40
MANUAL – INSTALLATION Laboratory Space Controller LSC Series v200 Issue Date: 03/26/15 © 2015 Price Industries Limited. All rights reserved.

MANUA – INSTALLATIONpricecriticalcontrols.com/content/uploads/assets/literature/manuals... · manua – installation aboratory pace ontroller ... l t f u m e h o o d s a i 1 5 t

  • Upload
    vothien

  • View
    214

  • Download
    1

Embed Size (px)

Citation preview

MANUAL – INSTALLATION

Laboratory Space ControllerLSC Series

v200 – Issue Date: 03/26/15© 2015 Price Industries Limited. All rights reserved.

LABORATORY SPACE CONTROLLERTABLE OF CONTENTS

This mark indicates an important point for the proper function of the fume hood and the FHC. Improper installation or setup may cause unit failure and contamination of the laboratory space. Pay close attention to all caution points throughout this manual.

CAUTION

IMPORTANT NOTES

Application Support

678.578.7495

[email protected]

www.pricecriticalcontrols.com

Product Overview

General .........................................................................1

Laboratory Space Controller (LSC) Features .................1

Laboratory Space Controller EXP 1 Features ................2

Laboratory Space Controller EXP 2 Features ................2

Accessory Overview

Room Pressure Sensor (RPS) Features .........................3

Room Pressure Interface (RPI) Features ........................3

Thermostat Features .....................................................3

Installation and Mounting Instructions

Price Laboratory Space Controller (LSC)Step-by-Step Installation ...............................................4

Wiring Diagrams

Laboratory Space Controller – EXP 2 ............................5

Wiring a Network of Multiple Price Fume Hood Controllers .............................................6

Display Navigation

RPI Initial Start Up .........................................................7

Controller ......................................................................8

Service Menu ................................................................8

Wizard Menu .................................................................9

Timing Menu ...............................................................14

Remote Panel Menu ....................................................15

Input Menu ..................................................................16

Output Menu ...............................................................20

Network Menu ............................................................23

RPI Setup Menu ..........................................................24

Diagnostic Menu .........................................................26

Room Control Menu ....................................................27

Temperature Control Menu ..........................................31

LABORATORY SPACE CONTROLLER

1pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

PRODUCT OVERVIEW

GeneralThe Price Laboratory Space Controller (LSC) is an excellent solution to ensure a safe laboratory space where airflow control is critical. The digital controller intelligently maintains a volumetric offset between the supply, general exhaust, and fume hoods in the VAV system to ensure accurate control of directional airflow. The LSC offers a high speed local network for fume hoods daisy chain wired to the controller for a less than 1 second response time between controllers. Terminal blocks are used on the inputs and outputs to facilitate wired connections to the controller. The LSC is capable of monitoring room pressure, temperature, room occupancy, and a variety of other measurements with added optional devices. The LSC has many configurable options that can be easily programmed using the user friendly setup wizard with the interface on initial startup. These options are highly configurable for exceptional accuracy and control.

LABORATORY SPACE CONTROLLER Laboratory Space Controller (LSC) Features:• 16 bit – high speed flash based

microprocessor with watch dog timer, brown out reset

• Multi-stage surge protection against voltage spikes on 24 VAC input

• Simple connections to room pressure sensors (RPS) using RJ-12 jacks

• Can read up to 16 fume hoods

• Up to 12 analog inputs (0-10 VDC)

• Up to 6 analog outputs (0-10 VDC)

• Up to 5 binary contact closure outputs rated at 0.1 amps

• Up to 6 binary inputs

• Optional switched Hot/common 24 VAC binary outputs

• Optional port dedicated for thermistor

• Pluggable terminal blocks

LABORATORY SPACE CONTROLLER

2 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

PRODUCT OVERVIEW

Laboratory Space Controller EXP 1 Features:T-STAT port enables the ability to use a RPI and LCD T-STAT simultaneously. An excellent option when fume hoods are not present.

Laboratory Space Controller EXP 2 Features:The EXP 2 is used when fume hoods are connected to the LSC (via Mnet) and the LSC is connected to the network via BACnet. Dedicated thermistor input for temperature monitoring.

EXP 1

EXP 2

LABORATORY SPACE CONTROLLER

3pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

ACCESSORY OVERVIEW

Room Pressure Sensor (RPS) Features (Optional):• High accuracy room

pressure sensor

• Quick keyed cable connection

• Indicator LED on sensor and LSC shows proper connection

• Stainless steel louvered plate for accurate readings and protection from cleaning

Room Pressure Interface (RPI) Features (Optional):• Backlit 14x2 LCD interface

with true character display

• LED side bars offer 180 degree viewing of current room status

• Green – Safe

• Red – Danger (exceeding low or high alarm set points)

• Blue - Unoccupied

• Password protected menu

• Easy to use MENU system for fast and simple setup of system

• Service port on back for use with Price LINKER2 setup software

• Included RJ45 plenum rated cable for fast, error free hookup

• Setup Wizard – walk through setup of LSC when first powered up

Thermostat Features (Optional):• 4 models of thermostats to choose

from: Room Sensor Thermostat, LCD Thermostat (Right), and LCD Thermostat with Motion Sensor (Left), LCD with Humidity Sensor

• Humidity sensor (optional) measures humidity levels to maintain a comfortable work space

• Motion sensor (optional) to detect occupancy and change control sequences accordingly

• RJ45 connection for ease of installation

• RJ12 connection for servicing

ROOM PRESSURE SENSOR

ROOM PRESSURE INTERFACE

THERMOSTATS

LABORATORY SPACE CONTROLLER

4 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

INSTALLATION AND MOUNTING INSTRUCTIONS

Price Laboratory Space Controller (LSC) Step-by-Step InstallationEnsure you have all components necessary for installation. Inspect components for signs of shipping/handling damage. Do not proceed if you suspect any components are damaged.

1. Mount the Laboratory Space Controller – LSC enclosure in the plenum space above the door inside the laboratory space. The LSC must NOT be installed outdoors or in an enclosure that is outdoors. The LSC is not environmentally rated for mounting in these locations. Using 4 screws (by others) mount the LSC enclosure horizontally to a flat, secure, and accessible surface. Mount the 120VAC-24VAC transformer provided to a field mounted enclosure (by others) near the LSC to allow for ease of wiring.

2. (OPTIONAL) Install the Room Pressure Sensor (RPS) assembly. The RPS-Main Sensor should be installed in the hallway using the drywall bracket supplied. The RPS-Reference Sensor must be installed within 12 inches of the Main sensor.

3. (OPTIONAL) Mount the Room Pressure Interface near the doorway using a standard electrical box (by others). Ensure LED bars are not blocked by other devices on wall.

1

2

Install LSC enclosure in plenum/ceiling space using 4 mounting holes

RPS-Reference Sensor Assembly – Mounted in Isolation room. Firmly attach air tubing (supplied) to brass pressure tap using supplied kink resistant tubing.

RPS-Main Sensor Assembly – Mounted in corridor/hallway. Firmly attach air tubing to brass pressure tap. Gently plug green c25 cable to black, quick connection on back of sensor assembly. Route other opposite end of cable to the LSC, plugging the RJ-12 (telephone type) connection into ‘Primary Sensor’ input.

Mount RPS Main Sensor above doorway using supplied bracket

3 Install RPI near doorway at height of 5 feet

LABORATORY SPACE CONTROLLER

5pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

WIRING DIAGRAM: LABORATORY SPACE CONTROLLER - EXP 2

CAT5E CABLE

FIELD ELECTRICAL WIRING

FACTORY ELECTRICAL WIRINGLEGEND

LSC

PR

IMA

RY

SE

NS

OR

AN

ALO

G IN

PUTS

LINKER

RPI

EXP

ANSIO

N

BACnetMSTP

COM

1

2

BI1

BI2

BO

1

STA

COM

24VAC

3

2

1

5

4

6

2AO2

1AO1

BO

2

COM

RJ-

45P

RIC

EA/+

B/-BA

Cne

t

TX

RX

HLH

MS

/TP

NETTRM

FLTCOM

*

24 VACPOWER IN

3

4

5

6

7

8

9

10

COM

AO6

AO5

AO4

AO3

EXP

ANSIO

N

BO3

BO4

BO5

COM

CAT5E CABLE BY PRICE

STA

LAB

OR

ATO

RY

SP

AC

E C

ON

TRO

LLE

R

AI14

AI13

AI12

AI11

BI3

COM

BI4

BI5

COM

BI6

RX

TXFLT

FUM

E HO

OD

S

AI1

5TH

ER

M

CAT5E CABLE

BY PRICE

TO FUME HOODCONTROLLER(S)-(PFHC)

TO PRIMARY EXHAUST VALVE

TO PRIMARY SUPPLY VALVE

COM

AO1

AI9

AI5

COMMON

ACTUATORSIGNAL

PRESSURESIGNAL

VALVEAIRFLOW

COM

ACT

PRES

FLOW

TO SECONDARY SUPPLY VALVE

CONTROLLERTERMINALS FUNCTION

TO PRIMARY SUPPLY REHEAT

COM

AO1

AI7

AI3

COMMON

ACTUATORSIGNAL

PRESSURESIGNAL

VALVEAIRFLOW

COM

ACT

PRES

FLOW

COM

AO2

AI8

AI4

COMMON

ACTUATORSIGNAL

PRESSURESIGNAL

VALVEAIRFLOW

COM

ACT

PRES

FLOW

HOT 24V24VACPOWER

COM

AO5

COMMON

VALVESIGNAL

HOT24VACPOWER

TO SECONDARY EXHAUST VALVE

COM

AI10

AI6

COMMONPRESSURESIGNAL

VALVEAIRFLOW

COM

PRES

FLOW

HOT 24V24VACPOWER

SE

CO

ND

AR

YS

EN

SO

R

Power In120V

L1

N/L2

HOT 24V24VACPOWER

CONTROLLERTERMINALS FUNCTION

VALVETERMINALS

CONTROLLERTERMINALS FUNCTION

VALVETERMINALS

CONTROLLERTERMINALS FUNCTION

VALVETERMINALS

CONTROLLERTERMINALS FUNCTION

VALVETERMINALS

HOT 24V24VACPOWER

ROOM PRESSURE SENSOR (RPS)

PLUG AND PLAYRJ12/LOCKINGCIRCULARCONNECTION ONSENSOR(S)

EX

P 2

C

PROJECT :

SUBMITTAL DATE:

ENGINEER:

CUSTOMER:

SPEC. SYMBOL:

R

R Control SequenceNumber

REVOFSHEET

PCC00002

2014/03/31

14 42 0

CRITICAL CONTROLS

Reference #: PTR1310429

CRITICAL CONTROLSPCC00075-14

Copyright PRICE INDUSTRIES 2013

WIRING DIAGRAMS

NOTE: Sample LSC with EXP 2 Wiring Diagram

LABORATORY SPACE CONTROLLER

6 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

WIRING DIAGRAM: WIRING A NETWORK OF MULTIPLE PRICE FUME HOOD CONTROLLERS

WIRING DIAGRAMS

NOTE: This is only an example of a laboratory wiring overview.

