    POWER PROTECTION

    Series 300 UPSThree Phase10 kVA to 125 kVA; 60 Hz

    Installation, Operation,

    & Maintenance Manual

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    2/113

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    3/113

    i

    TABLE OF CONTENTS

    IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

    1.0 INTRODUCTION

    'HILQLWLRQV

    0RGHVRI2SHUDWLRQ 7KURXJKWKH8360RGXOH

    6WDWLF%\SDVV/LQH

    0DLQWHQDQFH%\SDVV/LQH

    2.0 INSTALLATION

    6DIHW\3UHFDXWLRQV

    836,QVWDOODWLRQ

    ,QVWDOODWLRQ&RQVLGHUDWLRQV

    8QORDGLQJDQG([WHUQDO,QVSHFWLRQ

    ,QWHUQDO,QVSHFWLRQRIWKH8366\VWHP (TXLSPHQW/RFDWLRQ

    %DWWHU\,QVWDOODWLRQ

    0DWFKLQJ%DWWHU\&DELQHWV

    1RQ6WDQGDUG%DWWHULHV

    (OHFWULFDO:LULQJ

    836:LUH6L]H*XLGHOLQHV

    3RZHUDQG&RQWURO:LULQJ

    %DWWHU\:LULQJ

    :LULQJ&RQQHFWLRQV

    :LULQJ,QVSHFWLRQ

    3.0 OPERATION

    2SHUDWRU&RQWUROVDQG,QGLFDWRUV

    'LJLWDO'LVSOD\6FUHHQ

    6HOHFWLRQ3DGV

    3RZHU6WDWXV'LDJUDP

    5RWDU\6ZLWFK

    $GYLVRU\'LVSOD\

    'LVSOD\6FUHHQ0HQX

    'HIDXOW6FUHHQ0HVVDJHV

    1RUPDO2SHUDWLRQ

    :DUQLQJ/RDGRQ0DLQWHQDQFH%\SDVV

    :DUQLQJ/RDGRQ836

    :DUQLQJ/RDGRQ6WDWLF%\SDVV

    )DXOW6\VWHP6KXWGRZQ

    836RQ%DWWHU\

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    4/113

    ii

    $ODUP0HVVDJHV

    8365HVSRQVHWRDQ$ODUP

    2SHUDWRU5HVSRQVHWRDQ$ODUP

    6\VWHP6WDWXV6FUHHQV

    0HWHU)XQFWLRQV

    6\VWHP&RQILJXUDWLRQ

    $ODUP+LVWRU\ /DPS7HVW

    6WDUW8S

    6WDUW8S3URFHGXUH

    $EQRUPDO&RQGLWLRQV'XULQJ6WDUW8S

    5HVSRQVHWRDQ,QFRUUHFW6WDUW8S6HTXHQFH

    1RUPDO2SHUDWLRQ

    6KXWGRZQ

    6KXWGRZQWR0DLQWHQDQFH%\SDVV

    &RPSOHWH6KXWGRZQ (PHUJHQF\6KXWGRZQ

    5HVSRQVHWRD3RZHU)DLOXUH

    8365HVSRQVH

    2SHUDWRU5HVSRQVH

    $V%DWWHU\7LPH$SSURDFKHV=HUR

    5HVSRQVHWRD836)DLOXUH

    8365HVSRQVH

    2SHUDWRU5HVSRQVH

    $ODUP0HVVDJHV

    4.0 MAINTENANCE

    6DIHW\3UHFDXWLRQV

    :KHQ7R&DOO

    6WHSV7R7DNH

    3UHYHQWLYH0DLQWHQDQFH

    0DLQWDLQLQJDQ2SHUDWRUV/RJ

    &KDQJLQJWKH$LU)LOWHU

    3HULRGLF5HVWDUWRIWKH836

    0DLQWDLQLQJWKH%DWWHU\

    /LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUW

    5.0 SYSTEM OPTIONS

    *HQHUDO

    2SWLRQDO([WHUQDO0DLQWHQDQFH%\SDVV&DELQHW

    ,QVWDOODWLRQ

    2SHUDWLRQ

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    5/113

    iii

    2SWLRQDO6OLP/LQH'LVWULEXWLRQ

    2SWLRQDO5HPRWH6WDWXV3DQHO

    2SWLRQDO5HPRWH&RQWDFW%RDUG

    2SWLRQDO56,QWHUIDFH3RUW

    8VLQJD7HUPLQDODVD5HPRWH6WDWLRQ

    5HPRWH)URQW3DQHO7HUPLQDO0RGH (PHUVRQ6WDQGDUG3URWRFRO(63

    5HPRWH/RDG&RQWURO

    6HWWLQJWKH3DVVZRUG

    2SWLRQDO,QWHUQDO61036LPSOH1HWZRUN0DQDJHPHQW3URWRFRO6XSSRUW

    8VLQJDQ6103$GDSWHU2SWLRQDO

    2SWLRQDO,QWHUQDO0RGHP

    7KH&RPPXQLFDWLRQ0RGH6FUHHQ

    8VLQJWKH0RGHP

    6HWWLQJWKH'DWD5DWH

    2SWLRQDO6LWH6FDQ6LWHPDVWHU,QWHUIDFH

    2SWLRQDO,%0$66LJQDO,QWHUIDFH

    2SWLRQDO6\VWHP3RZHU:DUQLQJ6LJQDO

    2SWLRQDO%DWWHU\&LUFXLW%UHDNHU

    2SWLRQDO&RQWDFW,VRODWRU%RDUG

    2SWLRQDO'&*URXQG)DXOW$ODUP

    2SWLRQDO&RPSXWHU,QWHUIDFH6\VWHP

    2SWLRQDO0XOWL&RPSXWHU,QWHUIDFH6\VWHP

    2SWLRQDO,%0$60XOWL,QWHUIDFH6\VWHP

    6.0 SPECIFICATIONS

    (OHFWULFDO6SHFLILFDWLRQV

    $&,QSXWVWR836

    $&2XWSXW836,QYHUWHU

    5DWLQJV

    (QYLURQPHQWDO6SHFLILFDWLRQV

    0HFKDQLFDO6SHFLILFDWLRQV

    %DWWHU\

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    6/113

    iv

    FIGURES

    )LJXUH 6LQJOH/LQH'LDJUDPN9$

    )LJXUH 6LQJOH/LQH'LDJUDPN9$ZLWK2SWLRQDO([WHUQDO0DLQWHQDQFH%\SDVV

    )LJXUH 836&DELQHW,QVWDOODWLRQ'LDJUDPN9$

    )LJXUH 836&DELQHW,QVWDOODWLRQ'LDJUDPN9$

    )LJXUH 836&DELQHW,QVWDOODWLRQ'LDJUDPN9$

    )LJXUH %DWWHU\&DELQHW,QVWDOODWLRQ'LDJUDPLQFK)UDPH

    )LJXUH %DWWHU\&DELQHW,QVWDOODWLRQ'LDJUDPLQFK)UDPH

    )LJXUH &RQWURO:LULQJ'LDJUDPN9$

    )LJXUH &RQWURO:LULQJ'LDJUDPN9$

    )LJXUH &RQWURO:LULQJ'LDJUDPN9$

    )LJXUH )LHOG:LULQJ7HUPLQDWLRQV

    )LJXUH 2SHUDWRU&RQWUROVDQG,QGLFDWRUVRQ8360RGXOH&DELQHW)URQW

    )LJXUH %ORFN'LDJUDPRIWKH6HULHV836

    )LJXUH 'LVSOD\6FUHHQDQG6HOHFWLRQ3DGV

    )LJXUH 3RZHU6WDWXV'LDJUDP

    )LJXUH 5RWDU\6ZLWFKDQG$GYLVRU\'LVSOD\

    )LJXUH 0HQX6HOHFWLRQ$UUDQJHPHQW

    )LJXUH ([WHUQDO0DLQWHQDQFH%\SDVV5RWDU\6ZLWFK

    )LJXUH %ORFN'LDJUDPRIWKH([WHUQDO0DLQWHQDQFH%\SDVV

    )LJXUH &DEOH&RQQHFWLRQVEHWZHHQ836DQG7HUPLQDO

    )LJXUH 8365HPRWH0RQLWRU&RQWURO

    )LJXUH 2SWLRQDO0DLQWHQDQFH%\SDVV&DELQHW

    )LJXUH 2SWLRQDO0DLQWHQDQFH%\SDVV&DELQHWZLWK,VRODWLRQ7UDQVIRUPHU

    )LJXUH 2SWLRQDO6OLP/LQH'LVWULEXWLRQ

    )LJXUH 2SWLRQDO5HPRWH6WDWXV3DQHO

    )LJXUH 2SWLRQDO5HPRWH&RQWDFW%RDUG

    )LJXUH 2SWLRQDO,%0$66LJQDO,QWHUIDFH

    )LJXUH 2SWLRQDO,%0$66LJQDO,QWHUIDFHZLWK5HPRWH6WDWXV3DQHO

    )LJXUH 2SWLRQDO%DWWHU\&LUFXLW%UHDNHUN9$ )LJXUH 2SWLRQDO%DWWHU\&LUFXLW%UHDNHUN9$

    )LJXUH 2SWLRQDO&RPSXWHU,QWHUIDFH6\VWHP

    )LJXUH 2SWLRQDO0XOWL&RPSXWHU,QWHUIDFH6\VWHP

    )LJXUH 2SWLRQDO,%0$60XOWL,QWHUIDFH6\VWHP

    TABLES

    7DEOH 0RGHO1XPEHUVDQG5DWLQJV

    7DEOH 6LWH3ODQQLQJ'DWD6HULHV836WRN9$

    7DEOH 6LWH3ODQQLQJ'DWD6HULHV836WRN9$

    7DEOH 7DEOH

    7DEOH &RQQHFWLRQ7\SH:LUH6L]H5DQJH

    7DEOH 7RUTXH6SHFLILFDWLRQV8QOHVV2WKHUZLVH/DEHOHG

    7DEOH $ODUP0HVVDJHV'XULQJ6WDUW8S

    7DEOH $ODUP0HVVDJHV

    7DEOH 7HUPLQDO0RGH0HQX

    7DEOH 'LDO2XW(YHQWV

    7DEOH /DVW$WWHPSWV0HVVDJHV

    7DEOH 0DWFKLQJ%DWWHU\&DELQHWV

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    7/113

    1

    IMPORTANT SAFETY INSTRUCTIONS

    Save These Instructions.

    7KLVPDQXDOFRQWDLQVLPSRUWDQWLQVWUXFWLRQVWKDWVKRXOGEHIROORZHGGXULQJLQVWDOODWLRQDQGPDLQWHQDQFHRI\RXU6HULHV836DQGEDWWHULHV

    $:$51,1*

    (;(5&,6((;75(0(&$5(:+(1+$1'/,1*836$1'%$77(5

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    8/113

    2

    IBM-PC, Macintosh, Procomm, Microsoft Windows, CompuServe, and NECare registered trademarks of their

    respective companies.Telix, IBM, AS/400, and System/38 are trademarks of their respective companies.

    620(&20321(176:,7+,17+(&$%,1(76$5(127&211(&7('72&+$66,6*5281'$1

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    9/113

    Introduction 3

    1.0 INTRODUCTION

    /LHEHUW6HULHV8QLQWHUUXSWLEOH3RZHU6\VWHPVVXSSO\FULWLFDOORDGVZLWKFRQWLQXRXVFRPSXWHUJUDGHSRZHU5HOLDELOLW\DQGSHUIRUPDQFHDUHNH\GHVLJQFRQVLGHUDWLRQV7KH836GHVLJQDOVRPD[LPL]HVLVRODWLRQRIWKHORDGIURPGLVWXUEDQFHVDQGLQWHUUXSWLRQVPLQLPL]HVPDLQWHQDQFHDQGUHSDLUWLPHDQGSURYLGHVPRQLWRULQJRIVLJQLILFDQWV\VWHPRSHUDWLQJFKDUDFWHULVWLFV

    3URSHULQVWDOODWLRQDQGRSHUDWLRQRIWKH836DUHHTXDOO\LPSRUWDQWIDFWRUVLQV\VWHPUHOLDELOLW\

    7KLVPDQXDOFRQWDLQVFRPSOHWHLQIRUPDWLRQRQLQVWDOODWLRQRSHUDWLRQDQGSUHYHQWLYHPDLQWHQDQFHRIWKH8QLQWHUUXSWLEOH3RZHU6\VWHP836DQG%DWWHU\&DELQHW,OOXVWUDWLRQVVKRZLQJWKHIXQFWLRQRIDOORSHUDWRUFRQWUROVLQVWUXPHQWVDODUPVDQGLQGLFDWLQJOLJKWVDUHDOVRJLYHQ3HUIRUPDQFHVSHFLILFDWLRQVDWZKLFKWKH836ZLOORSHUDWHDUHJLYHQLQ 6SHFLILFDWLRQV3OHDVHQRWHWKDWVRPHLQIRUPDWLRQLVN9$VSHFLILF

    7KH/LHEHUW6HULHV836LVDYDLODEOHLQWHQSRZHUUDWLQJVDQGN9$6SHFLILFDWLRQVIRUHDFKPRGHODSSHDULQ 6SHFLILFDWLRQV7KHVDPHSULQFLSOHVRIRSHUDWLRQDSSO\WRDOOPRGHOV

    6KRXOGDVVLVWDQFHEHUHTXLUHGFDOO/LHEHUWVWROOIUHH&XVWRPHU6HUYLFHDQG6XSSRUWQXPEHU3OHDVHKDYHWKHIROORZLQJLQIRUPDWLRQDYDLODEOHIRUIDVWDVVLVWDQFH

    $&$87,21

    7KLVHQWLUHPDQXDOVKRXOGEHUHDGSULRUWRLQVWDOODWLRQSHUIRUPLQJVWDUWXSSURFHGXUHVRUV\VWHPRSHUDWLRQRUPDLQWHQDQFH,PSURSHULQVWDOODWLRQKDVSURYHGWREHWKHVLQJOH

    PRVWVLJQLILFDQWFDXVHRIVWDUWXSSUREOHPV

    $:$51,1*

    /(7+$/92/7$*(6(;,67:,7+,17+,6(48,30(17'85,1*23(5$7,21)$,/85(722%6(59($//6$)(7

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    10/113

    4 Introduction

    1.1 Definitions

    7KHVHGHILQLWLRQVGHVFULEHWHUPVDVWKH\UHODWHVSHFLILFDOO\WR6HULHVLQVWDOODWLRQRSHUDWLRQRUPDLQWHQDQFH5DWKHUWKDQEHLQJDOSKDEHWL]HGWKH\DUHSUHVHQWHGLQDQRUGHUPRVWDSSURSULDWHWRXQGHUVWDQGLQJWKH836

    Uninterruptible Power System (UPS)

    $OOFRPSRQHQWVZLWKLQ8360RGXOH&DELQHWDQGVHSDUDWH%DWWHU\&DELQHWZKLFKIXQFWLRQDVD

    V\VWHPWRSURYLGHFRQWLQXRXVFRQGLWLRQHG$&SRZHUWRDORDG

    UPS Module

    5HFWLILHU&KDUJHUDQG,QYHUWHUXQLWZKLFKXQGHUVXSHUYLVLRQRIWKH,QWHUQDO&RQWURO6\VWHPDQG2SHUDWRU&RQWUROVSURYLGHVVSHFLILHG$&SRZHUWRDFULWLFDOORDG

    UPS Module Cabinet

    0HWDOHQFORVXUHFRQWDLQLQJUHFWLILHUFKDUJHULQYHUWHUVWDWLFWUDQVIHUVZLWFKVWDWLFE\SDVVOLQHPDLQWHQDQFHE\SDVVOLQHH[WHUQDORSHUDWRUFRQWUROVDQGLQWHUQDOFRQWUROV\VWHPUHTXLUHGWRSURYLGHVSHFLILHG$&SRZHUWRDORDG

    Battery Cabinet

    /LHEHUW0DWFKLQJIDFWRU\VXSSOLHG%DWWHU\&DELQHWFRQWDLQLQJVHDOHGEDWWHU\FHOOVVXIILFLHQWWR

    PDLQWDLQ836RXWSXWDFFRUGLQJWRVSHFLILFDWLRQVLQ 6SHFLILFDWLRQV

    Input Power

    3RZHUSURYLGHGE\WKHHOHFWULFDOXWLOLW\FRPSDQ\RUDX[LOLDU\JHQHUDWRUDQGFRQQHFWHGWRWKH836LQSXW

    Input Filter

    5HGXFHVUHFWLILHULQSXWFXUUHQWGLVWRUWLRQWR7+'DWIXOOORDG7KLVILOWHUDOVRLPSURYHVWKHLQSXWSRZHUIDFWRU

    Input Isolation Transformer

    $GHOWDWRZ\HLVRODWLRQWUDQVIRUPHUIRUWKH836PRGXOHLQSXW3URYLGHVFRPPRQPRGHQRLVH

    DWWHQXDWLRQIRUDOOV\VWHPRSHUDWLQJPRGHVLQFOXGLQJZKLOHRQE\SDVV$OVRSURYLGHVVLQJOHSRLQWJURXQGIRUWKHV\VWHP

    Input Auto Transformer

    $GHOWDWRZ\HDXWRWUDQVIRUPHUIRUWKH836PRGXOHLQSXW(QDEOHV836PRGXOHWREHLQVWDOOHGZLWKH[WHUQDOPDLQWHQDQFHE\SDVVFDELQHWZLWKRXWUHTXLULQJDWUDQVIRUPHULQWKHH[WHUQDOPDLQWHQDQFHE\SDVVOLQH

    Rectifier/Charger

    836FRPSRQHQWFRQWDLQLQJHTXLSPHQWDQGFRQWUROVIRUFRQYHUWLQJLQSXW$&SRZHUWRUHJXODWHG'&SRZHUUHTXLUHGIRUEDWWHU\FKDUJLQJDQGIRUVXSSO\LQJSRZHUWRWKHLQYHUWHU

