Upload
kentroh
View
45
Download
3
Embed Size (px)
DESCRIPTION
Construction
Citation preview
Masonry Design Guide
www.boral.com.au/masonry Updated July 2005
BORAL MASONRY
Build something great™
SEGMENTAL BLOCK RETAINING WALLS VICTORIA BOOK 4
A2 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 A
A Introduction
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2
Fast Find Product & Application Guide . . . . . . . . . . . . . . . . . A3
Products @ a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A4
About This Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A6
B Planning & Design
C Gardenwall®
Gardenwall Product Information . . . . . . . . . . . . . . . . . . . . . . C2
Selection & Construction Guidelines . . . . . . . . . . . . . . . . . . . C3
Curved Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C4
D Heathstone®
HeathstoneProduct Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D2
Gravel-Fill Construction Guidelines . . . . . . . . . . . . . . . . . . . . D3
Curved Wall Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . D4
Step Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D4
Step Tread and Cap Unit Installation . . . . . . . . . . . . . . . . . . . D5
Corner Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D6
No-Fines Concrete Wall Construction . . . . . . . . . . . . . . . . . . D7
E Keystone® & Pyrmont®
Keystone Product Information . . . . . . . . . . . . . . . . . . . . . . . . E4
Pyrmont Product Information. . . . . . . . . . . . . . . . . . . . . . . . . E5
Gravel-Fill Wall Selection &Construction Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . E6
Typical Installation Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . E8
No-Fines Concrete Wall Construction Guidelines . . . . . . . . . . . . . . . . . . . . . . . . E11
Geogrid Soil-Reinforced Wall Construction Guidelines. . . . . . . . . . . . . . . . . . . . . . . . E13
Typical Specification for Keystone/Pyrmont Retaining Walls . . . . . . . . . . . . . . . . . . . E15
F Custom Engineered Walls
Engineered Retaining Walls . . . . . . . . . . . . . . . . . . . . . . . . . . F2
Keysteel Product Information. . . . . . . . . . . . . . . . . . . . . . . . . F4
Typical Soil-Anchor Application. . . . . . . . . . . . . . . . . . . . . . . . F6
Typical Rock-Anchor Application . . . . . . . . . . . . . . . . . . . . . . . F7
Typical Seawall Application. . . . . . . . . . . . . . . . . . . . . . . . . . . F8
Typical Terraced Wall Application . . . . . . . . . . . . . . . . . . . . . . F9
Typical Fencing Application. . . . . . . . . . . . . . . . . . . . . . . . . . F10
Typical Railing & Barrier Application . . . . . . . . . . . . . . . . . . . F11
The information presented herein is supplied in good faith and to the best of our knowledge was accurate at the time of preparation. No responsibility can be accepted byBoral or its staff for any errors or omissions. Users are advised to make their own determination as to the suitability of this information in relation to their particular purposeand specific circumstances. Since the information contained in this document may be applied under conditions beyond our control, no responsibility can be accepted by usfor any loss or damage caused by any person acting or refraining from action as a result of this information.
An Introduction to Segmental Block Retaining Walls . . . . . . . . . . . . . . . . . . . . . B2
Site Investigation – Preliminary Design . . . . . . . . . . . . . . . . . B6
PAG
E
PAG
E
A3BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 A
For technical support and sales office details please refer to the outside back cover
The quickest way to find a Boral Masonry Segmental Block Retaining Wall Solution.
Simply follow the FAST FIND guide on the right hand side of the table.
Vertical
Surcharge
Loading
Nil
≤ 5kPa
≤ 5kPa
or
≤ 1:4
Sloped
Backfill
≤ 25kPa
> 25kPa
Wall Height
(mm)
≤ 1125
≤ 1600
≤ 3000
> 3000
> 6000
Wall
Type
Set Back
Vertical
Set Back
Property
Boundary
Not
Boundary
Vertical
Set Back
Vertical
Set Back
Gar
denw
all
Hea
thst
one
Pyrm
ont
Key
stone
Key
stee
l
Core
Fill
ed B
lock
D E E ✱
C E
D✤ E✤ E✤ ✱
E✤
✱
E★ E★ ✱
E★E★
E★
F
F
Select your application criteria from the left hand columns
Go straight to the book section indicated by the letter at the intersection of application rows and product columns (e.g. Section E in this example)
Please refer to Book 1, Boral Masonry Design Guide and Book 2, Boral Masonry Blocks & Bricks Guide
Requires ‘No-fines Concrete Backfill ’ or ‘Geogrid’ systems
Requiring ‘Geogrid’ systems
✱
✤
★
BORAL
MASONRY
SEGMENTAL
BLOCK
RETAINING
WALLS PRODUCT
Fast Find
a Boral
Solution1
2
Max. wall heights disclaimer:
The gravity wall heights are maximum heights calculated in accordance with CMAA MA-53 Appendix D guidelines and a qualified engineer should confirm the suitability of the productfor each intended application. As such, due consideration must be given to but not limited to:
• Cohesion,
• Dry backfill: no ingress of any water into the soil behind the retaining wall,
• All retaining walls are designed for zero surcharge unless noted otherwise.
These walls are intended for structure Classification A walls only as defined in AS4678 Earth Retaining Structures as being where failure would result in minimal damage and/or loss of access.
A4 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 AAA AAAA4 Ak 4 ookkoookBBooBBia rriiaaaatorrcttoViiiiccVV
Landscape
Retaining Wall Systemsfor low-height domestic and commercial
garden beds and retaining wall applications
• Gardenwall®
Boral Gardenwall is ideal for gravity wall installationsof less than 1.125m wall height. The blocks are laidwith a slight set-back, and are located by a lug alongthe back edge. Gardenwall can also be used for curvedwall applications.
• Heathstone® & Heathstone® Grand
Boral Heathstone retaining wall systems combine theattractive impression of natural hewn stone, the eleganceof a vertical wall and the simplicity of mortarlessinstallation. Various installation formats cater for wallsup to 0.97m height. Heathstone Grand double-lengthblocks are particularly effective in larger installations.
A5BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 AA A4 k 4 ok BooBo Bia oriatorictVicV
Engineered
Retaining Wall Systemsfor domestic and commercial landscaping, roadside
and custom engineered retaining wall applications
• Pyrmont®
Boral Pyrmont retaining walls are a modern-day link toour pioneer heritage. Pyrmont combines modernengineering versatility with the elegance of a verticalwall and the style of hand-finished natural stone.Pyrmont gravity or soil reinforced retaining wall systemscan be engineered for applications up to 6m heightand can accommodate gentle curves and stepinstallations.
• Keysteel™ Custom Engineered Retaining
Wall Systems
Boral Keysteel is a high performance engineeredretaining wall system for applications requiring wallheights in excess of 6m and/or where critical surchargeloadings are present. Boral Keysteel is an internationallyproven system that integrates the superior strengthand durability of Keysteel blocks with steel-ladder soil-reinforcement to provide engineered solutions for themost demanding retaining structures.
• Keystone®
Boral Keystone walls have been proven time-and-time-again, by engineers, architects, councils, roadauthorities and landscapers throughout Australia.Keystone walls can cater for a wide range ofapplications from low height gravity walls to geogridsoil reinforced applications up to 12m wall height.Keystone walls can be constructed as near verticalwith curves as tight as 1m radius, or set-back. Blocksare available in a wide selection of colours and insplitface or flushface formats.
A6 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 A
A Guided Tour of a Typical Product Information Page
Product pages are laid out in a consistent manner to assist with easy selection and specification
of Boral Masonry products.
Product Range, Book andPage Identification
Product Name and otheridentifying features
Product informationrelating to features,applications, andaccessories
ProductSpecifications
Product Iconswith dimensionsfor productsavailable in yourregion/state
Colour andAvailabilityinformationfor productsdistributedin yourregion/state
Boral Masonry Product Range
Boral Masonry offers a comprehensive range of proven
products and systems including Segmental Block Retaining
Wall Systems, Segmental Paving Products, Masonry Blocks,
Masonry Bricks, Masonry Fire and Acoustic Wall Systems.
What’s in this Guide
The Boral Masonry Segmental Block Retaining WallsGuide, (this book), details a comprehensive selection of
retaining wall options ranging from low height gravity
landscaping walls to critically loaded reinforced-soil retaining
structures.
This guide has been prepared as a comprehensive Boral
Product Reference Guide. It does not attempt to cover all the
requirements of the Codes and Standards which apply to
retaining wall construction. All structural detailing should
be checked and approved by a structural engineer before
construction. Boral reserves the right to change the contents
of this guide without notice.
Please note that this guide is based on products available at
the time of publication from Boral Masonry Victorian sales
region. Different products and specifications may apply to
Boral products sourced from other regions.
Additional Assistance & Information
• Contact Details: Please refer to the outside back cover of
this publication for Boral Masonry contact details.
• Colour and Texture Variation: The supply of raw
materials can vary over time. In addition, variation can
occur between product types and production batches. Also
please recognise that the printed colours in this brochure
are only a guide. Please, always ask to see a sample of
your colour/texture choice before specifying or ordering.
• Terms and Conditions of Sale: For a full set of Terms
and Conditions of Sale please contact your nearest Boral
Masonry sales office.
E4 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
INTRODUCTION
Boral Keystone is an advanced,
highly versatile and thoroughly
proven high performance segmental
block retaining wall system which
can be used as a gravity structure
or it can incorporate geogrid soil-
reinforcement to cater for greater
heights and surcharge loading
situations.
DESIGN CONSIDERATIONS
• Suitable for straight and curved
wall installations with a minimum
convex curve radius of 1800mm
without trimming the tail width,
or 970mm radius by trimming the
tail to 300mm width.
• Can be installed as near vertical,
or for straightwalls without curves
or corners it can be installed with
a 1-in-8 setback.
COLOURS
Keystone is offered in a range of
colours to suit decorative and
engineering applications. Please
refer to colour swatch information
for an indication of current colours.
To reduce the possibility of staining
and to enable easier cleaning, a
masonry sealer can be applied to all
visible surfaces after installation.
Keystone®
Retaining Wall Systems
305
200
455
Standard Straight Sided Cap
275
100
455Flushface Straight Sided Cap
275
100
455
PinsLifting Bars
Description Wt kg Nº/m2
Standard Unit 35 11
Standard Straight Sided Cap 25 2.2/lin mtr
Flushface Unit 38 11
Flushface Straight Sided Cap 26.3 2.2/lin mtr
Pins 2 pins per full unit
(high strength pultruded fibreglass)
Lifting Bars (Keystone units should be lifted by
two people using the Keystone lifting bars)
Specifications
Standard Unit
305
200
455
Flushface Unit
Availability & Colours• No minimum order quantities apply.
• Lead time 0-4 weeks.
Bluestone Brown
Sunset Terracotta
Natural Parchment
Charcoal
SEGMENTAL BLOCK RETAINING WALLS VICTORIA BOOK 4
B PLANNING AND DESIGN
Masonry Design Guide
4B44BORAL MASONRY
Build something great™
B2
Victoria Book 4 B
July 2005 | BORAL MASONRY DESIGN GUIDE
An Introduction to Segmental
Block Retaining Walls
Background
For many years cantilever retaining walls have been
constructed with reinforced concrete masonry stems (steel
reinforcement grouted into hollow concrete block work) and
reinforced concrete footings. (Refer to Fig B1).