LABORATORY SPACE CONTROLLER

7pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATION

RPI Initial Start UpWhen the RPI is first powered by the LSC, it will display the following information. This information can be accessed anytime by pressing both the Up/Down buttons at the same time.

PRICE ELECTRONICS Start-up screen.

INTERFACE MODEL STANDARD MODEL Standard Interface model.

INTERFACE V3.XX.X Interface firmware version. V3.XX.X or higher.

LSC VX.XX.X LSC firmware version. V1.XX.X or higher.

MAC ADDRESS SOFTWARE 1 Displays current MAC Address (local MS/TP segment). Must be unique to MS TP segment.

LABORATORY SPACE CONTROLLER

8 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATION

ControllerDown ButtonUsed for menu selection and adjustment – press both up and down at same time to display Startup screens on the LCD interface.

Up Button Used for menu selection and adjustment – press both up and down at same time to display Startup screens on the LCD interface.

Menu/EnterUsed to enter service menu(s). The menu(s) are password protected.

MuteUsed to temporarily mute the local alarm for a certain number of minutes.

EmergencyUsed to trigger emergency mode. Local Alarm will sound and BACnet point will change to Alarm alerting the front end system.

Service Menu

The service menu contains all setup and configuration parameters. Each LSC ships with factory defaults, but virtually all settings can be adjusted in the field. All MAIN menus are listed on this page. Use the WIZARD and/ or below menus to setup the LSC for your application.

CONTROLLER

SERVICE MENU

SERVICE MENU:OCCUPANCY

Occupancy Menu – Allows user to force occupied/unoccupied modes.

SERVICE MENU:TIMING

Timing Menu – Allows configuration of alarm delays.

SERVICE MENU:REMOTE PANEL

Remote Panel Menu – Allows configuration of the Remote Panel alarms, key switch and LED indicators.

SERVICE MENU:INPUT

Input Menu – Allows configuration of binary and analog inputs.

SERVICE MENU:OUTPUT

Output Menu – Allows configuration of binary and analog outputs.

SERVICE MENU:NETWORK

Network – Allows configuration of network settings, such as number of fume hoods, Network types, Baud rate, RS-485 term, and etc.

SERVICE MENU:RPI SETUP

RPI Setup – Allows setup of LED bars color, Alarm type, what information is displayed, and Emergency button enabling.

SERVICE MENU:DIAGNOSTIC

Diagnostic – Provides manual control and monitoring of important LSC variables.

SERVICE MENU:ROOM CONTROL

Room Control – Allows primary and secondary room configuration such as Room Type, Control Type.

SERVICE MENU:TEMP CONTROL

Temp Control – Allow set point configuration for such things as Nite heat and cool set points, low and high set points.

PRESS MENUTO EXIT

Exit to default menu.To access the service menu hold ‘Enter/Menu’ for 5 seconds. This menu is password protected for safety.

Please contact your local rep for Passcode or contact -

Price Critical Controls:

678-578-7495

[email protected]

CAUTION

LABORATORY SPACE CONTROLLER

9pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATION

Wizard MenuDuring the wizard, press the ‘Enter/Menu’ button to proceed through the menus. These is no back button, so take time to ensure the correct information is entered. During the setup wizard, if incorrect information has been entered, there are two options available;

1. Proceed through the wizard and correct the information afterwards

2. Unplug the interface. This will cause the setup wizard to start from the beginning

SERVICE MENU: WIZARD

WELCOME! SETUP WIZARD

Setup Wizard – Press Menu key to advance through the wizard.

CONTROL TYPE SUP/EX TRACK

Control Type – Select the how the airflow for the room is being controlled:No Control - No room control.Sup/Ex Track - Supply and Exhaust tracking pair. LSC controls supply and exhaust dampers/valves using volumetric offset. ie: Supply 400 CFM, exhaust 500 CFM. Offset is -100 CFM.

ROOM MODE NEGATIVE

Select the type of pressure isolation for the laboratory space. Positive or Negative.

# VAVSUPPLIES 1

VAV Supplies - Enter the number of supplies that will the LSC will be controlling in the space.Ex: If the space has 2 supply valves, enter 2.

VAV SUPPLY #1

Current VAV Supply selected for configuration.

SPFLW 1 INPUTAI3

Supply Flow Input – Select the analog input to be used for the supply flow signal.

AI3 SELECTEDOK

Analog input selected. Press Enter to continue.

SPFLOW 1 TYPEVENTURI FLOW

Supply Flow Type – Select between Venturi or Terminal flow type.Select Venturi Flow when the selected supply valve is a venturi valve.Select Terminal Flow when the selected supply valve is a terminal unit.

SPFLW1 MINVAL90 CFM

Supply Flow Minimum Value – Set the minimum CFM value for the supply flow.This is the minimum airflow range that the valve is capable of operating at.

SPFLW1 MAXVAL1500 CFM

Supply Flow Maximum Value – Set the maximum CFM value for the supply flow.This is the maximum airflow range that the valve is capable of operating at.

SPFLW1 MINVIN2.00 VDC

Supply Flow Minimum Input Voltage - Set the minimum voltage that the selected analog input will receive. Ex: Set this to 2.00V when reading a 2-10V airflow signal.Default: 2.00 VDCAvailable with Terminal Flow selected only.

SPFLW1 MAXVIN10.00 VDC

Supply Flow Maximum Input Voltage - Set the maximum voltage that the selected analog input will receive. Ex: Set this to 10.00V when reading a 2-10V airflow signal.Default: 10.00 VDCAvailable with Terminal Flow selected only.

Continue to next page...

LABORATORY SPACE CONTROLLER

10 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATION

Wizard Menu Continued

SPFLW1MINVAL0.90 INH20

Minimum reading in inches of water that the LSC will read. This must match you transducer’s minimum value. Typically 0.0 inH2O.Default: 0.90 inH2ONOTE: Only available with Terminal Flow selected.

SPFLW1 MAXVAL15.00 INH2O

Maximum reading in inches of water that the LSC will read. This must match you transducer’s maximum value. Typically 1.0 inH2O. Default: 15.00 inH2ONOTE: Only available with Terminal Unit selected.

SPFLW1 KFACTR890

Advanced option. Contact your Price representative for more information. Only available with Terminal Unit selected. Default: 890

#SPLYPRESSURE1

Enter the number of analog inputs required for supply pressure.NOTE: If there are 2 supply valves are in the space and both are measuring valve pressure, enter 2.

SPLYPRESSURE#1 Indicates which supply pressure is being configured.

SPPRS 1 INPUTAI 4 Supply Pressure Input - Select analog input to be used for the supply pressure signal.

AI4 SELECTEDOK Analog input selected. Press Enter to continue.

SPPRS 1 TYPEPRESSURE Supply Pressure Type - Confirmation screen indicating that pressure is being monitored.

SPRS 1 MINVAL0.00 INH20

Supply Pressure Minimum - Range of the supply pressure sensor. Sets the minimum value that the input signal will read.NOTE: Set minimum value to 0.00 when using Price LMX.

SPRS 1 MAXVAL5.00 INH20

Supply Pressure Maximum - Range of the supply pressure sensor. Sets the maximum value that the input signal will read.NOTE: Set maximum value to 5.00 when using Price LMX.

SUPPLY MODECONSTANT VOL

Set the mode how air is supplied into the space. When the valve has no actuation control and the scheduled airflow is set at a fixed rate, select Constant Volume . When the valve is actuated and the scheduled airflow has a minimum and a maximum rate, select Variable Volume.

SUPPLYCOOLMIN100 CFM

Supply Cool Minimum - Minimum airflow rate the controller with target when the space is in cooling mode. Available with Variable Volume only.

SUPPLYCOOLMAX700 CFM

Supply Cool Maximum - Maximum airflow rate the controller with target when the space is in cooling mode. Available with Variable Volume only.

HEATING FLOW100 CFM Airflow rate the supply valve will target while the space is in heating mode.

SUPFLOWTARGET500 CFM

Supply Airflow Target - In cases where constant supply airflow is required for a lab this setting will set the airflow target. Available with constant airflow only.

UNOCCAIRFLOW100 CFM

Unoccupied Airflow - The airflow rate within a space that the controller will target while the space is in unoccupied mode. This is the airflow rate that the supply valve will target. The controller will maintain the volumetric offset (if applicable).

Continue to next page...

