6
1 AbstractThis paper presents a parametric study of the major factors affecting cable ampacity calculations. The current carrying capacity (or ampacity) of a cable depends on many of the installation properties and conditions. In this paper the effects on ampacity of conductor size, ambient temperature, bonding arrangement, duct size, soil thermal resistivity, resistivity and size of backfill (or duct bank) and depth of installation for underground installations are presented. For cables air the effects on ampacity of the intensity of solar radiation, the spacing from the wall and the grouping of cables are analyzed. For riser pole installations the effect of the solar radiation, wind speed, ventilation and diameter of the duct are shown. Index Terms — Ampacity. Cable Rating. Underground Cables. Cables in Air. Cables in Riser Poles. IEC Standards. CYMCAP. Neher-McGrath. I. INTRODUCTION MPACITY (or current-carrying capacity) of a cable is greatly affected by the installation conditions and material properties. In this paper a parametric study of the major factors affecting ampacity is presented. All simulations were performed using the commercial ampacity program CYMCAP, which works in accordance to the IEC standards; see references [1] to [7]. The IEEE Standard 835-1994 [8] gives very similar results to those of the IEC Standards for underground cables. Differences are more noticeable for cables in air. Both the IEC and IEEE Standards are based on the Neher-McGrath method published in 1957 [9]. The reader is referred to [10] for a thorough review the theory of ampacity calculations, the historical developments and the differences between the two methods. For underground installations the effects on cable ampacity due to the following parameters is studied: conductor size, native soil thermal resistivity, bonding type, directly buried versus duct bank installation and duct size. For cables in air the effect on cable ampacity of the following parameters is studied: conductor size, intensity of solar radiation, distance to the wall and cable grouping. For cables installed in riser poles the effect on ampacity of the following installation parameters is studied: conduit size, surface absorption coefficient of solar radiation, wind speed, type of ventilation, intensity of solar radiation and length of the riser pole. F. de León is with CYME International T&D, 1485 Roberval, Suite 104, St- Bruno, Quebec, Canada, J3V 3P8 (e-mail: [email protected]). II. UNDERGROUND CABLE INSTALLATIONS Several installation features were varied to study their effect in the ampacity. In the Appendix the reader can find the data of cables and installations used to perform the parametric studies. The ambient temperature was always 25°C while the target temperature has been set to 90°C for all ampacity calculations. The soil thermal resistivity is 1.0 [°K-W/m] except when indicated. All cases are balanced with a unity load factor. A. Varying Conductor Caliber The size of the cable has been varied from 250 MCM to 1500 MCM. Figure 1 shows the results for single-point and two- point bonding. 0 100 200 300 400 500 600 0 250 500 750 1000 1250 1500 1750 Conductor Size [MCM] Ampacity [A] Single-Point Bonded Two-Point Bonded Figure 1. Ampacity versus conductor size for two bonding types 0 100 200 300 400 500 600 0 250 500 750 1000 1250 1500 1750 Conductor Size [MCM] Ampacity [A] Duct Bank Directly Buried 6% Figure 2. Ampacity versus conductor size for directly buried and duct bank installations (two-point bonding) From the results presented in figures 1 and 2 one can appreciate that doubling the conductor cross-sectional area does not double the ampacity. Although the dc resistance of a Major Factors Affecting Cable Ampacity Francisco de León, Senior Member, IEEE A 1-4244-0493-2/06/$20.00 ©2006 IEEE.

Major Factors Affecting Cable Ampacity

Embed Size (px)

Citation preview

Page 1: Major Factors Affecting Cable Ampacity

1

Abstract—This paper presents a parametric study of the major factors affecting cable ampacity calculations. The current carrying capacity (or ampacity) of a cable depends on many of the installation properties and conditions. In this paper the effects on ampacity of conductor size, ambient temperature, bonding arrangement, duct size, soil thermal resistivity, resistivity and size of backfill (or duct bank) and depth of installation for underground installations are presented. For cables air the effects on ampacity of the intensity of solar radiation, the spacing from the wall and the grouping of cables are analyzed. For riser pole installations the effect of the solar radiation, wind speed, ventilation and diameter of the duct are shown.

