OPC Server Software for efector octavis VSExxx
2
Content1 System requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Config Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 OPC Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 .1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 .2 Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 .3 End . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 OPC Server tree structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 .1 Tree elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 [OPC-Server-Octavis] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 [General*] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 [Versions] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 [opcServer] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 [vseDll] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 [restartServer] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 [stopService] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 [stopService] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 [Configuration] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 [General**] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 [Selftest] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 [Monitoring] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 [Parameter] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 [Expert-Config] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 [configuredName] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 [configuredIpAddress] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 [configuredTcpPort] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 [vseId] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 [vseName] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 [macAddress] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 [ipAddress] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 [systemMode] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 [sensorName1 . . .4] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 [actualVariant] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 [rebootVse] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 [result] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 [sensorsNeeded] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 [sensorsConnected] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 [doSelftest] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 [Objects] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 [Object 1 . . .24] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 [Analysing-method] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 [HFFT:FFT] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 [isVelocity] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 [Peak:RMS] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 [name] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 [sensorId] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 [ReadState] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 [objectValue] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 [damageLevel] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 [speed] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 [IOs] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 [Io1 . . .8] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 [ioValue] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 [isInput] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 [Out] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 [Out1] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 [isAnalog] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 [isVoltage] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3
OPC Server Software for efector octavis VSExxx
UK
[Out2] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 [Aux] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 [Aux1 . . .2] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 [isCurrentInput] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 [Parameter] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 [Objects] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 [Object1 . . .24] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 [Damping] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 [averages] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 [responseDelay] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 [Limits] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 [yellow] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 [red] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 [Teach] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 [teachValue] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 [doTeach] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 [readTeach] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 [writeTeach] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 [name] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 [sensorId] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 [rpmId] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 [RPM-Objects] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 [RPM-Object1 . . .24] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 [rpmValue] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 [Read] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 [write] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 [unit] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
OPC Server Software for efector octavis VSExxx
4
1 System requirementsPC with Pentium II 266 MHZ processor or higher – Pentium III recommended
Microsoft Windows NT, 2000, XP, Server 2003
128 MB RAM for the operating system and additional 32 MB for the OPC Server
256 MB of available hard disk space, including NET Framework and OPC Core Components
Ethernet 10 / 100 Mbit
2 Installation� NOTE
Please deinstall any older versions on your computer of the OPC Core Components (e .g . Version 2 .0) be-forehand .
To install the OPC Server please start the installation wizard „Setup .exe“ .
During the installation the .Net Framework and the OPC Core Components 3 .0 will be installed if required .
●
●
●
●
●
►
>
5
OPC Server Software for efector octavis VSExxx
UK
The Default paths are as follows:
C:\Program Files\ifm electronic\efector octavis\octavis OPC\bin
They contain theEXE files („OctavisOpcServer .exe“, „ConfigTool .exe“) and the „VSE Communication DLL“ (VSExxx .dll) .
„OctavisOpcServer .exe“ is a service and is automatically started when an OPC Client has been connected or in certain cases when the Config Tool has been started .
C:\Documents and settings\All Users\Application Data\ifm electronic\efector octavis\octavis opc
with two sub-folders “Config” and “Log”, which contain Logfiles (of the OPC Server and the DLL) as well as the Config Tool confi-guration files .
3 Config ToolThe Config Tools creates an XML configuration file . This in turn is used as a configuration file for the OPC Server .
●
●
OPC Server Software for efector octavis VSExxx
6
4 OPC ServerOPC = OLE Proprocess Control
4.1 GeneralAs previously mentioned the OPC Server is started as a service and is included in the list of applications (→ Windows „Settings“ > „Control panel“ > „Admininstration“ > „Applications“).
4.2 StartThe OPC Server is automatically started by the client .
4.3 EndUnder normal use it is not necessary to manually end the software . If required you can exit using the Task Manager, Services or directly from the OPC Client ([stopService]) .
5 OPC Server tree structureThe tree structure is created as follows:
Nodes: has no own value, e .g . [Objects]
Element: has own values and is alloted to a node
Property: the contents belong to an element or a node .
In the following grafics the individual components are recognisable by the designated shape of the symbols:
Nodes = hexagonal symbols, e .g . [Selftest]
Elements = rectangular symbols, e .g . [[doSelftest]]
Properties = oval symbols, e .g . [[sensorsNeeded]] .
The following illustration 1 just shows the node model as an overview . To have a better overview the Elements are shown completely in the following grafics .