LABORATORY SPACE CONTROLLER

11pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATION

Wizard Menu Continued

SUPPLYACT.OUTAO1 Supply Actuator Output – Set which analog output will be used to control the supply valve(s).

SUPACTRUNTIME4 SEC.

Supply Actuator Runtime – The length of time that the supply actuator will run to meet its target.For High Speed actuators, enter 4 seconds. For standard speed actuators, enter 95 seconds.Default: 4 sec.

STATICSUPPLY0 CFM

Set the value for the static supply. Static supply is constant supply airflow that is being supplied into the space but is not modulated by the controller. Default 0 CFM for variable volume airflow.

# GEX INPUTS1

General Exhaust Inputs - Enter the number of general exhaust valves that will the LSC will be controlling in the space.Ex: If the space has 2 exhaust valves, enter 2.

GXFLOW 1 INPUTAI5 General Exhaust Airflow Input - Select the analog input to be used for the exhaust flow signal.

GEX INPUT #1 Indicates which GEX is currently being configure

AI 5 SELECTEDOK Analog input selected. Press Enter to continue.

GXFLW 1 TYPEVENTURI FLOW

General Exhaust Flow Type – Select between Venturi or Terminal flow type.Select Venturi Flow when the selected supply valve is a venturi valve.Select Terminal Flow when the selected supply valve is a terminal unit.

GXFLW1 MINVAL90 CFM

General Exhaust Airflow Minimum Value – Set the minimum CFM value for the exhaust flow.This is the minimum airflow range that the valve is capable of operating at.

GXFLW1 MAXVAL1500 CFM

General Exhaust Airflow Maximum Value – Set the maximum CFM value for the exhaust flow.This is the maximum airflow range that the valve is capable of operating at.

GXFLW1 MINVIN2.00 VDC

Exhaust Flow Minimum Input Voltage - Set the minimum voltage that the selected analog input will receive from the exhaust valve. Ex: Set this to 2.00V when reading a 2-10V airflow signal.Default: 2.00 VDCAvailable with Terminal Flow selected only.

GXFLW1 MAXVIN10.00 VDC Analog input selected. Press Enter to continue.

GXFLW1 MINVAL0.90 INH2O

Minimum reading in inches of water that the LSC will read from the exhaust valve. This must match you transducer’s minimum value. Typically 0.0 inH2O.Default: 0.90 inH2ONOTE: Only available with Terminal Flow selected.

GXFLW1 MAXVAL15.00 INH2O

Maximum reading in inches of water that the LSC will read from the exhaust valve. This must match you transducer’s maximum value. Typically 1.0 inH2O. Default: 15.00 inH2ONOTE: Only available with Terminal Unit selected.

Continue to next page...

LABORATORY SPACE CONTROLLER

12 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATION

GXFLW1 KFACTR890

Advanced option. Contact your Price representative for more information. Only available with Terminal Unit selected. Default: 890

#EXHAUSTPRESS1

Enter the number of analog inputs required for exhaust pressure.NOTE: If there are 2 exhaust valves are in the space and both are measuring valve pressure, enter 2.

EXHAUSTPRESS#1 Indicates which exhaust pressure is being configured.

EXPRS1 INPUTAI 6 Exhaust Pressure Input – Select analog input to be used for the exhaust pressure signal.

AI 6 SELECTEDOK Analog input selected. Press Enter to continue.

EXPRS1 TYPEPRESSURE Exhaust Pressure Type – Confirmation screen indicating that pressure is being monitored

EXPRS1 MINVAL0.00 INH2O

Exhaust Pressure Minimum Value - Range of the pressure transducer. Sets the minimum value that the input signal will read. NOTE: Set minimum value to 0.00 when using Price LMX

EXPRS1 MAXVAL5.00 INH2O

Exhaust Pressure Maximum Value - Range of the pressure transducer. Sets the maximum value that the input signal will read. NOTE: Set maximum value to 5.00 when using Price LMX

EXACTUATOROUTA02 Exhaust Actuator Output - Sets the analog output that will drive the exhaust valve(s).

EXACTRUNTIME4 SEC

Exhaust Actuator Runtime - The length of time that the exhaust actuator will run to meets it target. For High Speed actuators, enter 4 seconds. For standard speed actuators, enter 95 seconds. Default: 4 sec.

REHEAT OUTPUTA05

Exhaust Actuator Runtime - The length of time that the exhaust actuator will run to meets it target. For High Speed actuators, enter 4 seconds. For standard speed actuators, enter 95 seconds. Default: 4 sec.

STATICEXHAUST0 CFM

Set the airflow value for the static exhaust. Static exhaust is constant exhaust airflow that is exhausted out of the space and is not modulated by the controller. Default: 0 CFM for variable volume airflow.

CAL VALVEOK Start of valve calibration. There will be a count down from 120 sec to 0 while calibrating.

# FUME HOODS 1 Enter the number of fume hoods (up to 16 MAX) that are going to be required in a lab.

FLOW OFFSET0 CFM

Select the CFM offset value for the fixed offset type. This the volumetric offset that the LSC will target to maintain. Ex: Flow offset = 200 CFM. A negatively pressured room’s total exhaust airflow rate will be 200 CFM more than the total supply airflow rate. A positively pressured room will be the opposite.

ALARM DELAY30 SEC

User set time delay between an alarm condition being detected and an alarm sounding.Default: 30 sec.

Wizard Menu Continued

Continue to next page...

LABORATORY SPACE CONTROLLER

13pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATION

Wizard Menu Continued

RPI MUTE TIME15 MIN

Amount of time the interface, if in alarm mode, will remain muted after the mute button has been pressed. Visual alarm will continue to be displayed. Default: 15 min.

NETWORK TYPE BACNET, MNET

Choose the network type. The first option describes the network to the LSC, and the second describes the network to the EXP2.[BACnet,Mnet], [BACnet,Lnet], [Mnet, BACnet], [Mnet, Lnet]

MAC ADDRESS 1

Set the controller’s BACnet MS/TP MAC address. Range 1-99. NOTE: To prevent network issues, ensure no duplicate MAC addresses exist on the same MS/TP physical segment.

DEVICE INST. 0,158,001

Device Instance - This is the unique address for the controller. Note: To prevent network issues, set in tiers. Must be unique across entire network. Ex: First floor; 101, 102, 103. Second floor; 201, 202, 203

BAUD RATE 76800

Baud Rate - The rate with which the controller communicates over BACnet. Baud rate must be consistent across the MS/TP physi-cal segment. Options are: 9600, 19200, 38400, and 76800.

RS-485 TERM. DISABLE

This enables the RS-485 termination on the LSC MS/TP BACnet port. The network segment must be terminated at the beginning of the network chain (usually at the router) and at the end of the network chain (last device).

CALIBRATION COMPLETE

An indication that calibration is complete.

PRESS MENU TO EXIT

Controller will reset after pressing Menu.

LABORATORY SPACE CONTROLLER

14 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATION

Timing Menu

SERVICE MENUTIMING

ALARM DELAY30 SEC

Alarm Delay – This is the time between a room pressure alarm being sensed and the alarm sounding (5-3,600 sec). This gives the sensor time for the pressure to correct itself without alarm being sounded. Default: 60 sec.

CAUTN INDELAYNO

Caution in delay – Provides an option that causes the LSC to go into caution mode for the duration of the Alarm delay. Default: No.

RPI MUTE TIME15 MIN

RPI Mute Time – Amount of time the T-STAT interface, if in alarm mode, will remain muted after the mute button has been pressed. Visual alarm will continue to be displayed. Default: 15 min. (1-1440 min).

DOORALARMDLAY60 SEC

Door Alarm Delay – This delay is enabled via the binary inputs. Typically used with door switches. If door is open more than this value the monitor will alarm (10-20,000 sec). Default: 60 sec.

DOORRECOVERY5 SEC

Door Recovery – This allows for the room pressure to stabilize for a number of seconds after the door(s) have been closed before re-enabling room pressure control loops. (5-600 sec). Default: 5 seconds.

PRESS MENUTO EXIT Exit Menu – Exits back to Service menu.

DISPLAY NAVIGATION

LABORATORY SPACE CONTROLLER

15pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATIONDISPLAY NAVIGATION

Remote Panel MenuOnce in Service Menu, Scroll Down and Press Enter Menu to enter the Remote Panel Menu

SERVICE MENUREMOTE PANEL

CAUTIONCONFIGBLINK GREEN

Selection of LED color/blink during caution. Choose from: Solid Green, Blink Green, Solid Red + Green, Solid green + blinking red, Blinking red/green, Solid red, Blinking red. Default: Green Solid.

ALARM TYPEWAIL Selects the alarm sound type. Choose from: Wail, 2kHz tone, Red Alert, No Tone. Default: Wail.

ALARM CONFIGBLINK Select the LED action during alarm. Choose from: Blink, Solid ON, Off. Default: Blink.

MUTE TIME15 MIN Configure the amount of time the remote panel will mute for when the mute button is pressed.

KEYSWOVERRIDENO

Key Switch Override – This allows you to override the remote panel key switch when set to Yes. Default: No (Recommend: No).

PRESS MENUTO EXIT Exits back to Service Menu.

LABORATORY SPACE CONTROLLER

16 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATION

SERVICE MENUINPUT

INPUTSENSORS PRISENSREVRSE

NO

Primary Sensor Reverse - Gives the option to reverse the primary room pressure sensor if it is installed in the wall “backwards” (main sensor is in the isolation room and reference sensor in the corridor). Default: No.

SECSENSREVRSENO

Secondary Sensor Reverse - Gives the option to reverse the secondary room pressure sensor if it is installed in the wall “backwards” (main sensor is in the isolation room and reference sensor in the corridor). Default: No.