Segmental block gravity retaining structures, consisting of
dry-stacked concrete units which resist overturning byvirtue
of their own weight and setback,were introduced into Australia
in the early 1990’s, and rapidly became popular. This system
provides an attractive and cost effective solution, but its
stability is limited by the geometry of the units and wall
heights. (Refer to Fig B2).
In order to achieve greater heights, reinforced-soil walls (such
as Boral Keystone) were introduced. These walls typically
consist of geosynthetic materials, which are placed in
horizontal layers in the compacted backfill and mechanically
connected to the blocks. Such systems can be constructed
several metres high, and accommodate significant loads.
A further development of this system is the Boral Keysteel
system which utilises steel-ladder reinforcement. Here the
steel-ladder reinforcement is placed in horizontal layers in the
compacted backfill and mechanically connected to the blocks.
These systems are individually engineer designed, and are
suitable for walls in excess of 6m high and for critical
surcharge loadings. (Refer to Fig B3).
Steel reinforced and concrete grout filled hollow concrete block wall
Reinforced concrete footings
Fig B1 – Typical Reinforced Concrete MasonryCantilever Retaining Wall
Segmental block gravity retaining structure, dry-stacked against a soil slope
Fig B2 – Typical Segmental Block Gravity Retaining Wall
Segmental concrete gravity retaining structure, with reinforced soil
Fig B3 – Typical Reinforced-Soil Segmental Block Retaining Wall
B3
Victoria Book 4 B
BORAL MASONRY DESIGN GUIDE | July 2005
Behaviour of Segmental Block
Reinforced-Soil Retaining Walls
If unrestrained, a soil embankment will slump to its angle
of repose. Some soils, such as clays, have cohesion that enables
vertical and near-vertical faces to remain partially intact, but
even these may slump under the softening influence of ground
water. When an earth retaining structure is constructed, it
restricts this slumping. The soil exerts an active pressure on
the structure, which deflects a little and is then restrained
by the friction and adhesion between the base and soil
beneath, passive soil pressures in front of the structure and
bearing capacity of the soil beneath the toe of the structure.
If water is trapped behind the retaining structure, it exerts
an additional hydraulic pressure. This ground water also
reduces the adhesion and bearing resistance.
If massive rock formations are present immediately behind
the structure, these will restrict the volume of soil which can
be mobilised and thus reduce the pressure.
Reinforced-soil systems consist of a series of horizontal
geogrids that have been positioned and pulled tight within
a compacted soil mass, thus strengthening it and restricting
its slump. The geogrids are strategically placed to intersect
potential failure planes that are inclined from near the base
of the wall, up at an angle (depending on the soil properties),
to the top of the fill. The function of the geogrids is to
‘strengthen’ the soil mass and they are ‘anchored’ by compacted
backfill beyond the potential failure planes.
Local collapse and erosion of the front face is eliminated by
fixing concrete segmental facing units to the exposed ends
of the geogrids. However, the segmental concrete facing is
not designed to ‘retain’ the strengthened soil mass, which
should be able to stand independently of the facing except
for local effects. The connection spacing (and the geogrid
spacing) must account for the local stability of the facing,
including bulging and rotation above the top geogrid. The
top capping course is normally bonded to the course below
using a concrete to concrete adhesive.
A surface sealing layer and surface drainage system minimise
the quantity of rainwater entering the soil mass. A sub-surface
drainage system behind the segmental concrete facing and
(sometimes) beneath the wall reduce pore water pressures
and thus reduce the tendency for local or global slip.
Thus, the essential features of a properly designed and
constructed segmental block reinforced soil retaining wall are:
• Geogrids with adequate length and strength;
• Adequate connection to the facing to provide local stability;
• A drainage system that will relieve hydro static pressures
for the life of the structure.
Importance of a Geotechnical Report
The design of a reinforced soil retaining wall includes two
essential parts:
• Analysis of the proposed reinforced soil structure and the
adjacent ground for global slip, settlement, drainage and
similar global considerations; and
• Analysis and design of the reinforced soil structure itself.
These analyses must be based on an accurate and complete
knowledge of the soil properties, slope stability, potential slip
problems and ground water.
Except in the case of simple structures, a geotechnical report
by a qualified and experienced geotechnical engineer should
be obtained.
Such a report must address the following considerations, as
well as any other pertinent points not listed.
• Soil properties;
• Extent and quality of any rock, including floaters and
bedrock;
• Global slip and other stability problems;
• Bedding plane slope, particularly if they slope towards
the cut;
• Effect of prolonged wet weather and the consequence of
the excavation remaining open for extended periods;
• Effect of ground water;
• Steep back slopes and the effect of terracing;
• Effect of any structures founded within zone of influence.
Safety and Protection of Existing
Structures
Whenever soil is excavated or embankments are constructed,
there is a danger of collapse. This may occur through
movement of the soil and any associated structures by:
• Rotation around an external failure plane that encompasses
the structure;
• Slipping down an inclined plane;
• Sliding forward, or
• Local bearing failure or settlement.
B4
Victoria Book 4 B
July 2005 | BORAL MASONRY DESIGN GUIDE
These problems may be exacerbated by the intrusion of surface
water or disruption of the water table, which increase pore
water pressures and thus diminish the soil’s ability to stand
without collapse.
The safety of workers and protection of existing structures
during construction must be of prime concern and should
be considered by both designers and installers. All excavations
should be carried out in a safe manner and in accordance
with the relevant regulations, to prevent collapse that may
endanger life or property. Adjacent structures must be founded
either beyond or below the zone of influence of the excavation.
Where there is risk of global slip, for example around a slip
plane encompassing the proposed retaining wall or other
structures, or where there is risk of inundation by ground
water or surface water, construction should not proceed until
the advice of a qualified and experienced Geotechnical
Engineer has been obtained and remedial action has been
carried out.
Global slip failure
Soil retaining structures must be checked for global slip
failure around all potential slip surfaces or circles.
Designers often reduce the heights of retaining walls by
splitting a single wall into two (or more) walls, thus terracing
the site. Whilst this may assist in the design of the individual
walls, it will not necessarily reduce the tendency for global
slip failure around surfaces encompassing all or some of the
retaining walls.
Analysis for global slip is not included in this guide, but it is
recommended that designers carry out a separate check using
commercially available software.
Differential Settlement
The Concrete Masonry Association of Australia (CMAA)
recommends that for dry stacked mortarless retaining walls
employing masonry units (i.e. units with an area less than
0.2m2) on an aggregate levelling pad, the differential
settlement should be limited to 1% of the length. Whilst it is
permissible for the retaining wall to undergo differential
settlement up to 1% of the length, it may be preferable to limit
settlement to a lower figure giving consideration to aesthetics
(i.e. keeping the bedding planes level), in addition to the
structural considerations.
Techniques to reduce or control the effects of differential
settlement include:
• Articulation of the wall (in discontinuing the normal
stretcher bond) at convenient intervals along the length,
or
• Excavating, replacing and compacting areas of soft soil,
• Limiting the stepping of the foundation and bottom course
to a maximum of 200mm.
Unit Cracking/Gapping – Settlement
Keystone modular retaining wall structures can tolerate a
certain amount of settlement due to the flexible nature of the
system and small individual unit size.
Observation of a number of completed structures that have
undergone settlement indicates that the wall’s tolerance for
settlement without cracking is inversely proportional to the
wall height. Lower height walls (H<5m) appear to have
considerably more facial flexibility than taller walls (H>5m).
This increased flexibility is due to lower confining forces and
load transfer taking place on each block,which permits small
individual movements to occur, accommodating the settlement
experienced without facial distress. Taller walls place the
lower wall units under considerable confining pressure,
restricting unit movement and permitting shear and flexural
stresses to build up to the point where a block cracks as a
means of stress relief.
Low wall settlement problems are typically observed in
residential projects where soils adjacent to houses are
uncompacted and the walls settle differentially over a short
distance. Usually gapping or offset joints are visually noted
and the settlement is obvious.
Gapping and offset joints
Downward movement
Fig B4 – Typical Low WallSettlement
B5
Victoria Book 4 B
BORAL MASONRY DESIGN GUIDE | July 2005
Tall wall settlement is not as obvious but occasional facial
cracks can be observed in areas of f lexural stress
concentration, typically in small groupings in the bottom 1/3
of the wall. Settlement induced cracks are usually not
structurally significant and are just a means of facial stress
relief for the unreinforced dry-stack facing system. However,
cracked units can be a symptom of other types of problems,
so a review by an engineer is always recommended.
Importance of Drainage
This guide assumes that a properly functioning drainage
system is effective in removing hydraulic pressure. If this is
not the case, the designer will be required to design for an
appropriate hydraulic load.
Based on an effective drainage system, it is common to use
drained soil properties. For other situations, the designer
must determine whether drained or undrained properties are
appropriate. In particular, seawalls that may be subject to
rapid drawdown (not covered in this guide) require design
using undrained soil properties.
High confining pressure
Flexural stress
Facial cracks
Downward movement
Fig B5 – Typical Tall WallSettlement
B6
Victoria Book 4 B
July 2005 | BORAL MASONRY DESIGN GUIDE
B B4 k 4 ok ookBo Ba oriatorctoVicV
Site Investigation: Preliminary Design
Date: ____________________
Report prepared by: ____________________
Client: ______________________________________________________________________
Project: ______________________________________________________________________
Location: ____________________________________________________________________
Use for which retaining wall is intended: __________________________________________
Proximity of other structures to the face of the retaining wall:
Structure or load Distance (m)
Distance of live loads from top of wall (Dqi) ____________________
Distance of dead loads from top of wall (Dqd) ____________________
Distance of point loads from top of wall (Di) ____________________
Distance of other structures from base of wall (Ds) ____________________
Structure classification: __________________________________________________
For guidance refer AS4678, Table 1.1
Structure Classification Examples
2. Where failure would result in significant damage or risk to life
3. Where failure would result in moderate damage and loss of services
4. Where failure would result in minimal damage and loss of access
Required design life:______________________________________________________
For guidance refer AS4678, Table 3.1
Type of Structure Design life (years) Type of Structure Design life (years)
Temporary site works 5 Residential dwellings 60
Mine structures 10 Minor public works 90
Industrial structures 30 Major public works 120
River and marine structures 60
Wall geometry:
Wall height above GL (H’) __________ m
Embedment depth (Hemb)
H/20 or 200mm __________ m
Wall slope (�) __________ °
Angle of backfill slope (�) __________ °
Height of backfill (h) __________ m
Foundation material:
Allowable bearing pressure
Under reinforced soil block __________ kPa
Water profile:
Water table depth within wall fill __________m
Retained soil data:
Soil density (�r) __________ kN/m3
Internal friction angle (�r) peak __________ °
Cohesion (C*i) __________ kPa
Loading data:
Dead load surcharge (qd) __________kPa
Live load surcharge (ql) __________kPa
Horizontal line load (F) __________kN/m
Vertical line load (P) __________ m
Width of bearing (b) __________ m
SEGMENTAL BLOCK RETAINING WALLS VICTORIA BOOK 4
C GARDENWALL®
4C44Masonry Design Guide
BORAL MASONRY
Build something great™
C2
Victoria Book 4 C
July 2005 | BORAL MASONRY DESIGN GUIDE
INTRODUCTION
Boral Gardenwall is ideal for low
landscaping walls and edgings in
garden and communal areas.
Gardenwall’s rockface texture, multi-
faceted face and setback construction
produces an aesthetically pleasing
feature for landscaped areas.