Index Terms — Ampacity. Cable Rating. Underground Cables. Cables in Air. Cables in Riser Poles. IEC Standards. CYMCAP. Neher-McGrath.

I. INTRODUCTION

MPACITY (or current-carrying capacity) of a cable is greatly affected by the installation conditions and

material properties. In this paper a parametric study of the major factors affecting ampacity is presented. All simulations were performed using the commercial ampacity program CYMCAP, which works in accordance to the IEC standards; see references [1] to [7]. The IEEE Standard 835-1994 [8] gives very similar results to those of the IEC Standards for underground cables. Differences are more noticeable for cables in air. Both the IEC and IEEE Standards are based on the Neher-McGrath method published in 1957 [9]. The reader is referred to [10] for a thorough review the theory of ampacity calculations, the historical developments and the differences between the two methods.

For underground installations the effects on cable ampacity due to the following parameters is studied: conductor size, native soil thermal resistivity, bonding type, directly buried versus duct bank installation and duct size.

For cables in air the effect on cable ampacity of the following parameters is studied: conductor size, intensity of solar radiation, distance to the wall and cable grouping.

For cables installed in riser poles the effect on ampacity of the following installation parameters is studied: conduit size, surface absorption coefficient of solar radiation, wind speed, type of ventilation, intensity of solar radiation and length of the riser pole.

F. de León is with CYME International T&D, 1485 Roberval, Suite 104, St-

Bruno, Quebec, Canada, J3V 3P8 (e-mail: [email protected]).

II. UNDERGROUND CABLE INSTALLATIONS

Several installation features were varied to study their effect in the ampacity. In the Appendix the reader can find the data of cables and installations used to perform the parametric studies. The ambient temperature was always 25°C while the target temperature has been set to 90°C for all ampacity calculations. The soil thermal resistivity is 1.0 [°K-W/m] except when indicated. All cases are balanced with a unity load factor.

A. Varying Conductor Caliber

The size of the cable has been varied from 250 MCM to 1500 MCM. Figure 1 shows the results for single-point and two-point bonding.

0

100

200

300

400

500

600

0 250 500 750 1000 1250 1500 1750

Conductor Size [MCM]

Am

paci

ty [

A]

Single-PointBonded

Two-PointBonded

Figure 1. Ampacity versus conductor size for two bonding types

0

100

200

300

400

500

600

0 250 500 750 1000 1250 1500 1750

Conductor Size [MCM]

Am

paci

ty [

A]

Duct Bank

Directly Buried 6 %

Figure 2. Ampacity versus conductor size for directly buried and duct bank installations (two-point bonding)

From the results presented in figures 1 and 2 one can appreciate that doubling the conductor cross-sectional area does not double the ampacity. Although the dc resistance of a

Major Factors Affecting Cable Ampacity Francisco de León, Senior Member, IEEE

A

1-4244-0493-2/06/$20.00 ©2006 IEEE.

Page 2: Major Factors Affecting Cable Ampacity

2

cable reduces in inverse proportion to the conductor area, for ac excitation the skin and proximity effects play an important role. The larger the cross sectional area of the conductor the larger the effects of the induced eddy currents in single-point bonded installations and the circulating currents in two-point bonded installations.

Figure 2 shows that directly buried cables have a slightly higher ampacity, about 6%, than cables installed in PVC conduits. The reason is that the PVC has a higher thermal resistivity than the native soil.

B. Varying Soil Thermal Resistivity

The thermal resistivity of the native soil using 4-trefoils (for 500 and 1000 MCM) directly buried cables was varied from 0.4 to 4.0 [°K-W/m]; this covers the conditions for most installations. The computed ampacities are presented in Figure 3. One can note that the ampacity reduces as the thermal resistivity of the soil increases and seems to follow a hyperbolic function.