    Inverter

    836FRPSRQHQWFRQWDLQLQJHTXLSPHQWDQGFRQWUROVIRUFRQYHUWLQJ'&SRZHUIURP5HFWLILHU&KDUJHURUEDWWHU\WRUHJXODWHG$&SRZHUUHTXLUHGE\WKHFULWLFDOORDG

    Internal Control System

    6LJQDOSURFHVVLQJFLUFXLWVZKLFKUHJXODWHSRZHUFRQYHUVLRQSURFHVVHVGHWHFWIDXOWFRQGLWLRQVDQGFRQWUROWKH836RSHUDWLQJVHTXHQFH

    Operator Controls and Display

    5RWDU\VZLWFKVHOHFWLRQSDGVDQGGLJLWDOGLVSOD\XVHGE\RSHUDWRUVWRPRQLWRUDQGFRQWUROWKH8366HH 2SHUDWLRQRIWKLVPDQXDO

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    11/113

    Introduction 5

    Static Bypass Line

    /LQHFRQGXFWLQJXQFRQGLWLRQHGLQSXWSRZHUWRFULWLFDOORDGWKURXJK6WDWLF7UDQVIHU6ZLWFK7UDQVIHURIORDGEHWZHHQWKLVOLQHDQGWKH836LQYHUWHURXWSXWRFFXUVXQGHUVXSHUYLVLRQRIWKH,QWHUQDO&RQWURO6\VWHP

    Static Transfer Switch

    'HYLFHWUDQVIHUULQJWKHFULWLFDOORDGEHWZHHQ836LQYHUWHURXWSXWDQG6WDWLF%\SDVV/LQH

    Transfer

    7KHFULWLFDOORDGLVWUDQVIHUUHGIURPWKH836LQYHUWHURXWSXWWRWKH6WDWLF%\SDVV/LQH

    Retransfer

    7KHFULWLFDOORDGLVDXWRPDWLFDOO\UHWUDQVIHUUHGIURPWKH6WDWLF%\SDVV/LQHEDFNWRWKH836LQYHUWHURXWSXW

    Maintenance Bypass Line

    /LQHFRQGXFWLQJHOHFWULFLW\GLUHFWO\IURPLQSXWSRZHUWRFULWLFDOORDGGXULQJPDLQWHQDQFHRUZKHQHYHU836LVQRWFRPSOHWHO\RSHUDWLRQDO0DLQWHQDQFH%\SDVV/LQHLVFRQQHFWHGZKHQURWDU\VZLWFKLVLQ3RVLWLRQRU

    External Maintenance Bypass Cabinet$QH[WHUQDOPDLQWHQDQFHE\SDVVOLQHLQDPDWFKLQJFDELQHWZLWKVZLWFKLQJPHFKDQLVPDQGRSWLRQDOFLUFXLWEUHDNHUVDQGRSWLRQDOE\SDVVWUDQVIRUPHUWRWRWDOO\LVRODWHWKH836PRGXOHIURPWKHHOHFWULFDOV\VWHP

    Slim-Line Distribution Cabinet

    $FDELQHWH[WHQVLRQRIWKH836PRGXOHWRHQFORVHRQHRUWZRSROHSDQHOERDUGVZLWKDPDLQFLUFXLWEUHDNHUIRUHDFKSDQHOERDUG

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    12/113

    6 Introduction

    1.2 Modes of Operation

    7KH836SURYLGHVWKHIROORZLQJWKUHHSRZHUSDWKVEHWZHHQWKHXWLOLW\VRXUFHDQGWKHFULWLFDOORDG

    7KURXJKWKH8360RGXOH

    6WDWLF%\SDVV/LQH

    0DLQWHQDQFH%\SDVV/LQH

    1.2.1 Through the UPS Module

    'XULQJQRUPDORSHUDWLRQWKHRXWSXWRIWKH8360RGXOHLQYHUWHULVXVHG,QSXW$&SRZHUWRWKH836LVFRQYHUWHGWR'&E\WKHUHFWLILHUFKDUJHU7KH'&SRZHUFKDUJHVWKH836EDWWHU\DQGSURYLGHVLQSXWSRZHUIRUWKHLQYHUWHU7KHLQYHUWHUFRQYHUWVWKH'&SRZHUWRFRQGLWLRQHG$&SRZHUZKLFKVXSSOLHVWKHFULWLFDOORDG7KHFRQYHUVLRQLQYHUVLRQSURFHVVHOLPLQDWHVYROWDJHWUDQVLHQWVH[LVWLQJLQWKHLQSXWSRZHUEHIRUHLWUHDFKHVWKHFULWLFDOORDG,ILQSXWSRZHULVLQWHUUXSWHGWKHEDWWHU\ZLOOLPPHGLDWHO\VXSSO\WKH'&SRZHUUHTXLUHGE\WKHLQYHUWHUWRPDLQWDLQFRQWLQXRXV

    $&SRZHUWRWKHORDG$IXOO\FKDUJHGEDWWHU\ZLOOSURYLGHSRZHUIRUWKHVSHFLILHGWLPHDWWKHUDWHGORDGRUORQJHUDWDUHGXFHGORDG

    1.2.2 Static Bypass Line

    7KH6WDWLF%\SDVV/LQHSURYLGHVDQDOWHUQDWHSRZHUSDWKGXULQJDQRYHUORDGFRQGLWLRQRU836IDXOW,IWKHORDGGHPDQGVPRUHSRZHUWKDQWKHLQYHUWHUFDQVXSSO\DQRYHUORDGFRQGLWLRQWKHFRQWUROV\VWHPDXWRPDWLFDOO\HQHUJL]HVWKHVWDWLFWUDQVIHUVZLWFKWRWUDQVIHUWKHORDGIURPWKH8360RGXOHWRWKH6WDWLF%\SDVV/LQH,IWKHLQWHUQDOFRQWUROV\VWHPGHWHFWVDIDXOWLQWKH8360RGXOHZKLOHLWLVVXSSRUWLQJWKHORDGWKHVWDWLFWUDQVIHUVZLWFKWUDQVIHUVWKHORDGZLWKRXWLQWHUUXSWLRQWRWKH6WDWLF%\SDVV/LQHWKHUHE\PDLQWDLQLQJFRQWLQXRXVSRZHUWRWKHFULWLFDOORDG

    1.2.3 Maintenance Bypass Line

    7KH0DLQWHQDQFH%\SDVV/LQHLVDKDUGZLUHGOLQHWKURXJKWKH836ZKLFKVXSSOLHVWKHFULWLFDOORDGZLWKXQFRQGLWLRQHGSRZHUZKHQWKH5RWDU\6ZLWFKLVLQ3RVLWLRQRU7KHSXUSRVHRIWKLVOLQHLVWRURXWHSRZHUWRWKHFULWLFDOORDGGXULQJVWDUWXSRUZKLOHWKH8360RGXOHLVGHHQHUJL]HGIRUPDLQWHQDQFH7KH0DLQWHQDQFH%\SDVV/LQHFDQRQO\EHVHOHFWHGPDQXDOO\XVLQJWKH5RWDU\6ZLWFK:KHQWKH5RWDU\6ZLWFKLVLQ3RVLWLRQWKHLQWHUQDOFRQWUROV\VWHPGHWHUPLQHVZKLFKRIWKHRWKHUWZRSDWKVVXSSOLHVSRZHUWRWKHORDG

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    13/113

    Installation 7

    2.0 INSTALLATION

    2.1 Safety Precautions

    5HDGWKLVPDQXDOWKRURXJKO\SD\LQJVSHFLDODWWHQWLRQWRWKHVHFWLRQVWKDWDSSO\WR\RXEHIRUHZRUNLQJZLWKWKH836$OVRUHDGWKHEDWWHU\PDQXIDFWXUHUVPDQXDOEHIRUHZRUNLQJRQRUQHDUWKHEDWWHU\

    8QGHUW\SLFDORSHUDWLRQDQGZLWKDOO836GRRUVFORVHGRQO\QRUPDOVDIHW\SUHFDXWLRQVDUHQHFHVVDU\7KHDUHDDURXQGWKH836V\VWHPDQG%DWWHU\VKRXOGEHNHSWIUHHIURPSXGGOHVRIZDWHUH[FHVVPRLVWXUHRUGHEULV

    6SHFLDOVDIHW\SUHFDXWLRQVDUHUHTXLUHGIRUSURFHGXUHVLQYROYLQJKDQGOLQJLQVWDOODWLRQDQGPDLQWHQDQFHRIWKH836V\VWHPRUWKHEDWWHU\2EVHUYHSUHFDXWLRQVLQ ,QVWDOODWLRQEHIRUHKDQGOLQJRULQVWDOOLQJWKH836V\VWHP2EVHUYHSUHFDXWLRQVLQ 0DLQWHQDQFHEHIRUHDVZHOODVGXULQJSHUIRUPDQFHRIDOOPDLQWHQDQFHSURFHGXUHV2EVHUYHDOOEDWWHU\VDIHW\SUHFDXWLRQVEHIRUHZRUNLQJRQRUQHDUWKHEDWWHU\

    7KLVHTXLSPHQWFRQWDLQVVHYHUDOFLUFXLWVWKDWDUHHQHUJL]HGZLWKKLJKYROWDJH2QO\WHVWHTXLSPHQWGHVLJQDWHGIRUWURXEOHVKRRWLQJVKRXOGEHXVHG7KLVLVSDUWLFXODUO\WUXHIRURVFLOORVFRSHV$OZD\VFKHFNZLWKDQ$&DQG'&YROWPHWHUWRHQVXUHVDIHW\EHIRUHPDNLQJFRQWDFWRUXVLQJWRROV(YHQZKHQWKHSRZHULVWXUQHG2IIGDQJHURXVO\KLJKSRWHQWLDOVPD\H[LVWDWWKH

    FDSDFLWRUEDQNV2EVHUYHDOOEDWWHU\SUHFDXWLRQVZKHQQHDUWKHEDWWHU\IRUDQ\UHDVRQ21/

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    14/113

    8 Installation

    Notes1. Nominal (NOM) current is based on full rated output load.2. Maximum (MAX) current (125% of NOM) is short duration for battery recharge conditions.

    3. UPS input and bypass cables must be run in separate conduit from output cables.4. If the UPS module is to be upgraded in the future, it is recommended that the AC input, bypass AC input, battery, and AC output wiring and overcurrentprotection be sized initially for the fu ture upgraded size.

    5. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.6. Power cables from UPS DC link to batteries should be sized for a total maximum 2.0 volt line drop (measured at UPS) at maximum discharge current.7. Recommended bypass AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) per NEC 220-2(a).8. UPS output load cables must be run in separate conduit from input and bypass cables.9. Minimum sized grounding conductors to be per NEC 250-95. Parity sized ground conductors are recommended. Neutral conductors to be sized for full

    capacity per NEC-16 Note 10.10. Wiring requirements:

    AC INPUT: 3-phase, 3-wire plus ground (unit supplied with input isolation transformer).3-phase, 4-wire plus ground (unit supplied with input auto transformer).AC OUTPUT: 3-phase, 4-wire plus ground.DC INPUT: 2-wire (positive and negative), plus ground.

    11. All wiring is to be in accordance with national and local electrical codes.12. Minimum access clearance is 3 feet front and 1 foot above UPS.13. Top or bottom cable entry through removable access plates. Cut plate to suit conduit size, then replace.14. Control wiring and power wiring must be run in separate conduit.15. Battery cabinet not included.

    Additional Notes

    1. If site configuration includes a back-up emergency generator, it is recommended that the engine generator set be properly sized and equipped for a UPSapplication. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS compatible regulator(generator voltage regulation). Consult generator manufacturer for required generator options and sizing.

    2. If site configuration includes an automatic transfer switch, refer to the Liebert Power Line titled Criteria for Application of Automatic Transfer Switches(ATS) with Uninterruptible Power Supply (UPS) Systems. 91K-PLT-48-02. It is also recommended that the transfer switch be equipped with auxiliarycontacts for UPS on generator current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.

    3. If site configuration requires an external isolated maintenance bypass circuit, it should be noted that the Utility AC input is not in phase with the UPS ACoutput, with the optional delta-wye input isolation transformer. Consult with sales representative or UPS applications engineer.

    Table 2 Site Planning Data, Series 300 UPS, 10 to 50 kVA

    ModelPowerRating Vol tage

    RectifierAC Input

    RectifierAC Input

    with OptionalInput Filter Battery AC Output Mechanical Data

    CurrentRec

    ** CurrentRec**

    NominalVoltage

    FullLoad

    Max.Dis-

    chargeCurrent Current

    Rec**

    Dimen-sions Weight

    DFLLb./Ft.2

    HeatDis-sipa-tionBTU/hr.

    CoolingAir

    CFM

    kVA kW VAC/Freq Nom Max Nom Max kW Nom (WxDxH)

    311*

    10 8 208/60Hz240/60Hz480/60Hz600/60Hz

    35A29A15A12A

    44A36A19A15A

    60A50A25A20A

    30A26A13A11A

    37A32A16A14A

    50A40A20A20A

    204VDC(102 cells)

    9.3 58A 28A24A12A10A

    35A30A15A15A

    36x28x72 in91x72x183 cm

    1100 lbs499 kg

    157 6000 600

    321*

    15 12 208/60Hz240/60Hz480/60Hz600/60Hz

    50A43A22A18A

    63A54A28A23A

    80A70A40A30A

    44A38A19A15A

    55A48A24A19A

    70A60A30A25A

    204VDC(102 cells)

    13.8 85A 42A36A18A14A

    60A45A25A20A

    36x28x72 in91x72x183 cm

    1100 lbs499 kg

    157 6000 600

    331*

    20 16 208/60Hz240/60Hz480/60Hz600/60Hz

    65A56A28A23A

    81A70A35A29A

    100A90A50A40A

    57A50A25A20A

    72A62A31A25A

    90A80A40A30A

    360VDC(180 cells)

    17.8 62A 56A48A24A20A

    70A60A30A25A

    36x28x72 in91x72x183 cm

    1400 lbs635 kg

    200 8900 800

    341*

    30 24 208/60Hz240/60Hz480/60Hz600/60Hz

    96A83A42A33A

    120A104A53A41A

    150A125A70A50A

    85A74A37A29A

    108A92A46A37A

    150A110A60A50A

    360VDC(180 cells)

    26.4 92A 83A72A36A29A

    125A90A50A40A

    36x28x72 in91x72x183 cm

    1400 lbs635 kg

    200 12300 1050

    346

    *

    40 32 208/60Hz

    240/60Hz480/60Hz600/60Hz

    128A

    111A55A44A

    160A

    139A69A55A

    200A

    175A90A70A

    113A

    98A49A39A

    142A

    123A61A49A

    175A

    150A80A60A

    360VDC

    (180 cells)

    35.2 122A 111A

    96A48A39A

    150A

    125A60A50A

    36x28x72 in

    91x72x183 cm

    1900 lbs

    882 kg

    271 16400 1050

    356*

    50 40 208/60Hz240/60Hz480/60Hz600/60Hz

    158A137A68A55A

    198A171A85A69A

    250A225A110A90A

    140A122A61A49A

    175A152A76A61A

    225A200A100A80A

    360VDC(180 cells)

    43.7 150A 139A120A60A48A

    175A150A80A60A

    36x28x72 in91x72x183 cm

    1900 lbs882 kg

    271 18700 1050

    ApplicableNotes:

    1 2 3,49,10111314

    1 2 3,49,10111314

    5 4,69111314

    1 4,79

    111314

    12,13,15 15 15

    For explanation of Applicable Notes, see referenced numbers inNotes below.

    *Field-upgradeable to next larger model**Rec = Recommended External Overcurrent Protection

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    15/113

    Installation 9

    Notes1. Nominal (NOM) current is based on full rated output load.2. Maximum (MAX) current (125% of NOM) is short duration for battery recharge conditions.3. UPS input and bypass cables must be run in separate conduit from output cables.4. If the UPS module is to be upgraded in the future, it is recommended that the AC input, bypass AC input, battery, and AC output wiring and overcurrent

    protection be sized initially for the future upgraded size.5. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.6. Power cables from UPS DC link to batteries should be sized for a total maximum 2.0 volt line drop (measured at UPS) at maximum discharge current.7. Recommended bypass AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) per NEC 220-2(a).8. UPS output load cables must be run in separate conduit from input and bypass cables.9. Minimum sized grounding conductors to be per NEC 250-95. Parity sized ground conductors are recommended. Neutral conductors to be sized for full

    capacity per NEC-16 Note 10.10. Wiring requirements:

    AC INPUT: 3-phase, 3-wire plus ground (unit supplied with input isolation transformer).3-phase, 4-wire plus ground (unit supplied with input auto transformer).AC OUTPUT: 3-phase, 4-wire plus ground.DC INPUT: 2-wire (positive and negative), plus ground.

    11. All wiring is to be in accordance with national and local electrical codes.12. Minimum access clearance is 3 feet front and 1 foot above UPS.13. Top or bottom cable entry through removable access plates. Cut plate to suit conduit size, then replace.14. Control wiring and power wiring must be run in separate conduit.15. Battery cabinet not included.

    Additional Notes1. If site configuration includes a back-up emergency generator, it is recommended that the engine generator set be properly sized and equipped for a UPS

    application. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS compatible regulator(generator voltage regulation). Consult generator manufacturer for required generator options and sizing.

    2. If site configuration includes an automatic transfer switch, refer to the Liebert Power Line titled Criteria for Application of Automatic Transfer Switches(ATS) with Uninterruptible Power Supply (UPS) Systems. 91K-PLT-48-02. It is also recommended that the transfer switch be equipped with auxiliarycontacts for UPS on generator current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.

    3. If site configuration requires an external isolated maintenance bypass circuit, it should be noted that the Utility AC input is not in phase with the UPS ACoutput, with the optional delta-wye input isolation transformer. Consult with sales representative or UPS applications engineer.

    Table 3 Site Planning Data, Series 300 UPS, 65 to 125 kVA

    ModelPowerRating Vol tage

    RectifierAC Input

    RectifierAC Input

    with OptionalInput Filter Battery AC Output Mechanical Data

    CurrentRec** Current

    Rec**

    NominalVoltage

    FullLoad

    Max.Dis-

    chargeCurrent Current

    Rec**

    Dimen-sions Weight

    DFLLb./Ft.2

    HeatDis-sipa-tionBTU/hr.

