COVER PAGE REVISIONS DATE ENGR STD COMM 0 3/9/2020 T.D. 3/5/2020 CAD FILE: JU-001 TO BE USED IN CONJUNCTION WITH THE POLE ATTACHMENT LICENSE AGREEMENT (PALA) AND JOINT USE RULES AND REGULATIONS (JURR) MASON PUD 3 JOINT USE ATTACHMENT STANDARDS JOINT USE ATTACHMENT STANDARDS Y:Engineering / Standards, Specifications & Manuals / Specifications / Joint Use NOTE: STANDARDS COMMITTEE APPROVED JOINT USE ATTACHMENT STANDARDS WITH EDITS ON 3/5/2020, DRAWINGS UPDATED ON 3/9/2020

MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

COVER PAGE

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

TO BE USED IN CONJUNCTION WITH THE POLE

ATTACHMENT LICENSE AGREEMENT (PALA) AND

JOINT USE RULES AND REGULATIONS (JURR)

MASON PUD 3 JOINT USE ATTACHMENT

STANDARDS

JOINT USE ATTACHMENT

STANDARDS

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

NOTE: STANDARDS COMMITTEE APPROVED JOINT USE ATTACHMENTSTANDARDS WITH EDITS ON 3/5/2020, DRAWINGS UPDATED ON 3/9/2020

Page 2: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

PAGE:1

21of

ALL CLEARANCES BETWEEN CONDUCTORS AND COMMUNICATION EQUIPMENT SHALL MEET THE

MINIMUM REQUIREMENTS OF THE LATEST EDITION OF THE WASHINGTON ADMINISTRATIVE CODE

(WAC) 296, THE NATIONAL ELECTRIC SAFETY CODE (NESC), THE NEC (NATIONAL ELECTRIC CODE),

JOINT USE RULES AND REGULATIONS (JURR), THIS STANDARD, AND GOVERNING AGENCY.

DISTRICT, PUD 3 - MASON PUD 3

LICENSEE - A COMMUNICATION COMPANY LICENSED IN THE STATE OF WASHINGTON THAT HAS SIGNED A POLE

ATTACHMENT LICENSEE AGREEMENT (PALA) WITH MASON PUD 3.

ATTACHMENT - PER RCW 54.04.045(1)(A), MEANS THE AFFIXATION OR INSTALLATION OF ANY WIRE, CABLE, OR

OTHER PHYSICAL MATERIAL CAPABLE OF CARRYING ELECTRONIC IMPULSES OR LIGHT WAVES FOR THE

CARRYING OF INTELLIGENCE FOR TELECOMMUNICATIONS OR TELEVISION, INCLUDING, BUT NOT LIMITED TO

ANY RELATED DEVICE, APPARATUS, OR AUXILIARY EQUIPMENT ATTACHED TO ANY POLE OWNED OR

CONTROLLED IN WHOLE OR IN PART BY THE DISTRICT.

SUPPLY SPACE - THE SPACE USED ON JOINT-USE POLES WHERE SUPPLY FACILITIES ARE SEPARATED FROM

THE COMMUNICATION SPACE BY THE COMMUNICATION WORKER SAFETY ZONE.

COMMUNICATION WORKER SAFETY ZONE - ALSO REFERRED TO AS 'SAFETY ZONE' OR 'SAFETY SPACE' IS THE

VERTICAL SPACE ON A POLE SEPARATING THE SUPPLY SPACE FROM THE COMMUNICATION SPACE. THIS

SPACE IS INTENDED TO PROVIDE A SAFE WORKING CLEARANCE FOR WORKERS IN THE COMMUNICATION

SPACE (SEE WAC 296-45 AND NESC 235).

COMMUNICATION SPACE - THE SPACE USED ON JOINT-USE POLES WHERE COMMUNICATION FACILITIES ARE

SEPARATED FROM THE SUPPLY SPACE BY THE COMMUNICATION WORKER SAFETY ZONE.

COMMUNICATION CABLE - A WIRE, CABLE, OR OTHER PHYSICAL MATERIAL CAPABLE OF CARRYING

ELECTRONIC IMPULSES OR LIGHT WAVES FOR THE CARRYING OF INTELLIGENCE FOR TELECOMMUNICATIONS

OR TELEVISION.

NOTE: A REVISION BAR WILL BE USED ON THE LEFT SIDE OF THE PAGE TO SHOW CHANGES.

1. REFERENCE STANDARDS

2. DEFINITIONS

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 3: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

PAGE:2

21of

3.1 CABLES AND GUYS

GROUND CLEARANCES SHALL BE BASED ON CALCULATED WORST CASE DESIGN CONDITIONS (INITIAL AND FINAL

TEMPERATURE, ICE & WIND) PER NESC.

COMMUNICATION CABLES SHALL BE ATTACHED TO THE SAME SIDE OF THE POLE AS THE POWER NEUTRAL

CONDUCTOR. IF THE POWER NEUTRAL CONDUCTOR IS ON A PRIMARY CROSSARM, COMMUNICATION CABLES

SHALL BE INSTALLED ON THE ROAD SIDE OF THE POLE. ADDITIONAL CABLES AND CLIMBING SPACE MAY BE

ACCOMMODATED BY THE USE OF OVERLASHING AS DESCRIBED IN THE JOINT USE RULES and REGULATIONS.