0

200

400

600

800

0 1 2 3 4 5

Soil Thermal Resistivity [°K-W/m]

Am

paci

ty [

A]

1000 MCM

500 MCM

Figure 3. Ampacity as a function of soil thermal resistivity

C. Varying Bonding and Transposition

Figure 1 shows that two-point bonded cables have a smaller ampacity than single-point bonded cables. This is due to the large circulating currents in (sheaths or) concentric neutrals. The ampacity reduction effect of the circulating currents becomes more significant for larger cable sizes were larger circulating currents are present in the sheaths or concentric neutrals.

Table 1 shows the calculated ampacity for several bonding arrangements for the installation of the 4 trefoils specified in the Appendix using 1000 MCM cables. The ampacity for a two-point bonded installation is about 15% smaller than that of the single-point bonded case. The circulating currents cause this ampacity reduction. Cross bonding the cables with equal section lengths completely eliminates the circulating currents. However, in practice the lengths cannot be identical. Table 1 shows how for different ratios AM (longest/shortest) and AN (longer/shortest) one obtains different ampacity

reductions.

TABLE 1. VARIATION OF AMPACITY FOR TREFOILS WITH DIFFERENT BONDING

Bonding Arrangement Ampacity [A] Single-Point 464 Two-Point 394

Equal Section Lengths 464 AM = 1.5 / AN = 1.25 455 AM = 2.0 / AN = 1.5 441

Cross Bonding

AM = 3.0 / AN = 2.0 416 The same effects can be appreciated in flat formation

installations. Figure 4 summarizes the ampacity results for the flat formation installation shown in the Appendix. Different bonding arrangements were used and the distance between cables was varied.

0

200

400

600

800

1000

0 0.1 0.2 0.3 0.4 0.5 0.6Distance between phases [m]

Am

paci

ty

Single P oint = Cross Bonded

Two P oint (transposed)

Two P oint (not transposed)

Standing Voltage / km

Figure 4. Ampacity versus distance for different bonding arrangements (flat formation installation)

The ampacity for single-point bonding and cross bonding is

the highest and increases with the separation of phases. This is due to a reduction in the induced heating between cables. While cross bonding cables is more expensive, single-point bonded cable installations produce standing voltages in the ungrounded terminal. Those voltages increase with phase separation (see the bottom curve in Figure 4).

Two-point bonded installations not only have reduced ampacity as compared with single-point bonded installation, but the ampacity has the initial tendency to reduce even further as the separation between the phases increases. This is because the effect of the larger circulating currents is greater than the reduction of induced heating. There is a point, however, where the effect of the increased circulating currents is overcompensated by the reduction of mutual heating effects and the ampacity augments slightly as the phases separate.

D. Varying the Number of Neighboring Circuits

Induced heating from neighboring cables produces important reductions in cable ampacity. Consider the duct bank installation, with four trefoil circuits, shown in the

Page 3: Major Factors Affecting Cable Ampacity

3

Appendix. When only one trefoil circuit is present the computed ampacity is 650 A. When a second trefoil is added the ampacity reduces to 575 A while adding a third trefoil reduces the ampacity to 512 A. When the last (fourth) circuit is added the ampacity becomes only 464 A; this is about 70% of the case with only one cable. Further reductions are expected as the number of cables heating each other increases. Frequently, there is the need to account for the heating (or cooling) induced from neighboring heat sources (sinks) such as steam or water pipes running parallel to the cable installation. It is not possible, however, to give rules of thumb or to perform parametric studies because the installation possibilities are infinite.

E. Varying the Conduit Size

The diameter of a PVC conduit buried in native soil was varied from a very tight fit to very large size; see Figure 5. The plot of Figure 6 shows that the ampacity increases slightly as the diameter of the conduit increases. For steel conduits the slope is even smaller than for PVC conduits.

