: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

10. B 408.36, Ex. 2 276

Page 73: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 11. When rigid polyvinyl chloride conduit (PVC) is used to enclose conductors feeding a wet-niche luminaire in a permanently installed swimming pool, a ______ insulated copper grounding conductor shall be installed in this conduit, unless a listed low-voltage lighting system not requiring grounding is used.A. 12 AWGB. 10 AWGC. 8 AWGD. 6 AWG

Page 74: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

11. C 680.23(B)(2)(b)

581

Page 75: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 12. In general, what is the largest size transformer, in kVA, that may be installed in an area or room that is NOT constucted in a fire-resistant manner?A. 75 KVAB. 112 ½ KVAC. 150 KVAD. 50 KVA

Page 76: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

12. B 450.21(B) 352

Page 77: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 13. When calculating the total load of an office building, and the number of general-purpose receptacles to be installed is not yet determined, an additional load of _____ volt-amp(s) per square foot is required for the receptacle outlets.A. OneB. TwoC. One-HalfD. Three

Page 78: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

13. A 220.14(K)(2) 63

Page 79: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 14. When sizing time-delay Class CC fuses for motor branch-circuit, short-circuit and ground-fault protection, they are to be sized at the same value as ________.A. inverse-time circuit breakersB. Nontime-delay fusesC. Instantaneous trip circuit

breakersD. Adjustable trip circuit breakers

Page 80: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

14. B Tbl. 430.52, Note 1

323

Page 81: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 15. Conductors other than service-entrance conductors shall be permitted to be installed in a cable tray with service-entrance conductors provided __________.A. A solid fixed barrier of material

compatible with the cable tray is installed to separate the systems

B. The conductors are not in excess of 480 volts to ground

C. The voltage between the conductors is not in excess of 600 volts

D. The conductors have equal insulation and temperature ratings

Page 82: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

15. A 203.44, Ex 82

Page 83: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 16 The MAXIMUM allowable ampacity of a size 750 kcmil XHHW aluminum conductor where there are six (6) current-carrying conductors in the raceway, installed in a dry location, where the ambient temperature will reach 22°C is ________A. 323.40 amperesB. 365.40 amperesC. 361.92 amperesD. 348.00 amperes

Page 84: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

16. C Tbl. 310.15(B)(16)

154

Tbl. 310.15(B)(2)(a)

150

Tbl. 310.15(B)(3)(a)

152Size 750 kcmil AL ampacity (before derating) = 435 amperes435 amps x 1.04 (temp correction) x .8 (adj. factor) = 361.92 amperes

Page 85: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 17. In which of the following locations is a cable tray prohibited to be installed?A. BasementB. Storage RoomsC. Sealed Ceiling SpacesD. When Passing Through a Wall

Page 86: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

17. C 392.18 (D)&(E)

240

Page 87: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 18. What is the MINIMUM size copper common grounding electrode conductor required to run through a building to four (4) separately derived systems (transformers) each having size 3/0 AWG copper secondary conductors.A. 4 AWGB. 2 AWGC. 3/0 AWGD. 8 AWG

Page 88: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

18. C 250.30(A)(6)(a)(1)

108

Page 89: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 19. Where a commercial building has a 600 ampere, 3-phase, 208Y/120 volt service supplied with two (2) paralled sets of size 350 kcmil copper conductors installed in separate raceways, determine the MINIMUM size aluminum grounding electrode conductor permitted to the metal water piping system used as the grounding electrod.A. 250 kcmilB. 4/0 AWGC. 3/0 AWGD. 2/0 AWG

Page 90: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

19. B 250.66 115Tbl. 250.66 115

350 kcmil x 2 conductors = 750 kcmil

*NOTE – A size 4/0 AWG aluminum grounding electrode conductor should be selected

Page 91: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 20. The NEC permits trade size 3/8 in. flexible metal conduit (FMC) to be used to enclose tap conductors for luminaires, provided the length of the FMC does NOT exceed __________.A. 4 feetB. 6 feetC. 8 feetD. 10 feet

Page 92: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

20. B 348.20(A)(2)c.

206

Page 93: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 21. What is the MAXIMUM distance allowed to support intermediate metal conduit (IMC) from a junction box, where structural members do not readily permit fastening?A. 3 feetB. 5 feetC. 6 feetD. 8 feet

Page 94: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

21. B 342.30(A)(2) 203

Page 95: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 22. All of the following listed copper conductors are to be installed in an electrical metallic tubing (EMT) that is in excess of 24 inches long.24-size 10 AWG with TW insulation10-size 10 AWG with THW insulation14-size 12 AWG with THHN insulation

Determine the MINIMUM trade size of EMT required.A. 2 in.B. 2 ½ in.C. 3 in.D. 3 ½ in.

Page 96: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

22. A Chpt. 9, Tbl. 5 717&718

Chpt. 9, Tbl. 4 712Size 10 AWG TW = .0243 sq. in. x 24 = .5832 sq. in.Size 10 AWG THW = .0243 sq. in. x 10 = .2430 sq. in.Size 12 AWG THNN = .0133 sq. in. x 14 = .1862 sq. in.

TOTAL = 1.1024 sq. in. *NOTE – Trade size 2 inch EMT with a permitted fill of 1.342 sq. in. @ 40% should be selected

Page 97: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 23. When combination surface nonmetallic raceways are used both for signaling and for power and lighting circuits, the different systems shall be ________.A. ProhibitedB. Run in the same compartmentC. Separated by at least ½ in.D. Run in separate compartments

Page 98: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

23. D 388.70 238

Page 99: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 24. When sizing fuses for a branch circuit serving a hermetic refrigerant motor-compressor, the device shall NOT exceed ____ of the rated load current marked on the nameplate of the equipment.A. 115 percentB. 125 percentC. 175 percentD. 225 percent

Page 100: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

24. D 440.22(A) 343

Page 101: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

O 25. Where rigid metal conduit (RMC) is used to protect a grounding conductor, the conduit must ________.A. Be isolated from the grounding

conductorB. Be electrically continuous from

cabinet to ground clampsC. Be identified with green paintD. Not be connected to or touching

the ground clamp

Page 102: Master Examination Practice Drill #3 2011 O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded

Question

Answer

Reference NEC PG. #

25. B 250.64(E) 114