ALL COMMUNICATION CABLES SHALL HAVE CABLE MARKERS ATTACHED TO THE CABLE THAT IDENTIFY THE OWNER

OF THE CABLE AND EMERGENCY CONTACT INFORMATION LOCATED WITHIN SIX INCHES OF THE POLE (SEE FIGURE

3.4.2).

COMMUNICATION CABLES SHALL BE TENSIONED AND GUYED IN A WAY THAT DOES NOT ADVERSELY WEAKEN THE

POLE OR ALTER THE PLUMB OF THE POLE OR CHANGE THE SAG CHARACTERISTICS OF POWER CONDUCTORS.

COMMUNICATION CABLES SHALL BE ADEQUATELY GUYED TO WITHSTAND ALL TENSIONS ATTRIBUTED TO THE

ATTACHMENT UNDER APPLICABLE NESC WIND AND ICE LOADING CONDITIONS.

THE LICENSEE SHALL PROVIDE THEIR OWN ANCHOR FOR COMMUNICATION GUYS AND MAINTAIN AT LEAST SIX

FEET SEPARATION FROM EXISTING DISTRICT ANCHORS. COMMUNICATION GUYS MAY BE ATTACHED TO DISTRICT

ANCHORS ONLY WITH WRITTEN PERMISSION AND ONLY IF GUY STRAIN INSULATORS ARE USED. LOAD

CALCULATIONS MUST BE PROVIDED FOR DISTRICT REVIEW. ENGINEERING EVALUATION COSTS COULD BE

CHARGED. REFER TO EXHIBIT 'A' JOINT USE RATE / FEE SCHEDULE.

3.2 POLE DRILLING

ANY HOLE FIELD DRILLED IN A POLE MUST BE TREATED BY DRENCHING WITH HIGH STRENGTH PENTA

CHLOROPHENOL (PENTA) SOLUTION OR HIGH STRENGTH COPPER NAPHTHENATE (CU NAP) SOLUTION. CLASS 1 OR

H1 POLES ALSO REQUIRE FIBER WASHERS IMPREGNATED WITH APPROPRIATE PRESERVATIVE MATERIAL.

3.3 CABLE MOUNTING

THROUGH BOLT ENDS SHALL NOT PROTRUDE MORE THAN TWO INCHES BEYOND THE NUT. ATTACHMENTS TO

STEEL POLES SHALL BE BOLTED USING GALVANIZED HARDWARE. BANDING ATTACHMENTS TO STEEL POLES IS

NOT PERMITTED. GALVANIZED SURFACES DAMAGED DURING ATTACHMENT SHALL BE RECOATED PER

MANUFACTURES SPECIFICATIONS. BANDING TO WOOD POLES IS ONLY ACCEPTABLE FOR DECORATIVE OBJECTS

(SEE 3.8 FOR DECORATIVE OBJECT AGREEMENT DETAILS).

NOTE: STANDARDS COMMITTEE APPROVED ENTIRE DOCUMENT WITH THE EXCEPTION OF SECTION 3.3. REQUEST

FOR BREAK AWAY HARDWARE TO BE EVALUATED.

3. GENERAL ATTACHMENT REQUIREMENTS

PAGE:

of

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 4: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

ROAD

SIDE

RISERS

FIELD

SIDE

FIGURE 3.4.1

6

"

M

I

N

FIGURE 3.4.2

8'-10'

6" MIN

COMMUNICATION

MESSENGER

COMMUNICATION

SPACE

COMMUNICATION WORKER SAFETY

ZONE

JUST ABOVE

GROUND LEVEL

BONDING

REQUIRED

3.4 RISERS

ON PRIMARY POLES, COMMUNICATION CABLES INCLUDING SERVICE DROPS TRANSITIONING FROM OVERHEAD TO

UNDERGROUND SHALL BE INSTALLED IN RISER CONDUITS ON STANDOFF BRACKETS. LICENSEE RISERS SHALL BE

INSTALLED AS SHOWN IN FIGURE 3.4.1. ALL COMMUNICATION CABLES, INCLUDING SERVICE DROPS, EXCEPT THE

POLE GROUND SHALL BE INSTALLED IN CONDUIT AND MOUNTED ON 15 INCH STANDOFF BRACKETS TO PROVIDE A

MINIMUM SIX INCH CLEARANCE FROM THE POLE. EXISTING STANDOFF BRACKETS SHALL BE USED WHEN

AVAILABLE.

IF NEW STANDOFF BRACKETS ARE NEEDED, THE LICENSEES SHALL PROVIDE AND INSTALL STANDOFF BRACKETS

APPROVED BY THE DISTRICT. LOWER STANDOFF BRACKETS SHALL BE SPACED EIGHT FT - TEN FT APART. THE TOP

STANDOFF BRACKETS MAY HAVE CLOSER SPACING. (SEE FIGURE 3.4.2)

10' SCHEDULE 80 PVC

3. GENERAL ATTACHMENT REQUIREMENTS (CONTINUED)

SCHEDULE 40 PVC

LOCATION OF

APPROVED CABLE

MARKER

PAGE:3

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 5: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

3.5 ENCLOSURES

POLE MOUNTED LICENSEE POWER SUPPLIES AND OTHER MISCELLANEOUS CABINETS AND ENCLOSURES ARE NOT

ALLOWED FOR NEW APPLICATIONS. PLACE THESE A MINIMUM OF SIX FEET AWAY FROM BASE OF POLE OR PER

REGULATORY AGENCY REQUIREMENTS.