SWITCH PORTSNO

Give the ability to switch the secondary and primary sensor ports. If the primary and secondary room pressure sensors are inversely wired, select ‘YES’ to electronically switch them.

PRISCALEFACTR1.000

Primary Sensor Scale Factor - Adjust the scale for the primary room pressure sensor. Calibrate to a manual manometer reading. If the primary room pressure sensor reading is high compared to the manual reading, reduce the primary scale factor until the primary room pressure sensor reading matches the manual manometer reading. Ex: PrimarySensor = +0.0024, reduce the Primary Scale Factor to 0.900. Default: 1.000

PRISENSOFFSET0.0000”W.C.

Primary Sensor Offset - Adjust the offset for the primary sensor. Advanced option, not recommended. Use scale factor instead.

SECSCALEFACTR1.000

Secondary Sensor Scale Factor - Adjust the scale for the secondary room pressure sensor. Calibrate to a manual manometer reading. If the secondary room pressure sensor reading is high compared to the manual reading, reduce the secondary scale factor until the secondary room pressure sensor reading matches the manual manometer reading. Ex: SecondarySens = +0.0024, reduce the Secondary Scale Factor to 0.900. Default: 1.000

SECSENSOFFSET0.0000”W.C.

Secondary Sensor Offset - Adjust the offset for the secondary room pressure sensor. Advanced option, not recommended. Use scale factor instead.

PRESS MENUTO EXIT Exit back to Service Menu.

Input Menu

Continue to next page...

17

LABORATORY SPACE CONTROLLERDISPLAY NAVIGATION

pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

INPUTBINARY INPUTS

BI SELECT1 Choose the binary output to configure.

BI1 TYPEDISABLED

Configure the chosen binary input to:

Disabled

Door – N/O: Door switch(DSW) is a Normally Open DSW. Default Price DSW

Door – N/C: DSW is Normally Closed

Alarm on Clo – Alarm On Close. An alarm is triggered when the binary input is contacted (closed).

Alarm on Opn – Alarm On Open. An alarm is triggered when the binary input is not contacted (open).

Cautn on Clo – Caution On Close. Controller goes into caution mode when the binary input is contacted (closed).

Cautn on Opn – Caution On Open. Controller goes into caution mode when the binary input is not contacted (open).

Occ. On Clo – Occupied On Close. Controller goes into Occupied mode

when the binary input is contacted (closed).

Unocc. On Clo – Unoccupied On Close. Controller goes into Unoccupied mode when the binary input is contacted (closed).

AddSplyonClo – Add Supply On Close. This tells the controller that when this binary input is contacted (closed) that an extra supply is being added to the system.

AddSplyonOpn – Add Supply On Open. This tells the controller that when this binary input is not contacted (open) that an extra supply is being added to the system.

AddExshtOnClo – Add Exhaust On Close. This tells the controller that when this binary input is contacted (closed) that an extra exhaust is being added to the system.

AddExhstOnOpn – Add Exhaust On Open. This tells the controller that when this binary input is not contacted

(open) that an extra exhaust is being added to the system.

OpenSupplyGex – Open Suppy & General Exhaust. This tells the controlled to open the supply and exhaust valves when this binary input is contacted (closed).

CloseSupplyGe – Close Supply & General Exhaust. This tells the controller to close the supply and exhaust valves when this binary input is contacted (closed).

OpnSplyCloGex – Open Supply and Close General Exhaust. This tells the controller to open the supply valve(s) and close the exhaust valve(s) when the binary input is contacted (closed).

CloSplyOpnGex – Close Supply and Open General Exhaust. This tells the controller to close the supply valve(s) and open the exhaust valve(s) when the binary input is contacted (closed).

BI AIRFLOW10 CFM

Binary Input Additional Airflow - Adds X amount of CFM to the total supply/exhaust when the binary input condition has been satisfied. Only available with the following options: AddSplyOnClo, AddSplyonOpn (add supply on close/open), AddExhstOnClo, AddExhstOnOpn (add exhaust on close/open)

BINARY INPUTNOT CONTACTED Display if the chosen binary input is open (not contacted), or closed (contacted).

CAUTIONONDOORYES

Caution on Door - While the door(s) are ajat, the controller will go into caution mode.Default: Yes

PRESS MENUTO EXIT Exit back to Service Menu.

Input Menu Continued...

Continue to next page...

LABORATORY SPACE CONTROLLER

18 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATION

Input Menu Continued...

EXTHERM USAGETEMP MONITOR

External Thermistor Usage – Determine what the external thermistor will be used for. Temp Monitor: monitoring the air temperature in the ductDischarge Temp: Monitors the temperature of the air after the reheat valve Supply Temp: Monitors the temperature of the air being supplied to the valve

EXTHERM TEMP-59.0°F

External Thermistor Temperature – Displays the temperature that the external thermistor is reading. Will display 300.0°F if there isno EXP2 connected, or if there is no thermal coupler connected to the EXP2. If EXP2 is present and no thermistor detected, -59°F will be displayed.

EXTHERMOFFSET0.0°F

External Thermistor Offset – Adjust the offset for the external thermistor’s temperature reading.

RM TEMPOFFSET0.0°F Room Temperature Offset – Adjust the offset for the room temperature.

AI SELECT3 Select the analog input to configure.

AI3 TYPEVOLTS

1. Volts – Tells the controller to expect a voltage signal on this input

2. Venturi Flow – Tells the controller to expect to receive an airflow signal from a venturi valve

3. Terminal Flow – Tells the controller to expect to receive an airflow signal from a terminal unit cross flow sensor.

4. AirChngLinear – Air Change Linear. Set the input to Air Change Linear only if it is reading in the airflow rate from the venturi valve. Air change is calculated using the linear airflow signal from the valve and the user set room size. Advanced option, contact your Price Critical Controls rep.

This is for display over BACnet, no control function for this feature.

5. AirChng Press – Air Change Pressure. Set the input to Air Change Pressure only it is reading in the signal from a velocity pressure sensor from a terminal unit. Air Change is calculated using the pressure signal from the velocity pressure sensor and the user set room size. Advanced option, contact your Price Critical Controls rep. This is for display over BACnet, no control function for this feature.

6. Pressure – Tells the controller to expect a pressure signal on this input such as a venturi valve pressure signal

AI3 USAGEDISABLED

Available with Airflow Linear, Airflow Press, and Pressure only.

1. VAV Sply Flow - VAV Supply Flow. Specify that the signal being received is the supply valve airflow signal

2. DiscrSplyFlow - Discrete Supply Flow. If the airflow on this unit is a supply that is not controlled by a supply actuator

3. VAV Gex Flow - VAV General Exhaust. Specify that the signal being received is the exhaust valve airflow signal

4. DiscrExstFlow - Discrete Exhaust Flow. If the airflow on this unit is an exhaust that is not controlled by a general exhaust actuator

5. DCVSupplyTrgt - Demand Control Ventilation Supply Target - Allows you to set the minimum ventilation scaling requirement for the analog input. Used with Aircuity.

AI3 MIN VIN2.00 VDC

Minimum Input Voltage - Set the minimum voltage that the selected analog input will receive. For example: Set this to 2.00V when reading a 2-10V airflow signal. Default: 0.00 VDC

INPUTANALOG INPUT

Continue to next page...

LABORATORY SPACE CONTROLLER

19pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATION

Input Menu Continued...

PRESS MENUTO EXIT

AI3 MAX VIN10.00 VDC

Maximum Input Voltage - Set the maximum voltage that the selected analog input will receive. For example: Set this to 10.00V when reading a 2-10V airflow signal. Default: 10.00 VDC

AI3 MIN VAL90 CFM

Minimum Airflow Value - Set the airflow range of the valve.NOTE: This is the lowest CFM value that the valve is capable of, not the minimum scheduled CFM value of the valve. Available with Venturi Valve selected.

AI3 MAX VAL1500 CFM

Maximum Airflow Value - Set the airflow range of the valve. NOTE: This is the highest CFM value that the valve is capable of, not the maximum schedule CFM value of the valve. Available with Venturi Valve selected.

AI3 KFACTOR890

Select the proper k factor based on the valve size. Available with Airflow Press,Airchnge Press only. Advanced option. Contact your Price representative for more information.

AI3 RM SIZE1800 FT3

Enter the cubic footage of the room. Linear Airflow change, Airchnge Press, and Pressureonly.

AI3 OFFSET0.00 VDC Adjust the offset of chosen analog input.

SCALE FACTOR1.000 Adjust the voltage scale factor for accuracy.

AI3 LOW ALARMDISABLE

Low Alarm – Allow the user to configure at which value to sound the low value alarm. If the analog input drops below this value, the controller will go into alarm mode.

AI3 HIGH ALRMDISABLED

High Alarm – Allow the user to configure at which value to sound the high value alarm. If the analog input rises above this value, the controller will go into alarm mode.

AI3 LOW CAUTNDISABLED

Low Caution – Allow the user to configure at which value to trigger a low value caution alarm. If the analog input drops below this value, the controller will go into caution mode.

AI3 HIGHCAUTNDISABLED

High Caution – Allow the user to configure at which value to trigger a high value caution alarm. If the analog input rises above this value, the controller will go into caution mode.

AI3 CURRNTVAL0.00 VDC Display the current value of chosen analog input.

PRESS MENUTO EXIT Exit back to Service Menu.

LABORATORY SPACE CONTROLLER

20 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATION

Output MenuOnce in Service Menu, Scroll Down and press ‘Enter Menu’ to enter the LSC Output Menu.

