TensiNet Symposium 2003 I 128 I Stadia Roof Structures: Design Assisted By Experimental Analysis Abstract. Wide span structures are today widely applied for sport, social, industrial, ecological and other activities. The experience collected in the last decades has identified structural typologies as space structures, cable structures and membrane structures, which in combination with new tension- efficient materials provides lightweight structural systems which are state of art for long span struc- tural designs. In order to increase the reliability assessment of wide span structural systems knowledge based syn- thetical conceptual design approach is recommend- ed. Theoretical and experimental scale analysis, combined with monitoring and control of the subse- quent performance of the structural system, can calibrate mathematical modelling and evaluate long term sufficiency of design. Some special remarks concerning the influence on the reliability level of detail design are given at the end of the paper. Massimo Majowiecki IUAV University Institute of Architecture of Venice, IUAV Santa Croce 191 Tolentiné 30135 Venezia ITALY Email: [email protected]

Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

TensiNet Symposium 2003I 128 I

Stadia Roof Structures: Design Assisted By Experimental Analysis

Abstract. Wide span structures are today widely

applied for sport, social, industrial, ecological and

other activities. The experience collected in the last

decades has identified structural typologies as

space structures, cable structures and membrane

structures, which in combination with new tension-

efficient materials provides lightweight structural

systems which are state of art for long span struc-

tural designs.

In order to increase the reliability assessment of

wide span structural systems knowledge based syn-

thetical conceptual design approach is recommend-

ed. Theoretical and experimental scale analysis,

combined with monitoring and control of the subse-

quent performance of the structural system, can

calibrate mathematical modelling and evaluate long

term sufficiency of design. Some special remarks

concerning the influence on the reliability level of

detail design are given at the end of the paper.

Massimo Majowiecki

IUAV

University Institute of Architectureof Venice, IUAV

Santa Croce 191 Tolentiné30135 Venezia

ITALY

Email:[email protected]

Page 2: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

Designing Tensile Architecture I 129 I

1 INTRODUCTION

Considering the statistical results contained in reference [1], together with unusual typolo-gies, materials and the “scale effects”, several special design aspects arise for long spanstructures such as:

- the snow distribution and accumulations on large covering areas as a function ofstatistically correlated wind direction and intensity;

- the wind pressure distribution on large areas considering theoretical and experi-mental correlated power spectral densities or time histories;

- rigid and aeroelastic response of large structures under the action of cross-correlated random wind action considering static, quasi-static and resonant contributions;

- the time dependent effect of coactive indirect actions as pre-stressing, short andlong term creep and temperature effects;

- the local and global structural instability;- the non linear geometric and material behaviour;- reliability and safety factors of new hi-tech composite materials;- the necessity to avoid and short-circuit progressive collapse of the structural sys-

tem due to local secondary structural element and detail accidental failure;- the compatibility of internal and external restraints and detail design, with the

modeling hypothesis and real structural system response;- the parametric sensibility of the structural system depending on the type and

degree of static indeterminacy and hybrid collaboration between hardening andsoftening behaviour of substructures.

- In the case of movable structures, the knowledge base concerns mainly the mov-ing cranes and the related conceptual design process has to consider existingobservations, tests and specifications regarding the behaviour of similar structur-al systems. In order to fill the gap, the IASS working group n°16 prepared a stateof the art report on retractable roof structures [2] including recommendations forstructural design based on observations of malfunction and failures.

M. Majowiecki

Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution

Page 3: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

TensiNet Symposium 2003I 130 I

Stadia Roof Structures: Design Assisted By Experimental Analysis

2 SOME WIDE SPAN ENCLOSURES

Due to the lack of space, only some design and analysis illustrations of wide span enclo-sures, with which the author has been directly involved, will be included in the presentpaper with the intention to transmit some experiences that today may be part of theknowledge base. Long span structures need special investigations concerning the actual live load distribu-tion and intensity on large covering surfaces. Building codes normally are addressed onlyto small-medium scale projects. The uncertainties relating to the random distribution oflive loads on long span structures imply the need for very careful loading analysis usingspecial experimental analysis. From the author's direct experience in designing largecoverings, the most important experimental investigation regarding live load distributionconcerns the snow drift and accumulation factors and the dynamic action of wind loading.