MAXIMUM RISER DIAMETER IS TWO INCHES, UNLESS APPROVED BY THE DISTRICT.

POWER SUPPLIES SHALL BE DESIGNED FOR 120 VOLT, 15 AMP SINGLE PHASE SERVICE.

ELECTRIC SERVICE FOR ANY EQUIPMENT THAT IS NOT A SELF CONTAINED POWER SUPPLY SHALL BE SERVED BY A

DISTRICT INSTALLED UNDERGROUND SERVICE PEDESTAL OR OVERHEAD SERVICE DROP, PER CURRENT DISTRICT

RATES AND SERVICE POLICIES.

A STATE ELECTRICAL INSPECTION SHALL BE OBTAINED PRIOR TO DISTRICT CONNECTION OF ANY POWER SUPPLY.

BATTERY PACK POWER SUPPLIES AND POWER SUPPLIES THAT MAY BE POWERED BY PORTABLE GENERATORS

DURING OUTAGE CONDITIONS MUST BE EQUIPPED WITH FEEDBACK VOLTAGE PROTECTION.

3.6 BONDING AND GROUNDING

CONDUCTIVE MESSENGERS AND COMMUNICATION GUYS SHALL BE BONDED AND CONNECTED TO DISTRICT POLE

GROUND WITHIN THE COMMUNICATION SPACE WHEN DISTRICT POLE GROUNDS ARE PRESENT. THE POLE GROUND

SHALL NOT BE CUT OR DAMAGED WHEN CONNECTING LICENSEE GROUNDS.

IF A GROUND IS NEEDED AND NO DISTRICT POLE GROUND IS AVAILABLE, THE LICENSEE SHALL INSTALL THEIR

GROUND AND EXTEND A #6 SOLID SOFT DRAWN COPPER GROUND WIRE UP TO THE TOP OF THE COMMUNICATION

SPACE, LEAVING SUFFICIENT GROUND WIRE COILED TO REACH AND CONNECT TO THE DISTRICT'S NEUTRAL.

IMMEDIATELY NOTIFY THE DISTRICT OFFICE AT (360) 426-0888 THAT THE GROUND WIRE IS READY FOR CONNECTION

AND THE DISTRICT WILL EXTEND AND CONNECT THE GROUND WIRE TO THE DISTRICT'S NEUTRAL.

NOTE: NON-METALLIC/NON-CONDUCTIVE SELF-SUPPORTING MESSENGER (ADSS) DOES NOT REQUIRE BONDING AND

GROUNDING.

3. GENERAL ATTACHMENT REQUIREMENTS (CONTINUED)

PAGE:4

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 6: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

ROADWAY

GROUND

-NO VEHICLE ACCESS-

FIGURE 3.7.1

15' - 18'

3.7 DECORATIVE OBJECT ATTACHMENTS

ALL DECORATIVE FOREIGN ATTACHMENTS SUCH AS HANGING FLOWER BASKETS, BANNERS, OR

CHRISTMAS LIGHTS SHALL REQUIRE A SEPARATE AGREEMENT.

DECORATIVE OBJECTS SHALL BE MOUNTED BETWEEN 15 TO 18 FEET ABOVE GROUND AND SHALL

EXTEND NO FARTHER THAN 42 INCHES AWAY FROM THE POLE. MAXIMUM ALLOWABLE WEIGHT OF

DECORATIVE OBJECT AND MOUNTING BRACKET IS 50 lbs. DECORATIVE OBJECTS SHALL NOT

OVERHANG THE ROADWAY. BANNERS OR OTHER OBJECTS SHALL NOT BE STRUNG BETWEEN

DISTRICT POLES OR BETWEEN A DISTRICT POLE AND ANY OTHER SUPPORTING MEMBER. (SEE

FIGURE 3.7.1).

3. GENERAL ATTACHMENT REQUIREMENTS (CONTINUED)

42" MAX

PAGE:5

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 7: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

4.0 CLEARANCE REQUIREMENTS

PAGE:6

of

4.1 PROPER LOCATION OF COMMUNICATION ATTACHMENT (NEW CONSTRUCTION)

THE PROPER LOCATION FOR COMMUNICATION ATTACHMENT MUST ENSURE THAT A COMMUNICATION

WORKER SAFETY ZONE OF 40" HAS BEEN ESTABLISHED.

COMMUNICATION ATTACHMENTS ARE SPACED 12" APART.

IF A DISTRICT COMMUNICATION CABLE IS WITHIN 40" OF: NEUTRAL, SECONDARY, PRIMARY OR ENERGIZED

EQUIPMENT, THEN A COMMUNICATION WORKER SAFETY ZONE HAS NOT BEEN ESTABLISHED. LICENSEE

COMMUNICATION ATTACHMENT MUST BE 30" BELOW DISTRICT COMMUNICATION ATTACHMENT THAT IS

PLACED IN THE SUPPLY SPACE, AND A MINIMUM 40" TO POWER.