SERVICE MENUOUTPUT

OUTPUTBINARY OUTPUT

BO1 USAGEALARM

Alarm – The binary output will activate if the controller goes into Alarm mode Caution – The binary output will activate if the controller goes into Caution mode Normal – The binary output will activate while the controller is in Normal operating mode Neutral – The binary output will activate while the controller is in Neutral operating mode Caution/Alarm – The binary output will activate if the controller goes into either Caution or Alarm mode Low Pressure – The binary output will activate if the pressure drops below the Low Pressure value High Pressure – The binary output will activate

if the pressure exceeds the High Pressure value PriLoPressure – The binary output will activate if the Primary Room’s pressure drops below the Low Pressure range PriHiPressure – The binary output will activate if the Primary Room’s pressure is above the High Pressure range SecLoPressure – The binary output will activate if the Secondary Room’s pressure drops below the Low Pressure range SecHiPressure – The binary output will activate if the Secondary Room’s pressure is above the High Pressure range Emergency – The binary output will activate if the Emergency button has been pushed

Door – The binary output will activate if a door connected to the controller is ajar PriRm Alarm – The binary output will activate if the Primary Room Alarm is triggered SecRm Alarm – The binary output will activate if the Secondary Room Alarm is triggered Follow BI 1 – The binary output will activate if BI 1 is activated Invert BI 1 – The binary output will activate while BI1 is not active Follow BI 2 – The binary output will activate if BI2 is activated Invert BI 2 – The binary output will activate while BI2 is not active

BO2 USAGECAUTION See BO1 Usage for options

BO3 USAGEHEAT 1

BO4 USAGEHEAT 2 See BO3 Usage for options

Binary Outputs 1 and 2 are dry contacts that can signal the following events.Binary Outputs 3,4, and 5 are active 24 VAC triac outputs with the following options.

Unused

Heat 1 – Heat 1 is used for Stage 1 of the reheat stages. It will output a 24VAC signal when the controller is in Stage 1 of the reheat stages

Heat 2 – Heat 2 is used for Stage 2 of the reheat stages. It will output a 24VAC signal when the controller is in Stage 2 of the reheat stages

Heat 3 – Heat 3 is used for Stage 3 of the reheat stages. It will output a 24VAC signal when the controller is in Stage 3 of the reheat stages

Humidify – The binary output will output a 24VAC signal when there is a call for humidity

Alarm – The binary output will output a 24VAC signal while the controller is in alarm mode.

Normal – The binary output will output a 24VAC signal while the controller is in normal/setback mode.

Occupancy – The binary output will output a 24VAC signal while the controller is in occupied mode.

Cooling – When the controller goes into cooling mode, a 24VAC signal will be outputted from the selected binary output.Follow BI 1 – The binary output will activate if BI 1 is activated Invert BI 1 – The binary output will activate while BI1 is not active Follow BI 2 – The binary output will activate if BI2 is activated Invert BI 2 – The binary output will activate while BI2 is not active

Continue to next page...

LABORATORY SPACE CONTROLLER

21pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATION

Output Menu Continued...

AO1 USAGEHUMIDIFIER

Unused

PriPress5V=0” – Primary Room Pressure 5V = 0” W.C. This option outputs a analog voltage signal, starting at 5VDC, relative to the primary room’s pressure reading. For 0”W.C. the controller will output 5VDC

PriPress0-10V – Primary Room Pressure 0-10V. This option outputs a 0-10V signal relative to the primary room’s pressure reading.

SecPress5V=0” – Secondary Room Pressure 5V=0” W.C. This option outputs a analog voltage signal, starting at 5VDC, relative to the secondary room’s pressure reading. For 0”W.C. the controller will output 5VDC

SecPress0-10V – Secondary Room Pressure 0-10V. This option outputs a 0-10V signal relative to the secondary room’s pressure reading.

Alarm 5V – Output a 5 VDC signal when in alarm mode. Output will return to 0V when alarm is cleared.

PriAlarm 5V – Primary Room Alarm. If the primary room goes into alarm, this tells the controller to output a 5VDC signal out of the selected output. Output will return to 0V when alarm is cleared.

SecAlarm 5V – Secondary Room Alarm. If the secondary room goes into alarm, this tells the controller to output a 5VDC signal out of the selected output. Output will return to 0V when alarm is cleared.

PriRm SplyAct – Primary Room Supply Actuator. This sets the output to control the supply valves/dampers actuators for the primary room.

PriRm ExhAct – Primary Room Exhaust Actuator. This sets the output to

control the exhaust valves/dampers actuators for the primary room.

SecRm SplyAct – Secondary Room Supply Actuator. This sets the output to control the supply valves/dampers actuators for the secondary room.

SecRm ExhAct – Secondary Room Exhaust Actuator. This sets the output to control the exhaust valves/dampers actuators for the secondary room.

Reheat – Sets the selected analog output to control the reheat valve signal. The analog output will output a voltage when there is a call for heating.

Humidifier – Sets the selected analog output to control the humidifier signal. The analog output will output a voltage when there is a call for humidity.

AO2 USAGEREHEAT NOTE: See A01 for options.

AO3 USAGEUNUSED NOTE: See A01 for options.

AO4 USAGEUNUSED NOTE: See A01 for options.

OUTPUTANALOG OUTPUT

BO5 USAGEHEAT 3 See BO3 Usage for options

PRESS MENUTO EXIT Exits back to Service Menu.

Continue to next page...

22

LABORATORY SPACE CONTROLLERDISPLAY NAVIGATION

LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

Output Menu Continued...

AO5 USAGEUNUSED NOTE: See AO1 for options.

AO6 USAGEUNUSED NOTE: See AO1 for options

CURRENT AO12.00 VDC Provides the current voltage for AO1.

CURRENT AO25.00 VDC Provides the current voltage for AO2.

CURRENT AO30.00 VDC Provides the current voltage for AO3.

CURRENT AO45.00 VDC Provides the current voltage for AO4.

CURRENT AO50.00 VDC Provides the current voltage for AO5.

CURRENT AO60.00 VDC Provides the current voltage for AO6.

PRESS MENUTO EXIT Exit back to Service Menu.PRESS MENU

TO EXIT

LABORATORY SPACE CONTROLLER

23pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATION

Network Menu

SERVICE MENUNETWORK

# FUME HOODS 0 Enter the number of fume hoods in the network. Up to a maximum of 16.

HOODS DETECTED0

Indicates the number of hoods detected. The number of fume hoods detected should match the number of fume hood in the network. If not, there is a issue with one of the fume hoods.

NETWORK TYPEBACNET, MNET

Choose the network type. The first option describes the network to the LSC, and the second describes the network to the EXP2. [BACnet,Mnet], [BACnet,Lnet], [Mnet, BACnet], [Mnet, Lnet]

MAC ADDRESS1

Set the controller’s BACnet MS/TP MAC address. Range 1-99. NOTE: To ensure no duplicate MAC addresses exist on the same MS/TP physical segment.

DEVICE INST.158,001

Device Instance – is the unique address for the LSC. NOTE: To prevent network issues, set in tiers. Must be unique across entire network. Ex: First floor; 101, 102, 103. Second floor; 201, 202, 203

BAUD RATE76800

The rate with which the LSC communicates over BACnet. Baud rate must be consistent across the MS/TP physical segment: 9600, 19200, 38400 and 76800

RS-485 TERMDISABLED

This enables the RS-485 termination on the LSC MS/TP BACnet port. The network segment must be terminated at the beginning of the network chain (usually at the router) and at the end of the network chain (last device).

PRESS MENUTO EXIT Exits back to Service Menu.

LABORATORY SPACE CONTROLLER

24 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATION

RPI Setup Menu

SERVICE MENU:RPI SETUP

EMERG BUTTONDISABLED Emergency Button – This button on the RPI can be enabled or disabled

LITEBAR-NORM.GREEN

Light Bar in Normal Mode – This sets the color of the light bar while in normal conditions (no alarm, no caution and occupied room).

LITEBAR-ALARM.BLINK RED Light Bar in Alarm Mode – This sets the color of the light bar while in alarm conditions.

LITEBAR-CAUT.YELLOW Light Bar in Caution Mode – This sets the color of the light bar while in caution conditions.

LITEBAR-UNOCC.SKY BLUE Light Bar in Unoccupied Mode – This sets the color of the light bar while in unoccupied mode.

ALARM TYPEWAIL

Alarm Type – This sets the sound of the alarm. Choose between three different alarm sounds; No tone, Steady 2Khz, Wail, Red Alert

OCCUPACNYNAMESETBACK/ISO

Occupancy Name – Selects the name displayed for Occupancy. Choose between Occ/Setback, Alarm mode, Setback/Isolation, Nutrl/Pos-Neg, or Occupancy.

DISPLAY CODE3

Display Code – Provides options for what is displayed, such as room pressure, occupancy, and etc.Add the values together and enter the sum to display multiple screens of information. Ex: 2+16=18 will display Primary Room/-0.0100” W.C. and Secondary Room/-0.0100” W.C.

Main screen displays Value BinaryPrimary Room 1 0000 0001

Negative

Primary Room 2 0000 0010

-0.0100" W.C.

Negative 4 0000 0100

-0.0100" W.C.

Secondary Room 8 0000 1000

Negative

Secondary Room 16 0001 0000

-0.0100" W.C.

System Normal 32 0010 0000 (Available if no secondary room OR both pri/sec isolation modes match)

Negative

DisplayOptions 16384 Opens up the Display Options menu. See below.

Continue to next page...