Gardenwall is often used for garden
edges and raised beds, terraces and
to create decorative features such
as around pools.
DESIGN CONSIDERATIONS
Depending on the foundation and
retained soil characteristics,
Gardenwall is effective as a gravity
retaining wall structure up to
1125mm (maximum 9 courses).
Never install where loads (e.g.
buildings, driveways) will be located
within 1125mm of the wall. For
engineered walls (to AS4678) higher
than 1125mm, orwhere a surcharge
is present, Boral Keystone or
Pyrmontwalls should be considered.
ADVANTAGES
• Gardenwall does not require
concrete foundations.
• Easy installation of straight walls
and curved walls.
• Durable, low maintenance, long-
term landscaping.
• Solid units – eliminates the need
for capping and corner units.
COLOURS
Gardenwall is offered in a range of
colours to suit traditional and
contemporary settings. Please refer
to colour swatch information for an
indication of current colours.
To reduce the possibility of staining
and to enable easier cleaning, a
masonry sealer can be applied to all
visible surfaces after installation.
Product Description Finish HxLxDmm Approx Wt kg Nº/m2
Standard Unit Rockfaced 125x305x228 16.5 26.3 units/m2
Specifications
Gardenwall®
Retaining Wall System
228
125
305
Availability & Colours• No minimum order quantities apply.
• Lead time 0-2 weeks.
Standard Unit
Portstone
TerrainLight Sands
Kota Green
Hawkesbury YellowPaperbark
C3
Victoria Book 4 C
BORAL MASONRY DESIGN GUIDE | July 2005
IMPORTANT: Please consult with the regulating council for
local design requirements prior to the design and construction
of a retaining wall. Councils in general require that retaining
walls be designed and certified by a suitably qualified engineer
where the wall is over 0.5m in height and/or where there is
surcharge loading such as a roadway, house, or other structure
near the wall.
• Boral Gardenwall is only suitable for walls up to 1125mm
in height and where no loads or surcharge exists within
1125mm behind the wall.
Installation
• Remove the retaining lug on the base of the unit on those
Gardenwall blocks being used on the base course only
(this makes levelling the first course much easier).
To remove the lip, place at an angle on the ground and strike
the lug firmly with a hammer (safety glasses should
be worn).
• As a safety precaution to avoid lifting or movement of the
top units, it is recommended that the top course units are
secured using a construction adhesive. This is also
recommended in areas of possible vandalism.
• Standard units can also be used to construct convex curves.
Gardenwall Unit
1 in 5 set-back
150mm width of 12-20mmØ free draining granular material eg. blue metal
Backfill placed and compacted in 250mm layers
Compacted road base levelling pad on undisturbed inorganic soil
First course to be buried below final ground level (to engineer's specification - 100mm min.)
Drainage pipe (if required)
350mmmin.
100mm min.
Native soil
Dish drain to direct surface run-off (if required)
H
No loads to be located within 1125mm behind wall
Backfill should be no higher than the top of the wall
Fig C1 – Typical Gravity Wall Construction Detail – Gardenwall
Selection & Construction Guidelines
Note: Refer to max. wall heights disclaimer on page A3 of this guide.
The gravity wall heights are maximum heights calculated in accordance with CMAA MA-53 Appendix D guidelines and a qualified engineer should confirm
the suitability of the product for each intended application.
C4
Victoria Book 4 C
July 2005 | BORAL MASONRY DESIGN GUIDE
for 1st course
Radius = 1000mm
Minimum
Fig C2 – Construction of Curved Walls
• When designing Gardenwall for convex curves to the
maximum height of 8 courses, it is necessary to begin
with a minimum radius of 1000mm. It may also be
necessary to remove the outer portions of the retaining lug
from each unit to maintain a consistent setback. It is
important that the entire lug is not removed.
• When building curves, some blocks may also require
trimming of the length to maintain a half bond pattern.
Curved Walls
SEGMENTAL BLOCK RETAINING WALLS VICTORIA BOOK 4
D HEATHSTONE®
4D44Masonry Design Guide
BORAL MASONRY
Build something great™
D2
Victoria Book 4 D
July 2005 | BORAL MASONRY DESIGN GUIDE
INTRODUCTION
Boral Heathstone is ideal for low,
vertical landscaping walls in garden
and communal areas. The rockface
texture and bevelled edges add a
formal and elegant element to a
landscaped area. Heathstone is often
used to separate and highlight
entertaining areas, BBQ areas, paths,
garden beds, hedges, or to create and
differentiate levels. Heathstone is
also suitable for constructing steps,
planter boxes and for curved walls.
DESIGN CONSIDERATIONS
Depending on the foundation and
retained soil characteristics,
Heathstone is effective as a gravity
structure up to 972mm, or up to
1600mm when installed with no-
fines concrete backfill. Heathstone
should not be used where the base
soil or backfill is not firm, or is of
expansive clay. Never install where
loads (e.g. buildings, driveways) will
be located within 1000mm of the
wall. For walls higher than this, or
where a surcharge is present, Boral
Keystone or Pyrmont walls should
be considered.
The range of Heathstone components
is designed to optimise space, and
includes a ready-to-install corner
unit and a series of caps to
accommodate single or double sided
applications and curved installations.
Convex curves as tight as 900mm
radius can be constructed using the
standard unit. The Curved Cap can
be used to form curves of 1800mm
outside radius and 1500mm inside
radius.
COLOURS
Heathstone is offered in colours
which emulate natural hewn stone,
and which contrast beautifully with
soil, mulch, shrubbery and grassed
areas. Please refer to colour swatch
information for an indication of
current colours.
To reduce the possibility of staining
and to enable easier cleaning, a
masonry sealer can be applied to all
visible surfaces after installation.
Product Description Finish HxLxDmm Approx Wt kg Nº/m2
Standard Unit Rockfaced 162x220x280 11.0 28.1 units/m2
Standard Corner Unit Rockfaced x 2 Faces 162x380x270 15.6 1/course/corner
Grand Unit Rockfaced 162x440x280 26.3 14.05 units/m2
Grand Corner Unit Rockfaced x 2 Faces 162x380x160 10.5 1/course/corner
Splitface Cap Rockfaced x 1 Edge (225mm) 60x225x340 11.3 4.5/linear metre
Double Sided Rockface Cap Rockfaced x 2 Long Edges 50x600x300 22.0 1.6/linear metre
Rockface Corner Cap Rockfaced x 2 Adjacent Edges 50x300x300 10.7 1/corner
Double Sided Rockface Rockfaced x 2 Long Edges 50x392/470x300 15.6 24 per Full Circle (15° each)
Curved Cap 6 per Quarter Circle
Heathstone®
Retaining Wall System
280
162
220
Grand Unit
280
162
440
Grand Corner Unit
380
162
160
380
162
270
300
50
300
RockfaceCorner Cap
1800radius
392
300
470
50
Double Sided RockfaceCurved Cap
Specifications
Availability & Colours• No minimum order quantities apply.
• Lead time 0-2 weeks.
Hawkesbury Yellow
Charcoal
Portstone
340
60
225
Splitface Cap
Standard Unit Standard Corner Unit
300
50
600
Double Sided Rockface Cap
Note: Refer to max. wall heights disclaimer on page A3 of this guide.
D3
Victoria Book 4 D
BORAL MASONRY DESIGN GUIDE | July 2005
Maximum Courses Maximum Courses
For walls without gravel fills For walls with gravel fills
to all voids and cores to all voids and cores
Poor soils – including sands, gravelly
clays, sandy clays and silt clays 2 (324mm) 4 (648mm)
Average soils – including well graded
sands and gravelly sands 3 (486mm) 5 (810mm)
Good soils – including gravels, sandy
gravels and crushed sandstone 4 (648mm) 5 (810mm)
NOTES: Backfill retained by a retaining wall should be no higher than the top of the retaining wall.
For engineered retaining walls to AS4678, refer to the Heathstone No-Fines Concrete Wall Guidelines.
Refer to max. wall heights disclaimer on page A3 of this guide.
The gravity wall heights are maximum heights calculated in accordance with CMAA MA-53 Appendix D guidelines
and a qualified engineer should confirm the suitability of the product for each intended application.
Blocks to be embedded a minimum of 100mm
Native soil
No loads to be located within 1.0m of the wall
150mm min. of 12-20mmØ free draining granular material eg. blue metal
Dish drain to direct surface water or filter fabric to stop silt filling drainage layer
Voids in and around Heathstone blocks to be filled (if required) with 12-20mmØ free draining granular material eg. blue metal
Backfill (eg. excavated soil) to be placed and compacted as each course of blocks is laid
Agricultural drainage line 100mmØ
100mm min.
350mm min.
Refer to Heathstone Gravel-Fill Selection Table for maximum number of courses
Compacted roadbase
Fig D1 – Typical Construction Detail – Heathstone Gravel-Fill
IMPORTANT: Please consult with the
regulating council for local design
requirements prior to the design and
construction of a retaining wall. Councils
in general require that retaining walls be
designed and certified by a suitably
qualified engineer where the wall is over
0.5m in height and/or where there is
surcharge loading such as a roadway,
house, or other structure near the wall.
Heathstone® Gravel-Fill Construction
Table D1 - Maximum Wall Height – Heathstone Gravel-Fill
D4
Victoria Book 4 D
July 2005 | BORAL MASONRY DESIGN GUIDE
Curved Wall Construction
Curves as small as 900mm in radius can be constructed
with Heathstone Standard Units.
NOTE: Double Sided Rockface Curved Cap radius is 1500mm
to the inside face and 1800mm to the outside face.
Bolster back of blocks to form convex curves
NOTE: Premium Curved Caps have an outside radius of 1800mm
Fig D3 – Forming Convex Curve
1800mm
1500mm Heathstone Curved Cap
Fig D2 – Heathstone Curved Cap Radius
Concave (Internal) Curves
• For concave curves use Standard Units spaced evenly to
a scribed arc in conjunction with Double Sided Rockface
Curved Caps butted together to form a 1500mm radius
wall face.
Concave Curve Radius
Heathstone Standard Unit
NOTE: Premium Curved Caps have an inside radius of 1500mm
Fig D4 – Forming Concave Curve
1:10 Cement : Sand
Native soil
255
162
45
25
Heathstone Units
Remove locating lugs before laying
Fix cap units with construction adhesive
Double Sided Rockface Cap
Fig D5 – Construction of Heathstone Steps
Note: For alternative step detail, see page E10.
Convex (External) Curves
• For convex curves, the tails of the blocks must be trimmed
to suit the desired radius. Use a hammer and bolster on
the back, top and bottom of the tail. Use light hammer
blows first to trace the area to be removed, then a heavier
blow on top. Repeat the tracing and final blow if necessary.
Step Construction
D5
Victoria Book 4 D
BORAL MASONRY DESIGN GUIDE | July 2005
Step Treads and Cap Unit Installation
• Splitface Cap (225mm long) has a recess in the underside
to allow for the lug on the Heathstone Unit. Removal of the
lug is not required in this case
• To allow for installation of the Double-sided Rockface Cap
units and step treads, it is necessary to bolster locating
lugs from the blocks.
• Push the Heathstone split-face into sand for support. Trace
along the back of the lug with a bolster and hammer,
increasing the force of hammer blows until the lug splits
off. All blows must be from the back of the block, with the
bolster blade nearly parallel to the top of the Heathstone
unit. Refer to the illustration. Any remaining high spots
should be removed with a scutch hammer or an old
screwdriver and hammer.