    CoolingAir

    CFM

    kVA kW VAC/Freq Nom Max Nom Max kW Nom (WxDxH)

    361*

    65 52 208/60Hz240/60Hz480/60Hz600/60Hz

    197A171A85A68A

    246A214A106A85A

    300A300A150A110A

    182A158A79A63A

    228A197A99A79A

    300A250A125A100A

    360VDC(180 cells)

    57.1 198A 180A155A78A63A

    225A200A100A80A

    54x28x72 in137x72x183 cm

    2500 lbs1134 kg

    238 24200 1200

    366 75 60 208/60Hz240/60Hz480/60Hz600/60Hz

    234A203A101A81A

    293A254A126A101A

    400A350A175A125A

    208A180A90A72A

    260A225A113A90A

    350A300A150A125A

    360VDC(180 cells)

    65.2 225A 208A180A90A72A

    300A225A125A90A

    54x28x72 in137x72x183 cm

    2500 lbs1134 kg

    238 25400 1200

    376*

    100 80 208/60Hz240/60Hz480/60Hz600/60Hz

    312A270A135A108A

    390A338A169A135A

    500A450A225A175A

    277A240A120A95A

    347A300A150A120A

    450A400A200A150A

    360VDC(180 cells)

    88.5 307A 278A241A120A98A

    350A300A150A125A

    54x28x72 in137x72x183 cm

    2700 lbs1225 kg

    257 33800 1600

    381 125 100 208/60Hz240/60Hz480/60Hz600/60Hz

    386A334A167A134A

    483A418A209A168A

    600A600A300A225A

    343A297A148A119A

    429A371A185A149A

    600A450A225A175A

    360VDC(180 cells)

    108.1 383A 347A301A150A120A

    450A400A200A150A

    54x28x72 in137x72x183 cm

    2700 lbs1225 kg

    257 38000 1600

    Applicable

    Notes:

    1 2 3,4

    9,10111314

    1 2 3,4

    9,10111314

    5 4,6

    9,10111314

    1 3,4,7

    8,9,10111314

    12,13,15 15 15

    For explanation of Applicable Notes, see referenced numbers inNotes below.

    *Field-upgradeable to next larger model**Rec = Recommended External Overcurrent Protection

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    16/113

    10 Installation

    2.2 UPS Installation

    3URSHUSODQQLQJZLOOVSHHG836XQORDGLQJORFDWLRQDQGFRQQHFWLRQ0DNHVXUHWKHUHLVDGHTXDWHFOHDUDQFHIRUWKH836PRGXOHDQGEDWWHU\FDELQHWGRRUVWRRSHQIXOOVZLQJ&KHFNIRUDPLQLPXPRILQFOHDUDQFHDERYHERWKFDELQHWVIRUH[KDXVWDLUWRIORZZLWKRXWUHVWULFWLRQ$OVRDOORZDGHTXDWHFOHDUDQFHDWERWWRPIURQWRIHDFKFDELQHWIRUXQUHVWULFWHGLQWDNHDLUWRIORZ0DNHVXUHURRPKDVDGHTXDWHYHQWLODWLRQDQGFRROLQJDQGLQVWDOO836LQDFOHDQGU\ORFDWLRQ

    ,QVWDOO836DFFRUGLQJWRGUDZLQJV)LJXUH WKURXJK)LJXUH 7DEOH DQG7DEOH DQG

    WKHIROORZLQJSURFHGXUHV$IWHULQVWDOODWLRQLVFRPSOHWHFRQWDFW/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDWWRVFKHGXOHFKHFNRXWDQGVWDUWXSDVVLVWDQFH

    $/LHEHUWDXWKRUL]HGUHSUHVHQWDWLYHPXVWSHUIRUPDQLQLWLDOV\VWHPVWDUWXSWRHQVXUHSURSHU836RSHUDWLRQ(TXLSPHQWZDUUDQWLHVZLOOEHYRLGHGXQOHVVV\VWHPVWDUWXSLVSHUIRUPHGE\D/LHEHUWDXWKRUL]HGUHSUHVHQWDWLYH

    2.2.1 Installation Considerations 8WLOL]HWKHVKRUWHVWRXWSXWGLVWULEXWLRQFDEOHUXQVSRVVLEOHDWWKHLQVWDOODWLRQVLWHFRQVLVWHQW

    ZLWKORJLFDOHTXLSPHQWDUUDQJHPHQWDQGLQFRPSOLDQFHZLWK1(&DQGORFDOHOHFWULFDOFRGHV$OORZVSDFHIRUIXWXUHHTXLSPHQWDGGLWLRQV

    5HFRPPHQGHGDPELHQWWHPSHUDWXUHIRURSHUDWLRQLVWR&HOVLXVWR)5HODWLYHKXPLGLW\PXVWEHOHVVWKDQQRQFRQGHQVLQJ,QDOWLWXGHVDERYHPHWHUVIHHWWKH836UDWLQJZLOOEHUHGXFHG

    7KHURXWHDQGIRXQGDWLRQWRWKHLQVWDOODWLRQVLWHPXVWEHFDSDEOHRIVXSSRUWLQJWKHZHLJKWRIFDELQHWVDQGPRYLQJHTXLSPHQW5HIHUWR7DEOH 6LWH3ODQQLQJ'DWD6HULHV836WRN9$DQG7DEOH 6LWH3ODQQLQJ'DWD6HULHV836WRN9$IRUVSHFLILFLQIRUPDWLRQDERXWFDELQHWZHLJKWV

    3ODQWKHURXWHWRHQVXUHXQLWZLOOSDVVWKURXJKDOOHOHYDWRUVFRUQHUVDQGGRRUZD\VWRSUHYHQWGDPDJH

    +HDWRXWSXWRI836HTXLSPHQWLVVLJQLILFDQW%HVXUHHQYLURQPHQWDOFRQGLWLRQLQJV\VWHPVFDQDFFRPPRGDWHWKLVKHDWORDGHYHQGXULQJXWLOLW\RXWDJHV5HIHUWR7DEOH 6LWH3ODQQLQJ'DWD6HULHV836WRN9$DQG7DEOH 6LWH3ODQQLQJ'DWD6HULHV836WRN9$IRUPRUHVSHFLILFLQIRUPDWLRQ

    $&$87,21

    5HDGWKLVPDQXDOWKRURXJKO\EHIRUHDWWHPSWLQJWRZLUHRURSHUDWHWKHXQLW,PSURSHULQVWDOODWLRQLVWKHPRVWVLJQLILFDQWFDXVHRI836VWDUWXSSUREOHPV

    'RQRWLQVWDOOWKHHTXLSPHQWQHDUDQ\JDVRUHOHFWULFKHDWHUV,QVWDOOWKHHTXLSPHQWLQDUHVWULFWHGORFDWLRQWRSUHYHQWDFFHVVE\

    XQDXWKRUL]HGSHUVRQQHO

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

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    17/113

    Installation 11

    2.2.2 Unloading and External Inspection

    836DQGEDWWHU\FDELQHWVDUHVKLSSHGRQVHSDUDWHSDOOHWVWRDOORZHDVLHUKDQGOLQJDWWKHVLWH0RYHFDELQHWVDVFORVHDVSRVVLEOHWRWKHLQWHQGHGORFDWLRQEHIRUHUHPRYLQJIURPWKHSDOOHW

    ,QVSHFWHTXLSPHQWDQGVKLSSLQJFRQWDLQHUVIRUDQ\VLJQVRIGDPDJHRUPLVKDQGOLQJ'RQRWDWWHPSWWRLQVWDOOWKHV\VWHPLIGDPDJHLVDSSDUHQW,IDQ\GDPDJHLVQRWHGILOHDGDPDJHFODLPZLWKWKHVKLSSLQJDJHQF\ZLWKLQKRXUVDQGFRQWDFW/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDWWRLQIRUPWKHPRIWKHGDPDJHFODLPDQGWKHFRQGLWLRQRIWKHHTXLSPHQW

    &RPSDUHFRQWHQWVRIVKLSPHQWZLWKWKHELOORIODGLQJ5HSRUWDQ\PLVVLQJLWHPVWRWKHFDUULHUDQGWR/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWLPPHGLDWHO\

    &KHFNQDPHSODWHRQWKHLQVLGHRIFDELQHWIURQWGRRUWRYHULI\PRGHOQXPEHUN9$UDWLQJDQGLQSXWRXWSXWYROWDJHFRUUHVSRQGVZLWKWKHRQHVSHFLILHG5HFRUGPRGHODQGVHULDOQXPEHULQIURQWRIWKLVPDQXDO$UHFRUGRIWKLVLQIRUPDWLRQLVQHFHVVDU\VKRXOGVHUYLFLQJEHFRPHUHTXLUHG

    2.2.3 Internal Inspection of the UPS System 9HULI\WKDWDOOLWHPVKDYHEHHQUHFHLYHG

    ,IVSDUHSDUWVZHUHRUGHUHGYHULI\DUULYDO

    &KHFNIRUVKLSSLQJGDPDJHLQWHUQDOO\

    &KHFNIRUDQ\ORRVHFRQQHFWLRQVRUXQVHFXUHGFRPSRQHQWVLQWKH836PRGXOH

    &KHFNIRULQVWDOODWLRQRIVDIHW\VKLHOGVRQWKH836PRGXOH7KHUHVKRXOGQRWEHDQ\H[SRVHGWHUPLQDOVZKHQWKHFDELQHWGRRUVDUHRSHQHG

    &KHFNIRUDQ\XQVDIHIHDWXUHWKDWPD\EHDSRWHQWLDOVDIHW\KD]DUG

    2.2.4 Equipment Location

    8VHDIRUNOLIWRURWKHUPDWHULDOKDQGOLQJGHYLFHWRPRYHWKHFDELQHWVDVFORVHDVSRVVLEOHWRWKHILQDOLQVWDOODWLRQVLWH

    &DVWHUVDUHSURYLGHGRQWKHXQLWWRDLGLQILQDOSRVLWLRQLQJ

    $VZLWKDOOHOHFWULFDOHTXLSPHQWLQVWDOODWLRQDQGVHUYLFHDELOLW\ZLOOEHHDVLHULIDFFHVVLVSURYLGHGRQDOOVLGHVRIWKHHTXLSPHQW0LQLPXPDFFHVVUHTXLUHPHQWVDUHIHHWIURQWIRRWWRS

    9HULI\DGHTXDWHFOHDUDQFHIRUFDELQHWGRRUVWRRSHQ6HHGUDZLQJVDQGORFDWLRQFRGHV IHHWLVUHFRPPHQGHG

    9HULI\DGHTXDWHFOHDUDQFHDERYHFDELQHWVDOORZLQJXQUHVWULFWHGH[KDXVWDLUWRIORZ LQFKHVPLQLPXP

    9HULI\836V\VWHPLVLQVWDOOHGLQDFOHDQFRRODQGGU\ORFDWLRQ

    $&$87,21

    'RQRWUHPRYHWKHVXSSRUWLQJEDQGVXQWLO\RXLQWHQGWRUHPRYHXQLWIURPSDOOHW6KLSSLQJEDQGVDUHXVHGWRVHFXUHXQLWWRSDOOHW([WUHPHFDUHLVQHFHVVDU\GXULQJPRYLQJ7HVWOLIWDQGEDODQFHWKHFDELQHWVEHIRUHWUDQVSRUWLQJ0DLQWDLQPLQLPXPWLOWIURPYHUWLFDODWDOOWLPHV

    $:$51,1*

    ($&+83602'8/($1'0$7&+,1*%$77(5

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    18/113

    12 Installation

    2.3 Battery Installation

    Battery Safety Precautions

    6HUYLFLQJRIEDWWHULHVVKRXOGEHSHUIRUPHGRUVXSHUYLVHGE\SHUVRQQHONQRZOHGJHDEOHRIEDWWHULHVDQGWKHUHTXLUHGSUHFDXWLRQV.HHSXQDXWKRUL]HGSHUVRQQHODZD\IURPEDWWHULHV5HIHUWR 0DLQWHQDQFHIRUDGGLWLRQDOVDIHW\SUHFDXWLRQVUHJDUGLQJYHQWHGEDWWHULHV

    :KHQUHSODFLQJEDWWHULHVXVHWKHVDPHQXPEHUDQGW\SHRIEDWWHULHV

    $&$87,21

    /HDGDFLGEDWWHULHVFRQWDLQKD]DUGRXVPDWHULDOV%DWWHULHVPXVWEHKDQGOHGWUDQVSRUWHGDQGUHF\FOHGRUGLVFDUGHGLQDFFRUGDQFHZLWKIHGHUDOVWDWHDQGORFDOUHJXODWLRQV%HFDXVHOHDGLVDWR[LFVXEVWDQFHOHDGDFLGEDWWHULHVVKRXOGEHUHF\FOHGUDWKHUWKDQGLVFDUGHG

    'RQRWGLVSRVHRIEDWWHU\RUEDWWHULHVLQDILUH7KHEDWWHU\PD\H[SORGH

    'RQRWRSHQRUPXWLODWHWKHEDWWHU\RUEDWWHULHV5HOHDVHGHOHFWURO\WHLVKDUPIXOWRWKHVNLQDQGH\HV,WPD\EHWR[LF

    $EDWWHU\FDQSUHVHQWDULVNRIHOHFWULFDOVKRFNDQGKLJKVKRUW

    FLUFXLWFXUUHQW7KHIROORZLQJSUHFDXWLRQVVKRXOGEHREVHUYHGZKHQZRUNLQJRQEDWWHULHV

    5HPRYHZDWFKHVULQJVRURWKHUPHWDOREMHFWV

    8VHWRROVZLWKLQVXODWHGKDQGOHV

    :HDUUXEEHUJORYHVDQGERRWV

    'RQRWOD\WRROVRUPHWDOSDUWVRQWRSRIEDWWHULHV

    'LVFRQQHFWFKDUJLQJVRXUFHSULRUWRFRQQHFWLQJRUGLVFRQQHFWLQJEDWWHU\WHUPLQDOV

    'HWHUPLQHLIEDWWHU\LVLQDGYHUWHQWO\JURXQGHG,ILQDGYHUWHQWO\JURXQGHGUHPRYHVRXUFHRIJURXQG&RQWDFWZLWKDQ\SDUWRIDJURXQGHGEDWWHU\FDQUHVXOWLQHOHFWULFDOVKRFN7KHOLNHOLKRRGRIVXFKVKRFNZLOOEHUHGXFHGLIVXFK

    JURXQGVDUHUHPRYHGGXULQJLQVWDOODWLRQDQGPDLQWHQDQFH

    /HDGDFLGEDWWHULHVFDQSUHVHQWDULVNRIILUHEHFDXVHWKH\JHQHUDWHK\GURJHQJDV7KHIROORZLQJSURFHGXUHVVKRXOGEHIROORZHG

    '2127602.(ZKHQQHDUEDWWHULHV

    '2127FDXVHIODPHRUVSDUNLQEDWWHU\DUHD

    'LVFKDUJHVWDWLFHOHFWULFLW\IURPERG\EHIRUHWRXFKLQJEDWWHULHVE\ILUVWWRXFKLQJDJURXQGHGPHWDOVXUIDFH

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    19/113

    Installation 13

    2.3.1 Matching Battery Cabinets

    &DELQHW,QVSHFWLRQ5HPRYHDOOSDQHOVDQGYLVXDOO\LQVSHFWWKHEDWWHULHVEXVFRQQHFWLRQVDQGFDELQHWIRUDQ\GDPDJH([HUFLVHFDXWLRQYROWDJHLVSUHVHQWZLWKLQWKH%DWWHU\&DELQHWHYHQEHIRUHLQVWDOODWLRQ,IWKHUHDUHVLJQVRIGDPDJHGRQRWSURFHHG&DOO/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDW

    %DWWHU\6WRUDJH7KHEDWWHULHVXVHGLQWKH%DWWHU\&DELQHWKDYHDQH[FHOOHQWFKDUJHUHWDLQLQJFKDUDFWHULVWLF7KHEDWWHULHVFDQEHVWRUHGIRUXSWRVL[PRQWKVZLWKRXWDQ\DSSUHFLDEOHGHWHULRUDWLRQ6HOIGLVFKDUJHUDWHRIWKHEDWWHULHVLVDSSUR[LPDWHO\SHUPRQWK

    ZKHQWKHEDWWHULHVDUHVWRUHGLQWHPSHUDWXUHVRI&WR&)WR),IWKH%DWWHU\&DELQHWLVSODQQHGWREHVWRUHGIRUORQJHUWKDQVL[PRQWKVFRQWDFW/LHEHUW&XVWRPHU6HUYLFHIRUUHFRPPHQGHGDFWLRQ

    /RFDWLQJ7KH%DWWHU\&DELQHWFDQEHORFDWHGFRQYHQLHQWO\LQRURXWVLGHWKHFRPSXWHUURRP7KHIURQWDFFHVVRQO\GHVLJQHOLPLQDWHVVLGHDQGUHDUVHUYLFHFOHDUDQFHUHTXLUHPHQWV,WDOVRIHDWXUHVWRSRUERWWRPFDEOHHQWU\DUHDV+RZHYHUWKHUHDUHVHYHUDOFRQVLGHUDWLRQVWRORFDWLQJ\RXUQHZ%DWWHU\&DELQHW

    %ROW2Q&DELQHWVLQFKZLGHPDWFKLQJEDWWHU\FDELQHWVDUHGHVLJQHGDVDEROWRQVHFWLRQWRWKH836PRGXOHFDELQHW7KH\FDQQRWEHLQVWDOOHGVHSDUDWHIURPWKHPRGXOH