LABORATORY SPACE CONTROLLER

25pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATION

DISPLAYOPTIONS SETPOINT ONLY

Choose what is displayed on the interface. Options are:1. Temp and SetP – Temperature displayed on main screen, setpoint displayed/adjusted when up/down buttons are.2. Setpoint Only – Displays the setpoint only3. RoomTemp Only – Displays the room temperature only. No setpoint adjustment allowed4. CtlName/SP en – Display the controller name and temperature setpoint, and enable the setpoint to be adjustable5. CtlName/Spdis – Display the controller name and temperature setpoint, and disable theability to adjust the setpoint6. NameTemp/Spen – Display the controller name, room temperature, and

temperature setpoint. Enable the setpoint to be adjustable7. NameTemp/SPds – Display the controller name, room temperature, and

temperature setpoint. Disable theability to adjust the setpoint8. Name and Setp – Display the user set name and the temperature setpoint.9. Temp&Humidity – Display the room temperature and humidity reading *10. Humidity – Display the room’s current humidity reading *NOTE: All options require a Price Thermostat. Controller name settable with computer Wizard only.*Option requires the Price Humidity Thermostat to function correctly

OCC TIMEOUT120 MIN Occupancy Timeout – Amount of time before room goes into unoccupied mode.

PRESS MENUTO EXIT Exit Menu – Exits back to SERVICE menu

RPI Setup Menu Continued

LABORATORY SPACE CONTROLLER

26 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATION

Diagnostic MenuOnce in Service Menu, Scroll Down and press ‘Enter Menu’ to enter the LSC Service Menu.

SERVICE MENUDIAGNOSTIC

BACNET HEALTH100 %

BACnet Health – Shows current status of BACnet MS/TPconnection. No connection means no active connection. 100% means good connection. 0-99% means possible connection issues, check wiring, addresses, and polarity.

PRIMARYSENSORDISCONNECTED Primary Sensor – Shows current connection status of the Primary Room Pressure Sensor. Connected or Disconnected.

PRIMARYSENSOR0.0000”W.C. Primary Sensor – Shows current Primary Room Pressure sensor reading.

SECONDARYSENSDISCONNECTED Secondary Sensor – Shows current connection status of Secondary Room Pressure Sensor.

SECONDARYSENS0.0000”W.C. Secondary Sensor – Shows current Secondary Room Pressure sensor reading.

KEYSWITCHPSTNNO KEY

Key Switch Position – Displays the current key switch position. This is used when a remote Nurses Station (with key switch) is connected to the LSC.

TOTAL SUPPLY0 CFM Displays the current total amount of airflow being supplied into the space from the supply valves.

TOTAL EXHAUST0 CFM Displays the current total amount of exhaust airflow from all contributing exhaust valves.

GEX FLOW0 CFM General Exhaust Flow – Displays the current amount of exhaust airflow from only the general exhaust valves.

FHOODEXHSTSUM0 CFM Fume Hood Exhaust Sum – Displays the current CFM value from the fume hood exhaust valves.

RPC EXPANSIONDISCONNECTED

Room Pressure Controller Expansion - Displays the connection status of the LSC expansion. Connected or Disconnected.

HOODSDETECTED0 Displays the number of fume hoods detected.

DIAGNOSTIC:CAL VALVE Allows for calibration of the valves. A timer from 120 sec to 0 will count down while the valve is calibrating.

DIAGNOSTIC:LOAD DEFAULTS Resets all user settings back to factory default.

DIAGNOSTIC:RESETCONTROLR Reset Controller - Reboots the controller, mimicking a power cycle. No settings will be lost.

PRESS MENUTO EXIT Exit back to Service Menu.

LABORATORY SPACE CONTROLLER

27pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATION

Room Control Menu

SERVICE MENUROOM CONTROL ROOM SELECT

PRIMARY

Select the room to be configured.• Primary• Secondary

ROOM MODENEGATIVE Configure whether the room will have negative pressure or positive pressure.

CONTROL TYPENO CONTROL

Choose a control type:No Control - LSC will act as a room pressure monitor. Outputs not controlled.Sup/Ex Track - Supply and Exhaust tracking pair. LSC controls supply and exhaust dampers/valves using volumetric offset. ie: Supply 400 CFM, exhaust 500 CFM. Offset is -100 CFM.Sup/Ex Dynamic - Supply and Exhaust Dynamic - LSC continuously monitors the room pressure and adjusts the offset as required to maintain the room pressure. ie: Min offset = 50 CFM, max offset = 500 CFM.

PRESSSETPOINT0.0000” W.C.

Pressure Setpoint – Allows user to select the target pressure for the space. Range +0.1000” W.C. to -0.1000” W.C. Default: -0.0150” W.C. Not available with Sup/Ex Track.

ADAPT LOCKONS2

Adapt Lockons – This determines the time between adjustments of the dynamic room offset. Advanced option. Not available with Sup/Ex Track. Default: 2.

ADAPT STEPDIV10

Adapt StepDiv – Adapt Step Division. Set the room pressure deadband for the dynamic room pressure offset. Advanced option. Not available with Sup/Ex Track. Default: 10.

ADAPT MAXSTEP25 CFM

Adapt MaxStep – Adapt Maximum Step. Maximum CFM change for each step. Advanced option. Not available with Sup/Ex Track. Default: 25 CFM.

ROOM CONTROL:AIRFLOW SETUP NOTE: This menu is accessible only if the SupFlowInput has been configured

NOTE: SETUP INPT MENU 1ST

Following section is to setup the supply flow configurations. Note: Inputs must be setup first.

SUPPLY MODEVARIABLE VOL

Set the mode how air is supplied into the space. When the valve has no actuation control and the scheduled airflow is set at a fixed rate, select Constant Volume . When the valve is actuated and the scheduled airflow has a minimum and a maximum rate, select Variable Volume.

SUPPLYCOOLMIN100 CFM

Minimum airflow rate the supply valve will target when the space is in cooling mode. Available with Variable Volume only. Default: 100 CFM

SUPPLYCOOLMAX700 CFM

Maximum airflow rate the supply valve will target when the space is in cooling mode. Available with Variable Volume only. Default: 700 CFM

LABORATORY SPACE CONTROLLER

28 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATIONDISPLAY NAVIGATION

Room Control Menu Continued...

SUPPLYHEATMIN100 CFM

Minimum airflow rate the supply valve will target when the space is in heating mode. Available with Variable Volume only. Default: 100 CFM

SUPPLYHEATMAX700 CFM

Maximum airflow rate the supply valve will target when the space is in heating mode. Available with Variable Volume only. Default: 700 CFM

SUPPLYNEUTFLOW500 CFM

Supply Neutral Flow – The airflow rate the controller will target while there is no call for heating or cooling.

SUPSETBACKFLW100 CFM

Supply Setback Flow – Supply airflow rate that the supply valve will target while in setback mode.

EXHSTOFFSTMIN0 CFM

Exhaust Minimum Offset - Set the minimum offset value in CFM that the exhaust will target to maintain compared to the supply.

EXHSTOFFSTMAX500 CFM

Exhaust Maximum Offset - Set the maximum offset value in CFM that the exhaust will target to maintain compared to the supply.

EXHUNOCCCONFIGNEW OFFSET

Exhaust Unoccupied Configuration - Configuration that determines how the controller will react when the room goes into unoccupied mode. Only available with Sup&Ex Dynamic.

Maintain Pressure - The controller will maintain room pressure and will not change the exhaust offset.

New Offset - The controller will switch to the user set exhaust offset. This value can be set in the ExhUnocOffset menu option.

EXHAUSTOFFSET200 CFM

Exhaust airflow offset that the controller will target as compared to the supply airflow while in occupied mode. Not available with Sup&Ex Dynamic

EXHUNOCOFFSET50 CFM

Exhaust Unoccupied Offset – Exhaust airflow offset that the controller will target as compared to the supply airflow while in unoccupied mode. Available with Sup/Ex Track and with Sup&Ex Dynamic with New Offset option selected for ExhUnocConfig.

Continue to next page...

29

LABORATORY SPACE CONTROLLERDISPLAY NAVIGATION

pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

Room Control Menu Continued...

SUPPLYTEMPCFGFORCE COLD

Supply Temperature Configuration – Override to force heating or cooling. Available with Sup/Ex Track.SupplyTempCfg – Supply Temperature Configuration. Force cold, force hot, conventional, dynamic.Force Cold – If the supply to the valve will always be cold air, set to Force ColdForce Hot – If the supply to the valve will always be hot air, set to Force HotNote: Following options only available with ExThermUsage set to ‘Supply Temp’Dynamic – Heat/cool change over. Supply air from the duct is determined to be cold if it is 2° or more below current room temperature and determined to be hot when 2° or more over the current room temperatureConventional – Cold switch and hot switch are the points that determine if the duct temperature is hot or cold if they are above or below those points.

COLD SWITCH70.0°F

If the duct temperature is below this user set value, the controller will switch into heating mode. Only available with Conventional option selected in SupplyTempCfg. Default: 70.0*F

HOT SWITCH77.0°F

If the duct temperature is above this user set value, the controller will switch into cooling mode. Only available with Conventional option selected in SupplyTempCfg. Default: 77.0*F

SUPPLY STEP DIV3

Supply Step Divider – Allows user to set the deadband of the supply airflow target. Advanced use only.Default: 3.

EXHST STEP DIV3

Exhaust Step Divider – Allows user to set the deadband of the exhaust airflow target. Advanced use only.Default: 3.

SUPPLYSRVTIME10 SEC.

Supply Service Time – LSC will calculate and move the Supply Valve for every X amount of seconds that is entered. Available with Sup/Ex Track. 1-300 sec. Default is 10 sec. (recommended).

EXHST SRVTIME10 SEC.

Exhaust Service Time – LSC will calculate and move the Exhaust Valve for everyX amount of seconds that is entered. Available with Sup/Ex Track. 1-300 sec. Default is 10 sec. (recommended).

STATIC SUPPLY0 CFM

Set the value for the static supply. Static supply is constant supply airflow that is being supplied into the space but is not being controlled by the controller. Default 0 CFM for variable volume airflow.

Continue to next page...