2.1 SNOW LOADING EXPERIMENTAL ANALYSIS ON SCALE MODELS

Olympic Stadium in Montreal. During the design of the new roof for the Montreal OlympicStadium Figure 1 a special analysis of snow loading was made considering three roofgeometries varying the sag of the roof from 10 m, 11.5 m and 13 m in order to find a mini-mization of snow accumulation. The experimental investigation was carried out by RWDI [3] to provide design snow according to FAE (Finite Area Element) method, representing up-to-date state of the art onthe matter. The FAE method uses a combination of wind tunnel tests on a scale model and computer simulation to provide the most accurate assessment possible to estimate 30year snow loads.

Fig. 2 Comparative analysis of snow loading distribution in function of roofshape (rise: 10-13m)

Fig. 3 Sliding and wind snow accumulationsstep loads

Page 4: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

Designing Tensile Architecture I 131 I

Snow loads depend on many cumulative factors such as snowfall intensity, redistributionof snow by the wind (speed and direction), geometry of the building and its surroundingsaffecting the wind flow patterns, absorption of rain in the snowpack, and depletion ofsnow due to melting and subsequent runoff. The current NBCC (National Building Code ofCanada) provides minimum design loads for roofs which are based primarily on fieldobservations made on a variety of roofs and on statistical analysis of ground snow loaddata. There are, however, numerous situations where the geometry of the roof being stud-ied and the particulars of the site are not well covered by the general provisions of thecode. In these situations, a special study, using analytical, computational and model testmethods, can be very beneficial since it allows the specific building geometry, site particularsand local climatic factors all to be taken into account. The National Building Code allowsthese types of studies through its "equivalency" clause and various references to specialstudies in its commentary. The models of the three new roof shapes were each constructed at 1:400 scale for the windtunnel tests. The three model roof designs were each instrumented with 90o directional sur-face wind velocity vector sensors covering the surface. On the console roof, an additional 90sensors were installed. Measurements of the local wind speed and direction, at an equiva-lent full-scale height of 1 m above the roof surface, were taken for 16 wind directions. Thewind speed measurements were then converted to ratios of wind speed at the roof surfaceto the reference wind speed measured at a height equivalent at full scale to 600 m. The 30 year ground snow prediction is obtained by interpolation of the data using theFisher-Typett type I extreme value distribution method including both snow and rain( )S Ss r+ , to be 2.8 kPa, which is in agreement with the code value. Results of structural load cases and local peak loading, not to be considered as acting overthe roof simultaneously, are shown in Figs. 2 & 3. The shape of the roof with a rise of morethan 12m gives separation of the air flow and turbulence in the wake increasing consider-ably the possibility of snow accumulations. The order of magnitude of the leopardizedaccumulations in the roof are of 4-15 kN! Local overdimensioning was necessary in order toavoid progressive collapse of the structural system.

2.2 WIND LOADING-EXPERIMENTAL ANALYSIS ON SCALE MODELS: RIGID STRUCTURES-QUASI STATIC BEHAVIOUR.

The integration of the wind tunnel data into the design process presents significant prob-lems for wide span semi-horizontal enclosures; in contrast to buildings (high rise buildings)where knowledge of the base moment provides a sound basis for preliminary design, thereis no single simple measure for the roof. The study of the Stadium of the Alpes and the Romestadium [4-5-6] drew attention to the inability of the measuring system employed to providedata in a form that could readily be based as input to the sophisticated dynamic numericalmodel developed by the designer. This led to discussions between the designer and the windtunnel researchers to examine alternate techniques that might be used in future projects [7]. The discussions centered on the use of high speed pressure scanning systems capable ofproducing essentially simultaneous pressure measurements at some 500 points at rates ofperhaps 200 Hz per point. With such a system it would be possible to cover in excess of 200panels and produce a complete description of the load. Such a system would produce rough-ly 1 to 2x106 observations for a single wind direction and it is clear that some compressionof the data would be required.

M. Majowiecki

Page 5: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

TensiNet Symposium 2003I 132 I

Stadia Roof Structures: Design Assisted By Experimental Analysis

One possible approach would be to produce a set of load histories, ( )Q tj , such that:

( ) ( , , ) ( , )Q t p x y t x y dAdAA

j j8= U (1)

where:( , , )p x y t net load per unit area at position (x,y);

( , )x yjz weighting function.

For a series of pressure taps of the approximation to ( )tjz would be:

( ) ( , , ) ( , )Q t p x y t A x yi i i i ij i ji

N

1= z

=! (2)

Ai area of ith panel;pi pneumatic average of pressure at the taps in the ith panel;

,x yi i geometric centre of the taps on the ith panel;

N number of panels.

The requirements of a system designed to produce the load histories, ( )tjz , is discussed

in the following section.