After the grafics the tree elements are explained and their position is given in reference to the tree structure .
Node-titles always start with capital letters . The names of the Elements and Properties start with uncapitalized letters .
The Native datatype is always given according to the Softing standard .
–
–
–
–
–
–
9
OPC Server Software for efector octavis VSExxx
UK
Illustration 3: Expert-Config (Not implemented)
5.1 Tree elements
[OPC-Server-Octavis]
Child of [root]
Tree Structure Type Node
[General*]
Child of [OPC-Server-Octavis] (root)
Tree Structure Type Node
Server specific actions or data .
[Versions]
Child of [General*]
Tree Structure Type Node
Server specific actions or data .
[opcServer]
Child of [Versions]
Tree Structure Type Element
Native Datatype BSTR
Access Rights Read
[vseDll]
Child of [Versions]
Tree Structure Type Element
Native Datatype BSTR
Access Rights Read
OPC Server Software for efector octavis VSExxx
10
[restartServer]
Child of [General*]
Tree Structure Type Element
Native Datatype BOOL
Access Rights Read and write
The server is stopped, all connections to the VSEs are disconnected and then recreated . The service is not cancelled and the DLL remains in the memory .
To start again the server has to be reconnected .
[stopService]
Child of [General*]
Tree Structure Type Element
Native Datatype BOOL
Access Rights Read and write
The service is finished . Here in addition to disconnection the the DLL removed from the memory . To restart the server has to be reconnected and started .
[stopService]
Child of [OPC-Server-Octavis] (root)
Tree Structure Type Node
Contains all the settings which have been made with the Config Tool .
[stopService] is then the name for a VSE, with which you are connected (if the nodes are not completely shown this means that the Diagnostic Electronics is not parametised or not available) .
[Configuration]
Child of [stopService]
Tree Structure Type Node
All settings which have been made with the Config Tool .
Data update for all the related tags after [restartServer] or [stopService] .
[General**]
Child of [stopService]
Tree Structure Type Node
VSE specific settings or conditions .
[Selftest]
Child of [stopService]
Tree Structure Type Node
Refers to each sensor .
[Monitoring]
Child of [stopService]
Tree Structure Type Node
Queries the values of a VSE .
The query cycle can be set using the OPC Server (minimum 100 ms) .
11
OPC Server Software for efector octavis VSExxx
UK
[Parameter]
Child of [stopService]
Tree Structure Type Node
Reduced settings of a VSE parameter set .
The parameters cannot be set for the VSE using the OPC Server . It is only possible to made adjustments .
� NOTEParameters can only be changed by the OPC Server if no other client has switched the VSE to the Setup Mode (→ [systemMode]).
[Expert-Config]
Child of [stopService]
Tree Structure Type Node
Is not supported by this version .
[configuredName]
Child of [Configuration]
Tree Structure Type Element
Native Datatype BOOL
Access Rights Read
Name of theVSE, with which the OPC Server communicates (can be set in the Config Tool) . The VSE is shown as a node bearing this name (→ [stopService]).
[configuredIpAddress]
Child of [Configuration]
Tree Structure Type Element
Native Datatype BSTR
Access Rights Read
IP-Address (can be set in the Config Tool) . Default factory setting value is: 192 .168 .0 .1
[configuredTcpPort]
Child of [Configuration]
Tree Structure Type Element
Native Datatype I4
Access Rights Read
Port (can be set in the Config Tool) . Default factory setting value is: 3321
[vseId]
Child of [General**]
Tree Structure Type Element
Native Datatype I4
Access Rights Read
The number the DLL uses to communicate with the VSE results out of the sequence the VSEs activate Vse-Connect . This facilitates reading the Logfiles .
OPC Server Software for efector octavis VSExxx
12
[vseName]
Child of [General**]
Tree Structure Type Element
Native Datatype BSTR
Access Rights Read
Is composed of 5 fields (→ VES003 > Project > Header data) and is used for further identification of the VSE unit .
[macAddress]
Child of [General**]
Tree Structure Type Element
Native Datatype BST
Access Rights Read
The MAC-Address used to communicate with the VSE (included on the labelling of the VSE) . E .g . .: 00-02-01-30-02-81
[ipAddress]
Child of [General**]
Tree Structure Type Element
Native Datatype BSTR
Access Rights Read
The IP-Address which is programmed in the VSE can differ to the [configuredIpAddress], if the VSE e .g is accessed using a router .