Fig D6 – Bolstering Lug from Heathstone Units
D6
Victoria Book 4 D
July 2005 | BORAL MASONRY DESIGN GUIDE
Corner UnitCorner Unit
Fig D7 – Heathstone External Corner (270°)
Corner Unit
Standard Unit
Corner Unit
110mm
Fig D8 – Heathstone Internal Corner (90°)
Grand Corner Unit
Grand Unit
Grand UnitBolster lug to fit next course
Fig D9 – Heathstone Grand External Corner (270°)
Grand Unit
Grand Unit
Bolster lug tofit next course
Bolster lug tofit next course
220mm
NOTE: Internal 90º corners using Grand Units do not require corner units
Fig D10 – Heathstone Grand Internal Corner (90°)
Corner Construction
Constructing Internal and External Corners
• Corners are constructed using Corner Units and Standard
Units or Grand Units and Grand Corner Units.
• Lay the Corner Units’ largest splitface in alternate directions
in adjacent courses (see illustrations).
• Continue this step until the desired height of the wall is
achieved.
• Use a construction adhesive to secure corner blocks and
caps.
D7
Victoria Book 4 D
BORAL MASONRY DESIGN GUIDE | July 2005
No-Fines Concrete shall consist of cement, water and coarse
aggregate. Cement will complywith the definitions for cement
per AS3972-1991 – ‘Portland and Blended Cements’. The
quantity of cement is specified as 210kg/m3 with a total
water/cement ratio of between 0.45 and 0.55.
The particle size distribution of the aggregate shall comply
with the limitations for the nominal single sized 20mm
aggregate specified in AS2758.1.
NOTES:
• Table D2 is based on AS4678 : 2002, Earth Retaining
Structures. The code assumes a surcharge of 5kPa is
Wall Height Retained Soil Retained Soil Retained Soil
‘H’ (mm) CLAY � = 26° (POOR) SAND � = 30° (AVERAGE) GRAVEL � = 34° (GOOD)
‘T’ (mm) ‘T’ (mm) ‘T’ (mm)
972 670 570 570
1296 730 770 670
1620 1170 970 770
� Denotes the internal angle of friction of the retained material
H (Refer to Heathstone
No-Fines ConcreteSelection Table)
Blocks to be embedded to engineer‘s detail (1 course min.)
Retained soil
No loads above 5kPa to be located within 1.0m of the wall
T
25MPa concrete footing on 150kPa allowable bearing capacity material
15MPa ‘No Fines’ concrete.All voids within and around units to be completely filled.
Filter fabric or dish drain
Cap unit
Pour no-fines concrete directly onto prepared foundation material
Sub-soil drain connected to stormwater system or flood pit. Place loose aggregate around subsoil drain before pouring no-fines concrete.
150mm min.
600mm min.
Fig D10 – Typical Construction Detail – Heathstone No-Fines Concrete Wall
Heathstone® No-Fines Concrete Wall Construction
Table D2 – Heathstone Maximum Wall Heights – No-Fines Concrete Construction
applied to all retaining wall structures.
• Global stability and all design considerations should be
checked by an engineer in poor clay conditions.
• Design assumes a dry excavation (i.e. water table is below
bottom of footing level). If ground water exists in the
excavation the wall is to be re-designed by a suitably
qualified engineer.
• These tables are supplied free of charge and do not form
any part of any contract with the user.
• 15MPa No-Fines concrete with a 6:1 ratio (Gravel : Cement).
D8
Victoria Book 4 D
July 2005 | BORAL MASONRY DESIGN GUIDE
• The density of this product will vary with the density of
the aggregate used. The density range may be from
1650kg/m3 to 2100kg/m3.
• The void ratio of the mix is expected to be between 20%
and 30% and should be free draining.
• The compressive strength should generally exceed 15MPa
for design purposes.
• This product has no slump and exerts similar pressures
on the soil and formwork, as does loosely poured aggregate.
No-Fines Construction Steps
Special purpose construction such as waterside walls, post
fixing, earthquake zones, and terraces will require additional
engineer’s design.
STEP 1: Excavation/Preparation of Levelling Pad
Excavate a trench 600mm wide and sufficiently deep to allow
a 150mm levelling base plus 1 course below ground.
STEP 2: Installing the First Course
Lay the first course of Heathstone units side by side over the
prepared base. Bolster off the tails so that ‘No-Fines’ concrete
connects backfill to core-fill areas.
STEP 3:No-Fines Concrete Backfill
Backfill the first 21⁄2 courses of the wall with ‘No Fines’ concrete.
All voids inside and between the units must also be filled. The
vertical height of any pour of ‘No Fines’ concrete is limited
to 400mm. For walls greater in height, each pour must be
allowed to harden prior to pouring the next lift. Alternatively
the wall may be propped to support the lateral load from the
wet concrete.
STEP 4:
Installing Capping Units
Install capping units and fix with construction adhesive.
SEGMENTAL BLOCK RETAINING WALLS VICTORIA BOOK 4
E KEYSTONE® AND PYRMONT®
4E44Masonry Design Guide
BORAL MASONRY
Build something great™
E2 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
Keystone® & Pyrmont Retaining Wall Systems
The Keystone Retaining Wall System is a world-widesuccess story, and since its introduction by Boral intoAustralia in 1992, hundreds of thousands of square metreshave been installed along our highways, roads andtransport corridors, and around our sports facilities,buildings, foreshores and open spaces.
Boral Keystone retaining wall systems combine provenengineering capabilities with design versatility, costeffectiveness, lasting durability and an attractive dynamicappearance to provide total solutions for retained earthstructures.
Keystone®
Boral Keystone systems provide infinite flexibility fordesign variation and individuality. The range of componentsand installation methods cater for straight, curved andterraced walls, level or stepped foundations and capping,
and a near vertical or set-back face. Then there is a choiceof standard or flushface, and a selection of popularstandard colours or custom colours can be ordered forlarger projects.
Pyrmont®
Boral Pyrmont retaining wall system retains all of theengineering characteristics of the Keystone system andcombines them with a more traditional appeal of abevelled-edge splitface block, and vertical constructionto emulate walls built during Australia’s pioneering era.
The range of components and installation methods caterfor straight and gently curved walls as well as crisp90º corners, while the rock-faced caps provide a finishingtouch that completes the transformation into amasterpiece from the colonial era.
E3BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 E
Ease of Construction
Boral Keystone and Pyrmont systems are designed toreduce construction time and cater for all locations. Themodular blocks can be moved and installed without theneed for heavy lifting machinery, and the dry stacked,mortarless installation provides less complex, more rapidconstruction.
Proven Engineering
Various installation methods cater for simple gravity wallsthrough to geogrid soil-reinforced retaining structures. BoralKeystone and Pyrmont systems can also cater for criticalsurcharge loads, enabling the construction of buildings orroadways close to the wall to optimise land usage.
For high performance retaining walls, please refer to thesection on Boral Keysteel Custom Engineered RetainingWall Systems later in this guide.
Durability
Boral Keystone and Pyrmont systems combine thedurability of concrete units and interlocking fibreglasspins to produce maintenance free walls with lifeexpectancies of up to 120 years.
E4 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
INTRODUCTION
Boral Keystone is an advanced,
highly versatile and thoroughly
proven high performance segmental
block retaining wall system which
can be used as a gravity structure
or it can incorporate geogrid soil-
reinforcement to cater for greater
heights and surcharge loading
situations.
DESIGN CONSIDERATIONS
• Suitable for straight and curved
wall installations with a minimum
convex curve radius of 1800mm
without trimming the tail width,
or 970mm radius by trimming the
tail to 300mm width.
• Can be installed as near vertical,
or for straightwalls without curves
or corners it can be installed with
a 1-in-8 setback.
COLOURS
Keystone is offered in a range of
colours to suit decorative and
engineering applications. Please
refer to colour swatch information
for an indication of current colours.
To reduce the possibility of staining
and to enable easier cleaning, a
masonry sealer can be applied to all
visible surfaces after installation.
Keystone®
Retaining Wall Systems
305
200
455
Standard Straight Sided Cap
275
100
455Flushface Straight Sided Cap
275
100
455
PinsLifting Bars
Description Wt kg Nº/m2
Standard Unit 35 11
Standard Straight Sided Cap 25 2.2/lin mtr
Flushface Unit 38 11
Flushface Straight Sided Cap 26.3 2.2/lin mtr
Pins 2 pins per full unit
(high strength pultruded fibreglass)
Lifting Bars (Keystone units should be lifted by
two people using the Keystone lifting bars)
Specifications
Standard Unit
305
200
455
Flushface Unit
Availability & Colours• No minimum order quantities apply.
• Lead time 0-4 weeks.
Bluestone Brown
Sunset Terracotta
Natural Parchment
Charcoal
E5BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 E
Lifting Bars
INTRODUCTION
Boral Pyrmont retaining wall
systems integrate the engineering
capabilities of the Keystone system
with the versatility and pleasing
aesthetics of a vertical wall. The
Pyrmont unit is a split-face block
with four chamfered edges,
emulating the care, skill and
determination of stone masons from
Australia’s early settler period.
Boral Pyrmont retaining wall system
is also suitable for constructing
steps, planter boxes, gently curved
walls and crisp 90° corners.
DESIGN CONSIDERATIONS
Suitable for curved wall installations
with a suggested minimum convex
curve radius of 5m (resulting in
a 5mm lip).
COLOURS
Please refer to colour swatch
information for an indication of
current colours.
To reduce the possibility of staining
and to enable easier cleaning, a
masonry sealer can be applied to all
visible surfaces after installation.
222 222
200
450 450
Premium Cap Rockfaced(Hawkesbury Yellow only)
355
65
455
Premium Corner CapRockfaced(Hawkesbury Yellow only)
355
65
355
Description Wt kg Nº/m2
Standard Unit 37.3 11
Standard Cap (Rockfaced 1 side) 11.3 4.44/lin mtr
Premium Cap (Rockfaced 1 side) 24 2.2/lin mtr
Premium Corner Cap (Rockfaced 2 sides) 18.8 1/90° corner
90° Corner Unit (Right or Left Hand) 31 5/vertical metre
Pins 2 pins per full unit
(high strength pultruded fibreglass)
Lifting Bars (Pyrmont units should be lifted by
two people using the Keystone lifting bars)
Specifications
Pyrmont®
Vertical Retaining Wall System
305
200
455
Standard Unit
340
60
225
Standard Cap
Availability & Colours• No minimum order quantities apply.
• Lead time 0-4 weeks.
Hawkesbury YellowPortstone
Charcoal
90° Corner UnitRight or Left Hand
Pins
E6 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
226mm pin cts 226mm pin cts
Fig E1 – Installation of Pins
IMPORTANT: Please consultwith the regulating council forlocal
design requirements prior to the design and construction of a
retaining wall. Councils in general require that retaining walls be
designed and certified by a suitably qualified engineerwhere the
wall is over0.5m in heightand/orwhere there is surcharge loading
such as a roadway, house, or other structure near the wall.
Refer to Keystone and Pyrmont ‘No-Fines Concrete’ Guidelines
for engineered retaining walls to AS4678.
• Two sets of pin holes are provided in Keystone units.
• For near vertical construction, install pins in the front
holes, and maintain a distance of 226mm between pin
hole centres of adjacent units.
• For 1 in 8 setback construction, install pins in the back
holes, and maintain a distance of 226mm between pin
hole centres of adjacent units.