THE DISTRICT RESERVES THE FIRST TWO ATTACHMENT LOCATIONS BELOW THE COMMUNICATION

WORKER SAFETY ZONE FOR ITS OWN COMMUNICATION FACILITIES TO BE LOCATED AT 40" AND 52" FROM

LOWEST EQUIPMENT OR POWER. THE FIRST LOCATION FOR LICENSEE ATTACHMENT WILL BE AT 64" FROM

LOWEST EQUIPMENT OR POWER (SEE FIGURE 4.1.1).

4.2 COMMUNICATION CROSSARMS

THE DISTRICT DOES NOT PERMIT COMMUNICATION CROSSARMS ON NEW CONSTRUCTION.

AS A GENERAL RULE, THE DISTRICT DOES NOT PERMIT THE USE OF COMMUNICATION CROSSARMS ON

EXISTING POLES. THE REPLACEMENT OF A POLE VIA MAKE-READY WORK IS THE PRIMARY MEANS OF

GAINING NECESSARY CLEARANCES WHEN ATTACHMENT SPACE IS NOT AVAILABLE.

HOWEVER, COMMUNICATION CROSSARMS MAY BE APPROVED BY THE DISTRICT IN LIMITED SCENARIOS

WHEN THERE IS NO ADDITIONAL VERTICAL SPACE AVAILABLE ON CRITICAL POLES SUCH AS

TRANSMISSION POLES, COMPLEX POLES, OR POLE TOP WIRELESS POLES.

IF A COMMUNICATION CROSSARM IS APPROVED FOR INSTALLATION, THE DISTRICT WILL BE RESPONSIBLE

FOR THE INSTALLATION OF ALL COMMUNICATION CROSSARMS. THIS INSTALLATION WILL BE CONSIDERED

MAKE-READY WORK. ONCE INSTALLED, THE COMMUNICATION CROSSARM WILL BE CONSIDERED A PART

OF THE DISTRICT'S POLE. LICENSEES MAY BE REQUIRED TO RELOCATE THEIR EXISTING ATTACHMENT TO

THE NEW COMMUNICATION CROSSARM TO MEET NESC CLEARANCE REQUIREMENTS.

4.3 DISTRIBUTION CLEARANCES AT SUPPORTS (NEW CONSTRUCTION)

IF THE PRIMARY AND NEUTRAL CONDUCTORS ARE MOUNTED ON A CROSSARM AT THE SAME LEVEL AND

THERE IS NO OTHER SUPPLY EQUIPMENT MOUNTED BELOW THE PRIMARY ARM, THEN THE

RECOMMENDED CLEARANCE BETWEEN THE SUPPLY SPACE AND THE COMMUNICATION SPACE IS 148

INCHES (SEE FIGURE 4.3.1).

21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 8: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

4.0 CLEARANCE REQUIREMENTS (CONTINUED)

TELEPHONE

CATV

HIGHEST LICENSEE

COMMUNICATIONS

EQUIPMENT

40"

64"

52"

FIGURE 4.1.1

PUD 3 FIBER

PUD 3 FIBER

MEASURE FROM LOWEST

SUPPLY EQUIPMENT OR POWER

108"

SEPARATION

SPACE

FIGURE 4.3.1

COMMUNICATION

CABLE

COMMUNICATION

SPACE

PRIMARY

CONDUCTOR

SYSTEM

NEUTRAL

108"

SEPARATION

SPACE

40"

COMMUNICATION

WORKER

SAFETY ZONE

COMMUNICATION WORKER

SAFETY ZONE

COMMUNICATION SPACE

SUPPLY SPACE

PAGE:7

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 9: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

UPPER COMMUNICATION CABLE

138" MIN

DISTRIBUTION PRIMARY CONDUCTORS

30" MIN

UPPER COMMUNICATION CABLE

SECONDARY/SERVICE/NEUTRAL CONDUCTOR

FIGURE 4.4.2

FIGURE 4.4.1

COMMUNICATION

PRIMARY

NEUTRAL

4.0 CLEARANCE REQUIREMENTS (CONTINUED)

4.4 MID-SPAN DISTRIBUTION CLEARANCES (NEW CONSTRUCTION)

MIDSPAN CLEARANCE BETWEEN THE SUPPLY SPACE AND THE COMMUNICATION SPACE AT ANY POINT IN

THE SPAN CANNOT BE LESS THAN 30 INCHES FROM THE SECONDARY / SERVICE / NEUTRAL CONDUCTORS

AND 108 INCHES FROM DISTRIBUTION PRIMARY CONDUCTORS. MID-SPAN CLEARANCES ARE MEASURED

BASED ON THE FINAL UNLOADED SAG AT THE MAXIMUM OPERATING TEMPERATURE OF THE SUPPLY

CONDUCTORS (SEE FIGURES 4.4.1 & 4.4.2).