30

LABORATORY SPACE CONTROLLERDISPLAY NAVIGATION

LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

PRESS MENUTO EXIT

ROOM CONTROLOUTPUT SETUP

NOTE: SETUP OUTPTUSAGE1ST

Note: Setup output usages first. See Output section of the manual.

SUPPLYVOUTMIN2.00 VDC

Supply Voltage Output Minimum – Allows user to set the minimum voltage output when a call for supply is at minimum. Default: 2.00 VDC.

SUPPLYVOUTMAX10.00 VDC

Supply Voltage Output Maximum – Allows user to set the maximum voltage output when a call for supply is at maximum. Default: 10.00 VDC.

SUPACTRUNTIME4 SEC.

SupActRuntime – The length of time that the supply actuator will run to meet its target.For High Speed actuators, enter 4 seconds. For standard speed actuators, enter 95 seconds. Default: 4 sec.

EXHST VOUTMIN2.00 VDC

Exhaust Voltage Output Minimum – Allows user to set the minimum voltage output when a call for exhaust is at minimum. Default: 2.00 VDC.

EXHST VOUTMAX10.00 VDC

Exhaust Voltage Output Maximum – Allows user to set the maximum voltage output when a call for exhaust is at maximum. Default: 10.00 VDC.

EXHACTRUNTIME4 SEC.

Exh ActRuntime – The length of time that the exhaust actuator will run to meets it target. For High Speed actuators, enter 4 seconds. For standard speed actuators, enter 95 seconds. Default: 4 sec.

PRESS MENU TO EXIT Exit back to Service Menu.PRESS MENU

TO EXIT

Room Control Menu Continued...

STATIC EXHAUST0 CFM

Set the value for the static exhaust. Static exhaust is constant exhaust airflow that is exhausted out of the space but is not being controlled by the controller. Default 0 CFM for variable volume airflow.

DIVERSITYDISABLED

Diversity – If the demand for supply or exhaust exceeds the valves’ airflow range, the controller can go into the user selected Caution mode or Alarm mode. Default: Disabled.

PRESS MENUTO EXIT

LABORATORY SPACE CONTROLLER

31pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATION

Temperature Control MenuOnce in Service Menu, Scroll Down and press ‘Enter Menu’ to enter the LSC Service Menu. Continue scroll down to Temp Control and press ‘Enter Menu’.

SERVICE MENUTEMP CONTROL

ROOM TEMP300.0°F

Displays the current room temperature. Temperature reading is taken from connected Price Thermostat. Room temperature will read 300°F if no thermostat is connected.

ROOM LOAD0%

Shows the current room load. Range -100% to +100%. -100% is full cooling load, while +100% is full heating load. 0% means room is currently in deadband/satisfied.

TEMP. UNITSFAHRENHEIT Temperature Units - Choose between Fahrenheit or Celsius.

ROOM SETPOINT72.0°F

Sets the targeted temperature to be maintained by the controller.• Range is dependent on Set Lo Limit, and Set High Limit.• Default is 72.0°F.

SET LO LIMIT65.0°F

Sets the minimum user-settable limit for room temperature set point.• Range 10.00°F to 100°F.• Default is 65.0°F.

SET HI LIMIT80.0°F

Sets the maximum user-settable limit for room temperature set point.• Range 10.00°F to 100°F.• Default is 80.0°F.

DAY DIFF.1.0°F

Day Differential: Allows adjustment of the day differential aka deadband. If room temperature is within set point plus or minus this value - room load will be at 0%. Default: 1.0°F

PRO. BAND2.0°F

Proportional Band – Allows adjustments of the proportional band. If room temperature is outside of day differential and exceeds the proportional band, room load will be 100%. Default: 2.0°F

NITE HEAT SET62.0°F

Night Heat Set Point – Allows adjustment of the Night Heat Set Point. When in setback/night mode, heating will be off until this set point is reached. Default: 62.0°F

NITE COOL SET83.0°F

Night Cool Set Point – Allows adjustment of the Night Cool Set Point. When in setback/night mode, cooling will be off until this set point is reached. Default 83.0°F

TEMP CONTROL:REHEATCONTROL Temperature Control - Reheat - Allows adjustment of the reheat type and control. Note: Output Usage must be set up first.

DISPLAY NAVIGATION

NOTE: SETUPOUTPTUSAGE1ST Only available when SupplyVoutMin is set. See Output section in the manual

STAGE 11 %

This sets the trip point for staged (binary) reheat types. As room load goes up from +1% to +100%, up to 3 stages of binary reheat are triggered at these set points.

LABORATORY SPACE CONTROLLER

32 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

DISPLAY NAVIGATION

Temperature Control Menu Continued...

STAGE 2 33 %

This sets the trip point for staged (binary) reheat types. As room load goes up from +1% to +100%, up to 3 stages of binary reheat are triggered at these set points.

STAGE 3 66 %

This sets the trip point for staged (binary) reheat types. As room load goes up from +1% to +100%, up to 3 stages of binary reheat are triggered at these set points.

FAIL SAFEDISABLED

This sets reheat failsafe type. Disabled = normal - 24VAC output is active when heat is to be on. Enabled = failsafe - 24VAC output is active when heat is to be off. This ensures that cut wires/transformer failure will default heat to on. Necessary for cold climates. Default Disabled.

ANALOGHEATMIN 0.00 VDC This sets the minimum voltage for the analog reheat output. Default 0.00 VDC

ANALOGHEATMAX 10.00 VDC This sets the maximum voltage for the analog reheat output. Default: 10.00 VDC

ANALOGHEATIDL 0.00 VDC

This sets the idle voltage for the analog reheat output. For example, when in deadband or cooling. Default: 0.00 VDC. NOTE: Set this to the same value as HeatMin. in most situations.

REHEAT CTRL: DAT CONTROL

DISPLAY NAVIGATION

COOL TARGETDISABLED

Temperature the controller targets when in cooling mode. Disabled - 150°F. Default: Disabled

HEAT TARGET95.0°F

This is the Discharge Air Temperature (DAT) heating mode target temperature.

DEADBAND TRGT70.0°F

Deadband Target – When the room temperature is satisfied, the DAT will target for this temperature.

DATDEADBUNOCCDISABLED

Discharge Air Temperature target while room is unoccupied and room temperature is satisfied.

SERVICE TIME60 SEC.

Control loop update period. Amount of time that determines how often the control loop for the DAT is updated. Default: 60 sec. (10 - 3600 sec).

STEP DIVIDER10

This controls the rate at which the output is changed. Rate range is 1 to 50. 1 = maximum change rate. 50 = minimum change rate. Default: 10.

STEP MAX10%

The maximum amount the output will change at every loop service. Step range is 1% to 50%.The higher the percentage, the larger the change. Default: 10%

ACCEPTABLE DIFF3.0°F

Acceptable Difference – Acceptable difference in temperature before system makes changes.Range is 0.0°F to 25.0°F. Default: 3.0°F.

LABORATORY SPACE CONTROLLER

33pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

DISPLAY NAVIGATIONDISPLAY NAVIGATION

Temperature Control Continued...

PRESS MENUTO EXIT

DISCHG AIR TEMP300.0°F

Current temperature reading of the DAT. If display is at 300°F, thermistor is shorted or EXP2 is not present. If EXP2 is present and no thermistor detected, -59°F will be displayed.

PRESS MENU TO EXIT

PRESS MENUTO EXIT

34 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

LABORATORY SPACE CONTROLLERMAINTENANCE

BACnet Point ListObject Name Units Default Range Description R/WAI1 Primary Room Pressure inH2O Dynamic -0.1 to +0.1 Primary Room Pressure Reading R

AI2 N/A N/A N/A N/A N/A N/A

AI3 AI3 - Supply Airflow cfm Dynamic 0-10,000 Typically: supply valve (1) airflow R

AI4 AI4 - GEX Airflow cfm Dynamic 0-10,000 Typically: GEX valve (1) airflow R

AI5 AI5 - Supply Airflow cfm Dynamic 0-10,000 Typically: supply valve (2) airflow (if present) R

AI6 AI6 - GEX Airflow cfm Dynamic 0-10,000 Typically: GEX Valve (2) airflow (if present) R

AI7 AI7 - Supply Pressure inH20 Dynamic 0-5 Typically: supply valve (1) pressure R

AI8 AI8 - Exhaust Pressure inH20 Dynamic 0-5 Typically: GEX valve (1) pressure R

AI9 AI9 - Supply Pressure inH20 Dynamic 0-5 Typically: supply valve (2) pressure (if present) R

AI10 AI10 - Exhaust Pressure inH20 Dynamic 0-5 Typically: GEX valve (2) pressure (if present) R

AI11 Analog Input 11 Dynamic Dynamic Dynamic Input can be CFM, Inches of Water, etc - See O&M Manual for detail. Input Menu. R

AI12 Analog Input 12 Dynamic Dynamic Dynamic Input can be CFM, Inches of Water, etc - See O&M Manual for detail. Input Menu. R

AI13 Analog Input 13 Dynamic Dynamic Dynamic Input can be CFM, Inches of Water, etc - See O&M Manual for detail. Input Menu. R

AI14 Analog Input 14 Dynamic Dynamic Dynamic Input can be CFM, Inches of Water, etc - See O&M Manual for detail. Input Menu. R

AI15 Room Temperature °C/°F Dynamic -59° F to 300°F

Room temperature value read from the thermostat R

AI16 Expan Therm °C/°F Dynamic -59° F to 300°F

Temperature value read from the Expansion thermistor - typically discharge air temperature

R

AI17 Room Humidity % RH Dynamic 0-100 % RH RH % value read from a Price LCD with humidity thermostat. R

BI1 Binary Input 1 Contatcs Open/Close

Dynamic Contatcs Open/Closed

Binary Input can be tied to several signals. See O&M manual for detail. Input Menu. R