    836WREDWWHU\FDELQHW'&FDEOHVDUHSURYLGHGE\/LHEHUW6HH)LJXUH

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

    )LJXUH &DEOH'LVWDQFH7KH%DWWHU\&DELQHWVKRXOGEHORFDWHGDVFORVHDVSRVVLEOHWRWKH836

    FDELQHWWRPLQLPL]HYROWDJHGURSLQWKHSRZHUFDEOHV7KHPD[LPXPUHFRPPHQGHGGLVWDQFHLVFDEOHIHHWPHWHUV

    6HUYLFH&OHDUDQFH$OORZIURQWDFFHVVWRWKH%DWWHU\&DELQHWDWDOOWLPHVIRUPDLQWHQDQFHDQGVHUYLFLQJ(OHFWULFDOFRGHVUHTXLUHWKDWWKH%DWWHU\&DELQHWEHLQVWDOOHGZLWKQROHVVWKDQIHHWPHWHURIFOHDUDQFHDWWKHIURQWRIWKHFDELQHWZKHQRSHUDWLQJ6LGHDQGUHDUSDQHOVGRQRWUHTXLUHVHUYLFHFOHDUDQFH

    (QYLURQPHQW/RFDWHWKH%DWWHU\&DELQHWLQDFOHDQGU\HQYLURQPHQW5HFRPPHQGHGWHPSHUDWXUHUDQJHIRURSWLPXPSHUIRUPDQFHDQGOLIHWLPHLV&)WR&)

    $&$87,21

    $EDUULHUSDQHOPXVWEHSODFHGEHWZHHQWKHLQFKPDWFKLQJEDWWHU\FDELQHWDQGWKH836PRGXOH7KHEDUULHUPXVWEHLQVWDOOHGXWLOL]LQJWKHSDQHODQGKDUGZDUHZKLFKLVVXSSOLHGZLWKWKHLQFKPDWFKLQJEDWWHU\FDELQHW

    $&$87,21

    7ROHYHOEDWWHU\FDELQHWGRQRWDGMXVWOHYHOLQJIHHWZKLOHWKH\DUHVXSSRUWLQJWKHFDELQHWZHLJKW8VHDSU\EDURURWKHUH[WHUQDOGHYLFHWRSRVLWLRQDQGVXSSRUWWKHFDELQHW7KHQDGMXVWOHYHOLQJIHHWDQGUHPRYHVXSSRUWLQJGHYLFH

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    20/113

    14 Installation

    2.3.2 Non-Standard Batteries

    :KHQEDWWHULHVRWKHUWKDQDPDWFKLQJEDWWHU\FDELQHWDUHXVHGWKHFXVWRPHUPXVWSXUFKDVHIURP/LHEHUWDEDWWHU\GLVFRQQHFWVZLWFKDQGRYHUFXUUHQWSURWHFWLRQGHYLFHUDWHGIRU9'&0D[LPXPSHUPLWWHGDYDLODEOHIDXOWFXUUHQWLV$,&

    ,QVWDOOEDWWHU\UDFNVFDELQHWVDQGEDWWHULHVSHUPDQXIDFWXUHUVLQVWDOODWLRQDQGPDLQWHQDQFHLQVWUXFWLRQV

    9HULI\EDWWHU\DUHDKDVDGHTXDWHYHQWLODWLRQDQGEDWWHU\RSHUDWLQJWHPSHUDWXUHFRPSOLHV

    ZLWKPDQXIDFWXUHUVVSHFLILFDWLRQ

    ,I\RXKDYHDQ\TXHVWLRQVFRQFHUQLQJEDWWHULHVEDWWHU\UDFNVRUDFFHVVRULHVFRQWDFW/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDW

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    21/113

    Installation 15

    2.4 Electrical Wiring

    5HIHUWR7DEOH 6LWH3ODQQLQJ'DWD6HULHV836WRN9$DQG7DEOH 6LWH3ODQQLQJ'DWD6HULHV836WRN9$DQGLQVWDOODWLRQGUDZLQJV)LJXUH WKURXJK)LJXUH 5HIHUWR7DEOH DQG7DEOH DQG)LJXUH IRUZLUHWHUPLQDWLRQGDWD$OVRUHIHUWRHTXLSPHQWQDPHSODWHIRUWKHPRGHOQXPEHUUDWLQJDQGYROWDJHVRFRUUHFWYDOXHVDUHXVHGIURPWKHWDEOHVDVVRFLDWHGZLWKWKHGUDZLQJV

    2.4.1 UPS Wire Size Guidelines

    3URSHUZLUHVL]LQJPXVWEHEDVHGRQQXPHURXVVLWHVSHFLILFFRQGLWLRQV7DEOH DUHSULQWRI7DEOH

    RIWKH1(&1DWLRQDO(OHFWULFDO&RGH1)3$&RS\ULJKWLVLQFOXGHGZLWKSHUPLVVLRQRIWKH1DWLRQDO)LUH3URWHFWLRQ$VVRFLDWLRQDVDFRQYHQLHQFHWRDVVLVWLQGHWHUPLQLQJWKHPLQLPXPVL]HZLUHVIRU\RXU836DSSOLFDWLRQ5HIHUWRQRWHV WKURXJK EHORZWKHSUHVHQWHGLWLRQRIWKH1(&DQGDOODSSOLFDEOHORFDOFRGHVIRU\RXUSDUWLFXODUVLWHUHTXLUHPHQWV

    5HIHUWRWKH/LHEHUWFKDUWRUGUDZLQJWKDWVKRZVWKHDPSDFLWLHVIRU\RXU836

    ,QSXWDPSDFLW\PXVWEHEDVHGRQRILQSXWFXUUHQWDWIXOOUDWHGORDGSOXVRIEDWWHU\FKDUJLQJFXUUHQW

    %HVXUHWRUHIHUWRDOOUHTXLUHPHQWVZLWKLQ$UWLFOHRIWKH1(&

    0LQLPXPVL]HGJURXQGLQJFRQGXFWRUVDUHWREHSHU1(&

    1HXWUDOFRQGXFWRUVDUHWREHVL]HGSHU1(&QRWH

    7KH836V\VWHPPXVWEHLQVWDOOHGLQDFFRUGDQFHZLWKWKHSUHVHQWHGLWLRQRIWKH1(&DQGDOOORFDOFRGHVLQFOXGLQJWKHFRGHVRIIRUHLJQFRXQWULHVZKHUHDSSOLFDEOH

    2.4.2 Power and Control Wiring

    9HULI\WKDWSRZHUZLULQJLVUXQLQLQGLYLGXDOVHSDUDWHFRQGXLWRUFDEOHWUD\9HULI\WKDWFRQWUROZLULQJLVUXQLQLQGLYLGXDOVHSDUDWHVWHHOFRQGXLW

    2EVHUYHORFDOVWDWHDQGQDWLRQDOHOHFWULFDOFRGHV9HULI\XWLOLW\SRZHUDQGLWVRYHUFXUUHQWSURWHFWLRQUDWLQJZLOODFFRPPRGDWHWKH836,1387UDWLQJLQFOXGLQJEDWWHU\UHFKDUJLQJ

    $VDIHW\JURXQGZLUHPXVWEHUXQIURPEXLOGLQJJURXQGWRJURXQGSRLQWLQWKH8360RGXOH&DELQHW%DWWHU\&DELQHW([WHUQDO0DLQWHQDQFH%\SDVV&DELQHWLIDSSOLFDEOHDQG6OLP/LQH'LVWULEXWLRQLIDSSOLFDEOH7KHJURXQGLQJFRQGXFWRUVKDOOFRPSO\ZLWKWKHIROORZLQJFRQGLWLRQVRILQVWDOODWLRQ

    D $QLQVXODWHGJURXQGLQJFRQGXFWRUWKDWLVLGHQWLFDOLQVL]HLQVXODWLRQPDWHULDODQGWKLFNQHVVWRWKHJURXQGHGDQGXQJURXQGHGEUDQFKFLUFXLWVXSSO\FRQGXFWRUVH[FHSWWKDWLWLVJUHHQZLWKRUZLWKRXWRQHRUPRUH\HOORZVWULSHVLVWREHLQVWDOOHGDVSDUWRIWKHEUDQFKFLUFXLWWKDWVXSSOLHVWKHXQLWRUV\VWHP

    $:$51,1*

    $//32:(5&211(&7,2160867%(&203/(7('%

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    22/113

    16 Installation

    E 7KHJURXQGLQJFRQGXFWRUGHVFULEHGLQLWHPLVWREHJURXQGHGWRHDUWKDWWKHVHUYLFHHTXLSPHQWRULIVXSSOLHGE\DVHSDUDWHO\GHULYHGV\VWHPDWWKHVXSSO\WUDQVIRUPHURUPRWRUJHQHUDWRUVHW

    F 7KHDWWDFKPHQWSOXJUHFHSWDFOHVLQWKHYLFLQLW\RIWKHXQLWRUV\VWHPDUHDOOWREHRIDJURXQGLQJW\SHDQGWKHJURXQGLQJFRQGXFWRUVVHUYLQJWKHVHUHFHSWDFOHVDUHWREHFRQQHFWHGWRHDUWKJURXQGDWWKHVHUYLFHHTXLSPHQW

    2EVHUYHFORFNZLVHSKDVHURWDWLRQRIDOOSRZHUZLULQJ3KDVH$OHDGV3KDVH%OHDGV3KDVH&$TXDOLILHGHOHFWULFLDQVKRXOGFKHFNWKHSKDVHURWDWLRQ

    1(&&ODVVZLULQJPHWKRGVDUHUHTXLUHGIRUFRQWURODQGFRPPXQLFDWLRQ&ODVVFLUFXLWV

    2.4.3 Battery Wiring

    7KHPDWFKLQJ%DWWHU\&DELQHWLVGHVLJQHGIRUHDV\DQGFRQYHQLHQWLQVWDOODWLRQ2QFHWKHXQLWLVORFDWHGLQILQDOSRVLWLRQFRQQHFWZLULQJEHWZHHQEDWWHU\FDELQHWDQG836PRGXOH'&FDEOHVDUH

    SURYLGHGE\/LHEHUWIRULQFKZLGHPDWFKLQJERWWRPEDWWHU\FDELQHWV

    '&FDEOHVDUHSURYLGHGE\RWKHUVIRUDOORWKHUEDWWHU\V\VWHPV

    3RZHUZLULQJWRWKH%DWWHU\&DELQHWFRQQHFWVSRVLWLYHQHJDWLYHDQGJURXQGSRZHUFDEOHVIURP

    WKH%DWWHU\&DELQHWWRWKHDVVRFLDWHG836

    &RQQHFWLRQRIWKH836WRWKH%DWWHU\&DELQHWVHUYHVWRERWKFKDUJHDQGGLVFKDUJHWKHEDWWHULHVZKHQQHHGHG

    &DEOHVWRWKH%DWWHU\&DELQHWVKRXOGEHVL]HGIRUDPD[LPXPYROWWRWDOOLQHORVVDWWKHPD[LPXPGLVFKDUJHFXUUHQWIRUWKHHTXLSPHQW5HIHUWRWKH7DEOH 6LWH3ODQQLQJ'DWD6HULHV836WRN9$DQG7DEOH 6LWH3ODQQLQJ'DWD6HULHV836WRN9$IRU

    PD[LPXPEDWWHU\GLVFKDUJHFXUUHQW$TXDOLILHGOLFHQVHGHOHFWULFLDQFDQVL]HWKHZLULQJIRU\RXULQVWDOODWLRQXVLQJWKLVLQIRUPDWLRQ

    &DOO/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDWWRVFKHGXOHLQVWDOODWLRQFKHFNRXWILQDOEDWWHU\LQWHUFHOOFRQQHFWLRQVDQGVWDUWXS

    $&$87,21

    %HVXUHWKHEDUULHUEHWZHHQWKH836DQGLQFKPDWFKLQJEDWWHU\SDFNLVLQSODFH6HH)LJXUH

    $:$51,1*

    0$.(685($//32:(5$1'&21752/,)$33/,&$%/(:,5,1*)5207+(836,6'((1(5*,=('$1'3523(5/

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    23/113

    Installation 17

    Table 4 Table 310-16Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60 to 90C (140 to 194F)1

    Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient Temperature of 30 (86F)

    Size Temperature Rating of Conductor. See Table 310-13. Size

    AWGkcmil

    60C(140F)

    75C(167F)

    90C(194F)

    60C(140F)

    75C(167F)

    90C(194F)

    AWGkcmil

    TypesTW

    UF

    TypesFEPW+,

    RH,RHW,THHW,THW,

    THWN,XHHW,

    USE, ZW

    TypesTBS, SA,

    SIS,FEP,FEPB,MI,

    RHH, RHW-2THHN,THHW,THW-2,THWN-2,

    USE-2, XHH,XHHW

    XHHW-2,ZW-2

    TypesTW

    UF

    TypesRH, RHW,

    THHW,THW,

    THWN,XHHW,

    USE

    TypesTBS,

    SA,SIS,THHN,THHW,

    THW-2, THWN-2,RHH, RHW-2,

    USE-2,XHH, XHHW,XHHW-2, ZW-2

    Copper Aluminum or Copper-Clad Aluminum

    18161412108

    .......

    .......20253040

    .......

    .......20253550

    1418

    25304055

    .......

    .......

    .......202530

    .......

    .......

    .......203040

    .......

    .......

    .......253545

    .......

    .......

    .......12108

    64321

    55708595110

    6585

    100115130

    7595

    110130150

    4055657585

    50657590100

    607585

    100115

    64321

    1/02/03/04/0

    125145165195

    150175200230

    170195225260

    100115130150

    120135155180

    135150175205

    1/02/03/04/0

    250300350400500

    215240260280320

    255285310335380

    290320350380430

    170190210225260

    205230250270310

    230255280305350

    250300350400500

    600700750800900

    355385400410435

    420460475490520

    475520535555585

    285310320330355

    340375385395425

    385420435450480

    600700750800900

    10001250150017502000

    455495520545560

    545590625650665

    615665705735750

    375405435455470

    445485520545560

    500545585615630

    10001250150017502000

    Correction Factors

    AmbientTemp C

    For ambient temperatures other than 30C (86F), multiply the allowable ampacities shownabove by the appropriate factor shown below.

    AmbientTemp F

    21-2526-3031-3536-40

    41-4546-5051-5556-6061-7071-80

    1.081.00.91.82

    .71.58

    .41.....................

    1.051.00.94.88

    .82.75

    .67

    .58

    .33.......

    1.041.00.96.91

    .87.82

    .76

    .71

    .58

    .41

    1.081.00.91.82

    .71.58

    .41.....................

    1.051.00.94.88

    .82.75

    .67

    .58

    .33.......

    1.041.00.96.91

    .87.82

    .76

    .71

    .58

    .41

    70-7778-8687-9596-104

    105-113114-122123-131132-140141-158159-176

    Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with anobelisk () shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes forNo. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature andnumber of conductors have been applied.1 Reprinted with permission from NFPA 70-1993, the National Electrical Code, Copyright 1996, National Fire Protection Association,Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association, on thereferenced subject which is represented only by the standard in its entirety.

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    24/113

    18 Installation

    Table 5 Connection Type / Wire Size Range

    Connection Type

    UPS ModuleRating

    kVA AC Input BatteryBypass Input& AC Output Neutral Ground

    10 - 30 Compressionlug

    #14 to #1/0

    Compressionlug

    #14 to #1/0

    Compressionlug

    #14 to #1/0

    Compressionlug

    #14 to #1/0

    Ground studs3/8" - 16 x 1.00"

    Lug required

    40 - 50 Compressionlug

    #6 to 250 kcmil

    Compressionlug

    #6 to 250 kcmil

    Compressionlug

    #6 to 250 kcmil

    Natural studs3/8" - 16 x 1.00"

    Lug required

    Ground studs3/8" - 16 x 1.00"

    Lug required

    65 - 125 Bus bars (2 x 3-1/4) with connecting hardware (3/8) are provided for all power wiringterminations. A field-supplied lug is required.

    Use factory supplied connections for terminations where they are provided. Refer to Figure 11for field-supplied wiring termination details. Use commercially available UL listed solderless lugs for the wire sizerequired for your application. Connect wire to the lug using tool and procedure specified by the lugmanufacturer.