40" MIN

PAGE:8

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 10: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

4.0 CLEARANCE REQUIREMENTS (CONTINUED)

4.5 TRANSMISSION CLEARANCES

REQUESTS TO ATTACH TO TRANSMISSION POLES THAT HAVE NO UNDERBUILD WILL BE EVALUATED UPON

REQUEST.

4.6 STREET LIGHT CLEARANCES

PROVIDED NESC MINIMUM CLEARANCES ARE MET, STREET LIGHTS MAY BE MOUNTED IN THE

COMMUNICATION WORKER SAFETY ZONE. WHEN STREET LIGHTS ARE MOUNTED ABOVE

COMMUNICATION CABLES, A MINIMUM OF 12 INCHES OF CLEARANCE MUST BE MAINTAINED BETWEEN THE

TOP OF THE COMMUNICATION SPACE AND THE BOTTOM OF THE STREET LIGHT DRIP LOOP. THIS MAY BE

REDUCED TO THREE INCHES IF THE DRIP LOOP IS COVERED WITH A NON-CONDUCTIVE COVERING

(CONDUIT) EXTENDING AT LEAST TWO INCHES BEYOND THE LOOP. A MINIMUM OF 40" OF CLEARANCE

MUST BE MAINTAINED BETWEEN THE TOP OF THE COMMUNICATION SPACE AND THE BOTTOM OF THE

LUMINARY SUPPORT. THIS MAY BE REDUCED TO FOUR INCHES IF THE MAST ARM IS EFFECTIVELY

GROUNDED (SEE FIGURE 4.6.1)

NOTE: COMMUNICATION CABLES WILL NOT BE ALLOWED ABOVE LUMINARY SUPPORT BRACKETS.

LUMINARY SUPPORT

COMMUNICATION CABLE

40" COMMUNICATION

WORKER SAFETY ZONE

12" MIN. IF UNCOVERED

3" MIN. IF COVERED

FIGURE 4.6.1

COMMUNICATION SPACE

SUPPLY SPACE

40" MIN. IF UNBONDED

4" MIN. IF BONDED

PAGE:9

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 11: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

SERVICE DROP

COMMUNICATION

DRIP LOOP

SERVICE ENTRANCE

12" MIN.

SEPARATION

SPACE

8" MIN.

SERVICE DROP

COMMUNICATION

DRIP LOOP

SERVICE ENTRANCE

40" MIN.

COMMUNICATION

WORKER SAFETY ZONE

8" MIN.

4.0 CLEARANCE REQUIREMENTS (CONTINUED)

4.7 SECONDARY POLES AND METER LOOPS

COMMUNICATION CABLES SHALL HAVE A MINIMUM OF 12 INCHES OF CLEARANCE FROM CUSTOMER

DRIP LOOP AT THE POINT OF ATTACHMENT AT THE CUSTOMER SERVICE ENTRANCE ON THE POLE OR

BUILDING PER THE NEC (SEE FIGURE 4.7.1)

COMMUNICATION CABLES SHALL HAVE A MINIMUM OF 40 INCHES CLEARANCE FROM DISTRICT

SECONDARY ELECTRICAL WIRES. IF BOTH CONDITIONS EXIST ON A POLE OR BUILDING, THE MINIMUM

DISTANCE SHALL BE 40 INCHES PER THE NESC WHILE STILL MAINTAINING A MINUMUN OF 12 INCHES

FROM DRIP LOOPS (SEE FIGURE 4.7.2)

J-HOOK FOR SERVICE DROP ONLY

PAGE:10

of 21

DISTRICT

ELECTRICAL

SERVICE DROP

DISTRICT

ELECTRICAL

SERVICE DROP

FIGURE 4.7.1 FIGURE 4.7.2

NEC NESC

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 12: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

4.0 CLEARANCE REQUIREMENTS (CONTINUED)

ROAD

SIDE

COMMUNICATION

DROP WIRES

RISERS

FIELD

SIDE

24" MIN

24" MIN

DROP WIRES

COMMUNICATION

CABLES

COMMUNICATION

FIGURE 4.8.1

SPACE

CLIMBING

4.8 CLIMBING SPACE

TO PROVIDE ADEQUATE CLEARANCES ON THE POLE FOR SAFE CLIMBING BY DISTRICT PERSONNEL, A

CLEAR CLIMBING SPACE OF 24 INCHES BETWEEN COMMUNICATION CABLES AND COMMUNICATION DROP

WIRES MUST BE PROVIDED (SEE FIGURE 4.8.1). THIS SPACE MUST EXTEND 42 INCHES ABOVE AND BELOW

THE HIGHEST AND LOWEST COMMUNICATION CABLES (SEE FIGURE 4.8.2). THE CLIMBING SPACE MAY BE

ROTATED AROUND THE POLE FOR CONTINUED CLIMBING IF THE CLIMBING SPACES IN DIFFERENT

QUADRANTS OVERLAP.

42"

42"

12"

FIGURE 4.8.2

SPACE

CLIMBING

PAGE:11

of 21

CABLES

COMMUNICATION

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 13: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

FIGURE 5.1.1

VARIES

DISTRICT

SUPPLY

SPACE

40"

VARIES

COMMUNICATION

SPACE

COMMUNICATION

WORKER SAFETY

ZONE

EQUIPMENT

5.1 POLE ATTACHMENTS (NEW CONSTRUCTION)

50 FOOT MINIMUM POLES ARE STANDARD FOR NEW

THREE PHASE CONSTRUCTION, 45 FOOT MINIMUM

POLES FOR NEW SINGLE PHASE CONSTRUCTION.