Figure 5. Smallest versus largest conduit – 160 mm & 500 mm

0

200

400

600

800

1000

0 100 200 300 400 500 600Duct Internal Diameter [mm]

Am

paci

ty [

A]

500 MCM

1000 MCMSteel

PVC

Figure 6. Ampacity as a function of conduit diameter

III. CABLES IN AIR

A. Varying Conductor Caliber

The conductor caliber has been varied from 250 MCM to 1500 MCM. Figure 7 shows the results for single-point and two-point bonding for a solar radiation intensity of 1000 W/m2, which is typical for North America. One can appreciate that the ampacity increases with the caliber of the conductor at a larger rate that for underground cables; compare the results of Figure 7 with those of Figure 1.

0

200

400

600

800

1000

1200

0 250 500 750 1000 1250 1500 1750

Conductor Size [MCM]

Am

paci

ty [

A] Single-Point Bonding

Two-Point Bonding

Figure 7. Ampacity as a function of conduit diameter

B. Varying the Solar Radiation Intensity

The effects of the variation of the intensity of solar radiation on cable ampacity are shown in Figure 8. One can appreciate, as expected, that the ampacity of the cable reduces as the intensity of solar radiation increases. The behavior for several surfaces having different coefficients of solar absorption is also compared in the figure. As the surface absorption coefficient increases a larger ampacity derate is obtained for a given solar radiation intensity.

The solar radiation intensity, for not shaded installations, depends on the geographical location of the installation (latitude and altitude) and the day of the year and hour of the day. The surface absorption coefficient depends on the material type and color of the cable's external surface (the surface exposed to the sun).

0

200

400

600

800

1000

1200

0 250 500 750 1000 1250 1500Solar Radiation Intensity [W/m2]

Am

paci

ty [A

]

0 .20.4

0.6

0.8

Figure 8. Variation of ampacity with solar radiation intensity for several surface absorption coefficients

C. Varying the Distance to the Wall

In the IEC standard 287-2-1, reference [4], there are several arrangements for cables in air installations using non-continuous brackets, ladder supports or cleats; see Figure 9. Table 2 shows the effect on ampacity of the distance from the cable to the wall. The 1000 MCM concentric neutral cable,

Page 4: Major Factors Affecting Cable Ampacity

4

described in the Appendix, was used to compute the ampacities.

Figure 9. Standardized arrangements for cables in air

TABLE 2. AMPACITY FOR CABLES IN AIR

Arrangement Number

Ampacity [A]

1 1033 2 838 3 714 4 772 7 772 8 947 9 910 10 544

Comparing the ampacity of cases 1 with 9 and 3 with 10

one can see that cable installations near the wall show a substantially smaller ampacity than those separated from the wall. For the single-phase the obtained reduction is 12%, while for the trefoil the reduction is 24%. One can also note from cases 4 and 7 that there is no influence when installing the cables vertically or horizontally. Grouping the cables has the effect, as expected, of reducing ampacity; compare cases 1, 2 and 4.

D. Groups of Cables

The effect of the separation between cables for groups of cables was analyzed using the 1000 MCM cable (single-point bonded) described in the Appendix. Figure 10 shows the results for flat formations and Figure 11 the results for trefoils. In both cases when the cables are grouped horizontally there is a transition when (e/De) = 0.75. The ampacity before and after the transition point is independent of the separation between cables. When the cables are grouped horizontally and vertically as well, one can see two smoother transition points.

IV. CABLES IN RISER POLES

In Figure 12 the variation of ampacity as a function of the internal diameter is presented. The variation is shown for three different ventilation conditions. As expected, ventilation on both-ends gives the greatest ampacity followed by the case vented at the top. In all three cases the ampacity is highest with very tight ducts, i.e. when the internal diameter of the

duct is equal to the minimum circumference that encloses the trefoil formation. As the diameter of the ducts increases the ampacity reduces reaching a minimum and then slowly rises.

Figure 10. Ampacity as function of separation

Figure 11. Ampacity as function of separation

Figure 13 shows the variation of ampacity with the surface coefficient of solar absorption of the external surface of the installation (cable or duct). One notices that the ampacity reduces almost linearly with an increase of the surface coefficient of solar absorption. Figure 14 shows the variation of ampacity as a function of the intensity of solar radiation. The ampacity reduces in a quasi-linear fashion from shaded conditions as the intensity of solar radiation increases.