2.3 MEASUREMENT AND USE OF LOAD TIME HISTORIES: THE THESSALONIKI OLYMPIC SPORTS COMPLEX

In collaboration with the Boundary layer wind tunnel laboratory of the University of WesternOntario, a new very practical method to obtain the structural response under random windaction and small displacements (linear response) has been applied under the name of the“orthogonal decomposition method”. If the weighting functions, ( )tjz , are chosen as

mode shapes then ( )tjz is a modal load and its use in conjunction with a dynamic model

is clear; either as a set of time histories or a set of modal force spectra and cross-spectra.In the initial stages of a design the roof shape is probably known with reasonable accuracybut mode shapes not so. In such cases it might be appropriate to choose a suitable set of

jz from which modal loads corresponding to shapes i} can be estimated when the design

is more advanced. In such a case we can approximate j} as:

aj ji

ijiji

Mj,} } z! (3)

the values of a ijij can be evaluated by minimizing the discrepancy between j} and j} , ie:

( )a a dAdA 0ijij j ijij

i i

2

22

8 - =} z! (4)

,i M1=

If the functions iz are chosen as a set of orthogonal shapes ;dAdA i j0i j !=z z# then the coefficients aregiven as

Page 6: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

Designing Tensile Architecture I 133 I

M. Majowiecki

Fig. 5 Taps location

Fig. 6 Views of pressure model Fig. 7 Orthogonal decomposition: pressure mode shapes

Fig. 4 Relative contribution of Azimuthal Direction to theexceedance probability of various return periodwind speeds for Thermi, Thessaloniki, Greece

adAdA

dAdAijij

i

i j2

8

8=

z

z z(5)

For finite panel sizes the corresponding relationship is:

( , )

( , ) ( , )a

x y A

x y x y Aijij

i k k kk

i k k j k k kk

N

2=z

z z

!

!(6)

where:

, ,( ) ( )

i j

x y x y A 0i k k j kk

N

k k

!

=z z!

The experiment would involve the recording of the local histories ( )tj} from which the

model time histories could be constructed and the analysis conduced in either the time orfrequency domain (Figures 4-7). For the type of structure under consideration resonanteffects are small and the response is largely quasi-static to a spatially varied load. Thedeflections induced are closely related to the imposed loads and their distribution differssignificantly from the Gaussian form [7]. In such a case the time domain solution, which pre-serves the extreme value distribution, is to be preferred over a frequency domain approach.For the seismic analysis a frequency domain approach was adopted. The Kanai-Tajimi PSDwas used under the design response spectra prescribed by Eurocode 1; under strong-motion, an acceleration time history was artificially generated according to site and dura-bility characteristics [8].

Page 7: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

TensiNet Symposium 2003I 134 I

2.4 WIND LOADING-EXPERIMENTAL ANALYSIS ON SCALE MODELS: FLEXIBLE STRUCTURES-AERODYNAMIC BEHAVIOUR: THE OLYMPIC STADIUM IN ROME

The wind induced response of the cable supported stadium roof was analysed by a nonlinear model and a field of multicorrelated artificially generated wind loading time histo-ries [8]. Wind tunnel tests have been carried out at the BLWT Lab. of UWO on a model (Fig8) of 1:200 scale to determine:

- time histories of the local pressures for every 10° of incoming flow direction; themaximum, minimum and average values of the wind pressure have then beenevaluated, as well as the root mean square of its fluctuating part;

- pressure coefficients (maxima, minima and average) for every 10° of incomingdirection;

- auto and cross-spectra of the fluctuating pressure (averaged on every single panel).

The aerodynamic behaviour shows a clear shedding phenomenon. The external border ofthe structure, constituted of the trussed compression ring with triangular section and tubu-lar elements and by the roofing of the upper part of the stands, disturbs the incoming hor-izontal flow in such a way that vortex shedding is built up. This causes the roofing structureto be subjected to a set of vortices with a characteristic frequency. This is confirmed by theresulting Power Spectra Density Function of the fluctuating pressures, which shows a peakat about 0.15Hz even if the values rapidly decrease with increasing distance Fig. 10.

Stadia Roof Structures: Design Assisted By Experimental Analysis

Fig. 8 Aeroelastic model for Rome Olympic Stadium Fig. 9 Aeroelastic model for the Braga Stadium

Fig. 10 Target (1), simulated (2) and Kaimal's (3) normalizedspectra of wind velocity

Fig. 11 Time History of the displacement (leeward side attension ring, run #2)

A fluid-interaction non-linear analysis in time domain, made for the checking of La Plata stadiumdesign [9] shows a better agreement between theoretical model and experimental values.