TYPICAL DISTRICT AND COMMUNICATION

ATTACHMENTS ON 50 FOOT POLES ARE SHOWN IN

FIGURE 5.1.1.

35 FOOT MINIMUM POLES ARE STANDARD FOR NEW

SECONDARY ROAD CROSSINGS AND 30 FOOT MINIMUM

POLES ARE STANDARD FOR SAME SIDE OF ROAD

SECONDARY CONSTRUCTION.

SPACE IS RESERVED FOR DISTRICT COMMUNICATION

ATTACHMENTS (RESERVED CAPACITY). NO LICENSEE

ATTACHMENTS SHALL BE MADE WITHIN 64 INCHES OF

NEUTRAL OR LOWEST SUPPLY EQUIPMENT. NO

ATTACHMENTS WILL BE ALLOWED BELOW 18 FEET ON

THE POLE.

A 12 INCH SPACING SHALL BE MAINTAINED BETWEEN

ATTACHMENTS IN THE COMMUNICATION SPACE. NEW

ATTACHMENTS MUST BE MADE BELOW THE DISTRICT

RESERVED CAPACITY AT THE HIGHEST AVAILABLE

POSITION IN THE COMMUNICATION SPACE.

COMMUNICATION SERVICE DROPS SHALL BE

ATTACHED TO THEIR OWN MESSENGER OR CABLE,

AND NOT TO THE POLE. J-HOOKS WILL ONLY BE

ALLOWED ON DISTRICT POLES IF THE COMMUNICATION

SERVICE DROP IS THE ONLY LICENSEE CONTACT ON

THE POLE (SEE FIGURE 4.7.1)

5.0 POLE SPACE ALLOCATION

DISTRICT

RESERVED

CAPACITY

24"

NO ATTACHMENTS ALLOWED

BELOW 18 FEET

LOWEST SUPPLY

OR POWER

PAGE:12

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 14: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

6.1 POLE-TO-POLE GUY WIRES

POLE-TO-POLE GUY WIRES WHERE THE GUY IS ATTACHED BELOW THE COMMUNICATION SPACE ON ONE

POLE USING THE NEXT POLE AS AN ANCHOR SHALL NOT BE PERMITTED. EXISTING POLE-TO-POLE GUY

WIRES WHEN IDENTIFIED WILL REQUIRE REMOVAL OR REWORK (SEE FIGURE 6.1.1).

FIGURE 6.1.1

(NOT ACCEPTABLE)

COMMUNICATION

SPACE (VARIES)

DOWN GUY & ANCHOR

POLE-TO-POLE GUY

(ACCEPTABLE)

DOWN GUY & ANCHOR

(ACCEPTABLE)

6.0 POLE-TO-POLE GUY

OVERHEAD GUY

PAGE:13

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 15: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

7.1 SPLICE CASES, STORAGE LOOPS, SLACK SPAN, SNOW SHOES, OR OTHER EQUIPMENT.

TO LIMIT EXCESSIVE LOADING ON POLES AND ENSURE CLIMBING SPACE, THE FOLLOWING RESTRICTIONS

APPLY:

SPLICE CASES: PREFERRED METHOD IS TO RISER DOWN USING STAND OFF BRACKETS (SEE FIGURE 3.4.2) AND

PLACE SPLICE CASE IN A VAULT. ALTERNATELY, IF MOUNTED ON LICENSEE CABLE, SPLICE CASE MUST NOT BE

CLOSER THAN THREE FEET TO THE POLE, AND NOT FURTHER THAN SIX FEET FROM THE POLE (SEE FIGURE

7.1.1). SPLICE CASES MUST NOT EXCEED 50 POUNDS.

LICENSEE STORAGE LOOPS (COILS) ARE NOT ALLOWED ON POLES.

SLACK SPAN AND SNOW SHOES: A SLACK SPAN IS LIMITED TO A MAXIMUM OF 25 FEET ON EITHER SIDE OF THE

POLE AND A MAXIMUM OF 100 FEET OF SLACK PER POLE. SNOW SHOES SHOULD BE EQUALLY SPACED FROM

POLE TO DISTRIBUTE WEIGHT EVENLY.

IF LICENSEE PERFORMS WORK ON EXISTING POLES WITH SPLICE CASES, STORAGE LOOPS, SLACK SPANS OR

OTHER EQUIPMENT ATTACHED TO POLES, THE LICENSEE IS REQUIRED TO MEET CURRENT SPECIFICATIONS.