• Near vertical installation must be used when designing
walls with curves or corners.
Wall Height H (mm)
Surcharge LoadingBackfill
Near 1 in 8Type
Vertical Setback
SETBACK Poor 800 900
Average 900 1000
Good 1000 1200
Poor 600 900
Average 700 900
Good 800 1100
Poor 400 500
Average 500 600
Good 600 800
No
Su
rch
arge
Lo
adin
g15
°S
lop
ed B
ackf
illD
rivew
ay/C
arpa
rk L
oadi
ng (5
kPa)
Table E1 – Maximum Wall Height for Gravel-Fill WallsGravel-Fill Wall Selection
Gravel-Fill Wall Construction Guidelines
For low, non-critical walls, (i.e. walls covered in the adjacent
table) the Keystone and Pyrmont Retaining Wall Systems are
effective as a gravity wall structure, utilising their weight
and interaction of the units to resist earth pressures.
Retained Soil Descriptions
Poor Soils Include fine sands, gravelly
clays, sandy clays, silty sands.
Angle of internal friction ≥ 25°
Average Soils Include well graded sands,
gravelly sands.
Angle of internal friction ≥ 30°
Good Soils Include gravels, sandy gravels,
crushed sandstone
Angle of internal friction ≥ 35°
NOTES: Pyrmont walls can only be constructed in near
vertical format, and must be selected on the basis of data in
the near vertical column from Table E1.
Table E1: Refer to max. wall heights disclaimer on page A3 ofthis guide. The gravity wall heights are maximum heights
calculated in accordance with CMAA MA-53 Appendix D
guidelines and a qualified engineer should confirm the
suitability of the product for each intended application.
E7BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 E
• For curved installations, maintain 226mm between pin
hole centres of adjacent units. This will leave a small gap
between units for convex curves, and will require a small
overlap of adjacent units with concave curves. Refer to
curve installation details on Page E9 of this guide.
• If backfill is required behind the drainage zone, place and
compact existing site soils in 200mm maximum lifts.
Heavy clays and organic soils are not recommended due
to water holding problems.
• Provide a filter fabric between drainage layer and backfill
if the type of backfill is likely to wash into drainage layer
and clog it.
• Use only walk-behind compaction equipment within
1000mm of the wall face to prevent movement of the
Keystone units.
• In areas of possible vandalism, it is recommended that
capping units be secured using a masonry adhesive.
Fig E2 – Typical Installation Detail – Keystone Gravity Wall
Native soilCompacted footing
Free draining granular material
Drainage pipe
Compacted backfill soil (if required)
Cap Unit
Keystone or Pyrmont units
Optional 1:8 wall setback with Keystone units
12-20mm free draining granular material, fill all voids in and around units
Compacted roadbase, crushed stone or gravel levelling pad
First course to be buried below final ground level (to engineer's specification - 100mm min.)
Drainage pipe (if required)
300mm
Granular material for drainage
600mm min.
150mm min
H
Backfill
Fig E3 – Typical Construction Detail – Keystone Gravity Wall
E8 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
FIRST COURSE SECOND COURSE
Align centre of unit with face of adjoining wall
No pin in overlapping unit
No pin in overlapping unit
Align face of unit with thecentre line of adjacent unit
FIRST COURSE SECOND COURSE
Align face of unit with thecentre line of adjacent unit
Omit one pin only
Cut to suit on site
Omit one pin only
Cut to suit on site
Fig E4 – 90° Internal Corner – Standard Keystone Units
Fig E5 – 90° Internal Corner – Flushface Keystone/Pyrmont Units
455mm305mm
77mm
455mm
455mm
455mm
90˚ corner unit cut from face of Flushface unit and fixed in place with epoxy adhesive
Use Flushface unit and bolster face to suit
FIRST COURSE SECOND COURSE
Omit one pin only
Fig E6 – 90° External Corner with Standard Keystone Units
Typical Installation Details
E9BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 E
Use front pin holes for curves. Maintain a centre-to-centre distance of 226mm between pins in adjacent units (small overlaps between units will be required)
226mm centres
Fig E8 – Concave Curve
Pyrmont corner unit
Pyrmont corner unit
455mm450mm
222mm
455mm
455mm
455mm
FIRST COURSE SECOND COURSE
Fig E7 – 90° External CornerPyrmont Units
Rad
ius
‘r’
226mm
3 unit 90 corner : r = 900mm
4 unit 90 corner : r = 1250mm
5 unit 90 corner : r = 1540mm
6 unit 90 corner : r = 1830mm
7 unit 90 corner : r = 2120mm
Use front pin holes for curves. Maintain a centre-to-centre distance of 226mm between pins in adjacent units (small gaps between units will be required)
Bolster backs as required
Fig E9 – Convex Curve
E10 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
Keystone cap unit
Keystone unit
Bedding sand –compact before laying treads
Compacted bedding sand
Sand : cement = 6 : 1
40mm Boral Pavers
10mm mortar joint
Keystone Flushface Caps
Tread approx. 290mm for 40mm pavers (30˚)
10mm
10mm100mm
40mm
160mm riser
Fig E12 – Keystone section through steps
Fig E10 – Stepped Capping Units
290mm Treads
Bolster backs as required
Fig E11 – Plan view of step through Keystone
E11BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 E
H
Blocks embedded to engineer's detail (100mm min)
Retained soil
T
25MPa concrete footing on 150kPa allowable bearing capacity material (see note below Table E2)
15MPa ‘No-Fines’ concrete.All voids within and around units to be completely filled.
Filter Fabric
Cap unit
Keystone or Pyrmont unit
Pour no-fines concrete directly onto prepared foundation material
Sub-soil drain connected to stormwater system or flood pit
150mm min
600mm min.
Fig E13 – Typical Construction Detail – Keystone No-Fines Concrete Mass Gravity Wall
‘No-Fines Concrete’ Wall Construction Guidelines
Wall Height Retained Soil Retained Soil Retained Soil
CLAY � = 26° (POOR) SAND � = 30° (AVERAGE) GRAVEL � = 34° (GOOD)
‘H’ (mm) ‘T’ (mm) ‘T’ (mm) ‘T’ (mm)
1000 550 500 450
1400 750 700 650
1800 NA 1000 850
2200 NA 1250 1000
2600 NA 1350 1200
� Denotes the internal angle of friction of the retained material
Non-shaded Area = Compacted Roadbase Footing Shaded Area = Concrete Footing as per Fig E13
If material below no-fines concrete is of poor quality, then the material must be replaced with a 150mm thick layer of crushed sandstone
The ‘No-Fines Concrete’ backfill system increases the mass
of Keystone/Pyrmont allowing the maximum heights in Table
E1 to be exceeded without using geogrids.
This is ideal for boundary walls where the geogrids would
otherwise cross the boundary line.
No-Fines Concrete shall consist of cement, water and coarse
aggregate. Cement will complywith the definitions for cement
per AS3972 : 1991 – ‘Portland and Blended Cements’. The
quantity of cement is specified as 210kg/m3 with a total
water/cement ratio of between 0.45 and 0.55.
The particle size distribution of the aggregate shall comply
with the limitations for the nominal single sized 20mm
aggregate specified in AS2758.1.
NOTES:
• 15MPa No-Fines concrete with a 6:1 ratio (Gravel : Cement).
• The density of this product will varywith the density of the
aggregate used. The density range may be from 1650kg/m3
to 2100kg/m3. (Table based on density of 2100 kg/m3.)
• The void ratio of the mix is expected to be between 20%
and 30% and should be free draining.
Table E2 – Maximum Wall Heights for No-Fines Concrete Wall Construction
E12 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
• The compressive strength should generally exceed 15MPa
for design purposes.
• This product has no slump and exerts similar pressures
on the soil and formwork, as does loosely poured aggregate.
Table E2 is prepared as per AS4678 : 2002, and is based
on a 5kPa surcharge loading at the top of the wall. This
table is supplied as a guide, and does not form any part
of any contract with the user.
• The maximum slope of the backfill behind the wall is to
be 5% (1 vertical to 20 horizontal).
• The vertical height of any pour of ‘No Fines’ concrete is
limited to 600mm. Each pour must be allowed to harden
prior to pouring the next lift. Alternatively the wall may
be propped to support the lateral load from the wet concrete.
• For higherwalls orwalls with a greater surcharge loading,
Geogrid soil reinforced construction is required.
• For walls founded on clay with a height greater than 2.0m,
Geogrid reinforcement is required.
• Global stability considerations should be checked by an
engineer in poor clay conditions.
• Design assumes a dry excavation (i.e. water table is below
bottom of footing level). If ground water appears in the
excavation, the wall is to be re-designed by a suitably
qualified engineer.
Construction Steps
Special purpose construction such as waterside walls, post
fixing, earthquake zones, and terraces will require additional
engineer’s design.
STEP 1:Excavation/Preparation of Levelling Pad
For walls less than 900mm high, excavate a trench 600mm
wide and sufficiently deep to allow a levelling base of 150mm
+25mm height for each course. Spread coarse sand or 12-
20mm gravel for the levelling base and compact.
For higher walls or in poor foundation material, a footing as
shown in Fig E13 may be necessary. Refer to Table E2.
STEP 2:Installing the First Course
Lay the first course of units side to side over the prepared
base, with the 12mm pinholes on top and kidney holes on
the underside. Maintain the required distance between pinhole
centres of adjacent units. In straight walls, units will touch.
In concave or convex curves, the units will overlap or require
spacing to maintain the 226mm pin distance. Refer to Figs
E8 and E9 for curve installation details.
STEP 3:Installing the Pins
Place the high strength fibreglass connecting pins into each
unit. Use the front holes for a near vertical setback (corners
and curved walls). Use the rear holes for a 1 in 8 setback (i.e.
for every course the wall will set back 25mm). For straight
walls only.
STEP 4:Additional Courses
Sweep the top of the previous course of units clean of any
loose gravel. Place the next course of units so that the kidney
holes fit over the pins of the two units below. Pull the unit
towards the face of the wall until it locks with the pins on
both sides. Repeat steps 3 and 4.
STEP 5: No-Fines Concrete Backfill
Backfill the wall with ‘No Fines’ concrete. All voids inside
and between the units must also be filled. The vertical height
of any pour of ‘No Fines’ concrete is limited to 600mm. Each
pour must be allowed to harden prior to pouring the next lift.
Alternatively the wall may be propped.
STEP 6:Installing Capping Units
Lay capping units, backfill and compact to required grade.
In areas accessible to public vandalism, it is recommended
that the capping units be secured using masonry construction
adhesive or epoxy cement.