[systemMode]
Child of [General**]
Tree Structure Type Element
Native Datatype BST
Access Rights Read
The VSE has one of 4 possible modi for the the clients to which it is connnected:
1 . Mode [Selftest] Selftest
2 . Mode [Supervise[ Monitoring, i .e . sampling measurement values
3 . Mode [Meassurement] Measurement of the spectrum (not possible with the OPC Server)
4 . Mode [Setup] Adjusting the parameters
The basic modus is Mode [Supervise] (2) .
If the VSE is in a different modus, it does NOT supply any measurement values .
Switching from one to another of the above mentioned modi occurs automatically and the OPC Server resets automatically into the basic modus .
Example: [doSelftest]
All the clients which are connected to a VSE have the same modus!
[sensorName1...4]
Child of [General**]
Tree Structure Type Element
Native Datatype BSTR
Access Rights Read
The name for each sensor (Sensor1 to Sensor4) is shown as means of identification .
13
OPC Server Software for efector octavis VSExxx
UK
[actualVariant]
Child of [General**]
Tree Structure Type Element
Native Datatype UI2Access Rights Read and write
Current version of the VSE .
� NOTEIf the VSE has been programmed with an Event Object of type [ChangeVariant], it is no longer possible to write the variants .
If the variants are changed the [ReadState] mode for Objects (or subobjects), which are not active for the new variants, change to „15“ . If [Monitoring] values are sampled the value „zero“ is always given . The OPC server does not show which variants are active for an object .
●
●
[rebootVse]
Child of [General**]
Tree Structure Type Element
Native Datatype BOOL
Access Rights Read and write
The VSE has been reset, i . e . the VSE interrupts the connection and reboots . The [Monitoring] settings are automatically recovered .
[result]
Child of [Selftest]
Tree Structure Type Element
Native Datatype BOOL
Access Rights Read
Results of the last Selftest . The results are only shown for the sensors for which the Selftest is activated . This is NOT shown by the OPC server .
� NOTEIf the Selbsttest has been deactivated for a sensor, and a Selftest is performed then the result is automatical-ly reported as successful .
[sensorsNeeded]
Child of [result]
Tree Structure Type Property
Native Datatype BOOL ARRAY [4]
Access Rights Read
Sensor inputs required by the parameter set but are recognised as being faulty or not connected . This serves to facilitate error identification .
OPC Server Software for efector octavis VSExxx
14
[sensorsConnected]
Child of [result]
Tree Structure Type Property
Native Datatype BOOL ARRAY [4]
Access Rights Read
Sensor inputs recognised by the Selftest, i .e . which are not faulty and have been connected to the VSE .
[doSelftest]
Child of [Selftest]
Tree Structure Type Element
Native Datatype BOOL
Access Rights Read and write
To trigger a Selfsttest . The value for [doSelftest] remains „1“, untill the Selftest has been completed . Quality of [result], [sensorsNeeded] and [sensorsConnected] are temporarily changed to „Bad” (waiting for initial data) .
[Objects]
Child of [Monitoring]
Tree Structure Type Node
All parameterised Objects are shown (e .g .with parameter software VES003) .
[Object 1...24]
Child of [Monitoring] > [Objects]
Tree Structure Type Node
[Analysing-method]
Child of [Monitoring] > [Objects] > [Object n]
Tree Structure Type Node
[HFFT:FFT]
Child of [Analysing-method]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read
If TRUE = HFFT, else FALSE = FFT (→ VES003: Analysis method).
[isVelocity]
Child of [Analysing-method]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read
TRUE („1“) means that the delivered [objectValue] is an integrated measurement value (e .g . vibration velocity in mm/s) .
15
OPC Server Software for efector octavis VSExxx
UK
[Peak:RMS]
Child of [Analysing-method]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read
If TRUE („1“) Peak, else RMS (→ VES003).
[name]
Child of [Monitoring] > [Objects] > [Object n]
Tree Structure Type Element
Native Datatype BSTR
Access Rights Read and write
For Object identification purposes .
[sensorId]
Child of [Monitoring] > [Objects] > [Object n]
Tree Structure Type Element
Native Datatype UI2
Access Rights Read
Gives the allocation to the sensor . Numbering starts at „0“, i .e . „1“ is the Object allocated to Sensor2 .
[ReadState]
Child of [Monitoring] > [Objects] > [Object n]
Tree Structure Type Element
Native Datatype UI4
Access Rights Read
Indicates the current failure condition .