0

200

400

600

800

1000

1200

100 200 300 400 500Internal Diameter of Duct [mm]

Am

paci

ty [A

]

Not Vented

Vented Ends

Vented Top

Figure 12. Varying the internal diameter of the conduit for different

0

200

400

600

800

1000

1200

0 0.1 0.2 0.3 0.4 0.5 0.6Separation [m]

Am

paci

ty [

A]

0

200

400

600

800

1000

0 0.1 0.2 0.3 0.4 0.5 0.6Separation [m]

Am

paci

ty [

A]

Page 5: Major Factors Affecting Cable Ampacity

5

0

200

400

600

800

1000

1200

1400

0 0.2 0.4 0.6 0.8 1

Surface Absorption Coefficient

Am

paci

ty [

A]

Vented Ends

Not Vented

Figure 13. Ampacity as function of the surface absorption coefficient of solar radiation

0

200

400

600

800

1000

1200

1400

0 500 1000 1500 2000

Intensity of Solar Radiation [W/m2]

Am

paci

ty [

A]

Vented Ends

NotVented

Figure 14. Ampacity as function of intensity of solar radiation

Figure 15 shows a plot of ampacity versus wind speed. The

ampacity increases with an increase of wind speed. However, the ampacity increase is larger at the lower end. Thus increasing the wind speed form 0 to 5 m/s has a large effect than increasing it from 15 o 20 m/s. The length of the riser pole was varied from 1 to 20 meters and the ampacity did not show any significant variation (results are not shown).

0

100

200

300

400

500

600

700

800

0 5 10 15 20 25Wind Speed [m/s]

Am

paci

ty [

A]

Figure 15. Ampacity as function wind speed

V. CONCLUSIONS

A. Underground Cable Installations

The three major factors affecting ampacity in underground cable installation are: cable caliber, soil thermal resistivity and bonding method. Doubling the conductor cross-sectional area does not double the ampacity; see Figures 1 and 2. The soil thermal resistivity plays a very important role in the ampacity of an installation. Keeping all other conditions unchanged, a large variation on the soil thermal resistivity can affect the ampacity in more than 50% (Figure 3). Depending on the particularities of the installation, bonding type can also account for up 50% of the ampacity (Figure 4).

B. Cables in Air

For cables in air the three major factors affecting cable ampacity are: conductor size, the cable grouping and the distance to the wall. Doubling the conductor cross-sectional area does not double the ampacity, but the "reduction effect" is smaller than that of underground cables. Ampacity is less sensitive to the bonding type and somehow dependent on the intensity of solar radiation especially for large values of the absorption coefficient of solar radiation. However, ampacity is very much dependent on the distance from the cable to the wall and on cable groping; see table 2 and Figures 10 and 11.

C. Cables in Riser Poles

The ampacity of cables in riser poles greatly depends on the diameter of the guard, the intensity of solar radiation and the surface coefficient of solar absorption (Figures 12, 13 and 14). It is somehow dependent on the wind speed (Figure 15).

VI. REFERENCES [1] Electric Cables – Calculation of the current rating – Part 1: Current rating

equations (100% load factor) and calculation of losses – Section 1: General. IEC Standard 287-1-1 (1994-12).

[2] Electric Cables – Calculation of the current rating – Part 1: Current rating equations (100% load factor) and calculation of losses – Section 2: Sheath eddy current loss factors for two circuits in flat formation. IEC Standard 287-1-2 (1993-11).

[3] Electric Cables – Calculation of the current rating – Part 2: Thermal resistance – Section 1: Calculation of the thermal resistance. IEC Standard 287-2-1 (1994-12).

[4] Electric Cables – Calculation of the current rating – Part 2: Thermal resistance – Section 2A: A method for calculating reduction factors for groups of cables in free air, protected from solar radiation. IEC Standard 287-2-2 (1995-05).