E13BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 E
Surcharge Wall Geogrid Geogrid Height Above Geogrid Length
Height Layers Levelling Pad L (m)
H (m) Layers Soil Type (phi)
1 2 3 4 5 6 7 25 30 35
15 Degree 1.1 2 0.2 0.8 – – – – – 2.2 2.0 2.0
Backfill Slope 1.5 3 0.2 0.6 1.2 – – – – 2.5 2.0 2.0
1.9 4 0.2 0.6 1.0 1.6 – – – 2.4 2.0 2.0
2.3 5 0.2 0.6 1.0 1.4 2.0 – – 2.8 2.4 2.0
2.7 6 0.2 0.6 1.0 1.4 1.8 2.4 – 3.6 2.7 2.4
3.1 7 0.2 0.6 1.0 1.4 1.8 2.2 2.8 4.3 3.0 2.7
5kPa 1.1 2 0.2 0.8 – – – – – 2.4 2.0 2.0
Driveway 1.5 3 0.2 0.6 1.2 – – – – 2.7 2.1 2.0
1.9 4 0.2 0.6 1.0 1.6 – – – 3.0 2.4 2.0
2.3 4 0.2 0.8 1.4 2.0 – – – 3.3 2.7 2.3
2.7 5 0.2 0.6 1.2 1.8 2.4 – – 3.6 3.0 2.5
3.1 6 0.2 0.6 1.0 1.6 2.2 2.6 – 4.0 3.3 2.8
Geogrid Soil-Reinforced Wall Construction Guidelines
Table E3 – Maximum Wall Heights for Geogrid Soil-Reinforced Walls
For taller, more critical walls, the combination of Keystone units
with geogrid soil reinforcement allows walls to be built to heights
of12m and greater,withoutcostlystructural footings. When placed
between layers of compacted soil,geogrids create a reinforced soil
mass, which essentially acts as a larger gravity wall structure.
Geogrids can be used with most existing site-soils and are not
affected by water, micro organisms, alkali or acidic soils. Consult
your engineer for design requirements of Keystone walls using
geogrid soil reinforcement.
NOTES:
• Table E3 is prepared as per AS4678 : 2002. Suitability of
the information contained in the table must be referred to
a qualified professional engineer. These tables are supplied
as a guide, and do not form any part of any contract with
the user.
• Table E3 is based on foundation material with minimum
200kPa bearing capacity.
• Where site conditions and loadings vary from those in the
table, professional engineering advice should be obtained.
• The minimum embedment of wall below ground level is
assumed to be H/20 or 100mm, whichever is greater.
• The length of the 15° backfill slope is assumed to be equal
to the height of wall, H.
*Geogrid with Tul=55kN/m2
E14 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
Cap Unit
Keystone or Pyrmont unit
12-20mm free draining granular material, fill all voids in and around units
Geogrid soil reinforcement to engineer's specification
Compacted backfill material
Compacted roadbase or concrete footing
First course to be embedded below final ground level to engineer's detail (100mm min.)
Drainage pipe (as required)
Reinforced Soil Zone
300mm
Granularmaterial
600mm min.
150mm min.
H
L
Fig E15 – Typical Construction Detail – Keystone/Pyrmont Geogrid Reinforced-Soil Wall
Native soil
Native soil
Geogrid sections are located over pins at the front, pulled taught and staked at the back
Compacted roadbase footing
Free draining granular material
Drainage pipe
Compacted backfill soil
Fig E14 – Typical Installation Detail – Keystone/Pyrmont Geogrid Reinforced-Soil Wall
E15BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 E
Typical Specification for
Keystone or Pyrmont
Retaining Walls
1. Scope of Work
1.1 Extent
This specification covers the works for construction of
segmental, reinforced-soil retaining structures. The works
include footing excavation, foundation preparation, drainage,
backfill and compaction and related items necessary to
complete the work indicated on drawings and as further
specified.
All retaining wall construction is to be carried out in
accordance with the levels, distances and details as shown
on the drawings and in accordance with this specification.
The Keystone reinforced retaining wall system shall also be
constructed in accordance with the manufacturers installation
guidelines by a suitably qualified and experienced contractor.
1.2 Responsibilities
The Contractor shall be responsible for carrying out the
installation of all retaining walls in accordance with this
specification and the associated contract documents.
2. Standard Specification
Wherever reference is made to Standards Association of
Australia (SAA) the requirements of the editions and
amendments, shall apply to the relevant materials or operations
and be deemed to be incorporated in this specification.
In the case of a conflict between the referenced standard
specification and code and this specification, the more
stringent provisions shall apply.
The following is a summary of standard specifications
applicable to this subsection of the work:
AS1012 Methods of Testing Concrete
AS4456 Concrete Masonry Units
AS3600 Concrete Structures
AS4456.4 Masonry Units – Compressive Strength
AS4678 Earth Retaining Structures
AS1289 Methods of Testing Soils
Materials or operations not covered by the above standard
codes shall conform to the appropriate Australian Standard.
3. General Requirements
3.1 General
Terms used in this specification shall have the meanings
assigned to them as follows:
‘Approved’ shall mean approved in writing by the Engineer.
‘Or equal approved’ shall mean equivalent in performance,
quality and price to that specified and approved by the
Engineer.
Where limits to the properties of soils are defined elsewhere
herein these properties shall be determined by the methods
laid down in AS1289.
The term ‘construction area’ in this Part shall be defined as
an area to be excavated or an area to be cleared and filled.
3.2 Regulations
The Contractor shall complywith all relevantActs, Regulations
and By-Laws in respect of all work specified herein, including
temporary timbering, strutting, guard rails and all safety
measures to be adopted.
3.3 Certification
The Contractor’s Geotechnical Engineer shall certify that the
bearing capacity of the foundation is as per the foundation
requirements specified on the drawings. The Geotechnical
Engineer shall also inspect and certify that the Reinforced
Soil Block material is as specified on drawings with regard
to friction angle, and bulk density.
4. Materials
4.1 Masonry Units
The retaining wall units shall be manufactured in accordance
with AS4456 Concrete Masonry Units. Block types and sizes
for Keystone retaining walls shall be as shown on the drawings
or specified herein.
4.1.1 Tolerance
Permissible tolerance in the manufacture of retaining wall
units shall comply with AS4456.3 - 1997. In the case of
Keystone units, the tolerance of ± 2mm shall not apply to
profiled or textured faces. Non conforming concave distortions
shall be rejected.
E16 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
4.1.2 Strength
Retaining wall units shall be manufactured with a minimum
compressive strength of 10MPa. A minimum of ten (10)
samples must be tested to obtain a mean compressive
strength, tested to failure as per AS4456.4 – 1997 under
normal compressive and laboratory conditions.
4.1.3 Colour
The colour and texture of masonry units shall be as specified
and shall remain consistent with the ‘sample range’ approved
by the project Superintendent
4.1.4 Handling/Storage/Delivery
Keystone units shall be delivered on pallets to minimise
damage during transportation. The Contractor shall store and
handle units so as to prevent units from damage, which may
affect the aesthetic quality or structural integrity of the finished
wall.
4.2 Connecting Pins
High strength pultruded fibreglass pins shall be used to
interlock and align all Keystone units in a running bond
pattern. Pins shall also provide an integral connection between
the Keystone units and the geogrid.
4.3 Geogrids
The reinforcing elements for the reinforced soil structure
shall be as shown on the drawings.
If required, each consignment of geogrids delivered to site
shall be accompanied by a Quality Control Tensile Test
Certificate from the manufacturer.
4.4 Approved Reinforced Soil Block Backfill
Material for backfilling between geogrids for the Keystone
retaining wall shall be ‘Approved Backfill’ defined as sand,
crushed sandstone or broken rock obtained from excavations
or approved borrow areas. Such material shall be
• Free of rock fragments greater than 75mm in size.
• Free of clay lumps retained on a 75mm sieve.
• Free of organic matter.
• Within the following grading requirements;
Sieve Size % Passing by Weight
75mm 100
26.5mm 50 - 100
4.75mm 25 - 75
0.425mm 10 - 50
0.075mm 0 - 20
• Non-plastic in that the fraction passing 0.425mm has a
Plasticity Index of not greater than 15.
• Capable of being brought to a moisture content suitable
for compaction as specified elsewhere herein, under the
weather conditions prevailing on site.
The ‘Approved Backfill’ shall be stockpiled on site, and
inspected and approved by the Geotechnical Engineer that
the material satisfies the specification above the design friction
angle and dry densityvalues as specified on drawings. Testing
for dry density and friction angle shall be in accordance with
section 6 herein.
4.5 Drainage
All retaining walls are to contain drainage systems that
prevent the build up of hydrostatic pressure behind walls. This
is to include a 12-20mm free draining clean hard aggregate,
used to fill all voids within the retaining wall units and to
extend 300mm behind the units.
Drainage is to be installed as per the drawings and as per
the manufacturers recommendations.
4.6 Concrete Works
All concrete for use in footings for retaining walls shall have
a compressive strength after 28 days of 25MPa unless specified
otherwise.
The supply, placement, finishing and curing of reinforcement
and insitu concrete shall comply in every respectwith AS3600.
4.7 Hold and Witness Points
The following shall be deemed a Hold Point:
• Submission of test results and samples of all retaining
wall components.
The following shall be deemed a Witness Point:
• On-site slump and strength testing of concrete.
E17BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 E
5. Construction of Keystone/Pyrmont
Retaining Walls
5.1 Foundations
Excavation is to be to the lines and grades shown on the
drawings. The reinforced soil block foundation size shall be
constructed as per drawings unless alterations are made by
the Geotechnical Engineer,who may require tests on the sub-
grade material, to be carried out by a registered N.A.T.A.
Testing Laboratory.
The reinforced soil block foundation subgrade shall be proof
rolled with a heavy steel drum roller (minimum applied
intensity of 4t/m width of drum with at least 8 passes) without
vibration. Any material which is soft,visibly deformed, unstable
or deemed unsuitable by the Contractor’s geotechnical
consultant shall be excavated and replaced with approved
fill and compacted to achieve dry densities of between 98%
and 103% of Standard Maximum Dry Density at moisture
content of ±2% of Standard Optimum Moisture Content.
The foundation shall be inspected and approved by the
Geotechnical Engineer, who shall verify that the foundation
bearing capacity exceeds the required bearing capacity as
specified on drawings. The approval of the reinforced soil
block foundation shall be deemed a HOLD POINT.
Detailed excavation for the mass concrete footing shall proceed
following acceptance of the foundation. The footing subgrade
shall be inspected by the Contractor’s Geotechnical Engineer
and any areas deemed soft, unstable or unsuitable by the
Geotechnical Engineer shall be excavated and replaced as
described above.
The footing shall be constructed as shown on the drawings.
It could be shown as compacted roadbase or concrete. For
concrete, the footing shall be poured to the correct level using
formwork edge boards, or other methods which ensure the
correct level of the footing. The concrete footing shall be
screeded flat. The level of the footing or first course of blocks
shall be verified by survey methods, and approved by the
Contractors QA representative. This shall be deemed a
WITNESS POINT.
5.2 Unit Installation
Foundations and all courses are laid level. Batters are achieved
by inserting the fibreglass connecting pins into the appropriate
holes. The Keystone retaining walls shall be constructed with
batters as shown on the drawings.
First course of units shall be placed side by side on the base
levelling pad. Units shall be levelled side to side and front to
back and checked for alignment. The accurate placement of
the first course is most important, to ensure acceptable
horizontal and vertical tolerances. Two fibreglass connecting
pins shall be inserted into the appropriate holes to interlock
and align units.
The front set of pin holes shall be used for near vertical
setback.
The rear pair of holes shall be used for 25mm (1:8) setback.
All voids in units and between units shall be filled with
drainage fill as specified in section 4.5. Drainage fill shall
extend to 300mm behind units.
Units shall be placed in a running bond pattern. Top of units
shall be swept clean of excess material. Kidney holes of units
above shall be positioned over pins in units below. Units shall
be pulled toward the face of the wall to interlock the pins
with units on either side. Levels and alignment of each course
shall be checked. Each course shall be filled, backfilled and
compacted prior to placement of the next course. The Keystone
wall shall be surveyed for vertical level tolerance every 3
courses. This shall be deemed a HOLD POINT.