    Table 6 Torque Specifications (Unless Otherwise Labeled)

    Nut and Bolt Combinations

    Bolt Shaft Size

    Grade 2Standard

    Electrical Connectionswith Belleville Washers

    Lb-in N-m Lb-in N-m

    1/4 53 6.0 46 5.2

    5/16 107 12.1 60 6.8

    3/8 192 21.7 95 10.7

    1/2 428 48.4 256 28.9

    Terminal Block Compression Lugs (For Control Wiring)

    UPS ModuleRating

    kVA Wiring

    Wire Size or

    Range Lb-in N-m

    10 - 125 Control #22 - #14 3.5 to 5.3 0.4 to 0.6

    10 - 30 Power #6 - #1/0 50 5.6

    40 - 50 Power #6 250 28.2

    250 kcmil 275 31.1

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    25/113

    Installation 19

    2.4.4 Wiring Connections

    9HULI\WKHIROORZLQJFRQQHFWLRQVKDYHEHHQPDGH

    $&SRZHUFDEOHVIURPLQSXWSRZHUVRXUFHRURSWLRQDOH[WHUQDOPDLQWHQDQFHE\SDVVFDELQHWWR8360RGXOH,QSXW2EVHUYH$%&SKDVHURWDWLRQ

    6WDQGDUG6HULHV836PRGXOHVDUHSURYLGHGZLWKDQLQSXWDXWRWUDQVIRUPHU,IWKHUHDUHOLQHWRQHXWUDOORDGVFRQQHFWHGWRWKH836RXWSXWWKHLQSXWVRXUFHPXVWEHZ\HFRQQHFWHGDQGKDYHWKUHHSKDVHVSOXVQHXWUDOSOXVJURXQG

    ,IWKH6HULHV836PRGXOHLVSURYLGHGZLWKDQRSWLRQDOLQSXWLVRODWLRQWUDQVIRUPHUDQLQSXWQHXWUDOFRQGXFWRULVQRWUHTXLUHGDQGWKH836FDQEHIHGIURPHLWKHUGHOWDRUZ\HFRQQHFWHGXWLOLW\VHUYLFH

    '&SRZHUFDEOHVSRVLWLYHDQGQHJDWLYHIURPEDWWHU\FDELQHWWR836PRGXOH'&EXVREVHUYHSURSHUSRODULW\

    :KHQPXOWLSOHFRQGXFWRUVDUHXVHGIURPWKHEDWWHU\WRWKH836PRGXOHLWLVQHFHVVDU\WRUXQWKHVDPHQXPEHURISRVLWLYHDQGQHJDWLYHFDEOHVLQWKHVDPHFDEOHWUD\RUFRQGXLW

    $&SRZHUFDEOHVIURPWKH836RXWSXWWRWKHFULWLFDOORDGGLVWULEXWLRQRURSWLRQDOH[WHUQDOPDLQWHQDQFHE\SDVVFDELQHWRURSWLRQDOVOLPOLQHGLVWULEXWLRQSDQHO

    2EVHUYH$%&3KDVH5RWDWLRQ

    7KHRXWSXWVRXUFHVKRXOGKDYHWKUHHSKDVHVSOXVQHXWUDOLIOLQHWRQHXWUDOORDGVZLOOEHSRZHUHGIURPWKH836RXWSXWSOXVJURXQG

    $Q\DGGLWLRQDOVSHFLDOFRQWUROZLULQJPXVWEHUXQLQLQGLYLGXDOVHSDUDWHFRQGXLW 836LQSXWDQGRXWSXWQHXWUDOPXVWEHFRQQHFWHGWRRQO\RQHFRPPRQSRLQWLQWKH8367KLV

    QHXWUDOOLQHPXVWEHJURXQGHGDWWKHVRXUFH$QLQSXWQHXWUDOLVQRWUHTXLUHGZLWKWKHRSWLRQDOLQSXWLVRODWLRQWUDQVIRUPHU

    2.4.5 Wiring Inspection

    9HULI\DOOSRZHUFRQQHFWLRQVDUHWLJKW

    9HULI\DOOFRQWUROZLUHWHUPLQDWLRQVDUHWLJKW

    9HULI\DOOSRZHUZLUHVDQGFRQQHFWLRQVKDYHSURSHUVSDFLQJEHWZHHQH[SRVHGVXUIDFHVSKDVHWRSKDVHDQGSKDVHWRJURXQG

    9HULI\WKDWDOOFRQWUROZLUHVDUHUXQLQLQGLYLGXDOVHSDUDWHULJLGVWHHOFRQGXLW

    127(

    5HIHUWR 6\VWHP2SWLRQVIRULQVWUXFWLRQVDQGGUDZLQJVIRURSWLRQDOFRPSRQHQWV

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    26/113

    20 Installation

    Figure 1 Single Line Diagram 10-125 kVA

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    27/113

    Installation 21

    Figure 2 Single Line Diagram 10-125 kVA with Optional External Maintenance Bypass

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    28/113

    22 Installation

    Figure 3 UPS Cabinet Installation Diagram 10-30 kVA

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    29/113

    Installation 23

    Figure 4 UPS Cabinet Installation Diagram 40-50 kVA

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    30/113

    24 Installation

    Figure 5 UPS Cabinet Installation Diagram 65-125 kVA

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    31/113

    Installation 25

    Figure 6 Battery Cabinet Installation Diagram - 22-inch Frame

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    32/113

    26 Installation

    Figure 7 Battery Cabinet Installation Diagram - 36-inch Frame

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    33/113

    Installation 27

    Figure 7 Battery Cabinet Installation Diagram - 36-inch Frame (continued)

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    34/113

    28 Installation

    Figure 8 Control Wiring Diagram 10-30 kVA

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    35/113

    Installation 29

    Figure 9 Control Wiring Diagram 40-50 kVA

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    36/113

    30 Installation

    Figure 10 Control Wiring Diagram 65-125 kVA

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    37/113

    Installation 31

    Figure 11 Field Wiring Terminations

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    38/113

    32 Installation

    Figure 11 Field Wiring Terminations (continued)

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    39/113

    Operation 33

    3.0 OPERATION

    3.1 Operator Controls and Indicators

    7KH6HULHVRSHUDWRUFRQWUROVDQGLQGLFDWRUVDUHORFDWHGLQRQHUHFHVVHGSDQHORQWKH8360RGXOH&DELQHWGRRU6HH)LJXUH

    7KHUHFWDQJXODUSDQHOFRQWDLQV

    'LJLWDOGLVSOD\VFUHHQDQGVHOHFWLRQSDGV

    3RZHU6WDWXV'LDJUDP

    5RWDU\6ZLWFKDQG$GYLVRU\'LVSOD\

    3.1.1 Digital Display Screen

    7KHGLVSOD\VFUHHQLVFRPSRVHGRIOLTXLGFU\VWDOVDUUDQJHGLQIRXUOLQHVRIFKDUDFWHUVHDFK6HH)LJXUH 7KHLQWHUQDOFRQWUROV\VWHPH[HFXWHVSURJUDPVZKLFKJHQHUDWHPHVVDJHVRQWKLVGLVSOD\VFUHHQ6FUHHQPHVVDJHVLQVWUXFWWKHXVHUGXULQJVWDUWXSRSHUDWLRQDQGVKXWGRZQ7KHVFUHHQDOVRGLVSOD\VVWDWXVLQIRUPDWLRQRQUHTXHVW6HH)LJXUH 1RWHWKDWWKHUHLVDQLQWHUQDOFRQWURODGMXVWPHQWIRU/&'VFUHHQFRQWUDVW+DYHWKHFRQWURODGMXVWHGE\WKH/LHEHUW&66HQJLQHHUGXULQJVWDUWXS

    Figure 12 Operator Controls and Indicators on UPS Module Cabinet Front

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    40/113

    34 Operation

    Figure 13 Block Diagram of the Series 300 UPS

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    41/113

    Operation 35

    3.1.2 Selection Pads

    7KHWKUHHWRXFKVHQVLWLYHVHOHFWLRQSDGVDUH8S'RZQDQG$ODUP6LOHQFH7KHVHSDGVDUHODEHOHGZLWKV\PEROVUDWKHUWKDQZRUGV6HH)LJXUH

    7KH8SDQG'RZQVHOHFWLRQSDGVDUHORFDWHGEHORZWKHGLJLWDOGLVSOD\VFUHHQ8VHWKHPWRPRYHWKURXJKYDULRXVPHQXVSUHVHQWRQWKHVFUHHQ

    7KH$ODUP6LOHQFHSDGFDQFHOVWKHDXGLEOHDODUPZKLFKLVHPLWWHGZKHQDQDEQRUPDOFRQGLWLRQLVGHWHFWHG7KH$ODUP6LOHQFHSDGLVDOVRXVHGWRPRYHWKURXJKWKHYDULRXVPHQXVSUHVHQWRQWKH

    VFUHHQ

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    42/113

    36 Operation

    3.1.4 Rotary Switch

    7KH5RWDU\6ZLWFKLVORFDWHGLQWKHORZHUSDUWRIWKHUHFHVVHGSDQHO7KLVVZLWFKSURYLGHVVLQJOHSRLQWFRQWURORIWKH8366HH)LJXUH

    7KHILYH5RWDU\6ZLWFKSRVLWLRQVDUH

    3RVLWLRQ2IIGLVFRQQHFWVDOOSRZHUWRORDG836LVVKXWGRZQ$OODODUPVDQGLQGLFDWRUVDUHLQRSHUDWLYHQRSRZHULVVXSSOLHGWRWKHORDGWKURXJK836

    3RVLWLRQ2Q%\SDVVFRQQHFWVWKHFULWLFDOORDGWRLQSXWSRZHUWKURXJKWKH0DLQWHQDQFH%\SDVV/LQH8360RGXOHLVGHHQHUJL]HGIRUPDLQWHQDQFHSXUSRVHV

    3RVLWLRQ8366WDUWFRQQHFWVSRZHUWRFRQWUROVUHFWLILHUFKDUJHULQYHUWHUDQGLQLWLDWHVWHVWVRQ836FRPSRQHQWVZKLOHWKHORDGLVVXSSOLHGWKURXJKWKH0DLQWHQDQFH%\SDVV/LQH

    3RVLWLRQ836&KHFNFRQQHFWVWKHEDWWHU\WRWKH836DQGLQLWLDWHVWHVWVRQWKHEDWWHU\'&ZDONLQDQGVWDWLFE\SDVVOLQHZKLOHWKHORDGLVVXSSOLHGWKURXJKWKH0DLQWHQDQFH%\SDVV/LQH

    3RVLWLRQ2Q836FRQQHFWVWKHFULWLFDOORDGWRWKH8360RGXOHDQGHVWDEOLVKHVQRUPDORSHUDWLRQ

    3.1.5 Advisory Display

    7KH$GYLVRU\'LVSOD\LVORFDWHGDERYHWKH5RWDU\6ZLWFKDQGFRQVLVWVRI

    $EDQGODEHOHG3DXVH

    $FORFNZLVHDGYDQFHDUURZ

    $FRXQWHUFORFNZLVHUHWXUQDUURZ

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

    Figure 16 Rotary Switch and Advisory Display

    127(

    6LQJOHSRLQWFRQWUROVLPSOLILHVVWDUWXSDQGRSHUDWLRQRIWKH836+RZHYHUUHDGLQVWUXFWLRQVFDUHIXOO\EHIRUHRSHUDWLQJWKH5RWDU\6ZLWFK,PSURSHUSRVLWLRQLQJRI5RWDU\6ZLWFKFRXOGUHVXOWLQXQZDQWHGDFWLRQV

    )ROORZXVHUSURPSWVRQGLVSOD\VFUHHQ

    $&$87,21

    'RQRWRSHUDWH5RWDU\6ZLWFKGXULQJDSRZHUIDLOXUH'RLQJVRZLOOUHVXOWLQDQLPPHGLDWHORVVRISRZHUWRWKHORDG

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    43/113

    Operation 37

    3.2 Display Screen Menu

    2SHUDWLQJWKH836FRQVLVWVRIREVHUYLQJWKHLQGLFDWRUVRQWKHRSHUDWRUFRQWUROSDQHODQGPDNLQJDSSURSULDWHUHVSRQVHV)XUWKHU836PRQLWRULQJDQGWHVWLQJFDQEHDFKLHYHGE\PRYLQJWKURXJKDVHULHVRIPHQXVHOHFWLRQVSUHVHQWRQWKHGLVSOD\VFUHHQ6HH)LJXUH

    :KHQLQSXWSRZHULVILUVWDSSOLHGWRWKH836WKH'LVSOD\6FUHHQGLVSOD\VDPHVVDJHSURPSWLQJWKHRSHUDWRUWRFKHFNWKH6\VWHP&RQILJXUDWLRQDQGWKHQWRSURFHHGWRWKH6WDUW8SVFUHHQV

    2QFHVWDUWXSLVFRPSOHWHDQGQRUPDOFRQGLWLRQVH[LVWWKH1250$/23(5$7,21GHIDXOWVFUHHQPHVVDJHZLOOEHWKHRQO\VFUHHQPHVVDJHGLVSOD\HG7KLVDVVXUHVWKHRSHUDWRUWKDWSRZHUWRWKHORDGLVEHLQJFRQGLWLRQHGDQGEDFNHGXSDQGWKDWQRRSHUDWRUDFWLRQLVQHFHVVDU\

    $GGLWLRQDOPHQXVHOHFWLRQVDUHDYDLODEOHDQGDUHSUHVHQWHGLQDFLUFXODUDUUDQJHPHQW7KH\DUHFDWHJRUL]HGDVIROORZV$ODUP0HVVDJHV0HWHU)XQFWLRQV&RQILJXUDWLRQ6FUHHQV$ODUP+LVWRU\DQG/DPS+RUQ7HVW7RPRYHEHWZHHQHDFKFDWHJRU\VLPSO\SUHVVWKH'RZQ8SRU$ODUP6LOHQFHSDGDVSURPSWHGE\WKHLFRQSUHVHQWLQWKHORZHUULJKWKDQGFRUQHURIHDFKPHVVDJHVFUHHQ

    Figure 17 Menu Selection Arrangement

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    44/113

    38 Operation

    3.3 Default Screen Messages

    2QHRIVL[GHIDXOWPHVVDJHVZLOODXWRPDWLFDOO\DSSHDURQWKHGLVSOD\VFUHHQ7KH\DUH

    1RUPDO2SHUDWLRQ

    :DUQLQJ/RDGRQ0DLQWHQDQFH%\SDVV

    :DUQLQJ/RDGRQ836

    :DUQLQJ/RDGRQ6WDWLF%\SDVV

    )DXOW6\VWHP6KXWGRZQ 836RQ%DWWHU\

    3.3.1 Normal Operation

    7KH1250$/23(5$7,21PHVVDJHLVGLVSOD\HGGXULQJQRUPDORSHUDWLQJFRQGLWLRQV,WLQGLFDWHV

    7KDWV\VWHPFRQGLWLRQVDUHQRUPDODOOPHWHUUHDGLQJVDUHQRPLQDODQGWKH8360RGXOHLVV\QFKURQL]HGZLWKWKHLQSXWSRZHU

    7KDWWKHFULWLFDOORDGLVVXSSRUWHGE\WKH836

    7KHSHUFHQWDJHRISRZHUEHLQJXVHGE\WKHFULWLFDOORDGUHODWLYHWRWKH836UDWLQJ7KHYDOXHUHSUHVHQWHGE\;;;ZLOODOZD\VEHOHVVWKDQRUHTXDOWRLQD1250$/23(5$7,21PHVVDJH,IWKHFULWLFDOORDGLVGUDZLQJPRUHWKDQRIWKH836UDWHGORDGDZDUQLQJPHVVDJHZLOODSSHDU

    7KH8S'RZQRU$ODUP6LOHQFHV\PEROIODVKHVLQWKHORZHUULJKWKDQGFRUQHURIWKHVFUHHQ7KLVLVQRUPDODQGLQGLFDWHVWKDWWKHRSHUDWRUPD\F\FOHWKURXJKYDULRXVPRQLWRULQJDQGWHVWIXQFWLRQVE\SUHVVLQJWKHDSSURSULDWHVHOHFWLRQSDG

    3.3.2 Warning: Load on Maintenance Bypass

    7KLVPHVVDJHLQGLFDWHVWKDWWKHFULWLFDOORDGLVEHLQJVXSSOLHGSRZHUWKURXJKWKH0DLQWHQDQFH%\SDVV/LQH3UHVVWKH'RZQSDGWRYLHZWKHDFWLYH$ODUP0HVVDJHV

    127(

    $GGLWLRQDO$ODUP0HVVDJHVPD\EHDFWLYHDQGFDQEHYLHZHGE\SUHVVLQJWKH'RZQSDG:KHQWKHDODUPFRQGLWLRQLVFRUUHFWHGWKHPHVVDJHZLOOEH

    FOHDUHGIURPWKHPHVVDJHOLVWEXWZLOOUHPDLQLQWKHDODUPKLVWRU\EXIIHU)RUDOLVWRI$ODUP0HVVDJHVZLWKWKHLUPHDQLQJDQGUHFRPPHQGHGFRUUHFWLYHDFWLRQVUHIHUWR $ODUP0HVVDJHV

    NORMAL OPERATIONLoad on UPS

    Load XXX%

    WARNING: Loadon Maintenance

    Bypass

    Check Messages

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    45/113

    Operation 39

    3.3.3 Warning: Load on UPS

    7KLVPHVVDJHLQGLFDWHVWKDWDQDODUPFRQGLWLRQH[LVWV+RZHYHUWKHFULWLFDOORDGLVVWLOOUHFHLYLQJFRQGLWLRQHGSRZHUWKURXJKWKH8363UHVVWKH'RZQSDGWRYLHZWKH$ODUP0HVVDJHV

    3.3.4 Warning: Load on Static Bypass

    7KLVPHVVDJHPHDQVWKHORDGKDVEHHQDXWRPDWLFDOO\WUDQVIHUUHGIURP8360RGXOHRXWSXWWR

    6WDWLF%\SDVV/LQHEHFDXVHRIDQDODUPFRQGLWLRQ3UHVVWKH'RZQSDGWRYLHZWKH$ODUP0HVVDJHV

    3.3.5 Fault: System Shutdown

    7KLVPHVVDJHPHDQVWKH836KDVEHHQVKXWGRZQE\WKHLQWHUQDOFRQWUROV\VWHP3UHVVWKH'RZQSDGWRYLHZWKH$ODUP0HVVDJHVDQGWKHQSHUIRUPD836VWDUWXSSURFHGXUHDIWHUWKHDODUPFRQ

    GLWLRQKDVEHHQFRUUHFWHG

    3.3.6 UPS on Battery

    7KLVPHVVDJHDSSHDUVZKHQHYHUWKHLQSXWSRZHUWRWKH836LVQRWDYDLODEOHRULVRXWVLGHRIVSHFLILHGOLPLWV7KHORDGLVEHLQJVXSSRUWHGE\WKHEDWWHU\ZKLFKKDVDQHVWLPDWHG;;PLQXWHVRISRZHUUHPDLQLQJZLWKWKHSUHVHQWFRQQHFWHGORDG3UHVVWKH'RZQSDGWRYLHZWKH$ODUP0HVVDJHV

    WARNING:Load on UPS

    Check Messages

    WARNING:Load on Static

    Switch

    Check Messages

    FAULT:SYSTEM SHUTDOWN

    Check Messages

    UPS ON BATTERYTime Remaining

    >XX Minutes

    Check Messages

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    46/113

    40 Operation

    3.4 Alarm Messages

    3.4.1 UPS Response to an Alarm

    ,IWKHLQWHUQDOFRQWUROV\VWHPGHWHFWVDQDEQRUPDOFRQGLWLRQ

    $QDXGLEOHDODUPZLOOVRXQGDQGWKHGLJLWDOGLVSOD\ZLOOLQVWUXFW\RXWR&KHFN0HVVDJHV

    $Q$GYLVRU\'LVSOD\/('PD\LOOXPLQDWHSURPSWLQJ\RXWRWXUQWKH5RWDU\6ZLWFKLQDFRUUHFWLYHDFWLRQRUQRWWRWXUQWKH5RWDU\6ZLWFKDWDOO

    $Q$ODUP0HVVDJHZLOOEHGLVSOD\HGRQWKH$ODUP0HVVDJHVVFUHHQ5HIHUWR $ODUP0HVVDJHVIRUGHVFULSWLRQVDQGUHFRPPHQGHGFRUUHFWLYHDFWLRQV

    3.4.2 Operator Response to an Alarm &DQFHOWKHDXGLEOHDODUPE\SUHVVLQJWKH$ODUP6LOHQFHSDG

    3UHVVWKH'RZQSDGDVSURPSWHGWRYLHZWKH$ODUP0HVVDJHV5HIHUWR $ODUP0HVVDJHVIRUGHVFULSWLRQVDQGUHFRPPHQGHGFRUUHFWLYHDFWLRQV&DOO/LHEHUW&XVWRPHU