(SEE FIGURE 7.1.1)

FIGURE 7.1.1

SPLICE CASE, CABLE SPLITTERS, AMPLIFIERS, ETC...,

3' - 6'

COMMUNICATION

SPACE (VARIES)

COMMUNICATION

RISER

COMMUNICATION

EQUIPMENT LOCATION

7.0 JOINT USE ATTACHMENTS

DO NOT ATTACH COMMUNICATION

EQUIPMENT DIRECTLY TO POLE

PLACE A MINIMUM OF 6' FROM POLE

OR PER REGULATING AGENCY

PAGE:14

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 16: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

8.1 POLE TOP WIRELESS

INSTALLATIONS MUST MEET ALL APPLICABLE; FAA, FCC, NESC, NEC, FEDERAL, STATE, MUNICIPAL, LOCAL

CODES, THE DISTRICT JOINT USE RULES AND REGULATIONS AND POLE ATTACHMENT STANDARDS AND

PERMITTING REQUIREMENTS. LICENSEE IS SOLELY RESPONSIBLE FOR IDENTIFYING AND OBTAINING ALL

PERMITS AND PERMISSIONS AT THEIR SOLE EXPENSE.

THE DISTRICT DOES NOT ALLOW ANTENNA/RADIO INSTALLATIONS IN THE COMMUNICATION SPACE OR

COMMUNICATION WORKER SAFETY ZONE. ALL INSTALLATIONS MUST BE ABOVE THE ELECTRIC SUPPLY

SPACE ON A POLE OF SUFFICIENT HEIGHT TO ALLOW FOR MINIMUM VERTICAL SEPARATION FROM ANTENNA

TO ELECTRIC CONDUCTORS.

LICENSEE MUST INSTALL AND MAINTAIN SIGNAGE MADE OF A NON-CORROSIVE AND DURABLE MATERIAL,

SUITABLE FOR OUTDOOR USE, AND RESISTANT TO ULTRAVIOLET RADIATION THAT INDICATES THE NAME OF

THE EQUIPMENT OWNER AND OPERATOR; 24-HOUR EMERGENCY CONTACT INFORMATION; POTENTIAL FOR

RF EXPOSURE INCLUDING HORIZONTAL AND VERTICAL DISTANCE FROM THE ANTENNA AT WHICH IT IS SAFE

TO WORK CONTINUOUSLY; A UNIQUE IDENTIFIER FOR THE SITE; AND EMERGENCY SHUT OFF DETAILS. ALL

SIGNAGE MUST BE APPROVED BY THE DISTRICT AND MEET ALL APPLICABLE ANSI AND FCC STANDARDS.

LICENSEE MUST INSTALL AND MAINTAIN A CLEARLY MARKED UL-LISTED LOAD-BREAK DISCONNECT SWITCH

LOCATED ON THE COMMUNICATION PEDESTAL OR AT A LOCATION ON THE POLE THAT IS OPERABLE FROM

THE GROUND TO DE-ENERGIZE THE POLE TOP WIRELESS ANTENNA/RF EMITTER (OPERATIONAL AND BACKUP

POWER) WITHOUT NOTIFICATION AND AT THE DISTRICT'S DISCRETION, DURING SITUATIONS WHERE DISTRICT

PERSONNEL WILL BE WORKING ON OR AROUND THE POLE. THE SWITCH MUST BE READILY ACCESSIBLE AND

CAPABLE OF BEING LOCKED IN EITHER THE OPEN OR CLOSED POSITION AND INCLUDE A STANDARD DISTRICT

DOUBLE HASP WITH LOCK FROM THE LICENSEE (ALLOWING OPERATION OF SWITCH BY EITHER PARTY). THE

DISCONNECT SWITCH BLADES, JAWS, AND AIR-GAP BETWEEN THEM SHALL ALL BE CLEARLY VISIBLE WHEN

THE SWITCH IS IN THE OPEN POSITION.

8.0 POLE TOP WIRELESS

PAGE:15

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 17: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

FIGURE 8.2.1

6'

MINIMUM

LICENSEE EQUIPMENT

5' M

IN

IM

UM

LICENSEE EQUIPMENT

10'

SCHEDULE 40 PVC

SCHEDULE 80 PVC

OH GUYING

8' M

IN

IM

UM

10' M

AX

IM

UM

6-8" FROM GROUND

5' T

YP

IC

AL

8.2 GUY POLE, PREFERRED INSTALLATION

FIGURE 8.2.1 SHOWS THE PREFERRED INSTALLATION FOR POLE TOP WIRELESS ATTACHMENT

AND EQUIPMENT LOCATION FOR A GUY POLE.

8.0 POLE TOP WIRELESS (CONTINUED)

DISCONNECT SWITCH AND

REQUIRED LABELING PER

SECTION 8.1

PAGE:16

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 18: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

FIGURE 8.3.1

5' M

IN

IM

UM

LICENSEE EQUIPMENT

OH GUYING

8' M

IN

IM

UM

5' T

YP

IC

AL

16' M

AX

IM

UM

8.3 GUY POLE, ALTERNATE INSTALLATION

FIGURE 8.3.1 IS AN ALTERNATE METHOD FOR POLE TOP WIRELESS ATTACHMENT AND

EQUIPMENT LOCATION FOR A GUY POLE. THE ALTERNATE METHOD OF INSTALLATION WOULD

NEED TO BE APPROVED BY THE DISTRICT, UPON NEED RELATED TO THIRD PARTY APPROVALS.