BI2 Binary Input 2 Contatcs Open/Close

Dynamic Contatcs Open/Closed

Binary Input can be tied to several signals. See O&M manual for detail. Input Menu. R

BI3 Binary Input 3 Contatcs Open/Close

Dynamic Contatcs Open/Closed

Binary Input can be tied to several signals. See O&M manual for detail. Input Menu. R

BI4 Binary Input 4 Contatcs Open/Close

Dynamic Contatcs Open/Closed

Binary Input can be tied to several signals. See O&M manual for detail. Input Menu. R

BI5 Binary Input 5 Contatcs Open/Close

Dynamic Contatcs Open/Closed

Binary Input can be tied to several signals. See O&M manual for detail. Input Menu. R

BI6 Binary Input 6 Contatcs Open/Close

Dynamic Contatcs Open/Closed

Binary Input can be tied to several signals. See O&M manual for detail. Input Menu. R

AO1 Analog Output 1 Volts DC Dynamic 0-10 VDC Typically: supply valve(s) actuator output R/W

AO2 Analog Output 2 Volts DC Dynamic 0-10 VDC Typically: GEX valve(s) actuator output R/W

AO3 Analog Output 3 Volts DC Dynamic 0-10 VDC The Analog Output can be tied to several signals. See O&M manual for detail. Output Menu. R/W

AO4 Analog Output 4 Volts DC Dynamic 0-10 VDC The Analog Output can be tied to several signals. See O&M manual for detail. Output Menu. R/W

AO5 Analog Output 5 Volts DC Dynamic 0-10 VDC Typically: reheat valve R/W

AO6 Analog Output 6 Volts DC Dynamic 0-10 VDC The Analog Output can be tied to several signals. See O&M manual for detail. Output Menu. R/W

BO1 Binary Output 1 On/Off Dynamic On/Off The Binary Output can be tied to several signals. See O&M manual for detail. Output Menu. R/W

BO2 Binary Output 2 On/Off Dynamic On/Off The Binary Output can be tied to several signals. See O&M manual for detail. Output Menu. R/W

BO3 BO3 - Heat Stg. 1 On/Off Dynamic On/Off The Binary Output can be tied to several signals. See O&M manual for detail. Output Menu. R/W

BO4 BO4 - Heat Stg. 2 On/Off Dynamic On/Off The Binary Output can be tied to several signals. See O&M manual for detail. Output Menu. R/W

BO5 BO5 - Heat Stg. 3 On/Off Dynamic On/Off The Binary Output can be tied to several signals. See O&M manual for detail. Output Menu. R/W

35pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

LABORATORY SPACE CONTROLLERMAINTENANCE

BACnet Point List Continued...Object Name Units Default Range Description R/WAV1 Pri Room Pressure

SetpointinH2O Dynamic 0 to 0.1 "Set point for Primary Room Pressure. Available if room pressure sensor

is present and dynamic pressure control mode is enabled.R

AV2 Pri Room Low Alarm inH2O Dynamic 0 to 0.1 Low pressure alarm trip point for controlled room (Positive or Negative depending on room type.) Requires room pressure sensor.

R

AV3 Pri Room High Alarm inH2O Dynamic 0 to 0.1 High pressure alarm trip point for controlled room (Positive or Negative depending on room type.) Requires room pressure sensor.

R

AV7 Alarm Code Bitwise Numeric Dynamic 0-4095 See Manual - not typically used R

AV8 Caution Code Bitwise Numeric Dynamic 0-8191 See Manual - not typically used R

AV9 Total Supply Flow cfm Dynamic 0-10000 Total Supply Airflow into room. The sum of all supply inputs. R

AV10 Supply Airflow Target cfm Dynamic 0-10000 Supply Airflow Target R

AV11 Total Exhaust Airflow cfm Dynamic 0-10000 Total Exhaust flow includes General Exhaust, Hoods, Cabinets, snorkels, et R

AV12 GEX Airflow Target cfm Dynamic 0-10000 GEX Airflow Target R

AV13 Airflow Offset cfm Dynamic 0-10000 Targeted offset between all supplies/exhausts R

AV14 Room Temperature Setpoint

°C/°F Dynamic 65°F to 80°F (defaults)

Setpoint Range is defined by setpoint low and high limits set locally R/W

AV15 Humidity Setpoint % RH Dynamic 0-100 Humidity Setpoint R/W

AV16 Current DAT Target °C/°F Dynamic -59°F to 300°F

"Current dischare air temperature setpoint. Available when D.A.T. reheat control is enabled.

R

AV17 Room Load % Dynamic -100% to +100%

-100% is full cooling, while 0% is neutral and +100% is full heating R

AV18 Number of Fume Hoods

N/A Dynamic 0-16 Total number of fume hoods expected by the LSC R

AV19 Number of Fume Hoods Detected

N/A Dynamic 0-16 Number of currently detected fume hoods R

AV20 Total Fume Hood Exhaust

cfm Dynamic 0-10000 Total exhaust flow between al fume hoods R

AV21 Unocc. Heat Setpoint °C/°F Dynamic 0-150 Heating setpoint when controller in unoccupied mode R/W

AV22 Unocc. Cool Setpoint °C/°F Dynamic 0-150 Cooling setpoint when controller in unoccupied mode R/W

AV101 Fume Hood 1 Face Velocity

fpm Dynamic 0-250 Current Face Velocity Reading Fume Hood 1 R

AV102 Fume Hood 1 Airflow cfm Dynamic 0-10000 Current Airflow through valve Fume Hood 1 R

AV103 Fume Hood 1 Valve Pressure

inH2O Dynamic 0-5 Current Pressure across valve Fume Hood 1 R

AV104 Fume Hood 1 Sash Position

Inches Dynamic 0-100 Current Sash Position in inches Fume Hood 1 R

AV201 Fume Hood 2 Face Velocity

fpm Dynamic 0-250 Current Face Velocity Reading Fume Hood 2 R

AV202 Fume Hood 2 Airflow cfm Dynamic 0-10000 Current Airflow through valve Fume Hood 2 R

AV203 Fume Hood 2 Valve Pressure

inH2O Dynamic 0-5 Current Pressure across valve Fume Hood 2 R

AV204 Fume Hood 2 Sash Position

Inches Dynamic 0-100 Current Sash Position in inches Fume Hood 2 R

Repeats for up to 16 fume hoods R

MI1 Keyswitch Position N/A 7 states Current keyswitch position of the remote panel R

36 LABORATORY SPACE CONTROLLER - Manual | pricecriticalcontrols.com

LABORATORY SPACE CONTROLLERMAINTENANCE

BACnet Point List Continued...Object Name Units Default Range Description R/WMV1 Status Text Dynamic 4 states Room Status:

1 - Normal2 - Caution3 - Alarm4 - Setback

R

MV2 Isolation Mode Text Dynamic 2 states Room Isolation Mode1 - Positive2 - Negative

R

MV3 N/A N/A N/A N/A N/A R

MV4 Alarm Status Text Dynamic 23 states Alarm Status:1 - No Alarm2 - Emergency Button3 - Network Override4 - Contact Input5 - Missing Primary Sensor6 - Missing Secondary Sensor7 - Incorrect Keyswitch8 - Primary Sensor Low Pressure9 - Primary Sensor High Pressure10 - Secondary Sensor Low Pressure11 - Secondary Sensor High Pressure12 - Extended Door Open13 - Low Voltage on Input14 - Low Airflow15 - Low Pressure on AI16 - Low Air Changes17 - High Voltage on Input18 - High Airflow19 - High Pressure on AI20 - High Air Changes21 - Loss of Supply22 - Loss of Exhaust23 - Diversity

R

MV5 Caution Status Text Dynamic 25 states Caution Status:1 - No Caution2 - Network Override3 - Contact Input4 - Door Open5- Primary Sensor Low Pressure6 - Primary Sensor High Pressure7 - Secondary Sensor Low Pressure8 - Secondary Sensor High Pressure9 - Missing Primary Sensor10 - Missing Secondary Sensor11 - Primary Sensor Setpoint Range12 - Secondary Sensor Setpoint Range13 -Unknown Keyswitch14 - Low Voltage on Input15 - Low Airflow16 - Low Pressure on AI17 - Low Air Changes18 - High Voltage on Input19 - High Airflow20 - High Pressure on AI21 - High Air Changes22 - Missing Networked FHC23 - Loss of Supply24 - Loss of Exhaust25 - Diversity

R

37pricecriticalcontrols.com | LABORATORY SPACE CONTROLLER - Manual

LABORATORY SPACE CONTROLLERMAINTENANCE

BACnet Point List Continued...Object Name Units Default Range Description R/WMV6 Room Control Type Text Dynamic 5 states Control Type:

1 - No Control2 - Direct Exhaust3 - Supply + Direct Exhaust4 - Supply Exhaust Tracking5 - Supply Exhaust Tracking Dynamic

R

MV7 N/A N/A N/A N/A R

MV8 Occupancy Status Text Dynamic 2 states Occupancy Status:1 - Unocccupied2 - Occupied

R

MV9 Occupancy Override Text Dynamic 3 states Occupancy Override:1 - No Override2 - Force Unoccupied3 - Force Occupied

R

MV101 Fume Hood 1 Status Text Dynamic 6 states Fume Hood Status:1 - Missing FHC2 - Normal3 - Caution4 - Alarm5 - Setback6 - Off

R

MV201 Fume Hood 2 Status Text Dynamic 6 states Fume Hood Status:1 - Missing FHC2 - Normal3 - Caution4 - Alarm5 - Setback6 - Off

R/W

Repeats for up to 16 fume hoods

This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.price-hvac.com.

© 2015 Price Industries Limited. All rights reserved.