Page 8: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

Designing Tensile Architecture I 135 I

3 RELIABILITY ANALYSIS: THE SENSITIVITY ANALYSIS REGARDING THE NEW

SUSPENDED CABLE ROOF OF BRAGA (PORTUGAL)

3.1 RELIABILITY ANALYSIS OF THE ROOF STRUCTURAL SYSTEM. CABLE STRAIN PARAMETRIC SENSITIVITY.

Considering that in the basic solution the roof will be covered by a long span structural sys-tem with only uplift gravitational stabilization (Fig.9) it is essential to proceed to the analysisof the response of the structural system to loading patterns and wind induced oscillations.The analytical process will be organized in order to be controlled by experimental investiga-tions in reduced and full scale. The reduced scale experimental analyses on rigid and aero-elastic models are concerned with the determination of the dynamic loading on the roof sur-face and of the stability of the structural system. The full-scale experimental investigationsare addressed to check, by a monitoring program, the validity of the global analysis process. The uncertainties on the elastic modulus of the cables, geometrical and elastic long termcreeping, tolerances of fabrication and erection, differences with design prestress, non uni-form distribution of temperature and non linear behaviour, created a sensitive response onthe suspended roof hanging from a set of suspended cables. The sensitivity analysis showedthat the response is sensitive to the standard deviation of the cable strain (Of) variations. Thefailure probability is given by the probability that an outcome of the random variables (Of)belongs to the failure domain D. This probability is expressed by the following integral [10]:

( )P f dfD f

:O O= f fOf# (7)

The most probable failure mechanism will involve primarily the border cables. The sensitivityanalysis was, therefore, extremely important in detecting the weak points of the structuralsystem and permits proper local dimensioning to prevent chain failure, as illustrated with thefailure simulation of the same sensitive cable elements. The roof is composed of a structural concrete plate sustained by n prestressed cables. In theanalysis of the roof, the bending moments at m points will be considered. For a particular loadcombination, the n cables have computed strains given by the vector f. Considering that theseeffects are represented by the vector of random variables Ofwith mean values n and standardvariations v , the problem is to estimate the probability, P f , that the generated random bend-ing moments M will be larger than the plate ultimate resistance moments, M u, at any of them points of the structural plate system.

3.2 ROOF STRUCTURAL SYSTEM DATA

The following probabilistic description was considered for the random variables Of.n = Vector of mean values of Of = 0 (i.e., all possible actions on the cables are consid-

ered by the load combination itself).v = Vector of standard deviations of Of = 0. The 2 values were varied from 0.5 x 10-3 to

0.1 x 10-3 so that the sensitivity of the system can be studied. These values were select-ed to cover the range of failure probabilities of practical significance.

( )f OfOf = Probability density function = Normal distribution with parameters n and v.

M. Majowiecki

Page 9: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

TensiNet Symposium 2003I 136 I

Stadia Roof Structures: Design Assisted By Experimental Analysis

3.3 FAILURE CONDITION

For load case “i” the bending moments, andand,M x My M xyxy at 130 points of the plate canbe computed as follow:

.M M Ax GxGx x j

j 1

3434

i i O= + f=

! (8)

.AGyGyM M y j

jy

1

3434

,i jO+= f

=

!

.M M Axyxy GxyGxy xyxy

j

j

1

3434

,i i j O= + f=

!

Considering the bending moments in each direction, the failure functions at each point of

the plate ( )r1 130130# # , ( )G r Of , are the following hyperplanes,

<.( )M M A 0UpxUpx GxGx jxj 1

3434

,i i j O- + f=! <.( )M M A 0UpyUpy GyGy jy

j

3434

1 ,i i j O- + f=! (9)

<.( )AbsAbsM M A 0UnxUnx GxGx jxj 1

3434

,i i j O- + f=! <.( )AbsAbsM M A 0UnyUny GyGy j

jy

1

3434

,i i jO- + f

=! (10)

.( )<M AbsAbs M A 0UxyUxy GxyGxy xyxy jj 1

3434,i i j O- + f

=! (11)

where G 0r # is failure and MUxyUxy is computed from the Johanssen Theory as the smallestof the following expressions

( )/M M M 2UxyUxy UpxUpx UpyUpy= + (12)( )/M M M 2UxyUxy UnxUnx UnyUny= +

In these formulas, M M M M andand M, , , ,UpxUpx UpyUpy UnxUnx UnyUny UnyUny are considered always positive.The failure condition is obtained when failure is reached at any point of the plate, i.e., thestructural failure can be defined as

( ) ( ) ( )G G G0 0 01 2 130130, , ,f# # # (13)