Meaning of the displays:
1 Internal error Results invalid
2 Calculation error Results invalid
3 Speed not within operational range
During data recording the speed was not within the valid speed range . The evaluation of the results is therefore interrupted .
4 Speed deviations are too high During data recording the speed deviates too highly . The evaluation of the results is therefore interrupted .
5 [teachValue] is not valid The [teachValue] is not valid (NAN or < 1x10-20) . The evaluation of the results is therefore interrupted .
6 No valid reference value for signal weighting 1
The reference value for signalweighting 1 refers to an entry with the value 0 . The evaluation of the results is therefore interrupted .
7 No valid reference value for signal weighting 2
The reference value for signalweighting 2 refers to an entry with the value 0 . The evaluation of the results is therefore interrupted .
8 Deactivated by signalweighting 1 The current entry for signalweighting 1 is 0 . The evaluation of the results is therefore interrupted .
9 Deactivated by signalweighting 2 The current entry for signalweighting 2 is 0 . The evaluation of the results is therefore interrupted .
15 Deactivated by variants Will be set by the DLL (all other values are 0) .
� NOTE[ReadState] can only be used in combination with [speed], [objectValue] or [damageLevel], as else the value is not updated .
OPC Server Software for efector octavis VSExxx
16
[objectValue]
Child of [Monitoring] > [Objects] > [Object n]
Tree Structure Type Element
Native Datatype R4
Access Rights Read
Deadband Min: 0 Max: Sensor scaling factor
Object results according to the signal weighting .
[damageLevel]
Child of [Monitoring] > [Objects] > [Object n]
Tree Structure Type Element
Native Datatype R4
Access Rights Read
Deadband Min: 0 Max: [Limits .red]
[damageLevel] = [objectValue] / [teachValue]
[speed]
Child of [Monitoring] > [Objects] > [Object n]
Tree Structure Type Element
Native Datatype R4
Access Rights Read
Deadband Min: Speedobject operating range Min Max: Speedobject operating range Max
[IOs]
Child of [Monitoring]
Tree Structure Type Node
All 8 IOs (configurable in- and outputs) are always shown (even with VSE001) . The OPC server only indicates whether it is an in- or output .
[Io1...8]
Child of [IOs]
Tree Structure Type Node
[ioValue]
Child of [Io1 . .8]
Tree Structure Type Element
Native Datatype BOOL
Access Rights Read
[isInput]
Child of [ioValue]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read
17
OPC Server Software for efector octavis VSExxx
UK
[Out]
Child of [Monitoring]
Tree Structure Type Node
VSE ouputs .
[Out1]
Child of [Out]
Tree Structure Type Element
Native Datatype BOOL
Access Rights Read
Deadband Only if set as analog output *) Min = [valueAt4mA] Max = [valueAt20mA[
Output 1 can be programmed as analog or digital output .
*) For VES003 → switching output 4 mA or 20 mA
[isAnalog]
Child of [Out1]
Tree Structure Type Property
Native Datatype BOOL / R4 *)
Access Rights Read
*) Native Datatype is R4, if the switching output is programmed as an analog output (only possible with [Out1]), else it the datatype BOOL .
[isVoltage]
Child of [Out1]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read
If the switching output is programmed as analog (only possible for [Out1]) it can supply either a voltage value or a current value .
[Out2]
Child of [Out]
Tree Structure Type Element
Native Datatype BOOL
Access Rights Read
Unlike [Out1] it cannot be programmed as an analog output .
[Aux]
Child of [Monitoring]
Tree Structure Type Node
VSE inputs (e .g . [speed]) .
OPC Server Software for efector octavis VSExxx
18
[Aux1...2]
Child of [Aux]
Tree Structure Type Element
Native Datatype R4
Access Rights Read
Deadband Min und Max calculation *)
*) The calculation of Min and Max for the Deadband depends on settings (→ [isCurrentInput])
Analog input: Input of the minimum and maximum reference point it is possible to span a straight line which can be mea-sured off at 0 and 20 mA .
Pulse input: Freely definable values: Min = 0 / Max = 100 .000
[isCurrentInput]
Child of [Aux1 . . .2]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read
The inputs can be programmed as analog or pulse inputs .
([isCurrentInput] = FALSE): Pulse input The number of pulses per revoltion is not visible .
([isCurrentInput] = TRUE): Analog input It can either be a current or voltage input (not shown by the OPC server) .