5.3 Drainage Installation
The drainage measures shall be installed as shown on
drawings. 100mm diameter agricultural pipe shall be used
for subsoil drainage behind the first course of Keystone units.
The subsoil drain shall be placed with a minimum 1% fall as
shown on drawings.
‘T’ piece connection fittings shall be used at all outflow points
to connect the subsoil drainage to a 100mm diameter pipe
stub which extends 300mm past the face of the Keystone
wall. The pipe stub material shall be UPVC or HDPE and shall
be approved by the project Superintendent.
The outflow points shall be at a maximum of 60m centres.
The locations of the outflow points shall be determined by
the Superintendent. The outflow pipe stub shall be supported
on the concrete footing, and shall pass between two Keystone
units with 60mm of the facing removed by sawcutting. The
gap above the pipe in the first course shall be neatly patched
with cement mortar.
The drainage measures shall be inspected by the QA
representative after the installation of the first and second
course is complete. Inspection and approval of the drainage
installation shall be deemed a HOLD POINT.
E18 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
5.4 Placement of Geogrid
The Geogrid shall be placed between Keystone units as
specified on the drawings. Geogrids shall be cut to the
required length. Geogrids may be longer than required, but
shall not be shorter than the specified length shown on the
drawings.
The Geogrids shall be placed with the roll direction
perpendicular to the face of the Keystone wall. Correct
orientation of the geogrids shall be verified by the Contractor.
After compaction, the layer of select backfill below each geogrid,
shall be raked to a depth of 25mm to ensure good interlock
between the geogrid and the select backfill. The Geogrid shall
be laid horizontally on compacted backfill and connected to
the Keystone units by hooking geogrid over the fibreglass
pins. The geogrid shall be pulled taut against pins to eliminate
slack from connections and loose folds. The back edge shall
be staked or secured prior to backfilling to maintain tension
in the geogrid. Each block shall be checked for level accuracy,
as out of position transverse bars will lead to sloping blocks.
If the course above a layer of geogrid is found to be not level,
then the blocks shall be removed, and the geogrid repositioned
to ensure levelness.
For a straight length of wall, the geogrids shall be laid side
by side without joints or overlaps. Where the wall is convex,
the geogrids shall not be cut, but shall be overlapped with a
minimum of 75mm of compacted fill between them. For a
concave wall the position of the layers of grid shall be
alternated between consecutive geogrid layers to cover the
triangular gaps between strips of geogrid. Refer to Fig 5.4.
The QA Representative shall inspect and keep records of the
position of grid and the type of grid placed for each layer of
geogrid. The number of courses between each successive
layer of geogrid shall be noted. The QA Representative shall
also check this. This shall be deemed a WITNESS POINT.
5.5 Placement of Reinforced Soil Backfill
Prior to placement of ‘Approved Backfill’ in the reinforced soil
block, the Geotechnical Engineer shall approve the material
and confirm that the friction angle and dry density of the
material is in accordance with the drawings for that particular
section of the project. This shall be deemed a HOLD POINT.
All backfill imported or otherwise shall be as specified on
the drawings. Backfill shall be spread in a maximum of
200mm layers, in such a manner that minimises the voids
directly underneath the geogrid. Fill should be deposited
using suitable plantwhich causes fill to cascade onto geogrids.
Placement of fill on top of the geogrids shall start from the
wall face and work back from the wall face in order to minimise
slack or loss of pretension from the grid. Care should be taken
to not mix the reinforced soil block backfill material with the
drainage material. If backfill material mixes with the drainage
material, then the drainage material is to be removed and
replaced with clean material.
Compaction shall be to 98% of Standard Maximum Dry
Density. Compaction shall start at the wall face and work
back from the wall face. Compaction testing shall be in
accordance with section 6 specified herein. Compaction testing
shall be deemed a WITNESS POINT.
Tracked construction equipment shall not be operated directly
on the geogrid. A minimum thickness of 150mm of backfill
material shall be placed prior to the operation of tracked
construction equipment. Rubber tyred equipment may pass
over the geogrids at very slow speeds. Sudden braking or
sharp turning shall be avoided to prevent displacement of
geogrids.
Construction plant and all other vehicles having a mass
exceeding 1000kg shall be kept at least 1m from the back of
the Keystone units. Compaction of the 1m zone behind the
Keystone units shall be restricted to:
• Vibrating rollers with a mass < 1000kg
• Vibrating plate compacters with a mass < 1000kg
• Vibro tampers having a mass < 75kgWall Face
Geogrid
Fig 5.4 – Typical Geogrid Layout
E19BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 E
Surface drainage during and after construction of the wall
shall be provided to minimise water infiltration in the
reinforced soil zone.
5.6 Hold and Witness Points
The following shall be deemed a HOLD POINT:
• Approval of foundation material by the Geotechnical
Engineer.
• Inspection and approval of ‘Approved Backfill’ for use in
reinforced soil block by the Geotechnical Engineer.
• Survey of the Keystone Wall every 3 courses.
• Inspection and approval of the drainage installation by the
QA Representative.
The following shall be deemed a WITNESS POINT:
• Survey verification that the first course is installed at the
correct level, and inspection and approval of footing by
the QA Representative.
• Inspection of level and type of geogrid at each layer by the
QA Representative.
• Compaction Testing by the Geotechnical Engineer.
6. Material Testing
6.1 Testing of ‘Approved Backfill’
Each source of ‘Approved Backfill’ shall be pretreated by 5
cycles of repeated compaction, and then tested for dry density
and friction angle. Material for use as ‘approved backfill’ shall
be inspected and approved for use by the Geotechnical
Engineer. A stockpile at least equivalent to 5 days reinforced
soil wall construction shall be maintained on site at all times.
This will allow time for friction angle testing of the approved
backfill should visual inspection of the material when it is
received on site indicate that testing is required.
Notwithstanding the above the following minimum testing
shall be carried out:
• Dry Density shall be tested at a frequency of 1 test per
400m3 of approved backfill.
• Friction angle shall be tested at a frequency of 1 test per
2000m3 of approved backfill.
If the dry density results are not within ±5% of the specified
design value, then the Engineer shall be notified, and the
material not approved for use until the design has been
verified.
6.2 Testing for Compaction
Compaction will be checked by standard maximum dry density
test and field density test for materials other than sand or by
the density index and field density tests for sands as specified
on drawings and herein.
Tests will be carried out in groups of at least three, and
compaction of the layer concerned will be considered to be
satisfactory if no single result falls outside the specified
density range. Should the results not reach this standard the
Sub-Contractor shall again roll the area, if necessary after
scarifying, adding water, blading to reduce the moisture
content and/or removing and replacing excessively moist fill
as may be required.
Should the Geotechnical Engineer consider that the depth of
insufficiently compacted material is greater than can be
effectively compacted from the surface, material shall be
removed to a depth at which compaction is satisfactory and
replaced and compacted in 200mm maximum layers.
The standard maximum dry density referred to herein for
materials other than sand shall be maximum standard dry
density as determined in accordance with AS1289 - Test
numbers 5.1.1.
The modified maximum dry density referred to herein for
materials other than sand shall be the maximum modified
dry density as determined in accordance with AS1289 - Test
5.2.1.
The field density referred to herein for all materials shall be
the dry density of the material in place as determined in
accordance with AS1289 - Test 5.3.1
The percentage of the standard maximum dry density (Dry
Density Ratio) elsewhere herein for materials other than sand
shall be calculated from the formula given in AS1289.5.4.1.
The maximum and minimum densities of cohesionless
materials shall be determined in accordance with AS1289 -
Test E5.1
The Density Index specified elsewhere herein for sands shall
be calculated from the formula given in AS1289.E6.1.
6.3 Frequency of Testing
The following testing frequencies relate to acceptance on a
‘not-one-to-fail’ basis. The testing should be carried out in
essentially randomly chosen locations and at the frequencies
as given below. However, it may be appropriate to undertake
testing in specific locations, based on visual appearance or
past experience.
E20 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 E
Where a test or group of tests is carried out on an area which
has been subjected to essentially the same preparation and
compaction procedures, the whole of this area is considered
to be represented by this test or group of tests. The uniform
area is generally known as a work lot. On this basis, if one
or more tests indicate compliance with the specification has
not been achieved, the whole of the area which has been
submitted for testing is deemed not to comply, unless it can
be demonstrated that the area in which the non-complying
test result(s) can reasonably be separated from the whole. It
should not be assumed a test result applies only to the area
immediately surrounding it.
Required frequency of testing, is not less than 1 test per layer
of 200 mm thickness per material type per 400m3 which is
1 test per layer per 100 linear metres of wall construction. If
different sources of ‘approved backfill’ are used within the
100 linear metre work lot, then 1 test per type of material is
required. If the work is staged in sections of less than 100
linear metres, then 1 test per section is required.
The testing frequency may be re-assessed to the approval of
the Engineer, if a high degree of uniformity becomes evident
during construction.
SEGMENTAL BLOCK RETAINING WALLS VICTORIA BOOK 4
F CUSTOM ENGINEERED WALLS
444F44Masonry Design Guide
BORAL MASONRY
Build something great™
F2 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 F
Engineered
Retaining Wall Systemsfor domestic and commercial landscaping, roadside
and custom engineered retaining wall applications
Boral Keystone, Pyrmont and Keysteel Retaining WallSystems provide a proven and versatile platform for thedevelopment of custom engineered high performanceretained earth structures.
Boral has developed alliances with a number of suitablyexperienced engineering companies that can provideprofessional assistance with the custom design andinstallation of Keystone, Pyrmont and Keysteel retainingstructures.
Please contact Boral Masonry in your region for assistancewith your high performance, engineered retaining wallprojects.
F3BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 F
Keysteel Custom Engineered
Retaining Wall Systems
• Keysteel™ Custom Engineered Retaining
Wall Systems
Boral Keysteel is a high performance engineeredretaining wall system for applications requiring wallheights in excess of 6m and/or where critical surchargeloadings are present. Boral Keysteel is an internationallyproven system that integrates the superior strengthand durability of Keysteel blocks with steel-ladder soil-reinforcement to provide engineered solutions for themost demanding retaining structures.
• Gravity Retaining Walls
• Mass Gravity Retaining Walls
• Geogrid Reinforced-Soil Retaining Walls
• Steel-Ladder Reinforced-Soil Retaining Structures
• Bridge Abutments
• Stream or Drainage Channels
• Erosion Prevention
• Tunnel Access Walls
• Wing Walls
• Embankment Stabilisation
• Terraced Walls
• Seawall Applications
• Soil-Anchor & Rock-Anchor Walls
• Fencing, Railings & Barriers
F4 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 F
INTRODUCTION
Boral Keysteel is an internationally
proven, high performance retaining
wall system that integrates the
superior strength of Keysteel blocks
with steel-ladder soil-reinforcement,
and is ideally suited to retaining
structures in excess of 6m high and
for critical surcharge loadings.
DESIGN CONSIDERATIONS
Boral Keysteel installations are
individually engineered to match the
application criteria.
Boral has developed alliances with
a number of suitably experienced
engineering companies which can
provide professional assistance with
the design and installation of
Keysteel retaining structures.
Please contact Boral Masonry
Technical Services in your region for
assistance with Keysteel projects.
COLOURS
Boral Keysteel is made-to-order in
the same range of colours as
Keystone, allowing integration of the
two products within the one project.