    6HUYLFHDQG6XSSRUWDWLI\RXUHTXLUHDVVLVWDQFH 2EVHUYHWKHGHIDXOWVFUHHQIRUWKH1250$/23(5$7,21PHVVDJHRUWKHGLVSOD\RI

    DGGLWLRQDOLQVWUXFWLRQV

    ,ID836VWDUWXSLVUHTXLUHGDIWHUFRUUHFWLRQRIWKHDODUPFRQGLWLRQUHIHUWR 6WDUW8S

    127(

    $IWHUWKHDXGLEOHDODUPKDVEHHQVLOHQFHGE\SUHVVLQJWKH$ODUP6LOHQFHSDGWKHRFFXUUHQFHRIDQRWKHUDXGLEOHDODUPLQGLFDWHVWKHH[LVWHQFHRIDQRWKHUDEQRUPDOFRQGLWLRQ

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    47/113

    Operation 41

    3.5 System Status Screens

    3HULRGLFDOO\FKHFNWKHV\VWHPVWDWXVUHDGLQJVDQGFRPSDUHWKHPWRWKHQRUPDOUHDGLQJVIRU\RXU6HULHV836PRGHO6HH 6SHFLILFDWLRQV

    3.5.1 Meter Functions

    7RGLVSOD\YDULRXVPHWHULQJLQIRUPDWLRQGXULQJQRUPDORSHUDWLQJFRQGLWLRQVSUHVVWKH'RZQSDGIURPWKH1250$/23(5$7,21GHIDXOWVFUHHQXQWLOWKHIROORZLQJPHVVDJHDSSHDUV

    /RDG7KLVVFUHHQVKRZVWKHSHUFHQWRIUDWHGSRZHUEHLQJXVHGE\WKHFULWLFDOORDG7KHORDGRQHDFKSKDVH$%DQG&LVDOVRVKRZQ

    '&%XV7KLVVFUHHQVKRZVWKHYROWDJHRQWKH'&EXVEDWWHU\%DWWHU\FXUUHQWLVDOVRVKRZQ,IWKHEDWWHU\FXUUHQWLQGLFDWLRQLVSRVLWLYHWKHZRUG&KDUJLQJZLOODSSHDURQWKHVFUHHQ,IWKHEDWWHU\FXUUHQWLVQHJDWLYHWKHZRUG'LVFKDUJLQJZLOODSSHDU

    ,QSXW7KLV,QSXWVFUHHQLVGLVSOD\HGIRUHDFKSKDVHRILQSXWSRZHUSKDVHV$%DQG&7KHVFUHHQGLVSOD\VWKHLQSXWOLQHWROLQHYROWDJH$%%&RU&$OLQHWRQHXWUDOYROWDJHDQGFXUUHQWIRUWKDWSKDVH

    2XWSXW7KLV2XWSXWVFUHHQLVGLVSOD\HGIRUHDFKSKDVHRIRXWSXWSRZHUSKDVHV$%DQG&7KH

    VFUHHQGLVSOD\VWKHRXWSXWOLQHWROLQHYROWDJH$%%&RU&$OLQHWRQHXWUDOYROWDJHDQGFXUUHQWIRUWKDWSKDVH

    )UHTXHQF\7KLVVFUHHQGLVSOD\VWKHIUHTXHQF\RIERWKWKHLQSXWDQGRXWSXWSRZHU

    LOAD: XXX%A PHASE XXX kVAB PHASE XXX kVAC PHASE XXX kVA

    DC BUSVoltage 410

    Amps 15

    Charging

    INPUT A-PHASEA - B XXX VOLTSA - N XXX VOLTS

    A XXX AMPS

    OUTPUT A-PHASEA - B XXX VOLTSA - N XXX VOLTS

    A XXX AMPS

    FREQUENCY

    60.0 Hz OUTPUT60.0 Hz INPUT

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    48/113

    42 Operation

    3.5.2 System Configuration

    7RGLVSOD\6\VWHP&RQILJXUDWLRQLQIRUPDWLRQGXULQJQRUPDORSHUDWLRQFRQGLWLRQVSUHVVWKH'RZQSDGXQWLOWKHIROORZLQJVFUHHQDSSHDUV

    8VHWKHVHOHFWLRQSDGVWRVHWFXVWRPHUDGMXVWDEOHVLWHSDUDPHWHUVZKHQWKHDSSURSULDWHVFUHHQLVGLVSOD\HG7KHVHLQFOXGHODQJXDJHWLPHGDWHIUHTXHQF\VOHZUDWHDQGORZEDWWHU\ZDUQLQJWLPH7RPDNHWKHDGMXVWPHQW

    3UHVVWKH$ODUP6LOHQFHSDGWREHJLQWKHVHOHFWLRQSURFHVV7KHGLJLWWREHVHOHFWHGZLOOIODVK

    3UHVVWKH8SRU'RZQSDGWRFKDQJHWKHGLJLWWRWKHQHZYDOXH

    3UHVVWKH$ODUP6LOHQFHSDGWRVHW\RXUVHOHFWLRQDQGPRYHWRWKHQH[WGLJLWRUVFUHHQ

    3UHVVWKH'RZQSDGWRF\FOHWKURXJKWKHIROORZLQJ6\VWHP&RQILJXUDWLRQVFUHHQV

    /DQJXDJH6HOHFWLRQ7KLVVFUHHQHQDEOHVWKHRSHUDWRUWRFKRRVHIURP*HUPDQ(QJOLVK6SDQLVK)UHQFKRU,WDOLDQ3UHVVWKH8S'RZQDQG$ODUP6LOHQFHSDGVVLPXOWDQHRXVO\WRUHWXUQWR(QJOLVK

    8365DWLQJ7KLVVFUHHQVKRZVWKH836UDWLQJ7KH;;;LQGLFDWHVWKH836UDWLQJLQN9$

    ,QSXW9ROWDJH7KLVVFUHHQGLVSOD\VWKH836LQSXWYROWDJHUDWLQJ

    2XWSXW9ROWDJH7KLVVFUHHQGLVSOD\VWKH836RXWSXWYROWDJHUDWLQJ

    Press toreview System Options

    and Configuration

    Deutsche English

    Espanol FrancaisItalia

    Press to set

    UPS Rating

    XXX kVA

    Input VoltageRating

    XXX/XXX Volts

    Output VoltageRating

    XXX/XXX Volts

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    49/113

    Operation 43

    1RPLQDO)UHTXHQF\%RWKLQSXWDQGRXWSXWIUHTXHQF\UDWLQJVDUHVKRZQRQWKLVVFUHHQ

    ,QSXW)UHTXHQF\6\QF5DQJH7KLVVFUHHQGLVSOD\VWKHVHOHFWHGIUHTXHQF\WROHUDQFH7KHLQSXWIUHTXHQF\V\QFKURQL]DWLRQUDQJHLVDGMXVWDEOHE\LQWHUQDOFRQWUROVZLWFKHVDQGPD\EHVHWDWRU+]7KHLQSXWSRZHUPXVWEHZLWKLQWKLVUDQJHIRUWKH836RXWSXWWREHFRPHV\QFKURQL]HGZLWKWKHLQSXWSRZHU7KH836LVVKLSSHGZLWKWKLVVHWWLQJDW+]

    6OHZ5DWH7KLVVFUHHQGLVSOD\VWKHVHOHFWHGIUHTXHQF\VOHZUDWH7KHVOHZUDWHLVDGMXVWDEOHE\WKHVHOHFWLRQSDGVLQ+]LQFUHPHQWVIURPWR+]SHUVHFRQGWKHUHFRPPHQGHGYDOXHLV+]7KHVOHZUDWHGHWHUPLQHVWKHWUDFNLQJWLPHWKH836LQYHUWHUUHTXLUHVWRPDWFKDQHZLQSXWIUHTXHQF\)RUH[DPSOHLIWKHLQSXWIUHTXHQF\FKDQJHVIURPWR+]WKH836LQYHUWHUIUHTXHQF\ZLOOHYHQWXDOO\FKDQJHWR+]7KHVOHZUDWHLVWKHVSHHGDWZKLFKWKHIUHTXHQF\

    FKDQJHVIURPWR+]

    /RZ%DWWHU\:DUQLQJ7KLVVFUHHQVKRZVWKHVHOHFWHG/RZ%DWWHU\:DUQLQJ7LPH7KLVYDOXHLVIDFWRU\VHWDWPLQXWHV+RZHYHULWLVDGMXVWDEOHE\WKHVHOHFWLRQSDGVLQRQHPLQXWHLQFUHPHQWVIURPWRPLQXWHV:KHQWKH836LVRSHUDWLQJRQEDWWHU\SRZHUDQ$ODUP0HVVDJHZLOODSSHDUZKHQWKLVVHWWLQJLVUHDFKHG7KLVZDUQVWKHRSHUDWRUWKDWEDWWHU\VKXWGRZQLVLPPLQHQW

    '&%XV:DONLQ7KLVVFUHHQGLVSOD\VWKHFXUUHQW'&%XV:DONLQWLPH7KLVVHWWLQJLVVHOHFWDEOHE\LQWHUQDOFRQWUROVZLWFKWRSURYLGHHLWKHUDVORZVHFRQGVRUIDVWVHFRQGVUDPSXSWLPHRQWKH'&%XV7KH836LVVKLSSHGZLWKWKLVVHWWLQJDWVHFRQGV

    NominalFrequency

    60 HzInput / Output

    Input FrequencySync Range:

    0.5 Hz

    Slew Rate0.1 Hz/Second

    Press to set

    Low BatteryWarning Time

    05 Minutes

    Press to set

    FiveSecond

    DC Bus Walk-in

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    50/113

    44 Operation

    7LPHDQG'DWH7KLVVFUHHQHQDEOHVWKHRSHUDWRUWRVHWWKHFXUUHQWWLPHGD\DQGGDWH7RFKDQJHWKHFXUUHQWWLPHDQGGDWHVHWWLQJVSHUIRUPWKHIROORZLQJ

    3UHVVWKH$ODUP6LOHQFHSDG7KH++LQGLFDWLRQEHJLQVWRIODVK

    3UHVVWKH8SRU'RZQSDGWRFKDQJHVHWWLQJ

    3UHVVWKH$ODUP6LOHQFHSDGWRF\FOHWKURXJKWKHUHPDLQLQJWLPHDQGGDWHVHWWLQJV

    %DWWHU\7HVW7KH6HULHV836ZLOODXWRPDWLFDOO\SHUIRUPDVFKHGXOHGRQOLQHEDWWHU\WHVWLIWKLVIHDWXUHLVHQDEOHGE\WKHXVHU'XULQJDWHVWWKHFKDUJHULVWXUQHGRIIDQGWKHEDWWHU\VXSSOLHVSRZHUWRWKHORDGIRUVHFRQGV7KH'&EXVYROWDJHLVWKHQFRPSDUHGWRWKHVHWSRLQW7KHXVHUVHOHFWVWKHVFKHGXOLQJRIWKHWHVWVWKH'&YROWDJHVHWSRLQWDQGZKHWKHUWKHWHVWLVHQDEOHG7KHEDWWHU\WHVWFDQDOVREHPDQXDOO\LQLWLDWHGE\/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUW

    ,IWKH'&EXVYROWDJHUHPDLQVDERYHWKHVHWSRLQWWKHEDWWHU\KDVSDVVHGWKHWHVWDQGDPHVVDJHLV

    VWRUHGLQWKHDODUPKLVWRU\7KHFKDUJHULVWXUQGRZQDQGQRUPDO836RSHUDWLRQLVUHVXPHG

    ,IWKH'&EXVYROWDJHGHFUHDVHVWRWKHVHWSRLQWEHIRUHWKHWHVWLVFRPSOHWHWKHEDWWHU\KDVIDLOHGWKHWHVWDQGWKH836SHUIRUPVWKHIROORZLQJVWHSV

    7UDQVIHUORDGWRE\SDVV

    5HVWDUWWKHFKDUJHU

    6RXQGWKHDXGLEOHDODUPKRUQ

    'LVSOD\DEDWWHU\ZDUQLQJPHVVDJHQRWHWKDWWKHRQO\ZD\WRFOHDUWKLVZDUQLQJPHVVDJHLVWRSHUIRUPD836VWDUWXS

    5HFRUGDEDWWHU\WHVWIDLOHGPHVVDJH

    'LVDEOHIXWXUHEDWWHU\WHVWV

    5HWUDQVIHUORDGWRWKH836

    7RVFKHGXOHDQGHQDEOHWKLVWHVWDQGWRYLHZRUFKDQJHWKHVHWSRLQWSXVKWKH$ODUP6LOHQFHSDGZKHQWKHIROORZLQJVFUHHQDSSHDUV

    7KH%DWWHU\3DUDPHWHU6FUHHQZLOOEHGLVSOD\HG

    7KLVVFUHHQGLVSOD\VWHVWSDUDPHWHUVDQGWKHGDWHDQGWLPHRIWKHQH[WVFKHGXOHGWHVW'XULQJLQLWLDOVWDUWXSVHOHFWSUHIHUUHGWHVWGD\GDWHWLPHWKUHVKROGYROWDJHVHWSRLQWWHVWLQWHUYDODQGHQDEOHRUGLVDEOHWKHDXWRPDWLFWHVWV7HVWLQWHUYDOLVWRZHHNVIDFWRU\VHWDW8VHWKH8S'RZQDQG$ODUP6LOHQFHSDGVWRHQWHUSDUDPHWHUV1RWHWKDWLIDVFKHGXOHGWHVWFDQQRWEHSHU

    Time and Date:HH:MM:SS

    DDD DD MMM YY

    Press to set

    Auto BatteryTest Parameters:

    Press to view or set

    MON APR 15 17:30

    THRESHOLD: 360 VDCINTERVAL: 5 WEEKS

    TEST ENABLED

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    51/113

    Operation 45

    IRUPHGEHFDXVHWKHORDGLVQRWRQWKH836WKHWHVWZLOODXWRPDWLFDOO\EHVFKHGXOHGIRUZHHNODWHU

    $XWR5HVWDUW7KH836FDQUHVWDUWWKHORDGDIWHUDQH[WHQGHGSRZHUIDLOXUHIRUFHVDORDGVKXWGRZQ$VVKLSSHGIURPWKHIDFWRU\WKLVIHDWXUHLVGLVDEOHG7RHQDEOHWKHIHDWXUHORFDWHWKH$XWR5HVWDUW6WDWXVVFUHHQ

    7KLVVHWWLQJFDQEHHLWKHU(1$%/('RU',6$%/('8VHWKH83'2:1DQG$/$506,/(1&(EXWWRQVWRFKDQJHWKHYDOXHWR(1$%/('

    :KHQSRZHULVUHDSSOLHGDIWHUDQDXWRPDWLFORDGVKXWGRZQWKH836ZLOOUHVWDUWWKHORDGVHFRQGVDIWHUWKHSRZHUUHWXUQV:KLOHWKH836LVUHVWDUWLQJWKHORDGLWZLOOH[HFXWHVHOIWHVWVWRYHULI\WKDWWKHPDMRULQWHUQDOSRZHUDQGFRQWUROVHFWLRQVDUHRSHUDWLQJSURSHUO\EHIRUHWUDQVIHUULQJWKHORDGWRWKHLQYHUWHU,IDQ\SUREOHPVRFFXUGXULQJWKLVVHOIWHVWWKH836ZLOODERUWWKHWHVWVDQGGLVDEOHWKHORDG7KHORDGFDQEHSRZHUHGPDQXDOO\E\WXUQLQJWKHSRZHUURWDU\VZLWFKWRSRVLWLRQDQGDTXDOLILHGVHUYLFHHQJLQHHUVKRXOGLQYHVWLJDWHWKHSUREOHP

    127(

    :KHQ$XWR5HVWDUWLVHQDEOHGRQ6HULHVXQLWVZKLFKLQFOXGHRSWLRQDOEDWWHU\FLUFXLWEUHDNHUVWKHXQLWZLOOUHVWDUWWKHORDGDVGHVFULEHG+RZHYHUWRUHFRQQHFWWKHEDWWHU\WKHEDWWHU\FLUFXLWEUHDNHUVPXVWEHPDQXDOO\UHVHWDQGFORVHG

    Auto Restart:

    DISABLED

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    52/113

    46 Operation

    3.5.3 Alarm History

    7KH6HULHV836LVHTXLSSHGZLWKDGDWDEXIIHUWKDWUHFRUGVDFWLYH$ODUP0HVVDJHVRYHUDSHULRGRIWLPH7RYLHZWKH$ODUP+LVWRU\RIWKH836SUHVVWKH'RZQSDGXQWLOWKHIROORZLQJVFUHHQDSSHDUV

    3UHVVWKH$ODUP6LOHQFHSDGWRDFFHVVWKH$ODUP+LVWRU\VFUHHQ3UHVVWKH'RZQSDGWRYLHZWKH$ODUP0HVVDJHV

    7KH$ODUP0HVVDJHVDUHGLVSOD\HGLQWKHUHYHUVHRUGHURIRFFXUUHQFHEHJLQQLQJZLWKWKHPRVWUHFHQW7KHWLPHWRWKHVHFRQGDQGGDWHRIRFFXUUHQFHLVGLVSOD\HGZLWKHDFK$ODUP0HVVDJH)RUDOLVWRI$ODUP0HVVDJHVZLWKGHVFULSWLRQVDQGUHFRPPHQGHGFRUUHFWLYHDFWLRQVUHIHUWR