Page 10: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

Designing Tensile Architecture I 137 I

3.4 SOLUTION METHOD

Since a closed form solution is not possible for the integralin (7), for the failure domain defined by equations above,Montecarlo Simulation must be used. By MontecarloSimulation, the failure probability is obtained by computing

( )G r Of for several values of Of generated with normal distri-bution. An approximation to the failure probability isobtained by counting the number of times that Of belong tothe D f with respect to the total number of simulations. Forsmall failure probabilities, however, direct application ofMontecarlo Simulation is not possible because of the largenumber of iterations needed to get enough accuracy. Toavoid this problem, the Orientated Simulation Method wasused in this report. A complete description of the methodcan be found in the paper [10].

3.5 RESULTS AND CONCLUSIONS.

All the load cases were analysed and the following preliminary conclusions are describedas follows. In order to identify the most dangerous load case the minimum reliability index b for eachload case was calculated for a standard deviation v =0.5 x 10-3 for Of of all cables. Table 1summarizes the index b (computed with v =0.5 x 10-3).

The load cases 7, 10 and 11 have the lower values of b, i.e., the higher failure probability,and therefore they are the critical load conditions. Particularly critical is the load case 7.

3.6 FAILURE PROBABILITY AND SENSITIVITY ANALYSIS

The figure 12 shows the failure probability for load combination 7 as a function of thestandard deviation, v, of the cable strain variations, Of. The following can be noted:

a. The problem is extremely sensitive to the standard deviation, v, of the cablestrain variations, Of. For example for load case 7, if v is increased from 2 x 10-4 to3 x 10-4, Pf is increased from 2 x 10-5 to 480 x 10-5.

b. Cable standard deviation, v, should be maintained below 2 x 10-4 for the designedultimate bending moment.

c. Larger cable standard deviation, v, could be allowed if the slab reinforcement isincreased along x-direction in the critical roof zone.

The figure 13, shows the most probable values of Of (x10-3) in each cable at failurefor load combination 7.

M. Majowiecki

Table. 1 Analyzed load cases with theminimum reliability index

Page 11: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

TensiNet Symposium 2003I 138 I

Stadia Roof Structures: Design Assisted By Experimental Analysis

The following comments can be made:a. The most probable values of Of are practically independent of the standard

deviation v. In other words, the configuration at failure is constant. This configuration is reached with more probability as the standard deviation of Ofincreases.

b. The most probable configuration at failure is mainly due to variations in thestrains of cables 32 and 34. Since elongations of cables can be computed asO L=L.Of, the elongation at failure of cables 32 and 34 are approximatelyO L32=210m x (-0.2 x 10-3) = 4.2 cm and O L34= 210m x (0.3 x 10-3) = 6.3 cm.

Fig. 12 Failure probability in function of cable deformation standard deviation

Fig. 13 Predicted 50 year return period peak differential pressures

Page 12: Massimo Majowiecki 30135 Venezia - Tensinet · 2016. 6. 14. · M. Majowiecki Fig. 1 Montreal Olympic Stadium - A cable stayed roof solution. I 130 I TensiNet Symposium 2003 Stadia

Designing Tensile Architecture I 139 I

CONCLUSIONS

The following have been noted:- The influence of knowledge base on conceptual design in removing gross human

intervention errors from initial design statements.- Design assisted by experimental investigation is a useful integration for the design

process of wide span structures.- Sensitivity analysis is an extremely powerful tool to determine the influence of

parametric design uncertainties for unusual long span structural systems.

REFERENCES

[1] R.E. Melchers: Structural reliability, Elley Horwood ltd. 1987.[2] Structural Design Of Retractable Roof Structures, IASS working group n°16, WIT

Press, 2000[3] RWDI: Roof snow loading study-roof re-design Olympic Stadium Montreal,

Quebec. Report 93-187F-15, 1993.[4] M. Majowiecki: Observations on theoretical and experimental investigations on

lightweight wide span coverings, International Association for Wind Engineering,ANIV, 1990.

[5] B.J. Vickery, M. Majowiecki: Wind induced response of a cable supported stadium roof. Journal of Wind Engineering and Industrial Aerodynamics, 1992, pp. 1447-1458,

[6] B.J. Vickery: Wind loads on the Olympic Stadium - orthogonal decomposition anddynamic (resonant) effects. BLWT-SS28A, 1993.

[7] M. Majowiecki: Snow and wind experimental analysis in the design of long span sub-horizontal structures, J. Wind Eng. Ind. Aerodynamics, 1998.