8.0 POLE TOP WIRELESS (CONTINUED)

DISCONNECT SWITCH AND REQUIRED

LABELING PER SECTION 8.1

SECONDARY CONDUCTOR

LICENSEE EQUIPMENT

PAGE:17

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 19: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

SECONDARY CONDUCTOR

5' M

IN

IM

UM

6'

MINIMUM

15" STANDOFF

BRACKET

8' M

IN

IM

UM

10' M

AX

IM

UM

6-8" FROM GROUND

5' T

YP

IC

AL

10'

SCHEDULE 40 PVC

SCHEDULE 80 PVC

(2) 2" CONDUIT

FIGURE 8.4.1

40" MIN COMMUNICATIONS

WORKER SAFETY ZONE

COMMUNICATION

SPACE (VARIES)

8.0 POLE TOP WIRELESS (CONTINUED)

8.4 LIGHT POLE, PREFERRED INSTALLATION

FIGURE 8.4.1 IS THE PERFERRED INSTALLATION

FOR POLE TOP WIRELESS ATTACHMENT AND

EQUIPMENT LOCATION FOR A LIGHT POLE.

LICENSEE EQUIPMENT

DISCONNECT SWITCH AND

REQUIRED LABELING PER

SECTION 8.1

LICENSEE EQUIPMENT

PAGE:18

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 20: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

CONDUCTOR

5' M

IN

IM

UM

(2) 2" CONDUIT

FIGURE 8.5.1

40" MIN COMMUNICATIONS

WORKER SAFETY ZONE

COMMUNICATION

SPACE (VARIES)

8' M

IN

IM

UM

16' M

AX

IM

UM

5' T

YP

IC

AL

8.0 POLE TOP WIRELESS (CONTINUED)

8.5 LIGHT POLE, ALTERNATE INSTALLATION

FIGURE 8.5.1 IS AN ALTERNATE METHOD FOR

POLE TOP WIRELESS ATTACHMENT AND

EQUIPMENT LOCATION FOR A LIGHT POLE. THE

ALTERNATE METHOD OF INSTALLATION WOULD

NEED TO BE APPROVED BY THE DISTRICT, UPON

NEED RELATED TO THIRD PARTY APPROVALS.

DISCONNECT SWITCH AND REQUIRED

LABELING PER SECTION 8.1

LICENSEE EQUIPMENT

LICENSEE EQUIPMENT

PAGE:19

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 21: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

6'

MINIMUM

LICENSEE EQUIPMENT

SYSTEM PRIMARY CONDUCTORS

SERVICE CONDUCTOR

SYSTEM NEUTRAL

9' M

IN

IM

UM

10'

SCHEDULE 40 PVC

SCHEDULE 80 PVC

15" STANDOFF

BRACKET

(2) 2" CONDUIT

8' M

IN

IM

UM

10' M

AX

IM

UM

40" MIN COMMUNICATIONS

WORKER SAFETY ZONE

6-8" FROM GROUND

5' T

YP

IC

AL

FIGURE 8.6.1

COMMUNICATION

SPACE (VARIES)

8.0 POLE TOP WIRELESS (CONTINUED)

8.6 PRIMARY POLE, PREFERRED INSTALLATION

FIGURE 8.6.1 IS THE PERFERRED INSTALLATION

FOR POLE TOP WIRELESS ATTACHMENT AND

EQUIPMENT LOCATION FOR A PRIMARY

DISTRIBUTION POLE.

DISCONNECT SWITCH AND

REQUIRED LABELING PER

SECTION 8.1

LICENSEE EQUIPMENT

PAGE:20

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use

Page 22: MASON PUD 3 JOINT USE ATTACHMENT STANDARDS...communication guys may be attached to district anchors only with written permission and only if guy strain insulators are used. load calculations

LICENSEE EQUIPMENT

SYSTEM PRIMARY CONDUCTORS

SYSTEM NEUTRAL

9' M

IN

IM

UM

SCHEDULE 40 PVC

15" STANDOFF

BRACKET

(2) 2" CONDUIT

40" MIN COMMUNICATIONS

WORKER SAFETY ZONE

FIGURE 8.7.1

COMMUNICATION

SPACE (VARIES)

8' M

IN

IM

UM

16' M

AX

IM

UM

8.0 POLE TOP WIRELESS (CONTINUED)

8.7 PRIMARY\ POLE, ALTERNATE INSTALLATION

FIGURE 8.7.1 IS AN ALTERNATE METHOD FOR

POLE TOP WIRELESS ATTACHMENT AND

EQUIPMENT LOCATION FOR A PRIMARY

DISTRIBUTION POLE. THE ALTERNATE METHOD

OF INSTALLATION WOULD NEED TO BE

APPROVED BY THE DISTRICT, UPON NEED

RELATED TO THIRD PARTY APPROVALS.

DISCONNECT SWITCH AND

REQUIRED LABELING PER

SECTION 8.1

LICENSEE EQUIPMENT

PAGE:21

of 21

JOINT USE ATTACHMENT

STANDARDS

REVISIONS

DATE ENGR STD COMM

0 3/9/2020 T.D. 3/5/2020

CAD FILE: JU-001

Y:Engineering / Standards, Specifications

& Manuals / Specifications / Joint Use