[5] Electric Cables – Calculation of the current rating – Part 3: Sections on operating conditions – Section 1: Reference operating conditions and selection of cable type. IEC Standard 287-3-1 (1995-07).

[6] Calculation of the cyclic and emergency current rating of cables – Part 1: Cyclic rating factor for cables up to and including 18/30 (36) kV. IEC Publication 853-1 (1985).

[7] Calculation of the cyclic and emergency current rating of cables – Part 2: Cyclic rating of cables greater than 18/30 (36) kV and emergency ratings for cables of all voltages. IEC Publication 853-2 (1989-07).

[8] IEEE Standard Power Cable Ampacity Tables, IEEE Std 835-1994. [9] J.H. Neher and M.H. McGrath, “The Calculation of the Temperature Rise

and Load Capability of Cable Systems”, AIEE Transactions Part III - Power Apparatus and Systems, Vol. 76, October 1957, pp. 752-772.

[10] George J. Anders, "Rating of Electric Power Cables: Ampacity Computations for Transmission, Distribution, and Industrial Applications, IEEE Press / McGraw Hill, 1997.

Page 6: Major Factors Affecting Cable Ampacity

6

VII. APPENDIX: CABLE AND INSTALLATION DATA

Figure 16 describes the 15 kV, 1000 MCM, concentric neutral cable used in this paper. The cables with different calibers used in the parametric study have the same layers with different sizes; see Table 3. Figure 17 illustrates the installation used in this paper with four trefoil formations installed in a 2×2 duct bank. The directly buried case is shown in Figure 18 and the flat formation is shown in Figure 19.

Figure 16. Construction and dimensions of the concentric neutral cable used for most simulation

Figure 16. Construction and dimensions of the concentric neutral cable used for most simulations

TABLE 3. CONDUCTOR SIZES

External Diameter of Layer [inch]

Size [MCM] Conductor Shield Insulation Screen C. Wires Jacket

250 0.5748 0.6148 1.6384 1.7927 1.9541 2.1510

500 0.8129 0.8629 1.8866 2.0409 2.2023 2.3992

750 0.9980 1.0480 2.0716 2.2417 2.4448 2.6417

1000 1.1519 1.2119 2.2355 2.4056 2.6088 2.2805

1250 1.2889 1.3489 2.3726 2.5426 2.7458 2.9426

1500 1.4118 1.4718 2.4954 2.6655 2.8686 3.0655

Figure 17. Duct bank installation of a 2X2 duct bank with four trefoils (distances in feet)

Figure 18. Four directly buried trefoils (distances in feet)

Figure 19. Flat formation for the parametric study of cable separation (distances in feet)

VIII. BIOGRAPHY

Francisco de León (S’86, M’92, SM’02) was born in Mexico City in 1959. He received the B.Sc. and the M.Sc. (summa cum laude) degrees in Electrical Engineering from the National Polytechnic Institute (Mexico), in 1983 and 1986 respectively, and obtained his Ph.D. degree from the University of Toronto, Canada, in 1992. He has held several academic positions in Mexico and has worked for the Canadian electric industry. Currently working with CYME International T&D in St. Bruno (Quebec, Canada), he develops professional grade software for power and

distribution systems and is the leading technical support of CYMCAP, CYME's cable ampacity program. He has published over a dozen papers in refereed journals (IEEE/IEE), which have been cited over 100 times in journals listed in the Science Citation Index.

-6 -4 -2 0 2 4 6

0

1

2

3

4

5

6

Ambient temp = 25°C

Native Soil = 1.00 °C-m/W

-3 -2 -1 0 1 2 3

Ambient temp = 25°C

Native Soil = 1.00 °C-m/W

0

1

2

3

Voltage = 15.0 kV Cond. area = 0.7854 inch2 (1000 KCMIL)

-6 -4 -2 0 2 4 6

0

1

2

3

4

5

6

Ambient temp = 25°C

Native Soil = 1.00 °C-m/W