Please refer to colour swatch
information for an indication of
current colours.
Keysteel®
High Performance EngineeredRetaining Wall Systems
Standard Straight Sided Cap
275
100
455
Flushface Straight Sided Cap
275
100
455
Steel Pins(hot-dip galvanised)
Lifting Bars
Description Wt kg Nº/m2
Standard Unit 36 11
Standard Straight Sided Cap 25 2.2/lin mtr
Flushface Unit 39 11
Flushface Straight Sided Cap 26.3 2.2/lin mtr
Pins (steel) 2 pins per full unit
hot-dip galvanised steel
Lifting Bars (Keysteel units should be lifted by
two people using the Keysteel lifting bars)
Specifications
305
200
455
Standard Unit
305
200
455
Flushface Unit
Availability & Colours• All Keysteel products are made-to-order.
• Lead times apply Please consult with the Boral Masonry
sales office in your region.
Bluestone Brown
Sunset Terracotta
Natural Parchment
Charcoal
F5BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 F
Typical Keysteel® Application Layout
Keystone unit
Pylon
Cut ladder around pylon Where piles prevent installation of ladders refer to engineers detail.
Keysteel unit
Keysteel unit
Soil reinforcementladder
Wall face
Keysteel unit Soil reinforcingladder
Fig F1 – Typical Construction Detail – Keysteel wall
Fig F2 – Typical Curved Wall Detail – Keysteel Fig F3 – Typical Straight Wall Detail – Keysteel
F6 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 F
Finished grade Threaded pipe coupling
Footing step (optional)
Galvanised pipe
Top of wall stepped (optional)
Keystone unit
Granular backfillGeogrid (if required)
Stiff firm soil
Galvanised steel pipe
Soil anchors
Galvanised pipe loop connector
Galvanised pipe,loop connector and soil anchors (staggered installation)
1200mm cts nominal
TYPICAL PLAN VIEW
TYPICAL WALL ELEVATION
Keystone unit
Geogrid
Galvanised steel pipe
Loop connector
Granular fill
Soil anchor todesign details
TYPICAL CONNECTION DETAIL
Cap unit
Keystone units
Soil anchors to site specific design
Soil failure plane
5˚
Stiff firm soil
Finished grade
Leveling pad to engineer's detail
Drainage pipe
See connection detail
300mmnominal
TYPICAL SIDE ELEVATION
1
8
Typical Soil-Anchor Application
Fig F4 – Typical Soil-Anchor Detail
F7BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 F
Temporary face support and drainage system
Finished grade Footing step
Reinforcing barto design details
Geogrid Soil Anchor todesign details
Top of wall stepped (optional)
Keystone unit
Reinforcing bar to project specifications Geogrid to project
specifications Concrete backfillDrainage net
Rock anchors
Expansion joint materialto design details TYPICAL PLAN VIEW
TYPICAL WALL ELEVATION
Keystone cap
Keystone unit
Horizontal reinforcing bar to design details
Vertical reinforcing bar to design details
Concrete backfill to design detail
Geogrid at 600mm vertical centres extended to wall face between reinforcing barRock anchor
system to design details
Granular material wrapped in geotextile
Temporary concrete and mesh facing support system with drainage to design details
Drainage netto design details
Finished grade
Levelling pad
Drainage pipe
1
8
See anchorage detail
1500mmtypical
300mmnominal
TYPICAL SIDE ELEVATION
Keystone unit
Geogrid
Reinforcing barto design detail
Thread bar todesign details
Steel plate and securing nuts to design detail
Concrete backfill
Rock anchorto design detail
TYPICAL ANCHORAGE DETAIL
Typical Rock-Anchor Application Layout
Fig F5 – Typical Rock-Anchor Detail
F8 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 F
Engineering
All water application projects should be designed by a suitably
qualified engineer. The Keystone Retaining Wall System has
been used in numerous international projects where the
blocks are subjected to high velocity flood water, wave action
and tidal action.
Spacing of Geogrid
As with all geogrid soil reinforced Keystone walls, the spacing
of the geogrid should not exceed 600mm, to prevent bulging
between the grid layers.
Suitability of Keystone Blocks in a SeawallApplication
It is recommended that if the Keystone units are submerged
in salt water, then marine grade Keystone units should be
used. Minimum order quantities apply to these units.
NOTE: Product colours will be different due to the use of
marine grade cement.
Typical1900mm
Keystone Cap Unit
Filter Fabric
Keystone block
Nonwoven filter fabric
Geogrid as per design
Water level
Free draining granular material (less than 10% passing the #200 sieve, no organic material)
10-20mm crushed rock, fill cores and voids of Keystone units
Native soil
Impermeable soil layer 300mm
Compacted aggregate or crushed rock
150mm min.
600mm min.
150 - 200mmrip-rap
Fig F6 – Typical Construction Detail – Keystone Seawall Application
Undermining of Foundation Wall
Greater embedment of units, concrete footings (piered or
otherwise), Keystone units keyed to a concrete foundation
are all means of preventing undermining of the wall
foundation. Rip-Rap in front of the wall will also help to prevent
erosion.
Loss of Material through Wall Face
Filter fabric used behind the 300mm drainage layer will
prevent loss of retained soils during fluctuation in water level.
Differential Water Pressures
Fluctuations in water levels and rapid draw down may induce
differential water pressures across the face of the wall and
need to be addressed.
Test Reports
Tests have been carried out on the high velocity flow effects,
wave action and sudden draw down and Manning’s ‘n’
determination. These test results are available on request.
Typical Seawall Application Layout
F9BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 F
When terracing walls, they are effectively being split into
sections. This is done for a number of reasons. For example,
to level off a sloping front or backyard, to increase the aesthetic
appeal of the garden and in some instances to reduce the
single wall heights where by they still act as gravitywalls and
thus minimise the need for geogrid. In such instances,
however, the upper terrace wall can put pressure on the lower
terrace if the walls are too close together. Multiple terrace
walls in close proximity to each other, can have structural
stability issues related to the lower walls not having the
capacity to carry the loads developed by the upper walls.
Question:
How far apart do the terrace walls have to be to perform as
individual gravity walls?
Answer:
As a rule of thumb, the minimum distance between the wall
terraces must be at least 1.5 times the height of the lower
wall.
Example:
Cap unit
Keystone or Pyrmont wall
Keystone or Pyrmont wall
L = 1.5 x (H1)
L = minimum distance between terraces
H 2
H 1
Fig F7 – Typical Construction Detail – Terraced Wall Application
If the lower gravity wall is 1.2m tall, then the minimum
recommended spacing between terraces is 1.8m. This rule
also applies to walls with more than two terraces. The distance
between any two terraces must be at least twice the height
of the lower adjacent terrace wall for multiple terraces.
NOTE: This simple rule of thumb does not address global
stability issues where walls are built on steep slopes or over
poor soils of low friction strength. If these conditions exist,
then contact your engineer.
Question:
What if there isn’t enough room to space the terraces
according to this rule (1.5 x H1 minimum)?
Answer:
The wall can still be built, but the effect of the upper terrace
on the lower terrace and overall stability must be taken
into account when designing the walls. When the terraces
are close together, the design analysis may model the
structure as a single taller wall to account for the added
load from the upper terrace wall on the lower walls.
Typical Terraced Wall Application Layout
F10 July 2005 | BORAL MASONRY DESIGN GUIDE
Victoria Book 4 F
Fences can be incorporated into the Keystone Retaining Wall
System by placing fence posts into the Keystone cores or
behind the wall.
NOTE: The following recommendations are suitablefor fences with no wind loadings.
Fence posts should be embedded through a minimum of
three courses (600mm minimum) and then core filled with
concrete. Only those units with the fence posts need to be
core filled with concrete, the remaining filled with drainage
material.
Fence posts positioned behind the wall should be embedded
700mm minimum and encased in concrete.
When constructing a soil reinforced wall, the Geogrid may
be cut to allow for placement of fence posts as per the Geogrid
manufacturer specifications.
It is important that these walls be designed to accommodate
any additional wind loads from fencing (eg. extra embedment).
700mm
900mm
1824mm max.
Fig F8 – Typical Fencing Detail
Typical Fencing Application Layout
F11BORAL MASONRY DESIGN GUIDE | July 2005
Victoria Book 4 F
Railing, guard rail, and traffic barrier requirements for
retaining walls are not clearly defined in design codes nor
are they properly addressed in many site plans. Many times
railings and barriers are added as an afterthought which can
become a costly and logistical issue when no provisions are
made in the original retaining wall layout and site design.
Guards and barriers require a common sense approach by
the site designer considering the proximity of a wall structure
to people and traffic. Sufficient space must be reserved for
such installations.
It is important that these walls be designed to accomodate
any additional loading these guards and barriers may impose
on the Keystone wall.
Typical 800mm
Guardrail Traffic Barrier
Load
1000mm min.
Load
Typical 900mm
150mm
Typical 900mm
Railing – offset Railing – offset
Load Load
900mm min.
Additional Geogrid layer turned upwards and wrapped around void former at 400mm below ground level
Fig F9 – Railing & Barrier Details
Typical Railing & Barrier Application Layout
July 2005
Other Regional Sales Offices
NSW Clunies Ross Street, Prospect, 2148 T: (02) 9840 2333
F: (02) 9840 2344
ACT 16 Whyalla Street, Fyshwick, 2609 T: (02) 6239 1029
F: (02) 6280 6262
South Australia Main North Road, Pooraka, 5095 T: (08) 8262 3529
F: (08) 8260 3011
Queensland 62 Industrial Ave, Wacol, 4076 T: (07) 3271 9292
F: (07) 3271 1581
North Queensland:
Cairns 8 Palmer Street, Portsmith, 4870 T: (07) 4035 1888
F: (07) 4035 1208
Townsville 360 Bayswater Road, Garbutt, 4814 T: (07) 4725 6285
F: (07) 4725 6043
Mackay David Muir Street, Slade Point, 4740 T: (07) 4955 1155
F: (07) 4955 4130
Customer Support Victoria
1. Stock colours Colours other than stock colours are made to order. Not all colours displayed in this brochure are available in all states.
(Contact your nearest Boral Masonry office for your area’s stock colours.) A surcharge applies to orders less than the set minimum
quantity.
2. Brochure colours The printed colours in this Masonry Design Guide are only a guide. Please ask to see a sample of your colour/texture
before specifying or ordering.
3. Colour and texture variation The supply of raw materials can vary over time. In addition, variation can occur between product types and
production batches.
4. We reserve the right to change the details in this publication without notice.
5. For a full set of Terms and Conditions of Sale please contact your nearest Boral Masonry sales office.
6. Important notice Please consult with your local council for design regulations prior to the construction of your wall. Councils in general
require those walls over 1m in height and/or where there is loading such as a car or house near the wall be designed and certified by a
suitably qualified engineer.
Orders, Product Samples and Sales Enquires
Victoria Level 1 Port IT, 63-85 Turner Street, Port Melbourne, 3207 T: (03) 9363 1944
F: (03) 9363 6008
Technical Enquires
Specifier Line 1300 360 255
Internet www.boral.com.au/masonry
® Heathstone and Pyrmont are registered trademarks of Boral Masonry Limited.
® Keystone and Gardenwall are each registered trademarks of Keystone Retaining Wall Systems, Inc.
under licence by Boral Masonry Limited. ABN 13 000 223 718
© Boral Masonry - all rights reserved 2004.