    $ODUP0HVVDJHV

    3.5.4 Lamp Test

    3HULRGLFDOO\WKHRSHUDWRUVKRXOGYHULI\WKDWDOOVHJPHQWVLQWKH/&'GLVSOD\VFUHHQDUHIXQFWLRQLQJ

    )URPWKH1250$/23(5$7,21GHIDXOWVFUHHQSUHVVWKH8SSDGRUSUHVVWKH'RZQSDGIURPWKH$ODUP+LVWRU\VFUHHQ

    $OO/('VLOOXPLQDWHIRUDSSUR[LPDWHO\VHFRQGVDQGWKHKRUQVRXQGV7KH,QSXWDQG2XWSXW/('VRQWKH3RZHU6WDWXV'LDJUDPDUHGLUHFWO\ZLUHGWRWKHLUUHVSHFWLYHSRZHUOLQHVDQGDUHQRWLQFOXGHGLQWKLVWHVW:KHQWKHWHVWLVFRPSOHWHWKHVFUHHQZLOODXWRPDWLFDOO\GLVSOD\WKHDSSURSULDWHGHIDXOWVFUHHQPHVVDJH

    127(

    1RWHDQ\/('VQRWLOOXPLQDWHG&RQWDFW/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDWWRPDNHDSSURSULDWHUHSDLUV

    Alarm History

    Press to access

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    53/113

    Operation 47

    3.6 Start-Up

    6WDUWXSSURFHGXUHVDUHSHUIRUPHGDWWKHFRQWUROSDQHOORFDWHGRQWKH8360RGXOH&DELQHWGRRU3URPSWHGE\WKH$GYLVRU\'LVSOD\DQGVFUHHQPHVVDJHVWXUQ5RWDU\6ZLWFKWRH[HFXWHVWDUWXS

    3.6.1 Start-Up Procedure

    ,QLWLDOVWDUWXSPXVWEHSHUIRUPHGE\/LHEHUW6HUYLFHSHUVRQQHO6WDUWXSSURFHGXUHVGHVFULEHGLQWKLVPDQXDOUHIHUWRDVWDUWXSRIWKH836DIWHUDVKXWGRZQIRUPDLQWHQDQFHRUDIWHUDQDEQRUPDO

    FRQGLWLRQKDVEHHQFRUUHFWHG'HSHQGLQJRQWKHVLWXDWLRQVWDUWXSPD\EHJLQZLWK5RWDU\6ZLWFKLQ3RVLWLRQRU3RVLWLRQ%HJLQDW6WHSRU6WHS)ROORZGLUHFWLRQVJLYHQLQVFUHHQPHVVDJHVDQGWKH$GYLVRU\'LVSOD\5HIHUWR 6\VWHP2SWLRQVLI\RXKDYHDQ([WHUQDO0DLQWHQDQFH%\SDVV&DELQHW

    Start-Up from Position 0 9HULI\5RWDU\6ZLWFKLVVHWWR3RVLWLRQ

    $SSO\SRZHUWR836IURPXVHUVVXSSO\VRXUFHQRWSDUWRIWKH836

    7XUQ5RWDU\6ZLWFKWR3RVLWLRQ7KHIROORZLQJFRQGLWLRQVH[LVW

    D ,QSXWSRZHUIORZVWKURXJK0DLQWHQDQFH%\SDVV/LQHWRFULWLFDOORDG7KLVLVDKDUGZLUHGOLQHWKURXJKWKH836LQSXWSRZHULVQRWFRQGLWLRQHGRUEDFNHGXS

    E 7KH,QSXWDQG2XWSXW/('VRQWKH3RZHU6WDWXV'LDJUDPDUHLOOXPLQDWHG0HWHUVDQGDOORWKHULQGLFDWRUVDUHLQRSHUDWLYH7KLVLVDPDLQWHQDQFHSRVLWLRQ

    $&$87,21

    6WDUWXSPXVWEHSHUIRUPHGH[DFWO\DVLQVWUXFWHG)ROORZSURPSWVRQWKH$GYLVRU\'LVSOD\7XUQLQJWKH5RWDU\6ZLWFKWRRVRRQRULQWKHZURQJVHTXHQFHPD\UHVXOWLQLPPHGLDWHORVVRISRZHUWRWKHFULWLFDOORDG

    $:$51,1*

    ,1527$5

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    54/113

    48 Operation

    Start-Up from Position 1

    7XUQ5RWDU\6ZLWFKWR3RVLWLRQ7KHIROORZLQJPHVVDJHZLOODSSHDU

    3UHVV$ODUP6LOHQFH3DGDVSURPSWHG7KHFRQWUROV\VWHPEHJLQVH[HFXWLQJLQWHUQDOWHVWV0HWHUVDQGLQGLFDWRUVDUHRSHUDWLYH2EVHUYHWKHIROORZLQJ

    D $GYLVRU\'LVSOD\3DXVH/('LOOXPLQDWHV

    E ,QSXWSRZHUWRFULWLFDOORDGFRQWLQXHVWREHVXSSOLHGWKURXJK0DLQWHQDQFH%\SDVV/LQHDVLQGLFDWHGE\LOOXPLQDWHG,QSXWDQG2XWSXW/('VRQWKH3RZHU6WDWXV'LDJUDP

    F 7KHVFUHHQGLVSOD\VWKHIROORZLQJVHOIWHVWPHVVDJHV7KH;;LQHDFKVFUHHQLQGLFDWHVWKHVHFRQGVUHPDLQLQJLQWKHWHVW

    Press buttonto start system.

    Press to checkconfiguration.

    STARTUPChecking Input

    power

    [XX]

    STARTUP

    Testing charger[XX]

    STARTUP

    Testing inverter[XX]

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    55/113

    Operation 49

    $IWHUWKH836KDVVXFFHVVIXOO\SDVVHGWKHWKUHHSUHYLRXVWHVWVWKHIROORZLQJPHVVDJHZLOODSSHDU

    $GYDQFHWKH5RWDU\6ZLWFKWR3RVLWLRQDVSURPSWHG7KHEDWWHU\LVFRQQHFWHGWRWKH8360RGXOHDQGWKHFRQWUROV\VWHPFRQGXFWVLQWHUQDOWHVWVRQWKHEDWWHU\XQOHVVWKHEDWWHU\WHVWLVGLVDEOHG7KHVFUHHQZLOOGLVSOD\WKHIROORZLQJPHVVDJHV7KH;;LQHDFKVFUHHQLQGLFDWHVWKHVHFRQGVUHPDLQLQJLQWKHWHVW

    STARTUPTest passed. Turnrotary switch to

    Position 3.

    STARTUP

    Testing battery[XX]

    STARTUP

    Testing walk-in[XX]

    STARTUPTesting static

    switch[XX]

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    56/113

    50 Operation

    :KHQWKH3RVLWLRQWHVWVDUHFRPSOHWHGWKHIROORZLQJPHVVDJHZLOODSSHDU

    7XUQ5RWDU\6ZLWFKWR3RVLWLRQZKLFKLQLWLDWHV8360RGXOHQRUPDORSHUDWLRQ2EVHUYHWKHIROORZLQJ

    D $GYLVRU\'LVSOD\/('VH[WLQJXLVKLQGLFDWLQJWKDWWKH5RWDU\6ZLWFKZLOOUHPDLQLQ3RVLWLRQGXULQJQRUPDORSHUDWLRQ

    E 7KHVFUHHQGLVSOD\VWKHIROORZLQJPHVVDJH

    7KLVVFUHHQLQGLFDWHVWKH836LVWHPSRUDULO\XVLQJWKH6WDWLF%\SDVV/LQHWRVXSSO\SRZHUWRWKHFULWLFDOORDG

    7KH;;LQWKLVVFUHHQLQGLFDWHVWKHQXPEHURIVHFRQGVHODSVHGZKLOHWKH836LQWHUQDOFRQWUROV\VWHPV\QFKURQL]HVWKHLQYHUWHUZLWKWKHLQSXWSRZHU

    :KHQWKHLQYHUWHULVV\QFKURQL]HGWKHFRQWUROV\VWHPDXWRPDWLFDOO\UHWUDQVIHUVWKHFULWLFDOORDGIURPWKH6WDWLF%\SDVV/LQHWRWKH8360RGXOHZLWKQRLQWHUUXSWLRQRISRZHUWRWKHORDG7KHIROORZLQJGHIDXOWPHVVDJHZLOODSSHDU

    7KH1250$/23(5$7,21PHVVDJHLQGLFDWHVWKHIROORZLQJ

    7KHV\VWHPVWDWXVLVQRUPDODOOPHWHUUHDGLQJVDUHQRPLQDODQGWKH8360RGXOHLVV\QFKURQL]HGZLWKWKHLQSXWSRZHU

    7KHFULWLFDOORDGLVEHLQJVXSSOLHGFRQGLWLRQHGSRZHUWKURXJKWKH8360RGXOH

    7KHSRZHUEHLQJVXSSOLHGWRWKHFULWLFDOORDGLVLQGLFDWHGDVDSHUFHQWDJHRIWKH836SRZHUUDWLQJ

    7KH8S'RZQRU$ODUP6LOHQFHV\PEROIODVKHVLQWKHORZHUULJKWKDQGFRUQHURIWKHVFUHHQ7KLVLVDQRUPDOLQGLFDWLRQDQGPHDQVWKDW\RXPD\F\FOHWKURXJKYDULRXVPRQLWRULQJDQGWHVWIXQFWLRQVE\SUHVVLQJWKHDSSURSULDWHVHOHFWLRQSDG

    6WDUWXSLVFRPSOHWHZKHQWKH1250$/23(5$7,21PHVVDJHDSSHDUV1RIXUWKHUDFWLRQVDUHUHTXLUHGRIWKHRSHUDWRUXQOHVVDQDEQRUPDOFRQGLWLRQRFFXUV

    STARTUPTest passed. Turnrotary switch to

    position 4

    STARTUPTesting Input

    synchronization[XX]

    NORMAL OPERATIONLoad on UPS

    Load XXX%

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    57/113

    Operation 51

    3.6.2 Abnormal Conditions During Start-Up

    ,IWKHV\VWHPGHWHFWVDQDEQRUPDOFRQGLWLRQGXULQJVWDUWXS

    $Q$GYLVRU\'LVSOD\/('PD\LOOXPLQDWHSURPSWLQJPRYHPHQWRIWKH5RWDU\6ZLWFK5HDGWKHVFUHHQPHVVDJHEHIRUHWXUQLQJWKH5RWDU\6ZLWFK

    7KHVFUHHQGLVSOD\VDQDEQRUPDOFRQGLWLRQPHVVDJH6HH7DEOH IRUDQH[SODQDWLRQRIGLVSOD\HGPHVVDJHVDQGLPSOHPHQWWKHFRUUHVSRQGLQJFRUUHFWLYHDFWLRQ

    5HSHDWVWDUWXSVHTXHQFHLIDEQRUPDOFRQGLWLRQFDQEHFOHDUHG&DOO/LHEHUW6HUYLFHDQG

    6XSSRUWLI\RXUHTXLUHDVVLVWDQFH

    'XULQJVWDUWXSV\VWHPFRPSRQHQWVDUHWHVWHGDQGDQ\DEQRUPDOFRQGLWLRQVDUHGLVSOD\HGLQDQ$ODUP0HVVDJH:KHQDQDEQRUPDOFRQGLWLRQRFFXUVGXULQJVWDUWXSWKHFULWLFDOORDGFRQWLQXHVWRUHFHLYHSRZHUWKURXJKWKH0DLQWHQDQFH%\SDVV/LQH,IWKHGHIDXOWVFUHHQLQVWUXFWV\RXWR&KHFN0HVVDJHVSUHVVWKH'RZQSDGWRVHHWKHDFWLYH$ODUP0HVVDJHV

    7DEOH VKRZV$ODUP0HVVDJHV\RXPD\VHHGXULQJVWDUWXSDORQJZLWKRSHUDWRUFRUUHFWLYHDFWLRQ$ODUP0HVVDJHV\RXPD\VHHGXULQJQRUPDORSHUDWLRQDUHLQ $ODUP0HVVDJHV7DEOH &RQWDFW/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDWLI\RXUHTXLUHDVVLVWDQFH

    Table 7 Alarm Messages During Start-Up

    Alarm

    Message

    Meaning and

    Corrective Action in Brackets [ ]START-UP SEQUENCE ABORTED Check Messages.

    Input phase rotation incorrect The power conductors are not wired to the UPS input in the desiredsequence.

    [Disconnect power from the UPS input and correct the wiring. A LiebertCustomer Service and Support representative must be present duringinitial start-up of your UPS system.]

    Incorrect input frequency The frequency of the input power is outside the specified acceptablerange.

    [Check your utility source.]

    Rotary switch is in the wrong position Power has been applied to the UPS with the Rotary Switch in the wrongposition. This message is displayed when the input power is removed, thebattery is discharged, and the UPS system has completely shut down.

    This message indicates the Rotary Switch is still in Position 4 when inputpower is restored.

    [Turn the Rotary Switch to Position 1 and perform a UPS start-upprocedure.]

    Rotary switch improperly operated The Rotary Switch has been operated improperly. This means the switchhas been operated either too fast or in the wrong direction.

    [Turn the Rotary Switch to Position 1 and perform a UPS start-upprocedure.]

    Battery Failed Test The Start-up test routine has detected a failure in the battery.

    [Contact Liebert Customer Service and Support at 1-800-543-2378.]

    Static Switch Failure The Start-up test routine has detected a failure in the Static TransferSwitch.

    [Contact Liebert Customer Service and Support at 1-800-543-2378.]

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    58/113

    52 Operation

    3.6.3 Response to an Incorrect Start-Up Sequence

    ,I5RWDU\6ZLWFKLVDGYDQFHGWKURXJKVWDUWXSEHIRUHWKHDSSURSULDWHV\VWHPSURPSWVWKHIROORZLQJPHVVDJHLVGLVSOD\HG

    3UHVVWKH'RZQVHOHFWLRQSDGDVSURPSWHGE\WKHIODVKLQJDUURZLQWKHORZHUULJKWKDQGFRUQHUWRYLHZWKHIROORZLQJPHVVDJH

    7XUQURWDU\VZLWFKFRXQWHUFORFNZLVHWR3RVLWLRQ'RQRWWXUQURWDU\VZLWFKWR3RVLWLRQ'RLQJVRZLOOFDXVHDQLPPHGLDWHORVVRISRZHUWRWKHORDG

    )URP3RVLWLRQUHSHDWVWDUWXSVHTXHQFHEHJLQQLQJZLWK6WHSREVHUYLQJWKHSDFHVHWE\WKH$GYLVRU\'LVSOD\DQGVFUHHQPHVVDJHV

    ,IUHSHDWHGVWDUWXSDWWHPSWVDUHXQVXFFHVVIXOFDOO/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDW

    $&$87,21

    6WDUWXSPXVWEHSHUIRUPHGH[DFWO\DVLQVWUXFWHG)ROORZSURPSWVRQWKH$GYLVRU\'LVSOD\7XUQLQJWKH5RWDU\6ZLWFKWRRVRRQRULQWKHZURQJVHTXHQFHPD\UHVXOWLQLPPHGLDWHORVVRISRZHUWRWKHFULWLFDOORDG

    $:$51,1*

    &5,7,&$//2$',6&211(&7('727+(0$,17(1$1&(%

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    59/113

    Operation 53

    3.7 Normal Operation

    7KH1250$/23(5$7,21GHIDXOWPHVVDJHLVGLVSOD\HGGXULQJQRUPDORSHUDWLQJFRQGLWLRQV,WLQGLFDWHV

    6\VWHPFRQGLWLRQVDUHQRUPDODOOPHWHUUHDGLQJVDUHQRPLQDODQGWKH8360RGXOHLVV\QFKURQL]HGZLWKWKHLQSXWSRZHU

    7KHFULWLFDOORDGLVVXSSRUWHGE\WKH8360RGXOH

    7KHDPRXQWRISRZHUEHLQJXVHGE\WKHFULWLFDOORDGUHODWLYHWRWKH836UDWLQJ7KHYDOXH

    UHSUHVHQWHGE\;;;ZLOODOZD\VEHOHVVWKDQRUHTXDOWRLQD1250$/23(5$7,21PHVVDJH,IWKHFULWLFDOORDGLVGUDZLQJPRUHWKDQRIWKH836UDWHGORDGDZDUQLQJPHVVDJHZLOODSSHDU

    7KH8S'RZQRU$ODUP6LOHQFHIODVKHVLQWKHORZHUULJKWKDQGFRUQHURIWKHVFUHHQ7KLVLVQRUPDODQGLQGLFDWHVWKDWWKHRSHUDWRUPD\F\FOHWKURXJKYDULRXVPRQLWRULQJDQGWHVWIXQFWLRQVE\SUHVVLQJWKHDSSURSULDWHVHOHFWLRQSDG

    NORMAL OPERATIONLoad on UPS

    Load XXX%

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    60/113

    54 Operation

    3.8 Shutdown

    3.8.1 Shutdown to Maintenance Bypass

    7RUHPRYHWKH836IURPVHUYLFHIRUPDLQWHQDQFHRURWKHUUHDVRQVDQGVWLOOSURYLGHSRZHUWRWKHFULWLFDOORDGLWLVQHFHVVDU\WRFRQQHFWWKHORDGWRWKH0DLQWHQDQFH%\SDVV/LQHE\SHUIRUPLQJ6WHSV DQG EHORZUHIHUWR 6\VWHP2SWLRQVLI\RXKDYHDQ([WHUQDO0DLQWHQDQFH%\SDVV&DELQHW