[Parameter]
Child of [OPC-Server-Octavis] (root)
Tree Structure Type Node
Contains all OPC server settings which can be changed by default .
[Objects]
Child of [Parameter]
Tree Structure Type Node
Maximal 24 objects are shown . An object is only shown if it has been parametised (e .g . with the parameter software VES003) .
[Object1...24]
Child of [Parameter] > [Objects]
Tree Structure Type Node
[Damping]
Child of [Parameter] > [Objects] > [Object1 . . .24]
Tree Structure Type Node
Damping the object results .
1 .
2 .
19
OPC Server Software for efector octavis VSExxx
UK
[averages]
Child of [Damping]
Tree Structure Type Element
Native Datatype R4
Access Rights Read and write
The diagnosis object values ([objectValue] and [damageLevel]) are averaged using a so-called „exponentially weighted moving averages“ .
Formula: xn = α * xn-1 + (1 - α) * x
α = [averages]: 0 < α < 1
x = current measurement value
VES003 Averages: conversion [averages] = 1 - Averages
Beispiel: Averages = 1/8 → [averages] = 1 - 1/8 = 1 - 0.125 = 0.875
[responseDelay]
Child of [Damping]
Tree Structure Type Element
Native Datatype UI2
Access Rights Read and write
To avoid alarms caused by deviations in the process it is possible to set a response delay, giving the number of alarm conditions allowed before signalling alarm .
In this case an alarm condition means the surpassing of a damage level, → [Limits].
[Limits]
Child of [Parameter] > [Objects] > [Object1 . . .24]
Tree Structure Type Node
Limit values
[yellow]
Child of [Limits]
Tree Structure Type Element
Native Datatype R4
Access Rights Read and write
[red]
Child of [Limits]
Tree Structure Type Element
Native Datatype R4
Access Rights Read and write
[Teach]
Child of [Parameter] > [Objects] > [Object1 . . .24]
Tree Structure Type Node
OPC Server Software for efector octavis VSExxx
20
[teachValue]
Child of [Teach]
Tree Structure Type Element
Native Datatype R4
Access Rights Read and write
The values are written in the OPC Cache . After the implementation of [writeTeach] the set values are transferred to the VSE .
[doTeach]
Child of [teachValue]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read and write
Ás soon as the Teach function has been started the Quality of [teachValue] changes to „Uncertain“ . After su-cessfull completion it changes back to „Good“ .
[readTeach]
Child of [teachValue]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read and write
Active sampling of the VSE [teachValue] .
[writeTeach]
Child of [teachValue]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read and write
Transfers the [teachValue] (Cache) to the VSE .
[name]
Child of [Parameter] > [Objects] > [Object1 . . .24]
Tree Structure Type Element
Native Datatype BSTR
Access Rights Read and write
[sensorId]
Child of [Parameter] > [Objects] > [Object1 . . .24]
Tree Structure Type Element
Native Datatype UI2
Access Rights Read and write
Sensor allocation begins with „0“ for Sensor 1 .
[rpmId]
Child of [Parameter] > [Objects] > [Object1 . . .24]
Tree Structure Type Element
Native Datatype UI2
Access Rights Read
Speed object allocation .
21
OPC Server Software for efector octavis VSExxx
UK
Each object refers to a speed object . To save resources several objects can refer to the same speed object . Any changes made to the speed object are also made for the linked objects .
Tip: Using the VES003 to set parameters it is possible to enforce different speed objects which can be given different speeds (e .g . 3500 for the first and 3501 for the second object) .
[RPM-Objects]
Child of [Parameter]
Tree Structure Type Node
Only the speed objects which have been programmed are shown (max . 24) .
[RPM-Object1...24]
Child of [RPM-Objects]
Tree Structure Type Node
[rpmValue]
Child of [RPM-Object1 . . .24]
Tree Structure Type Element
Native Datatype R4
Access Rights Read and write
The item [rpmValue] can be changed if the speed object is of type „constant speed“ or „speed via bus“ . The changes made to [rpmValue] can have an effect on other objects, → [rpmId].
[Read]
Child of [rpmValue]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read and write
Automatic update .
[write]
Child of [rpmValue]
Tree Structure Type Property
Native Datatype BOOL
Access Rights Read and write
Transfers the „new“ [rpmValue] from the Cache to the VSE .
[unit]
Child of [RPM-Object1 . . .24]
Tree Structure Type Property
Native Datatype BSTR
Access Rights Read
Speed object unit . Default is RPM, i .e . speed .