    7XUQ5RWDU\6ZLWFKFRXQWHUFORFNZLVHIURP3RVLWLRQWR3RVLWLRQDQGREVHUYHWKHIROORZLQJPHVVDJH

    &RQWLQXHWXUQLQJWKHVZLWFKFRXQWHUFORFNZLVHWR3RVLWLRQ'RQRWWXUQ5RWDU\6ZLWFKWR3RVLWLRQ'RLQJVRZLOOFDXVHDQLPPHGLDWHORVVRISRZHUWRWKHORDG7KHUHLVQRSRZHUWRWKH8360RGXOHFRQWUROV\VWHPLQWKLVSRVLWLRQ7KHUHIRUHWKHGLJLWDOGLVSOD\ZLOOEHEODQN

    3.8.2 Complete Shutdown

    7RUHPRYHDOOSRZHUWRWKHORDGSHUIRUP6WHSV DQG DERYHWKHQUHIHUWR 6\VWHP2SWLRQVLI\RXKDYHDQ([WHUQDO0DLQWHQDQFH%\SDVV&DELQHW

    7XUQ5RWDU\6ZLWFKIURP3RVLWLRQWR3RVLWLRQ

    3.8.3 Emergency Shutdown

    ,QWKHXQOLNHO\HYHQWDQHPHUJHQF\VKXWGRZQLVQHFHVVDU\WKHRSHUDWRUVKRXOG7XUQWKH5RWDU\6ZLWFKFRXQWHUFORFNZLVHGLUHFWO\WR3RVLWLRQ5HIHUWR 6\VWHP2SWLRQVLI\RXKDYHDQ([WHUQDO0DLQWHQDQFH%\SDVV&DELQHW

    &DOO/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDW

    7RUHVWDUWWKH836DIWHUWKHFDXVHRIWKHHPHUJHQF\VKXWGRZQKDVEHHQFRUUHFWHGSHUIRUPWKHVWDUWXSSURFHGXUH

    $:$51,1*

    &5,7,&$//2$',6&211(&7('727+(0$,17(1$1&(%

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    61/113

    Operation 55

    3.9 Response to a Power Failure

    ,ILQSXWSRZHUIDLOVZKLOHWKHORDGLVRQ8365RWDU\6ZLWFKLQ3RVLWLRQWKH836EDWWHU\ZLOOVXSSO\SRZHUWRWKHLQYHUWHUZKLFKVXSSRUWVWKHORDG

    3.9.1 UPS Response 836EDWWHU\EHJLQVVXSSO\LQJSRZHUZLWKRXWLQWHUUXSWLRQWRWKHLQYHUWHU

    7KH,QSXW/('RQWKH3RZHU6WDWXV'LDJUDPH[WLQJXLVKHV7KH2XWSXW/('UHPDLQVLOOXPLQDWHG

    7KH3DXVH/('RQWKH$GYLVRU\'LVSOD\LOOXPLQDWHVZDUQLQJRSHUDWRUQRWWRWXUQWKH5RWDU\6ZLWFK

    7KHDXGLEOHDODUPZLOOVRXQGLIWKHSRZHUIDLOXUHODVWVORQJHUWKDQVHFRQGV

    7KHVFUHHQGLVSOD\VWKHIROORZLQJPHVVDJH

    7KHLQWHUQDOFRQWUROV\VWHPEHJLQVVHQVLQJDFWXDOFKDUJHLQWKHEDWWHU\LQRUGHUWRFDOFXODWHWKHDPRXQWRIWLPHWKHEDWWHU\FDQVXSSRUWWKHFULWLFDOORDG7KHLQLWLDOSURFHVVRIVHQVLQJDQGFDOFXODWLRQUHTXLUHVDSSUR[LPDWHO\IRXUPLQXWHV

    $IWHUWKHLQLWLDOFDOFXODWLRQSURFHVVWKHIROORZLQJPHVVDJHZLOODSSHDU

    7KHWLPHUHPDLQLQJQXPEHUUHSRUWHGLQWKH;;ILHOGZLOOEHWKHFDOFXODWHGEDWWHU\WLPHUHPDLQLQJ7KHUHDIWHUWKHSURFHVVRIVHQVLQJDQGUHFDOFXODWLRQZLOOFRQWLQXHXQWLOWKHEDWWHU\WLPHUHPDLQLQJKDVGHFUHDVHGWRPLQXWHV7KHWLPHUHPDLQLQJQXPEHULVXSGDWHGHYHU\VHFRQGV,IFRQGLWLRQVFKDQJHWKHWLPHUHPDLQLQJQXPEHUPD\EHLQDFFXUDWHIRUDIHZPLQXWHVDVWKHFRQWUROV\VWHPPDNHVLWVFDOFXODWLRQV

    :KHQYHU\OLJKWORDGVDUHVXSSRUWHGRUZKHQPXOWLSOHEDWWHU\EDQNVDUHFRQQHFWHGWKHGLVSOD\PHVVDJHPD\VKRZDOLPLWHGSURMHFWLRQLQGLFDWHGE\!RUDVPDOOHUQXPEHUEDVHGRQORDG

    $VPRUHGDWDLVJDWKHUHGE\WKHSURFHVVLQJV\VWHPWKHHVWLPDWHPD\EHUHYLVHGDQGPRUHWLPHDGGHGWRDPD[LPXPRI!,QH[WUHPHFDVHVRIVPDOOORDGVRQPXOWLSOHEDWWHU\EDQNVWKHGLVSOD\ZLOOVWD\DW!XQWLOWKHEDWWHU\GLVFKDUJHVEHORZPLQXWHV

    :KHQWKH836UHDFKHVWKH/RZ%DWWHU\:DUQLQJ7LPHWKHDXGLEOHDODUPZLOOVRXQGDJDLQ

    $&$87,21

    0RYHPHQWRI5RWDU\6ZLWFKGXULQJDSRZHUIDLOXUHZLOOUHVXOWLQDQLPPHGLDWHORVVRISRZHUWRWKHORDG

    UPS ON BATTERYCalculating Time

    RemainingCheck Messages

    UPS ON BATTERYTime Remaining

    >XX MinutesCheck Messages

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    62/113

    56 Operation

    3.9.2 Operator Response

    3UHVV$ODUP6LOHQFHSDGWRFDQFHOWKHDXGLEOHDODUP,WZLOOVRXQGDJDLQDWWKH/RZ%DWWHU\:DUQLQJ7LPH

    9HULI\DSRZHUIDLOXUHKDVRFFXUUHG,QDGGLWLRQWRLQGLFDWRUVDQGDODUPVRQWKH836WKHUHVKRXOGEHRWKHULQGLFDWLRQVVXFKDVWKHURRPOLJKWVEHLQJRII

    :KLOHWKHEDWWHU\LVVXSSRUWLQJWKHORDG\RXPD\UHGXFHWKHORDGWRH[WHQGWKHEDWWHU\WLPH5HPHPEHUWKDWWKHFDOFXODWLRQVIRUEDWWHU\WLPHUHPDLQLQJPD\WDNHDIHZPLQXWHV

    3.9.3 As Battery Time Approaches Zero

    ,ILQSXWSRZHULVUHVWRUHGZKLOHWKH836EDWWHU\LVVXSSRUWLQJWKHORDGWKH836ZLOODXWRPDWLFDOO\EHJLQFRQGLWLRQLQJLQSXWSRZHU7KLVFRQGLWLRQHGSRZHUVXSSRUWVWKHORDGDVLWVLPXOWDQHRXVO\UHFKDUJHVWKHEDWWHU\

    ,IHTXLSPHQWVXSSRUWHGE\WKH836LVGUDZLQJSRZHUIURPWKHEDWWHU\DVWLPHDSSURDFKHV

    ]HURWKH836FRQWLQXHVWRVXSSO\SRZHUWRWKDWORDGXQWLOWKHEDWWHU\UHDFKHVDSUHVHWYROWDJHOHYHO]HURWLPH7RSURWHFWWKHEDWWHU\IURPGDPDJHWKH836WKHQVKXWVLWVHOIRIIDQGQRORQJHUVXSSOLHVSRZHUWRWKHORDG

    ,IWKHFRQWUROV\VWHPVKXWVGRZQWKH836DW]HURWLPHDQG$XWR5HVWDUWLVGLVDEOHGWKH836UHPDLQVRIIHYHQZKHQLQSXWSRZHULVUHVWRUHG7RUHVWRUHSRZHUWRWKHORDGWXUQ5RWDU\6ZLWFKFRXQWHUFORFNZLVHWR3RVLWLRQ7KHFULWLFDOEXVZLOOEHHQHUJL]HGDVVRRQDVWKH5RWDU\6ZLWFKLVLQ3RVLWLRQ 3HUIRUPVWDUWXS 6WDUW8SIURP3RVLWLRQ0DQXDOO\UHVHWDQGFORVHWKHEDWWHU\FLUFXLWEUHDNHUVZKHQVXSSOLHGWRUHFRQQHFWWKHEDWWHU\

    ,IWKHFRQWUROV\VWHPVKXWVGRZQWKH836DW]HURWLPHDQG$XWR5HVWDUWLVHQDEOHGWKH836ZLOOUHVWDUWWKHORDGVHFRQGVDIWHULQSXWSRZHULVUHVWRUHGUHIHUWR 6\VWHP&RQILJXUDWLRQ0DQXDOO\UHVHWDQGFORVHWKHEDWWHU\FLUFXLWEUHDNHUVZKHQVXSSOLHGWRUHFRQQHFWWKHEDWWHU\

    127(

    'HWHUPLQHWLPHUHTXLUHGWRSHUIRUPDQRUGHUO\VKXWGRZQRIWKHFULWLFDOORDG%HJLQVKXWGRZQVRLWZLOOEHFRPSOHWHGZKLOHWKHEDWWHU\LVVWLOOVXSSRUWLQJWKHORDG

    :KHQEDWWHU\WLPHUHPDLQLQJKDVGHFUHDVHGWRPLQXWHVUHGXFLQJWKHORDGZLOOQRWH[WHQGEDWWHU\WLPH

    $&$87,21

    7XUQLQJWKH5RWDU\6ZLWFKFRXQWHUFORFNZLVHIURP3RVLWLRQWR3RVLWLRQZLOOHQHUJL]HWKHFULWLFDOEXV0DNHVXUHFULWLFDOORDG

    HTXLSPHQWLVUHDG\IRUSRZHUEHIRUHWXUQLQJ5RWDU\6ZLWFK

    $&$87,21

    5HFKDUJHEDWWHULHVDVVRRQDVSRVVLEOHDIWHUGLVFKDUJH%DWWHULHVVKRXOGEHUHFKDUJHGZLWKLQKRXUVWRDYRLGVXOSKDWLRQDQGWRSUHVHUYHEDWWHU\OLIH

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    63/113

    Operation 57

    3.10 Response to a UPS Failure

    3.10.1 UPS Response 7KH6WDWLF7UDQVIHU6ZLWFKLQVWDQWO\WUDQVIHUVWKHORDGWRWKH6WDWLF%\SDVV/LQHZLWKRXW

    LQWHUUXSWLRQRISRZHU

    $QDXGLEOHDODUPZLOOVRXQG

    7KHIROORZLQJPHVVDJHZLOODSSHDU

    $Q$GYLVRU\'LVSOD\/('PD\LOOXPLQDWHSURPSWLQJPRYHPHQWRIWKHURWDU\VZLWFK

    3.10.2 Operator Response 3UHVV$ODUP6LOHQFHSDGWRFDQFHOWKHDXGLEOHDODUP

    3UHVVWKH'RZQSDGWRYLHZWKH$ODUP0HVVDJHVVFUHHQ

    7XUQ5RWDU\6ZLWFKFORFNZLVHRUFRXQWHUFORFNZLVHLQUHVSRQVHWRWKH$GYLVRU\'LVSOD\

    &RQWLQXHWXUQLQJ5RWDU\6ZLWFKWR3RVLWLRQZKLFKGHHQHUJL]HVWKH836ZKLOHPDLQWDLQLQJWKHFULWLFDOORDGWKURXJKWKH0DLQWHQDQFH%\SDVV/LQH

    &DOO/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDW

    $&$87,21

    'RQRWWXUQ5RWDU\6ZLWFKWRSRVLWLRQ'RLQJVRZLOOFDXVHDQLPPHGLDWHORVVRISRZHUWRWKHORDG

    WARNING: Loadon StaticSwitch

    Check Messages

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    64/113

    58 Operation

    3.11 Alarm Messages

    :KHQWKHGHIDXOWVFUHHQLQVWUXFWV\RXWR&KHFN0HVVDJHVSUHVVWKH'RZQSDGWRVHHWKH$ODUP0HVVDJHVVFUHHQ$FWLYH$ODUP0HVVDJHVZLOOEHGLVSOD\HGDORQJZLWKDVHTXHQFHQXPEHUDQGWLPHRIRFFXUUHQFH1RWHWKDWWZRRUPRUH$ODUP0HVVDJHVFDQKDYHWKHVDPHVHTXHQFHQXPEHUZKLFKPHDQVWKH\RFFXUUHGVLPXOWDQHRXVO\&RQWLQXHSUHVVLQJWKH'RZQSDGXQWLODOODFWLYH

    $ODUP0HVVDJHVKDYHEHHQGLVSOD\HG

    7DEOH VKRZV$ODUP0HVVDJHVZLWKUHODWHGDODUPVJURXSHGWRJHWKHUDQGRSHUDWRUFRUUHFWLYH

    DFWLRQLIDQ\&RQWDFW/LHEHUW&XVWRPHU6HUYLFHDQG6XSSRUWDWLI\RXUHTXLUHDVVLVWDQFH

    Table 8 Alarm Messages

    AlarmMessage

    Meaning andCorrective Action in Brackets [ ]

    AC INPUT

    Input power out of tolerance Frequency or voltage of the input power is outside the acceptable range. Thebattery supplies power to the critical load through the UPS Module.

    DC BUS

    Charger in reduced current mode Customer has selected reduced current operation of the charger from a contactexternal to the UPS.

    Battery charger problems The battery is not being charged. The voltage produced by the charger is

    insufficient to maintain a charge on the battery.[Contact Liebert Customer Service and Support at 1-800-543-2378.]

    Low battery warning issued Battery has been discharging and the Low Battery Warning Time (factory set at5 minutes, adjustable range 1 to 99 minutes) has been reached. Note timestamp on alarm message.

    [Follow appropriate procedures to shut down the critical load in an orderlysequence.]

    Low battery shutdown Battery has discharged to the minimum allowable voltage and the UPS is shutdown. No power is being supplied to the critical load.

    [When input power becomes available, perform a UPS start-up procedure.]

    DC bus overvoltage DC bus voltage has exceeded the specified limit and the charger has beenturned off. The charger will automatically restart when the DC bus voltagereturns to within tolerance.

    [Contact Liebert Customer Service and Support at 1-800-543-2378 if this

    condition persists for more than 2 minutes.]

    BYPASS

    Bypass frequency out of tolerance Input power frequency is outside of the specified tolerance (adjustable range .5to 5 Hz). Automatic transfers to the Static Bypass Line are prohibited.

    [Do not operate the Rotary Switch while this condition is present.]

    Load transferred to bypass due tooverload

    Critical load connected to the UPS has exceeded the UPS power rating. Theload has been automatically transferred to the Static Bypass Line. Power to theload is not being conditioned by the UPS. An automatic retransfer will beattempted when the load is reduced.

    [Determine cause of the overload and reduce the load.]

    Load transferred to bypass due to DCovervoltage

    DC bus voltage has exceeded the specified limit. The load has beenautomatically transferred to the Static Bypass Line. An automatic retransfer willbe attempted when the DC bus voltage returns to within tolerance.

    [Contact Liebert Customer Service and Support at 1-800-543-2378 if thiscondition persists for more than 2 minutes.]

    Excessive retransfers attempted Several automatic retransfer attempts (15 attempts during 20 minutes or less)have been made to retransfer the load from the Static Bypass Line back to theUPS. The UPS has not been able to consistently sustain the load because ofan overload condition or an inverter failure. The load will remain on the StaticBypass Line. Power to the load is not being conditioned by the UPS.

    [Check other messages for inverter failure. Determine cause of the overloadand reduce the load.]

    Static Switch failure A fault has been detected in the Static Transfer Switch. Automatic transfers tothe Static Bypass Line are prohibited.

    [Contact Liebert Customer Service and Support at 1-800-543-2378.]

  • 8/22/2019 Manual de IOM UPS serie 300.pdf

    65/113

    Operation 59

    UPS SYSTEM

    UPS output not synchronized to inputpower

    UPS inverter output is not synchronized with the input power. Automatictransfers to the Static Bypass Line are prohibited. This is usually a temporarycondition that is corrected automatically by the UPS internal control system.

    Input power single phased This message indicates an input power problem.

    [Check all input power phases.]

    Input voltage sensor failed Each input voltage phase has two sensors. One of these sensors has failed.

    [Contact Liebert Customer Service and Support at 1-800-543-2378.]

    Inverter leg over current in X-phase A fault has been detected in the inverter, caused by a UPS failure. The loadhas been automatically transferred to the Static Bypass Line. Power to the loadis not being conditioned by the UPS.

    [Contact Liebert Customer Service and Support at 1-800-543-2378.]

    Output undervoltage UPS output voltage is below a specified minimum. The load has beenautomatically transferred to the Static Bypass Line. Power to the load is notbeing conditioned by the UPS. An automatic retransfer will be attempted whenthe output voltage is within tolerance.

    [Contact Liebert Customer Service and Support if this condition persists.]

    Output overvoltage UPS output voltage is above a specified maximum. The load has been

    automatically transferred to the Static Bypass Line. Power to the load is notbeing conditioned by the UPS. An automatic retransfer will be attempted whenthe output voltage is within tolerance.

    [Contact Liebert Customer Service and Support if this condition persists.]

    Output overcurrent An output overcurrent surge has been detected. The load has beenautomatically transferred to the Static Bypass Line. An automatic retransfer willbe attempted when the output current returns to nominal.

    [Contact Liebert Customer Service and Support if this condition persists.]

    System output overloaded An overload condition is present. If the load is on the UPS inverter, the load willbe automatically transferred to the Static Bypass Line if the overload exceedsthe UPS Module capacity.

    [Determine cause of the overload and reduce the load.]

    Load transferred to bypass due tooverload

    The load has been automatically transferred to the Static Bypass Line becauseof an over